AIR CIRCUIT BREAKERS
L&T’s Air Circuit Breakers (ACBs) are specially designed for extreme tropical conditions and have a proven
track record of more than 45 years. Presently more than 5,00,000 Air Circuit Breakers supplied by L&T are
being used for diverse applications. The Air Circuit Breakers provide technologically driven
solutions to meet customer needs.
Complete selectivity
Unique feature of lcu=lcs=lcw for 1 second across the entire range. This ensures complete selectivity for
system with time based discrimination.
Optimal compactness
Designed to ensure
lLow inherent temperature rise
lAdequate interface clearances
Thermo-magnetic release-DN1
l
2
New user friendly feature
lOperational Counter will be standard offering from rating 4000A and above
Lockable sliding shutters to prevent unauthorized access to “TRIP” and “CLOSE” push buttons
l
Facility for site conversion of manually operated ACBs to electrically operated ACBs
l
Safety
“ ’’ marked for C, S1 & H ranges
l
Superior quality engineering grade plastics used for insulation purpose; conforms to Glow wire test
l
In-built rating error preventor in drawout ACBs ensure correct rating of drawout portion in corresponding
l
cradle
Safety shutters prevent accidental contact with live cradle terminals
l
Operating voltage ranges from 10% Un to 110% Un for shunt release ensures intentional tripping even at
l
Conformance to standards
IEC - 60947 (Part 1 & 2)
l
IEC 60695 - 2 - 1
l
BS EN 60947 - 2
l
Special applications
690V Application for C Power ACB
Solution for 690V application available in C Power Family. For further details please consult our nearest
branch office.
Breaking capacities:
Icu = Ics = Icw for 1 sec
Rated Current 400A 630A 800A 1000A 1250A 1600A 2000A 2500A 3200A 4000A 5000A 6300A
CN-CS : E 50kA 50kA 50kA 50kA 50kA 50kA 50kA
Frame-1
CN-CS : S1 50kA 50kA 50kA 50kA 50kA 50kA 50kA 60kA 60kA
Frame-1 Frame-2
4
TECHNICAL DATA SHEET
Rating (A) 400 630 400/ 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
630
NEW NEW
Type Designation E E S1 E S1 C H E S1 C H E S1 C H E S1 C H E S1 C H S1 C H S1 H2 H1 H2 H C C C
Rated current (A) at 50°C In 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Rated operational voltage (V), 50/60Hz Ue* 415 415 415 415 415 415 415 415 415 415 415 415
Rated insulation voltage (V), 50/60Hz Ui 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
No. of poles 3 3 3/4 3 3/4 3 3/4 3 3/4 3 3/4 3 3/4 3/4 3/4 3/4 3/4 3/4
380/415/500V 105 105 105 105 105 105 143 105 105 105 143 105 105 105 143 105 105 105 143 105 105 121 165 132 132 165 132 165 220 165 220 154 209 209
Rated making capacity Icm
50/60Hz (kA peak) 690V - - - - - 73.5 105 - - 73.5 105 - - 73.5 105 - - 73.5 105 - - 84 143 - 84 143 - 143 187 143 187 DDD
Rated impulse withstand voltage Uimp 8 8 12 8 12 8 12 8 12 8 12 8 12 12 12 12 12 12
of main circuit (kV)
Rated impulse withstand voltage Uimp 4 4 4 4 4 4 4 4 4 4 4 4
of aux. circuit (kV)
Utilization category B B B B B B B B B B B B
Manual PPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPPP
Electrical & Mechanical life (operating cycles) ‡ 15000 15000 20000 15000 20000 15000 20000 20000 20000 20000 20000 10000 10000 5000 5000 5000
Electrical life without maintenance 6000 6000 8000 6000 8000 8000 8000 6000 8000 8000 8000 6000 7000 7000 7000 6000 7000 7000 7000 4500 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 2500 2500 2500
Dimensions (in mm) Fixed H 385 385 394 385 394 385 394 385 394 385 394 385 - 394 - 394 - D D - - -
3 Pole 316 316 326 316 326 316 326 316 326 316 326 316 - 482 - 482 - D D - - -
W
4 Pole - - 414 - 414 - 414 - 414 - 414 - - 628 - 628 - D D - - -
D 423.5 423.5 431 423.5 431 423.5 431 423.5 431 423.5 431 423.5 - 431 - 431 - D D - - -
Draw out H - - 468 - 468 - 468 - 468 - 468 - 468 468 468 468 468 468 583 583 583
3 Pole - - 399 - 399 - 399 - 399 - 399 - 399 555 555 555 701 701 711 913 913
W
4 Pole - - 487 - 487 - 487 - 487 - 487 - 487 701 701 701 909 909 913 1182 1182
D - - 587 - 587 - 587 - 587 - 587 - 587 587 587 587 587 587 691 691 691
‡
* Please consult us for application at dc voltages & higher operational voltage upto 690V AC. Electrical life = Mechanical life. However, arcing contacts need to be replaced depending upon wear & tear. New H2 range has replaced old HO range
D
Please consult us.
