You are on page 1of 132

 PART 5      STRUCTURAL LOADS AND DESIGN 

 
TABLE OF CONTENTS 
 

SECTION            

 5.1     SCOPE                                                                                                                                2 

 5.2     DEFINITIONS                                                                                                                    2 

 5.3    DESIGN REQUIREMENTS                                                                   …………………       3 

 5.4    DESIGN LOADS AND EFFECTS                                                                  ……………      6 

5.5    LIMIT STATE DESIGN                                                                    …………………………    7  

 5.6    DEAD LOADS                                                                     …………………………………….14 

 5.7    LIVE (IMPOSED) LOADS DUE TO USE AND OCCUPANCY                                   .…14  

 5.8    DYNAMIC LOADING                                                                   …………………………..19  

 5.9  EFFECTS OF WIND                                                                  ………………………………..21   

 5.10  EFFECTS OF EARTHQUAKE                                                                  …………………..58 

APPENDIX A                                                               ……………………………………………     …127 

   

 
 
 
 
 
 
 
 
 
 
 

 
PART 5      STRUCTURAL LOADS AND PROCEDURES 
 
5.1   SCOPE 
5.1.1  This  section  covers  all  dead  loads  and  imposed  loads  which  shall  be 
sustained and transmitted by a building and certain structures without exceeding 
the stress limitations specified elsewhere in the Code. It applies to:  
 
(1) new buildings and new structures;  
(2) alterations and additions to existing buildings and structures; 
(3) existing constructions on change of use.  
 
5.1.2 This part of the code does not cover  
(1) loads on roads and rail bridges;  
(2) loads on structures subject to internal pressure from contents,(e.g. bunkers 
silos and water tanks) which should be calculated individually;  
(3) loads due to machinery vibration, except those due to some gantry cranes; 
(4) loads due to lifts; 
(5) loads incidental to construction;  
(6) test loads.  
These loads are covered by specialized (proprietory) documents produced by manufacturers. 
 
5.2  DEFINITIONS 
5.2.1  Unless  otherwise  specified  the  following  definitions  shall  apply  for  the 
purposes of this part of the Code.  
 
Dead  Loads:  The  force  due  to  the  static  weight  of  all  permanent  structural  and 
non‐structural  components  of  a  building,  such  as  walls,  partitions,  floors, 
roofs, fixed service equipment and all other permanent construction.  
 
Live  (Imposed)  Loads:  The  load  assumed  to  be  produced  by  the  intended 
occupancy  or  use  including  distributed,  concentrated,  impact,  inertia  forces  but 
excluding wind and earthquake loads.  
Wind Loads: All loads due to the effect of wind, pressure or suction.  

 
Earthquake Loads: All loads due to the effect of earthquake.  
 
5.3  DESIGN REQUIREMENTS 
5.3.1  (1)      Buildings  and  their  structural  members  including  formwork  and 
falsework  shall  be  designed  to  have  sufficient  structural  capacity  to  resist  safely 
and effectively all loads and effects of loads and influences that may reasonably 
be expected, having regard to the expected service life of buildings.  
 
5.3.1(2)  All  permanent  and  temporary  structural  members,  including  formwork 
and  falsework  of  a  building,  shall    be  protected  against  loads  exceeding  the 
design loads during the construction period except when, as verified by analysis 
or  test,  temporary  overloading  of  a  structural  member  would  result  in  no 
impairment of that member or any other member. In addition, precautions shall 
be  taken  during  all  stages  of    construction  to  ensure  that  the  building  is  not  
damaged or distorted due to loads applied during construction. 
 
5.3.2   Design Basis 
Buildings and their structural members shall be designed by one of the following 
methods:  
(1) analysis based on well‐established principles of mechanics ; 
(2)  evaluation of a given full‐scale structure or a prototype    
     by a loading test; 
(3) Studies of model analogues (modeling). 
       
5.3.3   Deflections 
(1) Structural  members  shall  be  designed  so  that  their  deflections  under 
expected service loads will be acceptable with regard to:  
(a) the intended use of building or member;  
(b) possible damage to non‐structural members and materials;  
(c) possible  damage  to  the  structure  itself  and,  where  significant,  the  
additional effects of loads acting on the deformed structure. 
 
(2) Deflections listed in clause 5.3.3(1) shall be taken into account in all structures 
and  structural  members  made  of  material  susceptible  to  deflections, 

 
deformations or changes in load distribution due to creep, shrinkage or other 
effects in the materials of which they are composed.  
 
(3) The lateral deflection of buildings due to design wind and gravity loads shall 
be checked to ensure that non‐structural elements, whose nature is known 
at the time the structural design is carried out, will not be damaged. Except 
as provided in Clause 5.3.3(4) and unless otherwise approved, the total drift 
per storey under design wind and gravity loads shall not exceed 1/500 of the 
storey height.  
 

