Professional Documents
Culture Documents
ENGINEERING CONSULTING
BUREAU
SOIL INVESTIGATION
REPORT
May 2002
CONTENTS
1. INTRODUCTION.
1.1. Authorization.
2. FIELD EXPLORATION.
2.2. Sampling.
3. LABORATORY TESTING.
4. SOIL CONDITION.
5. CONCLUSIONS.
6. RECOMMENDATIONS.
7. APPENDEX.
1. INTRODUCTION:
1.1. AUTHORIZATION:
2.2 SAMPLING:
Undisturbed soil blocks were taken from the pits in addition to
the disturbed soil samples. All these samples were wrapped,
sealed tightly in plastic bags, labeled and transported to the soil
mechanics laboratory, Engineering College, University of Tikrit
to perform the required tests.
3. LABORATORY TESTING:
The obtained samples were tested according to the procedure
of the American Society for Testing and Materials (ASTM) or
the British Standards (BS) whichever is appropriate. The test
program of the samples includes the followings:
4. SOIL CONDITION:
Depending on the results of the laboratory tests and the field
observations, the soil condition at the proposed location can be
summarized as follows:
ㄱ The upper 1.0m of the soil is almost silty sand and gravel
It also contains some organic matters and crystals of
gypsum. This layer has insignificant effects on the
foundations because the depth of foundations is usually
greater than the thickness of this layer.
ㄱ The most important layer is that located below the
foundations and most of the laboratory tests carried on
representative samples obtained from this layer. The
results indicate that this layer is poorly graded gravel with a
mixture of sand and silt. The gypsum content is about 24%
while the total soluble salts is slightly greater than 28%.
ㄱ From the values of strength parameters an estimated
value for the ِallowable bearing capacity of about 100 kN/m 2
(10 ton/m2) can be proposed.
ㄱ The value of the compression index (Cc) indicates that the
expected settlement of the foundation will be the control
factor for the foundation design and must be within
acceptable limits.
5. CONCLUSIONS:
ㄱ It can be concluded that the upper 1.0 m of the soil is not
suitable to be a bearing layer because of the significant
amount of soluble salts and organic materials.
ㄱ Below 1.5m depth the soil is more suitable for placing the
building foundations. The existence of high amount of
soluble salts (about 28%) makes it necessary to account for
some precautions regarding preventing the water from
reaching relevant depths.
ㄱ No signs were indicated regarding the depth of ground
water table which is expected to be countered at relatively
greater depths in this region.
6. RECOMMENDATIONS:
The following recommendations can be presented:
1. Considering the nature of the building and the soil condition, the
suggested foundation of the building is continuous wall footing.
2. The depth of excavated soil for placing the foundation is
recommended to be about 1.5 m. Not less than 0.50 m thick
compacted sub-base to be placed below the footing.
3. The footing width should not be less than 1.0 m.
4. The external walkways are recommended to be not less than 2.0m
wide. Sulphate resisting cement plus adequate protective coating
is recommended to be used in the foundation concrete which must
be reinforced.
Amera I. Hussian Rafi’ M. Sulaiman Dr. Ala’ N. Al-Jorany
Asst. Prof. Asst. Prof. Asst. Prof.
Geologist Soil Mech. & Found. Eng. Soil Mech. & Found. Eng
Univ. of Tikrit Univ. of Tikrit Univ. of Tikrit