A27147

Release 4.4.9
sadia VG 3 ou 4

Munters ICA-750-020

Prepared for :
Date : 27/set/07

,
Prepared by : ANTONIO FABIO
Reference No. : Quote
System Flow Diagram

Altitude 0 ft

sala 3 ou 4
A B C D E F G
SCFM 883 883 883 1,766 1,766 1,766 1,766
°F 100 100 50 75 45 93 98
gr/lb 140.0 140.0 35.0 87.5 43.7 2.1 2.1
A27147

Release 4.4.9
sadia VG 3 ou 4
ICA-750-020
Altitude 0 ft

System Configuration Data

System Level Configuration Items:

Model No. ICA-0750-020

Internal Material Stainless Steel

External Material Galvalume

Wall Thickness 2.5 inch

Roof Flat - Indoor locations

Length Limit NONE

Access/Removal side * From the LEFT looking in the direction of air flow

Floor Drains No Floor Drains

Entering Air Connection Open

Leaving Air Connection End Discharge

System Power 460/3/60

System FLA 9.7

Component Options:

Component View Plenum Other


Name Port Light
Med. Eff Filter No No Side Loading

Mixing Box No No RA Connection on Non-Access Side

Cooling Coil No No None

Dehumidifier No No None

Fan No No None

* See the system drawing for further details on component access and removal.
A27147

Release 4.4.9
sadia VG 3 ou 4
ICA-750-020
Altitude 0 ft

Equipment Schedule
Air Filter
Media Type Panel
Filter Thickness in 2.0
Filter Efficiency % 30%
Filter Class UL 1
Face Velocity FPM 466
Initial Resistance ''WC 0.25
Final Resistance ''WC 0.90
Filter Sizes 1 @ 12 in x 24 in

Cooling Coil - Chilled Water with Ethylene Glycol


Entering Conditions °F / gr/lb 75 / 87.5
Leaving Conditions °F / gr/lb 45 / 43.7
Capacity Btuh 113,184
Air Flow SCFM 1,766
Face Area ft² 4.0
Face Velocity FPM 442
Air Resistance ''WC 0.62
Water Consumption GPM 23.8
Percent Glycol % 20
Fluid Resistance feet 11.5
Connection Size Sweat 1.5
Rows 8
Tubes .625 dia x .035 thk Copper
Fins 8 FPI, .0075 thk Aluminium
Case GalvanizedSteel

Dehumidifier Module
Type of Rotor Tigel
Entering Conditions °F / gr/lb 45 / 43.7
Leaving Conditions °F / gr/lb 93 / 2.1
Process Air Flow SCFM 1,766
By Pass Air Flow SCFM 0
Air Pressure Loss ''WC 1.54
Wheel Speed rph 8.00
Design Capacity lb/hr 47

Reactivation Air Heater - Steam


Entering Conditions °F / gr/lb 95 / 120.0
Leaving Conditions °F / gr/lb 295 / 120.0
Required Capacity Btuh 124,087
Power Consumption Btuh 48
Air Resistance ''WC 0.34
Rows 6
Steam Pressure psig 100.0
Steam Temperature °F 338
Steam Consumption lb/hr 141.0
Tube Material Copper
Fin Material Aluminium
Case Material Galvanized Steel
A27147

Release 4.4.9
sadia VG 3 ou 4
ICA-750-020
Altitude 0 ft

Equipment Schedule
Reactivation Air Fan
Model 12-1/4-7
Type BI-AF - SISW
Air Flow SCFM 574
Total Pressure ''WC 6.25
External Pressure ''WC 3.08
Design Temperature °F 148
Fan Speed RPM 3450
Motor Speed RPM 3450
Motor Power hp 3
Motor Enclosure TEFC
Motor Class Class B

Supply Air Fan


Model 13-1/2
Type BI-AF - SISW
Air Flow SCFM 1,766
Entering Conditions °F / gr/lb 93 / 2.1
Leaving Conditions °F / gr/lb 98 / 2.1
Total Pressure ''WC 8.78
External Pressure ''WC 5.52
Fan Speed RPM 3450
Fan Power hp 3.6
Motor Speed RPM 3450
Motor Power hp 5.0
Motor Enclosure TEFC
Motor Class Class B
Housing Construction Welded Alum.
Vibration Isolation None
A27147