(4) The deflection limits required in Clause 5.3.3(3) does not apply to industrial 
buildings  or  sheds  if  it  is  known  by  experience  that  greater  movement  is 
acceptable.  
 
5.3.4   Vibrations of Floors  
(1) Special  considerations  shall  be  given  to  floor  systems  susceptible  to 
vibration  to  ensure  that  such  vibration  is  acceptable  for  the  intended 
occupancy of the building.  
 
(2) Lateral  Deflections  of  Tall  Buildings:  Unusually  flexible  buildings  and 
buildings whose ratio of height to minimum effective width exceeds 4 to 1 
shall  be  investigated  for  lateral  vibrations  under  dynamic  wind  loading. 
Lateral  accelerations  of  the  building  shall  be  checked  to  ensure  that  such 
accelerations are acceptable to the intended occupancy of the building. 
 

(3) Stability  under  Compressive  stress:  Provision  shall  be  made  to  ensure 
adequate stability of a structure as a whole, and adequate lateral, torsional 
and  local  stability  of  all  structural  parts  which  may  be  subject  to 
compressive stress.  
 
5.3.5  Design drawings and Calculations  
(1)  Structural  drawings  submitted  with  the  application  to  build  shall  bear  the 
signature of the designer. 

 
(2) Drawings submitted with the application to build shall indicate in addition to 
those items specified elsewhere in other sections of Part 5, applicable to a specific 
material:   
 
   (a)  the  name  and  address  of  persons  responsible  for  the  structural             
  design;  
   (b) the code or standard to which the design conforms; 
   (c)  the dimensions, location and size of all structural members in   sufficient  
  detail to enable the design to be checked; 
   (d)  sufficient detail to enable the loads due to materials  of        
  construction incorporated in the building to be determined;    
   (e)  all intended uses and occupancies;  
   (f)    all  effects  and  loads,  other  than  dead  loads  used  in  the  design  of 
  structural members. 
 
(3)  The calculations and analysis made in the design of the structural  members, including parts and 
components of a building shall be  available upon request for inspection by the authority having     
      jurisdiction. 
(4) Structural  integrity:  Buildings  and  structural  systems  shall  provide  such  structural  integrity, 
strength  or  other  defenses  that  the  hazards  associated  with  progressive  collapse  due  to  local 
failure  caused by severe  overloads  or  abnormal  events not specifically covered in this  section 
are reduced to a level commensurate with good engineering practice. 
 
5.3.6   Inspection of Construction 
(1) Inspection  of  the  construction  of  any  building  or  part  thereof  shall  be  carried  out  by  the 
designer, or by another suitably qualified person responsible to the designer, to ensure that 
the construction conforms with the design. 
(2) The  designer  or  another  suitably  qualified  person  familiar  with  the  design  concept  and 
responsible to the  designer,  shall review  all  shop  drawings  and  other  drawings relevant to 
the design to ensure conformance to the design. 
(3) Workmanship and Materials: Workmanship and materials shall be inspected and all reports 
of  material  tests  shall  be  reviewed  by  the  designer  or  another  suitably  qualified  person 
responsible to the designer during the process of construction. 

 
(4) Off‐site  inspections:  Where  a  building  or  a  component  of  a  building  is  assembled  off  the 
building  site,  in  a manner that  it  cannot be  inspected on  site,  approved  off‐site  inspection 
shall  be provided when required by the authority having jurisdiction to ensure compliance 
with this Code. 
(5) Inspection Reports: Copies of all inspection reports shall be made available by the designer 
upon request to the authority having jurisdiction. 
 

5.4  DESIGN LOADS AND EFFECTS 
5.4.1 (1) Except as provided for in Clause 5.4.2, the following characteristic loads, forces and effects 
shall  be  considered  in  the  design  of  a  building  and  its  structural  members  and 
connections: 
GK –     Dead  load:  Is  the  self‐weight  of  the  structure  and  the  weight  of  finishes,  ceilings,  services   
  and  partitions  (see  BS  6399:  Part  1,  Loadings  for  buildings.  Code  of  practice  for  dead  and 
  imposed loads) and Appendix A. 
QK–   Live (or Imposed or Variable) load: Due to intended use and occupancy (include loads due 
to  movable  partitions  and  vertical  loads  due  to  cranes)  and  rain  (see  BS  6399:Part1  and 
Table 5.6). 
WK–   Wind  load:  Depends  on  the  location,  shape  and  dimension  of  the  buildings  (see  BS  6399: 
  Part 2, Loadings for buildings: Code of practice for wind loads) and Section 5.9 of this Part. 
En ‐        Nominal earth loads:   Earth and hydrostatic pressure, surcharge, horizontal components of 
  static or inertia forces (see BS 8004: Code of practice for Foundations). 
E   –       Earthquake load (See Section 5.10 of this Part) 
T  –      Contraction  or  expansion  due  to  temperature  changes,  shrinkage,  moisture 
changes,  creep  in  component  materials,  movement  due  to  differential 
settlement or combination thereof. 
 

