KONGUNADU COLLEGE OF ENGINEERING AND TECHNOLOGY

(AUTONOMOUS)
NAMAKKAL- TRICHY MAIN ROAD, THOTTIAM, TRICHY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING
ASSIGNEMENT –III
EE8501 – POWER SYSTEM ANALYSIS

Answer all the Questions


Q.No. Questions CO
For the radial network shown in fig. 3-ph fault occurs at point F. determine the
fault current and the line voltage at 11.8kV bus under fault condition.

1. 3

A symmetrical fault occurs at bus 4 for the system shown in fig. Determine the
fault current using
(i) Thevenin’s Equivalent circuit
(ii)Z-Bus algorithm

2. 3

G1, G2: 100MVA, 20kV, X’’=15% T1, T2: Xleak=9% L1, L2:X’’=10%

A 3 phase salient pole synchronous generator is rated 30MVA, 11kV and has a
direct axis subtransient reactance of 0.25 p.u. the negative and zero sequence
reactances are 0.35 and 0.1 p.u respectively. The neutral of the generator is solidly
3. grounded. Calculate the subtransient current in the generator and line to line 4
voltages when
(i) L-G Fault (iii)L-L Fault
(ii) LL-G Fault occurs at the terminals of the generator.