5 6
PROTECTION RELEASES
Protection
Overload Protection (Phase)
lUnique individual phase O/L setting adjustment helps to avoid the nuisance
tripping of ACBs in unbalance load condition (due to single phase loads) on
distribution transformer. Overload pick-up range: 0.75 to 1 times In
Short-Circuit Protection
lTwo taps on CTs (working as rating plug) help in selecting operating threshold.
Short-Circuit pickup range: 5.5 to 7.5 times In with minimum impulsion time of
25 ms to prevent nuisance tripping due to transients
Earth Fault Protection
lOffered with auxiliary earth fault release module. Earth-fault pick-up
range: 0.2 to 0.5 times In
- Power ON condition
- Test mode
Individual fault annunciation through LEDs
l
AN1 module for remote fault indication through LEDs with changeover contact
l
Setting Range
Type of
Protection Pick-up Current Time Delay
2 to 10 times In 20 ms to 600 ms
Short-Circuit
Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 Steps: 20, 60, 100, 160, 200,260, 300, 400, 500, 600 ms
Instantaneous 6 & 12 In -
7
PROTECTION RELEASES
Salient Features
Self –powered &True RMS sensing
l
with display
2 to 16 times In -
Instantaneous Steps : 2, 3, 4, 6, 8, 10, 12, 14, 16, OFF
*In 3 phase, 4 wire system, Neutral CT is required for earth fault protection
Test-kit UN-ES1
Salient Features
Test-kit for SR18G/SR18Gi with display
l
Operates from 230V AC supply & generates single-phase voltage test signals
l
- For phase faults: 2.5 In, 4.5 In, 6.5 In, 9.5 In, 11 In, 13 In
- For earth fault: 0.25 In, 0.35 In, 0.45 In, 0.55 In
Five 7-segments LED display indicates the trip time (two places after decimal)
l
8
PROTECTION RELEASES
Salient Features
Self-powered & True RMS sensing
l
- Power ON condition
- Test mode
Individual fault annunciation through LEDs
l
Provision for AN1 module for remote fault indication through LEDs with
l
Realistic hot and cold curves which take into account integrated heating
l
effect
Conformance to EMI/EMC standards
l
2 to 10 times In 20 ms to 600 ms
Short-Circuit
Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 Steps : 20, 60, 100, 160, 200, 260, 300, 400, 500, 600 ms
2 to 16 times In -
Instantaneous
Steps : 2, 3, 4, 6, 8, 10, 12, 14, 16, OFF
Test-kit SRT-2
Salient Features
l Test-Kit for SR18/SR18G/SR21i Releases
l Operates from 230V AC supply & generates single-phase voltage test signals
l Tests the release for
- Phase fault i.e. for overload, short-circuit and instantaneous protection
- Earth fault protection
Test current multiples
l
- For phase faults: 2.5 In, 4.5 In, 6.5 In, 9.5 In, 11 In, 13 In
- For earth fault: 0.25 In, 0.35 In, 0.45 In, 0.55 In
Five 7-segments LED display indicates the trip time
l
Salient Features
True RMS sensing
l
LED indication for POWER ON, different faults and Pre-trip alarm
l
Last 5 trips & 128 Event records with time & date stamping
l
fault annunciation
4 relay contacts for indication of exceeding maximum demand, Pre-trip