 
5.4.2 (1) Where a building or structural member can be expected to be  
          subjected to loads, forces or other effects not listed in Clause 5.4.1(1);  
             such effects shall be taken into account in the design based on the most  
                appropriate information available. 
           (2)  If it can be shown by engineering principles or if it is known from  
            experience, that neglect of some or all the effects due to T do not 
            affect the structural safety and serviceability, they need not be  
            considered in the calculations.  
5.4.3  Structural  design  shall  be  carried  out  in  accordance  with  Section  5.5  ‘Limit 
State Design’.  
 
5.5   LIMIT STATE DESIGN 
5.5.1 (1)  In this section the term Limit State means those conditions of a building structure 
         in which the building ceases to fulfill the function or to satisfy the conditions for which  
         it was designed. 
         Limit State Design admits that a structure can become unsatisfactory in various ways,  
         all of which need to be considered against defined limits of acceptability.  
         By providing sufficient margins of safety against inherent variability in loading (actions),  
        material properties, environmental conditions, design methods and construction  
        practices, limit state design aims at giving an acceptable probability that the structure 
        will perform satisfactorily during its intended working life. 
 
      The limit states can be placed in two categories: 
    (a) Ultimate limit states, which are those corresponding to maximum load‐carrying 
         capacity  and safety of people and the structure e.g. 
(i)  Loss of equilibrium (overturning) of part or the whole of the structure when    
          considered as a rigid body. 
 
(ii)  Rupture of critical sections of the structure. 
 
(iii)  Transformation of structure into a mechanism.  
 
(iv)  Failure through excessive deformation. 
 
(v)  Deterioration arising out of fatigue effects. 
 

(b) Serviceability  limit  states,  which  are  related  to  the  criteria  governing  normal  use  or 

 
durability e.g.  
(i) Excessive deformations with respect to normal use of structure. 
(ii)  Premature or excessive cracking.  
(iii) Undesirable damage (corrosion).  
(iv)  Excessive displacement without loss of equilibrium.  
(v) Excessive vibrations. 
(vi) The comfort of people. 
(vii) The appearance of the structure. 
 
(2) Characteristic loads (GK, QK, WK, En, E, T ) means those loads defined in Clause 5.4.1. 
(3)  Partial safety factors to the value of loads (γf), used in design in section 5.5.2 that takes account 
         of the possibility of unfavourable deviations of the action values, uncertainties in modeling the 
        effects of actions, and the significance of the particular limit state. 
(4) Partial safety factors to the values of material properties (γm) used in design. This makes 
 allowances  for  sub‐standard  materials  or  for  the  deterioration  of  materials  during  the  life  of 
the    structure. 
(5) Action combination factor, ψ, which for imposed (variable) loads, are used in multiplying  
  characteristic  values  to  obtain  representative  values.  The  use  of  factors  ψ  reduce  the  design 
values of more than one variable load when they act together (see Table 5.3). 
(6) For imposed (variable) loads, under Eurocode (see 5.3): 
          representative values = characteristic value  x  ψ 
(7) In most cases, the design value of an action ( load combination) can be expressed as: 
         design value = representative value x  γf 
 

5.5.2        Methods of Limit State Design 
5.5.2.1     Ghana, British System GS( BS 8110: Part 1) 
5.5.2.1.1     Required Strength for Ultimate Limit State 
 (1) The required strength R provided to resist dead load GK and imposed  load QK shall  be at least 
equal to:  
R = 1.4GK + 1.6QK                                        ……… (5‐1) 
 
(2) In the design of a structure or member, if resistance to the structural effects of a specified wind 
load WK, must be included in the design the following combinations of GK, QK and WK shall be 
investigated in determining the greatest required strength R. 

 
R = 1.2GK + 1.2QK + 1.2WK                  ……… (5‐2) 
where the cases of QK having its full value or being completely absent shall both be checked to 
determine the most severe condition using 
R = 0.9GK + 1.4WK                                    ……… (5‐3) 
In any case, the strength of the member or structure shall not be less than required by Eq. (5‐1). 
 
(3)  If  resistance  to  specified  earthquake  loads  or  forces  E  must  be  included  in  the  design,  refer  to 
Section 5.10 of this Part on Effects of Earthquake. 
 
