XC22B PRESET COUNTER TERMINAL CONNECTIONS

SPECIFICATIONS
OPERATING INSTRUCTIONS Supply : 90 to 270V AC/DC, AC: 50/60 Hz. 1 2 3 4 5 6

Modes : On Delay / Interval. +12V COM PNP NPN RST

Accuracy : ± 1 Count (max error). 13 L 15

Sensor supply : 12 VDC, 30 mA (±10%) short circuit 14 N 16


protected. NO1 COM1 NC1 NO2 COM2 NC2
Reset : a) Front Panel Reset b) Remote Reset c) Auto 7 8 9 10 11 12
Reset (optional).
Output : 2 C/O relay rated 5A @ 230 VAC/24 VDC.
Memory retention : 30 Days (optional) TERMINAL DESCRIPTION
INTRODUCTION: XC22B is a single set point Input : 3-30 VDC from Proximity Switch, Encoder, 1 +12V (sensor supply positive).
preset counter. On application of input pulses, the 2 COM (sensor supply return).
Solid State Device, Mechanical Switch, Potential Free
counter counts up till the set point. The relay switches 3 Count input for PNP sensor.
Contact. 4 Count input for NPN sensor.
according to the mode of operation selected - On Delay
or Interval. These are user selectable using DIP
Max input frequency: a) Slow - 30Hz, b) Fast - 5kHz 5 Reset input.
switches provided on the instrument. The counter has an Temperature : 0 - 500c (operating temperature). 7-8-9 NO - COM - NC of relay 1
auto reset feature on request with variable auto reset Over all size : 72mm (H) X 72mm (W) X 125mm (D). 10-11-12 NO - COM - NC of relay 2
time (using the potentiometer on the front bezel). The Panel cutout : 68mm (H) x 68mm (W). 15 Live (supply)
front panel thumb-wheels set the count at which the 16 Neutral (supply)
Depth Behind Panel : 115mm.
relay operates. The current count value is retained in
absence of power for units with battery backup facility.

(Sensor color codes:- Red = +12V, Green = CNT, Black =


OPERATING MODES DIP SWITCH SETTINGS GND; Brown = +12V, Black = CNT, Blue = GND)
SET POINT (The DIP switch is at the side of the instrument)
ON DELAY EXTERNAL WIRING FOR PNP SENSOR
RELAY RESET COUNT 4 MODE PNP
2 3
INTERVAL 1 2 3 4 5 6
OFF ON OFF INTERVAL +12V COM PNP

RELAY RESET COUNT OFF OFF ON ON DELAY


short 2&4
ON ON OFF AUTO RESET INTERVAL
AUTORESET ON DELAY ON OFF ON AUTO RESET ON DELAY EXTERNAL WIRING FOR NPN SENSOR

RESET NPN
RELAY COUNT RESET COUNT
1 5
t OFF ON NON OVERRUN 1 2 3 4 5 6

t - user selectable (0.1-15 sec. max.) ON OFF OVERRUN +12V COM NPN

short 1&3
(Specifications subject to change as development is a continuous process). 6. ON - BATTERY CONNECTED TO CIRCUIT
OFF - BATTERY DISCONNECTED EXTERNAL WIRING FOR POTENTIAL FREE CONTACT
Selec Controls Pvt. Ltd., India,
(Formerly Selectron Process Controls Pvt. Ltd.) 7. ON - SLOW SPEED (30 Hz maximum) Potentia l free contact

Tel:91-22-28476443/1882, Fax:91-22-28471733, OFF - FAST SPEED (5 KHz maximum) +12V COM NPN RST
Website: www.selecindia.com 1 2 3 4 5 6
E- mail: sales@selecindia.com. Auto Reset Function and battery are optional features.
Document name: Operating/0607/XC22B/Ver2a OP010-V02a Their selection (as above) valid only when present. short 1&3 RST