9.3.2 Button Functions
• ON: Switches on the compressor.
a03 A01 A03 A04 S. • OFF: Switches off the compressor.
• RESET: Resets alarms and displays hour
meter.
SM 1588 9.3.3 Indicator Functions
• x10 LED (green): indicates that the 10
Fig. 9.1 - AirBASIC Control Panel
multiplying factor is active.
1. LCD Display (3 Digits/7 Segments)
• x100 LED (green): indicates that the 100
2. LED Status Indicators (3 Green)
multiplying factor is active.
3. Control Pushbuttons (3)
• LED (green), steadily on: indicates load
The Control Panel is mounted on the operation mode.
compressor. It is used to operate the
compressor and observe system status using • LED (green), flashing: indicates unload
the LCD display, LED status indicators and operation mode.
buttons.
The Control Panel displays a comprehensive
9.4 Compressor Operation with the
overview of the compressor status and allows AirBASIC Controller
access to operational parameters such as 9.4.1 Starting The Compressor
alarm set points.
The starting procedure depends on the
current status of the compressor.
a) Starting the compressor in “OFF” status
DL105AA 41
9 AirBASIC Electronic Controller CompAir
The “OFF” message on the controller display When the compressor is started (either locally
indicates that the compressor is properly via the ON button or from a remote location),
powered, waiting to be started, and that the the controller performs a number of checks at
last switch-off was caused by pressing the the inputs to make sure that there are no
“OFF” push button on the controller (local conditions likely to pose hazards to the
switch-off). machine and/or the operators.
To start the compressor, use local controls, If abnormalities are found, the compressor
that is, press the “ON” button on the control start-up is inhibited and an error message
unit. appears on the controller display. If no
abnormality is found, the compressor is
Note: In this condition, opening and closing
allowed to start.
the remote contact will produce no effect
whatsoever. When start-up is initialised (and no alarms are
active), the controller checks the status of the
b) Starting the compressor in “---” status
line pressure switch contact. If the pressure
The “---” message on the controller display switch contact is closed, the motor is started
indicates that the compressor is properly according to the star/delta start-up sequence.
powered, waiting to be started, and that the If the pressure switch contact is open
remote START/STOP contact is in the OPEN (pressure in the network ), the compressor
position (STOP position). goes into stand-by mode and the motor is not
started until the network pressure drops to the
To start the compressor, use the relevant
load value level.
procedure described below, depending on
how the last switchoff occurred. When the load value level is reached, the
pressure switch contact closes. The relay
- If the compressor was running (no matter
outputs relating to the line and star contactors
whether loaded, unloaded or in stand-by) and
are energised for the equivalent of the star
was then switched off remotely, the “---”
time (parameter P06 - default 5 s). When the
message appears. To restart the compressor,
star time has elapsed, the controller switches
close the remote contact again.
from star to delta with a ‘safety’ delay (applied
- If the compressor was switched off locally, between the release of the star contactor and
that is, by pressing the OFF button on the the coming into operation of the delta
controller, and the remote contact was then contactor). This delay is equivalent to the time
opened AFTER the switch-off, the “---” value set up on the star/delta switching timer
message appears. (parameter P07 - default 20 ms). When the
switching timer has elapsed, the outputs
1. To restart the compressor, close the remote relating to the line and delta contactors are
contact. energised.
2. Press the ON button on the controller. In order to stabilise the motor’s rotation
This feature allows the operation of the speed, the load solenoid valve is energised
compressor to be disabled from a remote with a delay that is equivalent to the time
position in order to prevent unauthorised value set up on the “launch timer” parameter
personnel from starting the compressor with (parameter P08 - default 2s). The delay is in
the push buttons on the controller. relation to the closure of the delta contactor.
Once the solenoid valve has been energised,
Warning: If the remote control feature is to the compressor enters into load-operation
be used with the START/STOP contact stage.
connected to the controller, it is strongly
advisable to affix a sign by the machine 9.4.2 Controlling The Compressor Load/Unload
warning that the compressor may be Operation
started at any time from a remote location.