Release 4.4.9
sadia VG 3 ou 4
ICA-750-020
Altitude 0 ft

Filter Specifications

Filter

COARSE FILTERS

1. Air is filtered through filters of 25% to 30% minimum efficiency with 90% to 92% arrestance minimum as rated by
ASHRAE Test Standard 52-76. Filters are disposable 2" deep, pleated disposable type with non-woven media held in
place by a welded wire grid. Filters are held in aluminum channels top and bottom with spacers and back-up plates to
minimize bypass. Filter channels are welded and sealed in place to eliminate air bypass.

FINE FILTERS

1. Air is filtered through 12 inch deep pleated disposable filter of efficiency show in the schedule. All filters are
constructed of a non-woven media held in a rigid frame with welded wire support grid. The 12 inch deep filter also contains
contour supports and is held in a specifically designed rigid frame using spring type clamping fasteners. Filter mounting
partitions are welded and sealed in place to eliminate air bypass.

INITIAL DUST SPOT E0 <= 20 % E0 20 => %


EFFICIENCY (E0) Average Average
Type Of Filter Arrestance AM % Efficiency Em% EN 779 EUROVENT 4/5 ASHRAE
----------------------------------------------------------------------------------------------------------------------------------------------------------------
Coarse Filter (Panel) Am < 65 ---------- G1 EU 1 G 60
Coarse Filter (Panel) 65 <= Am < 80 ---------- G2 EU 2 G 70
Coarse Filter (Panel) 80 <= Am < 90 ---------- G3 EU 3 G 85
Coarse Filter (Panel) 90 <= Am - - - ---------- G4 EU 4 G 90
Fine Filter (Bag) -------- 40 <= Em < 60 F5 EU 5 F 45
Fine Filter (Bag) -------- 60 <= Em < 80 F6 EU 6 F 65
Fine Filter (Bag) -------- 80 <= Em < 90 F7 EU 7 F 85
Fine Filter (Bag) -------- 90 <= Em < 95 F8 EU 8 F 95
Fine Filter (Bag) -------- 95 <= Em - - F9 EU 9 F 95
A27147

Release 4.4.9
sadia VG 3 ou 4
ICA-750-020
Altitude 0 ft

Cooling Coil

Outlet

1,766 SCFM 1,766 SCFM

75 °F 45 °F

87.5 gr/lb 43.7 gr/lb

Inlet

Performance Data:

Air Side Capacity Sensible 58,808 Btuh


Latent 54,376 Btuh
Total 113,184 Btuh

Face Velocity 442 FPM Pressure Loss 0.62 ''WC

Coolant Flow Rate 23.8 GPM Tube Velocity 3.6 FPS


Entering 34 °F Leaving 44 °F
Pressure Loss 11.5 feet

Physical Data:
Dimensions 24.0 in FH 24.0 in FL 4.0 ft²
8 Rows 8.0 fpi 0.625 in Tubes
Copper Tubes 0.625 in Diameter 0.035 in wall
Aluminum Fins 0.0075 in Thick Corrugated Fins
Galvanized Casing
1.5 Conn. Size Circuiting 1/2 Serpentine
(MPT)
A27147

Release 4.4.9
sadia VG 3 ou 4
ICA-750-020
Altitude 0 ft

Cooling Coil Specifications


CHILLED WATER COOLING COILS

1. Coils shall be sized to provide the full capacity scheduled. Coils shall be arranged to condition the full volume of
process air with bypass or balancing dampers as required. Tube water velocities are 7 fps or less and air face velocities
are 500 fpm or less. Coil circuiting provides for optimum performance with minimum pressure loss. Coil shall be designed
for 250 PSI working pressure and factory tested under water at 300-PSI air pressure.