l
Selectable I2t based current for short-time and earth fault zones
l
Note: Both Protection Groups 1 & 2 carry the same factory settings. 10
ADDITIONAL PROTECTIONS
11
METERING
Parameter Screen Abbreviation Details
Current I Phase, Earth and Neutral
Imax Maximum running Current per Phase
%Load Percent Loading
Voltage# V Phase-Neutral
Vph-Vph Phase-Phase
Frequency # F System Frequency
Power Factor # PF System Power Factor
Power # kW Active Power per Phase and Total (kW)
kVAr Reactive Power per Phase and Total (kVAr)
kVA Apparent Power per Phase and Total (kVA)
kW Maximum Demand (kW)
Energy # kWh Total Active Energy (kWh)
kVArh Total Reactive Energy (kVArh)
kVAh Total Apparent Energy (kVAh)
Harmonic-Current I1HAR R-Phase Current Harmonics
I2HAR Y-Phase Current Harmonics
I3HAR B-Phase Current Harmonics
Harmonic-Voltage # V1HAR R-Phase Voltage Harmonics
V2HAR Y-Phase Voltage Harmonics
V3HAR B-Phase Voltage Harmonics
Display High Resolution Backlit LCD
ADDITIONAL FEATURES
Parameter Screen Abbreviation Details
LED Indications Auxiliary Power ON P
Overload P
Short-Circuit P
Instantaneous P
Earth Fault P
Neutral Fault P
Trip P
Alarm P
Auxiliary Supply 24V DC
Digital Inputs 4 Nos.
Output Relays 3 Internal + 4 External Relays
240V AC / 5A, 30V DC / 5A (resistive load)
Rating Plug In Multiplier 630-800-1000-1250-2000-3200-5000
Communication Protocol MODBUS RTU
Link used RS 485
Maintenance Indication I2t based
Event Records (128) Pick-up, Alarm, Trip, Date, Time and Cause of Event,
voltage and current readings in all phases
Trip Records Last 5 records with date and time stamping,
Testing Self-Diagnostic Test P
Supplementary Modules Comunication Module (SR71-COM) MODBUS RTU using RS 485
Power Supply Module (UN-PS) Input : 26V to 60V DC, 90 to 300V AC/DC Output : 24V DC
Power Metering Module (SR71-PM) 240V AC, 415V AC
Relay Module (SR71-REL) 4 Relay Outputs (Breaker OPEN, Breaker CLOSE, Pre
Trip alarm and MD Exceed)
No. of Storable Settings 2
12
PROTECTION CHARACTERISTIC
Time-current
(DN1)
10000
}1.05
1.2
Operating Limits
Thermal
1000
100
Overload
0.4
(SR18/18G)
0.3
M1
1000
0.2
M2
0.1
DN1
25ms
10
0.1
1 1.2 1.5 2 3 4 5 6 7 8 9 10 20
13
PROTECTION CHARACTERISTIC
Short-Circuit
(SR18/18G)
1
2 10
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.26
0.2 0.2
0.16
Trip Time (s)
0.1 0.1
0.06
Earth Fault
(SR18G)
1
0.02
0.2 0.6
0.4
0.3
0.01
1 2 3 4 5 6 7 8 910 20 100
0.1 0.1
0.01
0.1 1 10 100
14
PROTECTION CHARACTERISTIC
Overload
(SR18G/SR18Gi with display)
10000
1000
100
Trip Time (s)
10 30s
17s
12s
6s
1 3.5s
2s
1.5s
1s
0.5s
0.1
0.2s
400ms
Trip Time (s)
300ms
200ms
0.1 100ms
20ms
15
PROTECTION CHARACTERISTIC
400ms
300ms
200ms
Trip Time (s)
0.1 100ms
20ms
20ms
16
PROTECTION CHARACTERISTIC
2
Earth Fault I t ON
(SR18G/SR18Gi with display)
10
1
Trip Time (s)
0.1
400ms
300ms
200ms
100ms
400ms
Trip Time (s)
300ms
200ms
17
PROTECTION CHARACTERISTIC
Overload
(SR21i)
10000
1000
100
Trip Time (s)
