Bracketary Design For MEP Support at PSG Steel Roof - 150kg

Design Load:
P= 150 kg
= 150x9.81/1000
= 1.4715 kN

Load Factor = 1.4

R=V= 2.06 kN
Mmax = 0.13 kNm

Structural Check:
fb = M/Z Dimensions:
= 112 MPa L= 130 mm
< 275 MPa, OK a= 65 mm
b= 65 mm
fv = V/A
= 1.7 MPa Section and Material Properties:
< 159 MPa, OK t= 6 mm
Width = 200 mm
Deflection Check:
δmax = 0.46 mm A= 1200 mm2
δallowable = L/180 Z= 1200 mm3
= 0.72 mm, OK I= 3600 mm4
E= 205 GPa

Welding Check:
Induced Push Pull Force, T=C = M/X tw = 3 mm
= 1.34 kN min. X = 100 mm

fw = 1.34x1000 / (0.7x3x200)
= 3.19 N/mm2
< 220 MPa, OK
Bracketary Design For MEP Support at PSG Steel Roof - 250kg
Design Load:
P= 250 kg
= 250x9.81/1000
= 2.4525 kN

Load Factor = 1.4

R=V= 3.43 kN
Mmax = 0.22 kNm

Structural Check:
fb = M/Z Dimensions:
= 105 MPa L= 130 mm
< 275 MPa, OK a= 65 mm
b= 65 mm
fv = V/A
= 2.1 MPa Section and Material Properties:
< 159 MPa, OK t= 8 mm
Width = 200 mm
Deflection Check:
δmax = 0.32 mm A = 1600 mm2
δallowable = L/180 Z = 2133.33 mm3
= 0.72 mm, OK I = 8533 mm4
E= 205 GPa

Welding Check:
Induced Push Pull Force, T=C = M/X tw = 3 mm
= 2.23 kN min. X = 100 mm

fw = 2.23x1000 / (0.7x3x200)
= 5.31 N/mm2
< 220 MPa, OK
Bracketary Design For MEP Support at PSG Steel Roof - 350kg
Design Load:
P= 350 kg
= 350x9.81/1000
= 3.4335 kN

Load Factor = 1.4

R=V= 4.81 kN
Mmax = 0.31 kNm

Structural Check:
fb = M/Z Dimensions:
= 146 MPa L= 130 mm
< 275 MPa, OK a= 65 mm
b= 65 mm
fv = V/A
= 3.0 MPa Section and Material Properties:
< 159 MPa, OK t= 8 mm
Width = 200 mm
Deflection Check:
δmax = 0.45 mm A = 1600 mm2
δallowable = L/180 Z = 2133.33 mm3
= 0.72 mm, OK I = 8533 mm4
E= 205 GPa

Welding Check:
Induced Push Pull Force, T=C = M/X tw = 3 mm
= 3.12 kN min. X = 100 mm

fw = 3.12x1000 / (0.7x3x200)
= 7.44 N/mm2
< 220 MPa, OK
Bracketary Design For MEP Support at PSG Steel Roof - 450kg
Design Load:
P= 450 kg
= 450x9.81/1000
= 4.4145 kN

Load Factor = 1.4

R=V= 6.18 kN
Mmax = 0.40 kNm

Structural Check:
fb = M/Z Dimensions:
= 188 MPa L= 130 mm
< 275 MPa, OK a= 65 mm
b= 65 mm
fv = V/A
= 3.9 MPa Section and Material Properties:
< 159 MPa, OK t= 8 mm
Width = 200 mm
Deflection Check:
δmax = 0.58 mm A = 1600 mm2
δallowable = L/180 Z = 2133.33 mm3
= 0.72 mm, OK I = 8533 mm4
E= 205 GPa

Welding Check:
Induced Push Pull Force, T=C = M/X tw = 3 mm
= 4.02 kN min. X = 100 mm

fw = 4.02x1000 / (0.7x3x200)
= 9.56 N/mm2
< 220 MPa, OK
Bracketary Design For MEP Support at PSG Steel Roof - 550kg
Design Load:
P= 550 kg
= 550x9.81/1000
= 5.3955 kN

Load Factor = 1.4

R=V= 7.55 kN
Mmax = 0.49 kNm

Structural Check:
fb = M/Z Dimensions:
= 230 MPa L= 130 mm
< 275 MPa, OK a= 65 mm
b= 65 mm
fv = V/A
= 4.7 MPa Section and Material Properties:
< 159 MPa, OK t= 8 mm
Width = 200 mm
Deflection Check:
δmax = 0.71 mm A = 1600 mm2
δallowable = L/180 Z = 2133.33 mm3
= 0.72 mm, OK I = 8533 mm4
E= 205 GPa

Welding Check:
Induced Push Pull Force, T=C = M/X tw = 3 mm
= 4.91 kN min. X = 100 mm

fw = 4.91x1000 / (0.7x3x200)
= 11.69 N/mm2
< 220 MPa, OK