When the compressor is on load, the LED
Note: Machine start and machine restart on the right hand side of the display lights
operations can be performed via a control steadily. When the pressure reaches the set
device other than the one provided, as long as value of the pressure switch, the pressure
this does not pose any hazards. switch contact opens and the compressor
switches to unload operation for a period of
c) Compressor Start-up Process
time that is equivalent to the time value set up
42 DL105AA
CompAir AirBASIC Electronic Controller 9
on the “unload time” timer (parameter P09 - 9.4.3 Switching Off The Compressor
default 3 min).
The compressor can be switched off locally or
During the unload phase, the LED flashes remotely (if a remote contact is connected to
to indicate that the compressor is running in the appropriate terminals). In both cases,
unload mode. When the timer has elapsed, when the machine is commanded OFF, the
the motor is stopped. As soon as the pressure controller de-energises all the relay outputs
drops to the load value that is set up on the controlling the contactors as well as the
pressure switch, the motor is restarted solenoid valve, thereby causing the
automatically via a star/delta sequence. When compressor to stop immediately.
the motor is stopped, the LED is turned off The control unit activates a safety (“blowdown
and if no alarms are active, the value of the oil time”) timer (parameter P10 - default 20 s) to
temperature appears on the display. prevent the compressor from restarting with
If the pressure drops to the load value level pressure in the inner tank when the OFF
before the unload timer has elapsed, the button is pressed (or when the remote
compressor immediately switches back to start/stop contact is opened). Compressor
load mode without any stopping of the motor. restart is inhibited throughout the count down
When the “Unload time” timer elapses, the of the blowdown time. Pressing the ON button
motor stops. The oil temperature remains or closing back the remote start/stop contact
steady on the display to indicate that the during blow-down produces no effect
machine is not OFF but is still in stand-by whatsoever.
condition. The blow-down stage is indicated by the
Warning: Be very careful, as in this flashing of LED x10. When the count down of
condition, the compressor will restart the “blow-down time” is over, LED x10 is
without prior notice as soon as the turned off. At that point, you can restart the
pressure drops to the load value level. compressor.
See fig. 9.2 for an example of the operating
cycle.
Motor running
pressure
Network pressure
Unload pressure
Load pressure
LOAD LOAD
START
UNLOAD TIME
Motor running
Motor OFF
SM 1575 time
DL105AA 43
9 AirBASIC Electronic Controller CompAir
44 DL105AA
CompAir AirBASIC Electronic Controller 9
DL105AA 45
9 AirBASIC Electronic Controller CompAir
46 DL105AA
CompAir AirBASIC Electronic Controller 9
DL105AA 47
9 AirBASIC Electronic Controller CompAir
48 DL105AA
CompAir AirBASIC Electronic Controller 9
Fig. 9.4 - Wiring Diagram
Input
Pin Function Status
connector
M1 power supply connector 24 Vac
M2 digital input connector, type: 5 poles Combicon 5 mm
C3 1 Common digital inputs
l1 2 Line pressure switch Closed=loaded Open=unloaded
l2 3 Motor thermal relay Alarm if open
l3 4 Phase-sequence relay Alarm if open
l4 5 Remote Start/Stop Closed=start Open=stop
M3 alarm relay connector, type: 2 poles Combicon 5 mm
C2 1 Common relay
R 2 Auxiliary alarm relay Energised=closed De-energised=open
M4 output relay connector, type: 5 poles Combicon 5 mm
C1 1 Common relay
K1 2 Line contactor Energised=closed De-energised=open
K2 3 Star contactor Energised=closed De-energised=open
K3 4 Delta contactor Energised=closed De-energised=open
EV 5 Solenoid valve Energised=closed De-energised=open
M5 temperature probe connector, type: screw terminals welded on the I.C.
1 Temperature probe
2 Temperature probe