30
10
17
12
3.5 Short-Circuit
1
2.0 (SR21i)
1.5
1.0
0.5
2 10
0.1 0.6 0.6
0.2
0.5 0.5
0.4 0.4
0.3 0.3
0.01
1 1.2 1.5 2 3 4 5 6 7 8 9 10 0.26
0.16
Trip Time (s)
0.1 0.1
0.06
0.02
0.01
1 2 3 4 5 6 7 8 9 10 20 100
18
PROTECTION CHARACTERISTIC
Earth Fault
(SR21i)
1
0.2 0.6
0.4
0.3
0.2
Trip Time (s)
0.1 0.1
Overload Curve
(SR71)
10,000
1000
0.01
0.1 1 10 100
100
Trip Time (s)
10 30 sec
24 sec
18 sec
12 sec
6 sec
4 sec
1
2 sec
1 sec
0.5 sec
Tolerance:
0.01 Trip Time: ±20%
1.5 2 3 4 5 6 9
19
PROTECTION CHARACTERISTIC
Short-Circuit - I2t ON
(SR71)
10,000
0.6
1000
1.0
1.5
2.0
100 3.0
4.0
6.0
8.0
Trip Time (s)
9.0
10
10.0
0.3
0.2
1000
1.0
0.02 1.5
0.01 2.0
0.05 0.1 1 10 50
Current Multiples ( x In) 100 3.0
4.0
6.0
8.0
Trip Time (s)
9.0
10
10.0
0.4
0.3
0.2
0.1 0.1
0.01
0.05 0.1 1 10 50
20
PROTECTION CHARACTERISTIC
Instantaneous
(SR71)
10.000
1000
100
Trip Time (s)
10
2.0
3.0
10.0
16.0
0.1
1000
0.01
0.05 0.1 1 10 50
100
Current Multiples ( x In)
Trip Time (s)
10
0.2
0.3
0.4
0.5
0.6
0.4s
0.1 0.1s
0.01
0.8 2.4
0.05 0.1 1 10 50
21
PROTECTION CHARACTERISTIC
1000
100
0.2 0.3
0.4
0.5
Trip Time (s)
10 0.6
5.0
1 1.0
0.4s
0.3s
0.2s
0.1 0.1s
0.01
0.05 0.1 1 10 50
Current Multiples ( x In)
22
23
N R Y B
(+24V DC)
1 3 5 AS+ 7 9 11 13 15 E C 81 42 41 H 50 73 70 E
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
R
x x x x
CA-1
C11
(
Only for DC
4
(
Electrical
DN1/SR18
SR18G/SR18G+D
anti-pumping
CC NCT MV CP
SR21i/SR71
SR18G+D
F H
Internal Wiring
EA/
EA1
(
ECD
Internal Wiring
81
(
WIRING DIAGRAM
82
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
(
C6
(-24V DC)
@
Load 2 40 6 AS- 8 10 12 14 16 A B D 82 41 42 F 52 55 74 75 71 72 B
Main Protection & Aux Shunt Aux Power Aux Aux Aux Aux Electric U/V Closing Spring Common Separate Shunt Under
Supply
Aux Closing Neutral Electrical
Circuit Control Unit NC Release NC For NO NC NO NC NO Coil Charging C.T. Release Preventer Charging fault fault trip voltage anti-pumping
SR18G+D Device Indication Indication Indication Indication Indication
Ref no. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
As per order/requirement
The above drawing is for EDO breakers. FCA Limit switch(Shown in breaker reset condition)
1) For MDO/MF versions R Economy Resistor
Ref no. 3, 10, 11 are not applicable C11 Limit switch operates when closing electromagnet is held on
E, B, C, D, A, 15 are applicable only in electrical breakers. C6 ‘Service’ position microswitch for withdrawable circuit breakers
(shown in ‘test’ position)
2) For EF versions
The ref. no. 12, 13, 14, 15, 16, 17, 18, 19, 20, 21 are provided as
per customer requirement. For SR21i release (P&C unit)
SI, SO i discrimination Short circuit i/p & o/p
5. When using An1 Annunciator Module with SR18G/18Gi (with display releases) GI, GO i discrimination Earth fault i/p & o/p
A) AS+ & AS- always appear after 5,6 nos. of the SIC. G Earth
B) If 1,2,3,4,5,6 nos. of SICs are not there, AS+ & AS- will appear first.