(4)  If  lateral  earth  pressure  H  must  be  included  in  design  the  strength  R  shall  be  at  least  equal  to 
1.4GK  +  1.6QK  +  1.6H  but  where  GK  or  QK  reduce  the  effect  of  H  (i.e.  favourable),  the 
corresponding  coefficients  shall  be  taken  as  0.90  for  GK  and  zero  for  QK  i.e.  the  governing 
equations are: 
R = 1.4GK + 1.6QK + 1.6H 
R = 0.9GK + 1.6H  
R = 1.4GK + 1.6QK  
 
(6) For lateral loads F due to liquids, the provisions for Clause 5.5.2.1.1(4) shall apply, except 
  that  1.4F  shall  be  substituted  for  1.6H.  The  vertical  pressure  of  liquids  shall  be  considered  as 
dead load, with due regard to variation in liquid depth. 
 
(6) Where the structural effects of differential settlement, creep, shrinkage or temperature T may be 
significant the governing equation shall be 
R = 1.2GK + 1.2QK + 1.2T 
The above actions are summarized in Table 5.1 
 
 
 
 
 
 
 
 
 

 
Table 5.1 – Load combinations for Ultimate Limit State 
Load  Load Type 
Combination  Dead Load  Imposed Load Earth and  Wind 
  Adverse  Beneficial  Adverse  Beneficial  Water 
pressure 
1.Dead and Imposed 
(and earth and water  1.4  1.0  1.6  0  1.4  ‐ 
pressure) 
2.Dead and Wind 
(and earth and water  1.4  1.0  ‐  ‐  1.4  1.4 
pressure) 
3.  Dead,  Wind  and 
Imposed  (and  earth  1.2  1.2  1.2  1.2  1.2  1.2 
and water pressure) 
 
 
5.5.2.1.2  Values for a Serviceability Limit State  
A  building  and  its  structural  components  shall  be  checked  for  serviceability  limit 
states as defined in Clause 5.5.1(b). Where more than one load contributes to the 
stress in the member the combination of loads shall be assumed to be: 
 
GK + ψ ((QK + (E or WK) + T)) 
 
Where ψ shall be equal to: 
(a) 1.0 when only one of the loads QK, (E or WK) and T act;  
(b) 0.70 when two of the loads QK, (E or WK) and T act;  
(c) 0.60 when all of the loads QK, (E or WK) and T act. 
 
5.5.2.2    Eurocode System GS (BS EN 1990, 1991, 1992) 
One of the main differences between the Eurocodes and the British/Ghanaian system is the use of 
different partial safety factors and the option to refine/reduce load factors when different load cases 
are combined. 
5.5.2.2.1  Required strength for Ultimate Limit State 
The  design  loads  are  obtained  by  multiplying  the  characteristic  loads  by  the  appropriate  partial 

10 

 
safety factor, γf, from Table 5.2. 
When more than one imposed load (variable action) is present, the secondary imposed load may be 
reduced by the application of a combination factor, ψ0  (see Table 5.4). 
The basic load combination for the required strength at ultimate limit state for a typical building is: 
 
R = γGGK + γQQK1 + ΣγQψ0QKi 
where: 
 QK1,  QK2,  QK3  etc. are the actions due to vertical imposed loads, wind load, snow etc., QK1 being the 
leading action for the situation considered. 
The  ‘unfavourable’  and  ‘favourable’  factors  should  be  used  so  as  to  produce  the  most  onerous 
condition. Generally, permanent actions from a single load source may be multiplied by either the 
‘unfavourable’ or the ‘favourable’ factor. 
 
Table 5.2 – Action Combinations for Ultimate Limit States ( BS EN 1990: Table NA.A1.2 (B)) 
Option  Permanent Actions Variable Actions Earth and 
(Dead Loads)  ( Imposed, Wind Loads)  Water* 
Unfavourable  Favourable  Leading  Others( i > 1) 
1  1.35GK  1.0GK 1.5QK,1  1.5Σψ0,iQK,i  1.35QK 

2a  1.35GK  1.0GK  1.5ψ0,1QK,1  1.5Σψ0,iQK,i  1.35QK 

2b  1.25GK  1.0GK  1.5QK,1  1.5Σψ0,iQK,i  1.35QK,i 


*Note: If the water pressure calculated is the most unfavourable value that could occur during the life of the structure, a 
partial factor of 1.0 may be used. 

 
Based on Table 5.2, a summary of Eurocode Partial Load Factors is given in Table 5.3 for 
the ultimate limit state. 
 
