Capacity : Ah
Total battery : Ea
Voltage/ battery :V
Overall voltage :V
Duration test (hour) :h
It=discharge current at t ° C
Discharge time 0°C 5°C 10°C 15°C 20°C 25°C 30°C 35°C 40°C
10 minutes to 0.58 0.68 0.79 0.91 1 1.05 1.09 1.12 1.14
59 minutes
1 hour to 24 0.81 0.86 0.91 0.96 1 1.03 1.05 1.06 1.07
hours
Measure the battery voltage and temperature of pilot cell every hour during
discharge test
After 12 hours, shut down the dummy load and switch off the breaker
Overall voltage of the battery should be greater than 104V (1V+104) after h hours
discharging
b. Battery recharging
Check the battery polarity and connect to the charger, make sure the breaker is
switch off
The charging mode used by floating charge. The current is limited to below 0.2CA (C
= battery capacity), the constant voltage is 3.35V/monomer, the charge time
depends on the depth of discharge, see table-2
Depth of discharge Constant-current Constant-voltage
Charge time (h)
(%) charge current charge voltage
0.1C 2.35 12
20
0.125C 2.35 10
0.1C 2.35 18
50
0.125C 2.35 16
0.1C 2.35 22
80
0.125C 2.35 20
0.1C 2.35 26
100
0.125C 2.35 24
CB commissioning
a. Simultaneity (synchronize) and close/open time
Take off the CB module and reverse the position of the contact finger to outside
Connect the control terminal to the panel
Put on the measurement cable on every phases
Start the breaker analyzer machine according to the close-open command
Analize the result on the computer, the result will be shown in numeric and graphic
Record also the cycle operating test open-close-open time
Record pole discrepancy each contact
b.