C) SIC 13 and 14 Nos. are not offered in 3P EDO and 3P MDO standard breakers.
ACCESSORIES
Type Data
Lockable Trip Push Mounted in place of normal trip push button. With this, ACB can be locked
Button (LTPB)
in trip condition. For interlocking, LTPBs are offered in the following
combinations:
l 4 different types of keys i.e. AA, BB, CC and DD suitable for 2 I/C & 1 B/C
schemes
l Combination of L, M, N, LM and MN locks, which are suitable for
3 I/C & 2 B/C schemes
l Combination of K, L, M, N, KL, LM and MN locks, which are suitable for
4 I/C & 3 B/C schemes
l Combination of J, K, L, M, N, JK, KL, LM and MN locks, which are
suitable for 5 I/C & 4 B/C schemes
Door Interlock
This ensures:
Door Racking Locking in lUnless the panel door is closed, breaker cannot be racked in or out
Interlock Interlock ‘Isolated’ lUnless the breaker is in Isolated Position, it is not possible to open the
Position panel door
Racking Interlock
This ensures that breaker cannot be racked in/out unless the ACB is in
tripped/open condition.
24
ACCESSORIES
Type Data
C1
Common indication of tripping due to overload, short-circuit
and earth faults.
lProvided by micro-switch C1 fitted inside the ACB
lAvailable as an option in all releases
C2
Separate indication of tripping due to overload, short-circuit
and earth faults.
lFor release type DN1, this is provided by micro-switch C1 &
C2 (C2 fitted inside release)
AN1-Annunciator Module
Remote indication of tripping due to overload, short-circuit
and earth faults.
lCan be used with releases type SR18/SR18G/SR21i/SR18G
& SR18Gi with display
lIndividual fault indication provided by three separate LEDs for
- Long time faults
- Short time fault/instantaneous fault
- Earth fault
- One potential free contact rated 5A at 230V AC available for
each type of fault
lFlush mounting on panel (H-W-D=92mm x 46mm x 105mm)
lOperating voltage: 240V AC
C5
Indication for operation of shunt release or undervoltage
release.
l Provided by micro-switch C5 fitted on the shunt release or
undervoltage release
25
ACCESSORIES
Watt loss 6W
Non- 24 to 415 AC 16
resistive 250V AC 1.0 #
Fixed Breakers
To Remove
340 min Arc Chute
For Insulating Sheet
200 min
36 min 36 min 7
140 min
Door
100 min
A 20 min Bezel
26 58 264 26 9
27
394
385
256
33
309
16
22
104
68.8
27
230
21 16 Earthing Terminal 30 35
20 301 54
2 Holes-Ø6.3 2.6 min
405 86 10
D E F E D
20 min
58 102 102 56
23.5
Rating X Y
Type
400E -1250E 5 150
X
1600E 10 145
385
286
Ø12 X
227
216
32
20 20
298
22 137.5
402 21
179.5
Fixed Breakers
Terminal
2 Holes-Ø13 3 Holes-Ø13
30 15 30 15
12.5
25 50 25
25
50 100
Terminal Connections
23.5 23.5 23.5
8 10 15
8 10 15
227
227
227
140
147
145
305
12 Holes-Ø4 101
332
Hinge Hinge
112
112
325
363
112
5.5
A
Drawout Breakers
For 800A to 2500A C/H, 3200A H2/H1, 4000A H2/H, 400A to 3200A S1 3P/4P
For Metallic Components
75 Isolated Position
A
380 min
51 Test Position
200 min
122 For Insulating Sheet
7
100 min
94.5 264 40 max Service Position
Door
40 64.5 26 Bezel
*5
256
468
397.5
404
68.8
160
M 10
46 28
74
4
6 10 54
17.5 min.
199.5 20
6 18.9 max.