 
 
 
 
 
 
 
 
11 

 
Table 5.3 – Partial safety factors for loads at the ultimate limit state 
 
Variable Actions  

Permanent Actions  Leading variable action Accompanying variable 


(GK)  (QK,1)  actions 
Limit State  (QK,I) 
Unfavourable  Favourable  Unfavourable  Favourable  Unfavourable  Favourable   

       
   

 (a)Static 
1.10  0.90  1.50  0.00  1.50  0.00 
   equilibrium 
(b)Structural 
1.35  1.00  1.50  0.00  1.50  0.00 
    strength 
(c)As an 

alternative 
to (a) and (b) 
above to 
design for 
1.35  1.15  1.50  0.00  1.50  0.00 
both 
situations 
with one set 
of 
calculations 
(d)Geotechni
1.35  0.00  1.35  0.00  1.35  0.00 
cal strength 

 
 
5.5.2.2.2   Values for Serviceability Limit State 
The  action  (load)  combination  for  checking  the  requirement  at  the  serviceability  limit 
state is generally of the form: 
GK + QK,1 + Σψ0,iQK,i 
 
Where,  GK,  QK,1  and  QK,i  are  permanent  action  (dead  load),  leading  variable  action 
(imposed  load)  and  other  secondary  variable  actions  (  where  more  than  one  imposed 
load  contributes  to  the  stresses)  respectively.  In  the  case  of  the  secondary  variable 
load(s), their effect(s) may be reduced by the application of the combination factors as 
given  in  Table  5.4.  The  corresponding  load  cases  for  the  serviceability  limit  states  are 
given in Table 5.5. 
12 

 
 
Table 5.4 – Combination reduction factors, ψ, for buildings 
Action  Ψ0  Ψ1  Ψ2 
Domestic, residential area 0.7 0.5 0.3 
Office area 0.7 0.5 0.3 
Congregation areas 0.7 0.7 0.6 
Shopping areas 0.7 0.7 0.6 
Storage areas 1.0 0.9 0.8 
Traffic area
0.7  0.7  0.6 
Vehicle≤30kN 
Traffic area
0.7  0.5  0.3 
30kN≤Vehicle≤160kN 
Roofs  0.7 0.0 0.0 
Wind loads 0.5 0.2 0.0 
Temperature (non‐fire) 0.6 0.5 0.0 
 
Table 5.5 – Serviceability Load cases 
Design requirement  Action  Permanent(Dead  Variable (Imposed load) 
Combinations load) Actions  Actions 
GK  Leading QK,1  Others QK,i 
Function and  Characteristic 1.0 1.0 Ψ0 
damage to elements, 
including partitions 
and finishes 
User comfort, use of  Frequent  1.0 Ψ1  Ψ2 
machinery, avoiding 
ponding of water 
Appearance of the  Quasi‐ 1.0 Ψ2  Ψ2 
structure or element  permanent 
 
 
 
 
 
 

13 

 
5.6   DEAD LOADS 
5.6.1 (1) Dead loads shall be calculated from unit weight given in Appendix A to this part or from  
                 materials not provided for in that Appendix as specified or agreed upon with the  
               Authority having jurisdiction. 
 
(2)  When partitions are shown in plans, their actual weights shall be included in the dead 
load. For all floors in which partition walls are or may be intended but are not located 
on  the  plans,  the  beams  and  the  floor  slabs  where  these  are  capable  of  effective 
lateral distribution of the load, shall be designed to carry in addition to other loads, a 
uniformly distributed load per square metre of not less than one third of the weight 
per metre run of the finished partitions, but not less than 1kN/m2 if the floor is used 
for office purposes. 
 
5.7    LIVE (IMPOSED) LOADS DUE TO USE AND OCCUPANCY 
5.7.1 The minimum live load to be provided for shall be as set out in the Clauses of this Part, or, 
where  not  covered  by  these  Clauses,  as  specified  or  agreed  upon  with  the 
Administering Authority. In all cases the live load or loads shall be so placed 
that  in  combination  with  dead  load  the  maximum  stresses  are  produced  in 
the member or members being designed. 
 
5.7.2 Floor Live Loads 
(1)  The  minimum  floor  live  loads  to  be  provided  for  shall  be  taken  as  being 
equal to an equivalent uniform static Load or concentrated load whichever 
produces  greater  stresses  and  shall  be  based  on  the  intended  use  and 
occupancy  as  set  out  in  Table  5.6  of  this  Clause.  The  concentrated  loads 
applied  over  a  specified  area  of  a  square  with  a  300mm  side  shall  be 
located so as to cause maximum effects. 
Table  5.6  provides  for  normal  effects  of  ordinary  impact  and  acceleration 
but does not include any allowance for special concentrated loads. Special 
provision  shall  be  made  for  moving  loads  other  than  those  in  garages  for 
machinery and other concentrated loads as set out in Section 5.8. 
 
