(SE970182)
Application RAMDE can be used for both synchronous Overload protection (Ib)
and asynchronous motors. There are two ver- The protection, which is a thermal overcur-
sions available; RAMDE 1 and RAMDE 2. rent relay, protects the motor against over-
RAMDE 1 should be used for synchronous heating. The thermal time constant is
motors where the idle running current is less determined on the basis of the size and con-
than 10% of rated current. RAMDE 2 can be struction of the motor. To be able to use the
used in most other applications. motor’s optimal thermal capacity at start-up,
the time constant can be increased. At 95%
The current measurements are based on thermal content an alarm is triggered, which
RMS-values, therefore taking into consider- is indicated by a light emitting diode (LED),
ation the harmonics common in today’s and which can be connected to an output
industrial environments. The current-unbal- relay. The cooling-down time constant can be
ance protection is independent of frequency prolonged to suit all types of cooling-down
and phase sequence and therefore also works methods if the motor stops.
for motors fed via frequency convertors or for
reversible motors. Restarting of the motor is blocked after trip-
ping until the thermal content has decreased
All settings are made on the front of the unit. below 50%. The relay’s thermal content can
Set values, service current, thermal content, also be quickly emptied with a switch and the
current unbalance, start time and start current blocking will be released.
are shown on the display.
Motor protection relay RAMDE
1MRK 503 001-BEN
Page 2
Application (cont’d) The relay can be set with the “Lock-out” sequence-currents, to detect inter-turn short
switch so that manual resetting must always circuits, two phase short circuits close to the
be done before restarting. stator’s zero point as well as phase failure.
LED’s to the left of the potentiometers for If the push sequence is not completed the dis-
each protective function will light up with a play and the LED will go out after about 8
steady glow. minutes.
Technical data
Table 1: Common data
Rated current Ir 1 or 5 A
Basic current Ib 0,5-1,2 times Ir
(Ib prop. to the motor’s rated current)
Rated earth current INr 3, 10 100 or 500 mA
Rated frequency 50-60 Hz
Auxiliary voltage 48-220 V ±20% dc or ac 50-60 Hz
Power consumption per
phase: current circuits (at rated current):
Ir = 1 A <50 mVA
Ir = 5 A <250 mVA
INr = 3 mA and 10 mA <1 mVA
INr = 100 mA <1,5 mVA
INr = 500 mA <4 mVA
Auxiliary voltage circuit
(dependent on auxiliary voltage):
normal service maximum 9 W
after operation maximum 12 W
Overload capacity:
Continuous:
Ir = 1 A and 5 A 3 times Ir
INr = 3, 10 and 100 mA 20 times INr
INr = 500 mA 10 times INr
For 1 s 100 times Ir resp INr (max. 350 A for COMBIFLEX)
Motor protection relay RAMDE
1MRK 503 001-BEN
Page 4
Diagrams