538 8.9 min. 18 245
308.5
308.5
221.5
221.5
221.5
221.5
Drawout Breakers
58.4
58.4
58.4
38
38
8.5 x 9.5 8.5 x 9.5
38
8.5 x 9.5
800 - 1000C & 400 - 1250S1 800 - 1000H, 1250/1600C/H & 1600 - 2000S1 2000C
6 Holes-Ø14 6 Holes-Ø14
70
50
67
25
67
43
43
62
38
12.5
6 Holes- Ø14
2500C/H & 2000H 2500S1 3200S1 3200H2/H1 & 4000H2/H
102 26
404
467
M 10
160
46 28
6 5 74
D E E E D 160
25 25 25 25 25
63
17.5 6 Holes-Ø14 28
17.5
40 50 40 43.5
50
25
683
Terminal Connections
12.5
5000C/6300C
42 Terminal Connections 54 67
4000C
64.5
Earthing Terminal 15 15
Dimensions (mm)
Ratings
A D E
4000C 3P 711 155.5 200
356
368
256
256
Mounting Details
Front
2000/2500A 3P C/H 436.3
2000/2500A 4P C/H 582.3
2500/3200A 3P S1 436.3
24
2500/3200A 4P S1 582.3
64.1
3200A 3P H2/H1 582.3
20 481 37 3200A 4P H2/H1 790.3
4000A 3P H2/H 582.3
For 3200D/4000C/5000C/6300C 3P/4P 4000A 4P H2/H 790.3
592
10 Holes-Ø11 3P C 863
522 5000/6300A
25
5000/6300A 4P C 1132
Dimensions
Ratings CN-CS
A
A
3200D/4000C 711
3200D/4000C 913
5000C/6300C 913
25 5000C/6300C 1182
50
108.5
184.5
Hinge Hinge
224
412
450
199
1 5.5
Base of
Cradle
Terminals
10
15
15
308.5
221.5
800 - 1000C 1250 - 1600C/H 2000C 2500C/H
& 800/1000H & 2000H
2 Holes-Ø14 3 Holes-Ø14 4 Holes-Ø14 6 Holes-Ø14
12.5
20
12.5
15
25 25 25
16.5
33 33
160
100
50
63
25
16.5
12.5 25 12.5 30
12.5 25 12 43
Vertical Terminals
V S W
U 40
4 Holes-Ø T O P Top
R
M N
387.5
X
308.5
221.5
Ratings M N P Q R S T U V W X
400-1250 S1 & 800-1000 C 10.2 38 20 25 29.2 5 9 65 95 10 58.4
1600-2000 S1 & 1250-1600 C/H
20 40 20 25 29.2 5 9 65 95 10 80
800-1000 H
2000 C 20 40 20 40 29.2 22.5 14 80 110 15 80
2500 S1/ C/H
20 40 20 40 33.5 7.5 14 80 110 15 80
2000 H
3200 S1 30 60 20 40 33.5 7.5 14 105 100 15 120
Note : 1) All Dimensions are in mm. 2) Consult us for other Terminal Orientations. 32
OVERALL DIMENSIONS
Terminals
V S W
U 60.0
6 Holes - ØT Q P Top
M NN
R
387.5
X
308.5
221.5
The dimensions for 3200 H2/H1 and 4000 H2/H are as under:
Ratings M N P Q R S T U V W X
3200 H2/H1, 4000A H2/H 30 50 45 40 29.5 95 14 80 140 15 160
REGISTERED OFFICE AND Khairasol, Degaul Avenue EBG North Wing Office-Level 2
HEAD OFFICE Durgapur 713 212 Gate 7, Powai Campus
L&T House, Ballard Estate Tel: 2559848, 2559849, 2559844 Mumbai 400 072
P. O. Box 278 Fax: 0343-2553614 Tel: 022-67052874 / 2737 / 1156
Mumbai 400 001 e-mail: esp-dgp@LNTEBG.com Fax: 022-67051112
Tel: 022-67525656 e-mail: esp-bom@LNTEBG.com
Fax: 022-67525858 5, Milanpur Road, Bamuni Maidan
Website: www.Larsentoubro.com Guwahati 781 021 12, Shivaji Nagar
Tel: +91 8876554410 / 8876554417 North Ambajhari Road
ELECTRICAL STANDARD PRODUCTS (ESP) Fax: 361-2551308 Nagpur 440 010
501, Sakar Complex I e-mail: hazrasudipto@LNTEBG.com Tel: 0712-2260012 / 6606421