(2)   The  concentrated  imposed  load  need  not  be  considered  where  the  floor 
slab is capable of effective lateral distribution of this load.  
14 

 
(3)   All beams shall be designed to carry the distribution load appropriate to the 
uses to which they are to be put as given in Table 5.6. 
(4)   Beams,  ribs  and  joists  spaced  at  not  more  than  1  metre  centres  may  be 
designed as floor slabs.  
(5)   Where  in  Table  5.6  no  values  are  given  for  concentrated  load,  it  may  be 
assumed  that  the  tabulated  distributed  load  is  adequate  for  design 
purposes. 
(6)   Where an area of floor is intended for 2 or more occupancies at different 
times, the value to be used from Table 5.6 shall be the greatest value for 
any of the occupancies concerned. 
(7) When the occupancy of a building is changed the building shall conform to 
the requirements of this part of the Code for the new occupancy.  
 
5.7.3 Reduction in Total Imposed Floor Loads  
(1) Except as provided for in 5.7.3(2) and 5.7.3(3), the reduction in assumed total  
imposed  floor  loads  defined  below  may  be  taken  in  designing  columns,  piers,       
walls, their support and foundations. For purposes of 5.7.2(1) to 5.7.3(3), a roof 
may be regarded as a floor.  
Let,  Le  be  the  imposed  load  upon  the  roof  and  let  L1,  L2,  L3  ‐‐‐  Ln  be  the   
respective  imposed  loads  upon  the  floors  numbered  1,  2,  3  ‐‐‐  n  starting  from 
the top of the building.  
For the design of the points of support the following imposed loads may be  
adopted:  
Supports under roof                             LO 
Supports under top floor (floor 1)    LO + L1  
    Supports under floor 2                                       LO + 0.95(L1+L2) 
    Supports under floor 3                                       LO + 0.9 (L1+L2 + L3) 
    Supports under floor 4                                       LO + 0.85 (L1+L2 + L3 + L4) 

    Supports under floor n                                      LO +  (L1+L2 + L3 ‐‐‐ Ln) 

    The coefficient (3+n)/2n is valid for n > 5 
    For factories and workshops designed for 5kN/m2 or more, the reductions    
    shown above may be taken provided the loading assumed is not less than it   
    would have been if all floors had been designed for 5kN/m2 with no reductions. 

15 

 
(2) Where a single span of a beam or girder supports not less than 46m2 of floor at  
      one general level, the imposed load may, in the design of beam or girder, be  
      reduced by 5% for each 46m2 supported, subject to a maximum reduction of 
      25%. This reduction or that given in 5.7.3(1), whichever is greater, may be  
      taken into account in the design of columns or other type member supporting  
      such a beam. 
 
(3) No reduction shall be made for any plant or machinery which is specifically  
      allowed for or for buildings for storage purposes, warehouses, garages and  
      those office areas which are used for storage and filing purposes. 
 

5.7.4 Roof Live Loads other than Wind Loads or Rain Loads.       

(1) Flat Roofs 
Flat  roofs  to  which  there  is  no  direct  access  (except  only  such  cases  as  is 
necessary for cleaning and repairs) shall withstand an imposed load of 
0.25kN/m2 measured on plan or a load of 0.9kN concentrated on a square 
with 300mm side whichever produces the greater stress. 
 
(2) On  flat  floors  where  access  (in  addition  to  that  necessary  for  cleaning  and 
repair) is provided to the roof, allowance shall be made for an imposed load 
of 1.5kN/m2 measured on plan or a load of 1.8kN concentrated on a square 
with a 300mm side.  
 
 
 
 
 
 
 
 
 
 

16 

 
Table 5.6 ‐   Uses and Loads 
 
Concentrated Load to be applied 
Occupancy or Use  
Intensity of Distributed Loads  unless otherwise stated over any 
(kN/m2)  square with a 300‐mm side 
2
(kN/m ) 

 
1. Residential     
Multifamily house   4.0  4.5 
      Private apartments  2.0  1.8 
      Public rooms   5.0  ‐ 
      Corridors   4.0  4.5 
   
2. Dwellings      
     Not exceeding 2 storeys   1.5  1.4 
     Exceeding 2 storeys   2.0  1.8 
3. Hotels      
  Guest rooms      2.0  1.8 
       Public rooms      5.0  4.5 
     Corridors serving public rooms   5.0  4.5 
     Corridors above first floor   4.0  4.5 
   
4. Office buildings     
Areas (not including computer rooms) located in basement and     
first floor  5.0  4.5 
File, rooms in offices  5.0  4.5 
Floors above first floor  2.5  2.7 
Area with computing data processing and similar equipment  3.5  4.5 
Toilet rooms  2.0  ‐ 
   
5. Assembly areas with fixed seats    
     including :     
    Auditoria      
    Churches  4.0  ‐ 
    Courtrooms  
    Lecture halls  
     Theatres and other areas  
    with similar uses  
     
6. Assembly areas without fixed seats including :  
        Arenas      
         Balconies      
        Dance floors      
        Dining areas      
      Foyers and entrance hall      
      Grandstands      
      Reviewing stands      
      Gymnasia     
     Museums     
     Stadia      
     Stages and other areas with      
     similar uses  5.0  3.6 
17 