2. Chilled water coils are fin and tube type, constructed of seamless copper tubes of .625 inch diameter with .035
inch wall thickness and aluminum plate type fins of .0075 inch thickness, mechanically bonded to tubes. Casing and tube
support sheets are 16 gauge galvanized steel formed to provide mounting flanges and structural support for the finned-tube
assembly. Supply and return headers are heavy wall copper pipe with vent and drain connections. Supply and return
connections are brazed in place with sweat connections for piping. Coils conform to ARI standard 410.

3. Chilled water coils shall be equipped with a drain pan for removal of condensate and to collect and remove coolant
in case of leaks. The drain pan is to be constructed of welded 304 SS and bolted in place. Cooling coil drain pans shall
extend the entire length of the coil and shall extend a minimum of 6 inches beyond the air leaving side of the coil. The drain
pan shall be a minimum of 2 inches deep and have a minimum pitch of 1 inch. The drain pan shall be triple sloped to ensure
zero standing water. Drain connection shall extend through unit base. Connection to be 1 inch male NPT.
A27147

Release 4.4.9
sadia VG 3 ou 4
ICA-750-020
Altitude 0 ft

Dehumidifier

Reactivation Outlet Reactivation Reactivation Inlet


Ext. Pressure
574 SCFM
3.08 ''WC
148 °F 1.88 295 °F 95 °F
Pressure Loss
3.18 ''WC 248.1gr/lb ''WC 120 gr/lb

Tigel

Process Inlet Process Outlet


1,766 SCFM 1,766 SCFM
1.24
45 °F ''WC 93 °F
43.7 gr/lb 2.1 gr/lb
Process

Dehumidifier Module
Type of Rotor Tigel
Power Source 460/3/60
Full Load Amps ampere 3.8
Design Capacity lb/hr 47
Reactivation Air Heater
Required Capacity Btuh 124,087
Rows 6
Steam Pressure psig 100.0
Steam Temperature °F 338
React Filter Type Metal Mesh Filter
Reactivation Air Fan
Model 12-1/4-7
Type BI-AF - SISW
Design Temperature °F 148
Fan Speed RPM 3450
Motor Speed RPM 3450
Motor Power hp 3
Motor Enclosure TEFC
Motor Class Class B
A27147

Release 4.4.9
sadia VG 3 ou 4
ICA-750-020
Altitude 0 ft

Dehumidifier Specifications

Dehumidifier Steam Reactivation Heater


1. Steam heaters are of a stainless steel weld constrution provididing a wide range of operating pressure upto 24 Bar /
224°C dry saturated steam. Connection to the coil is with carbon steel flanges.

2. [OPTION] Test Certificates can be provided only upon request at the time of ordering. Testing is carried out with 30 Bar
air under water at 20°C.

3. [OPTION] Control Valves can be provided. These are typically a 3-way cast steel valve controlled by a electric
modulating assembly.

Reactivation Fan Specification


1. Reactivation air fans are typically single inlet, single width, Centrifugal type direct driven. Fan housing material is of
galvanised steel painted to a thickness of 120 microns. Flexible inlet and outlet connections ensure a minimium level of
direct transmited sound and vibration. The fan assembly is mounted on rubber type anti-vibration mounts.

2. Fans are balanced dynamically to minimum quality level of Q=6.3 positioned over the shaft.
A27147

Release 4.4.9
sadia VG 3 ou 4
ICA-750-020
Altitude 0 ft

Supply Air Fan


Description:
Fan: Motor and Drive:
Size: 13-1/2 Motor Power 5.0 hp
Type: SISW BI-AF Motor Speed 3450 rpm
Fan Speed: 3450 Drive Type Direct Drive
Rotation: CW
Vibration Isolation: None

Performance:
Component Initial Final
Med Eff Panel Filter .25 .90
Mixing Box .20 .20
Cooling Coil .62 .62
Dehumidifier 1.54 1.54
Total 2.61 3.26

External Static 6.17 5.52


Pressure

Fan Performance @ 93 °F
Design Point
9.0

8.0

7.0
Static Pressure ''WC

6.0

5.0

4.0

3.0
System
Final
2.0

1.0

1000 2000 3000 4000 5000


Air Flow - CFM