Opp. Gandhigram Rly. Station Fax: 2260030 / 6606434
Ashram Road II Floor, Vasantha Chambers e-mail: esp-nag@LNTEBG.com
Ahmedabad 380 009
5-10-173, Fateh Maidan Road
Tel: 079-66304006-11
Hyderabad 500 004 32, Shivaji Marg
Fax: 079-66304025
e-mail: esp-ahm@LNTEBG.com Tel: 040-67015052 P. O. Box 6223
Fax: 040-23296468 New Delhi 110 015
38, Cubbon Road, P. O. Box 5098 e-mail: esp-hyd@LNTEBG.com Tel: 011-41419514 / 5 / 6
Bangalore 560 001 Fax: 011-41419600
Tel: 080-25020100 / 25020324 Monarch Building, 1st Floor e-mail: esp-del@LNTEBG.com
Fax: 080-25580525 D-236 & 237, Amrapali Marg
e-mail: esp-blr@LNTEBG.com Vaishali Nagar L&T House
Jaipur 302 021 P. O. Box 119
131/1, Zone II Tel: 0141-4385914 to 18 191/1, Dhole Patil Road
Maharana Pratap Nagar Fax: 0141-4385925 Pune 411 001
Bhopal 462 011 e-mail: esp-jai@LNTEBG.com Tel: 020-66033395 / 66033279
Tel: 0755-3080511 / 05 / 08 / 13 / 17 / 19 Fax: 020-26164048 / 26164910
Fax: 0755-3080502 Akashdeep Plaza, 2nd Floor e-mail: esp-pnq@LNTEBG.com
e-mail: esp-bho@LNTEBG.com P. O. Golmuri
Jamshedpur 831 003 Crystal Tower,
Plot No. 559, Annapurna Complex Jharkhand 4th Floor, G. E. Road
Lewis Road Tel: 0657-2312205 / 38 Telibandha
Bhubaneswar 751 014 Fax: 0657-2341250 Raipur - 492 006
Tel: 0674-6451342, 2436690, 2436696 e-mail: esp-jam@LNTEBG.com Tel: 0771-4283214
Fax: 0674-2537309 e-mail: esp-raipur@LNTEBG.com
e-mail: nayakd@LNTEBG.com Skybright Bldg; M. G. Road
Ravipuram Junction, Ernakulam 3rd Floor
SCO 32, Sector 26-D Kochi 682 016 Vishwakarma Chambers
Madhya Marg, P. O. Box 14 Tel: 0484-4409420 / 4 / 5 / 7 Majura Gate, Ring Road
Chandigarh 160 019 Fax: 0484-4409426 Surat 395 002
Tel: 0172-4646840, 4646853
e-mail: esp-cok@LNTEBG.com Tel: 0261-2473726
Fax: 0172-4646802
e-mail: esp-chd@LNTEBG.com Fax: 0261-2477078
3-B, Shakespeare Sarani e-mail: esp-sur@LNTEBG.com
L&T Construction Campus Kolkata 700 071
TC-1 Building, II Floor Tel: 033-44002572 / 3 / 4 Radhadaya Complex
Mount-Poonamallee Road Fax: 033-22821025 / 7587 Old Padra Road
Manapakkam e-mail: esp-ccu@LNTEBG.com Near Charotar Society
Chennai 600 089 Vadodara 390 007
Tel: 044-2270 6800 A28, Indira Nagar, Faizabad Road Tel: 0265-6613610 / 1 / 2
Fax: 044-22706940 Lucknow 226 016 Fax: 0265-2336184
e-mail: esp-maa1@LNTEBG.com Tel: 0522-4929905 / 04 e-mail: esp-bar@LNTEBG.com
Fax: 0522-2311671
67, Appuswamy Road e-mail: esp-Lko@LNTEBG.com Door No. 49-38-14/3/2, 1st floor,
Post Bag 7156 NGGO's Colony, Akkayyapalem,
Opp. Nirmala College No: 73, Karpaga Nagar, 8th Street Vishakhapatnam - 530 016
Coimbatore 641 045 K. Pudur Phone: 0891 6581023
Tel: 0422-2588120 / 1 / 5 Madurai 625 007 e-mail: esp-viz@LNTEBG.com
Fax: 0422-2588148 Tel: 0452-2537404, 2521068
e-mail: esp-cbe@LNTEBG.com Fax: 0452-2537552
e-mail: esp-mdu@LNTEBG.com