 
   
7. Drill rooms and Drill halls  5.0  9.0 
     
8. Garage for passenger cars unloaded buses and light trucks not     
exceeding 2500kg including driveways and ramps  2.5  9.0 
All  repair  workshops  for  all  types  of  vehicle  and  parking  for  To  be  determined  but  not  less  To  be  determined  but  not  less  than 
vehicles  exceeding  2500kg  gross  weight  including  driveways  than 5.0  9.0 
and ramps 
     
9. Libraries     
Reading and study rooms without book storage   2.5  4.5 
Rooms with book storage (eg. Public lending libraries)  4.0  4.5 
Stack Rooms  2.4  For each metre stack    7.0 
  height with a minimum of 6.5 

   

10. Schools and Colleges     
Classrooms   3.0  2.7 
Dormitories  1.5  1.8 
Gymnasia  5.0  3.6 
     
Kitchens   To  be  determined  but  not  less  4.5 
  than 3.0   
Laboraties including equipment  To  be  determined  but  not  less  4.5 
than 3.0 
   
11. Hospitals      
      Bedrooms and Wards   2.0  1.8 
      Laundries   3.0  4.5 
      Toilet rooms   2.0  ‐ 
     Utility rooms   2.0  4.5 
      X‐ray room and Operating      
      theatres   2.0  4.5 
12. Factories    
Light  5.0  4.5 
Medium  7.5  6.7 
Heavy   10.0  9.0 
     
13. Warehouses     
General storage space in industrial and commercial buildings  10.0  9.0 
 
(Note:  For concentrated loads Pigeaud’s or Westergaard’s theory may be used)
 
 
(3) Sloping Roofs up to angle of 65o to the horizontal shall withstand an imposed 
load of 0.25kN/m2 measured on plan or a vertical load of 0.9kN concentrated 
on a square with 300mm side whichever produces the greater stress. 
 
 
18 

 
(4) Curved Roofs   
The  imposed  load  on  a  curved  roof  shall  be  calculated  by  dividing  the  roof 
into  not  less  than  five  equal  segments  and    then  by  calculating  the  load  on 
each, appropriate to its mean slope in accordance with 5.7.4(1) to 5.7.4(3). 
    
(5) Roof  coverings  and  purlins  at  a  slope  of  less  than  450  shall  be  capable  of 
carrying a load of 0.9kN concentrated on any square with 125mm side.  
 

5.8   DYNAMIC LOADING 

5.8.1   Where  loads  arising  from  machinery,  runways,  cranes  and  other  plant 
producing  dynamic  effects  are  supported  by  or  communicated  to  the 
framework,  allowance  shall  be  made  for  these  dynamic  effects,  including 
impact,  by  increasing  the  dead‐weight  values  by  an  adequate  amount.  In 
order  to  ensure  economy  in  design,  the  appropriate  dynamic  increase  for 
all members affected shall be ascertained as accurately as possible. 

 
5.8.2  The  minimum  design  load  due  to  equipment,  machinery  on  other  objects  or 
persons  that  may  produce  impact,  is  the  total  weight  of  equipment  or 
machinery  plus  its  maximum  lifting  capacity,  or  appropriate  live  load, 
multiplied  by  an  appropriate  factor  listed  in  Table  5.7;  except  in  cases 
where the actual multiplying factor has been supplied by the manufacturer 
or supplier of the equipment in which case this factor shall be used in lieu 
of those listed in Table 5.7. Where dynamic effects such as resonance and 
fatigue  are  likely  to  be  important  as  a  result  of  vibration  of  equipment  or 
machinery, a dynamic analysis shall be carried out. 
 
Table 5.7 ‐   Impact Loads 
Impact due to  Factor 
Operation of motor driven cranes  1.25 
Operation of hand driven cranes  1.10 
Live loads on hanger supported floors and stairs  1.33 
Supports for light machinery, shaft or motor driven  1.20 
Supports for reciprocating machinery or power driven units  1.50 

19 

 
 
5.8.3  The minimum horizontal design loads on cranes runway rails are:  
(a)  Lateral force which shall be: 
(i) for power operated crane trolleys, 20% and for hand operated trolleys, 10% of the 
sum of the weights of the lifted loads and of the crane trolley excluding other parts 
of the crane; 
(ii) applied at the top of the rail, one‐half in each side of the runway, and 
(iii) considered acting in either direction normal to the runway rail. 
(b)  Longitudinal force which shall be: 
(i) 10 percent of the maximum wheel loads of the crane, and  
(ii) applied at the top of the rail. 
5.8.4 (1) Loads on Railings 
     The minimum design load applied horizontally at the top of a railing which guards a drop of more  
      than  460mm shall be:  
                 (a) 5.8kN/m for exterior balconies of individual residential units and a concentrated load of  
                      0.9kN applied concurrently; 
                 (b) 1.5kN/m for exits and stairs; 
                 (c)  2.2kN/m for assembly occupancies, except for    grandstands and stadia; 
              (d) 3.6kN/m for grandstands and stadia including ramps; 
              (e) 4.4kN/m for vehicle guard rails for parking garages applied 530mm above   
              the  roadway  and  minimum  total  load  of  (11kN)  uniformly 
distributed over                   each  vehicle  space  applied  530mm  above  the 
roadway, and  
(f) O.6kN concentrated load applied at any point for industrial catwalks and 
other areas where crowding by many people is very improbable.  
(2)  The minimum design load applied horizontally to panels under railings which 
guard a drop of more than 460mm shall be 1.0kN/m2.       

(3) The minimum design load applied vertically at the top of a railing  which guards a 
drop  of  more  than  460mm  shall  be  1.5kN/m  acting  separately  from  the 
horizontal load provided in Clause 5.8.4(1). 

(4) Grandstands and any building used for assembly purposes to accommodate large 
numbers of people at one time shall be designed to resist all inertia sway forces 

20 

 
produced  by  use  and  occupancy  of  the  building  or  structure.  The  inertia  force 
shall  be  not  less  than  0.30kN/m  of  seat  parallel  to  each  row  of  seats  or 
0.2kN/m of seat perpendicular to each row of seats. 

5.9  EFFECTS OF WIND 
5.9.1 Scope 
This Subsection deals with methods for calculating wind loads that should be taken 
into  account  when  designing  buildings,  structures  and  components  of  buildings 
and structures.  
It  does  not  apply  to  building  or  structures  whose  light  weight,  low  frequency  and 
1ow damping properties make them susceptible to vibration. 
 
5.9.2 Definitions 
Unless  otherwise  specified,  the  following  definitions  shall  apply  for  the  purposes 
of this Subsection. 
1. Breadth: The dimension of the building normal to the direction of the wind. 
2. Depth: The dimension of the building measured in the direction of wind.  
3. Height: The height of a building above the ground adjoining that building. 
4. Length:  The  greater  horizontal  dimension  of  a  building  above,  the  ground 
adjoining  that  building;  or  the  length,  between  supports,  of  an  individual 
structural member. 
5. Width:  The  lesser  horizontal  dimension,  of  a  building  above  the  ground 
adjacent  to  that  building,  or  the  width  of  a  structural  member  across  the 
direction of the wind.  
6. Height above ground: The dimension above general level of the ground to 
windward.  
7. Element  of  Surface  Area:  The  area  of  surface  over  which  the  pressure 
coefficient is taken to be constant. 
8. Effective  Frontal  Area:  The  area  normal  to  the  direction  of  the  wind  or 
‘shadow area’.  
9. Dynamic Pressure of Wind: The free dynamic pressure resultant from   
    the design wind speed.  
 
10.    Pressure  Coefficient:  The  ratio  of  the  pressure  acting  at  a  point  on  a 

21 

 
surface to the dynamic pressure of the incident wind.  
11.  Force Coefficient: A non‐dimensional coefficient such that   
      the total wind force on a body is the product of the force   
      co‐efficient multiplied by the dynamic pressure of the  
      Incident wind and the appropriate area as defined in  
      text.  
12. Topography: The nature of the earth’s surface as   
      influenced by the hill and valley configurations. 
13. Ground  Roughness:  The  nature  of  the  earth’s  surface  as  influenced  by 
small‐scale  obstruction  such  as  trees  and  buildings  (as  distinct  from 
topography)    
 
Note:  Breadth and Depth of a building are to the direction of   
            wind. Length and Width are dimensions related to the plan form.  
 
5.9.3   Nomenclature 
A    =  element of surface 
Ae    =  effective frontal area 
b    =  breadth 
Cf    =  force coefficient 
Cfn    =  normal force coefficient 
Cft    =  transverse force coefficient 
1
Cf     =  frictional drag coefficient 
Cp     =  pressure coefficient 
Cpe    =  external pressure coefficient 
Cpi    =  internal pressure coefficient 
d    =  depth 
D    =  diameter 
F    =  force 
Fn    =  normal force 
Ft    =  transverse force 
F1    =  frictional force 
h    =  height 
H    =  height above ground 

22 

 
j    =  width of member as indicated in diagram 
ja    =  width of member across direction of wind 
k    =  a constant 
K    =  reduction factor 
l    =  length 
p    =  pressure on surface 
Pe    =  external pressure 
Pi    =  internal pressure 
B    =  total load intensity 
q    =  dynamic pressure of wind (stagnation pressure) 
Re    =  Reynolds number 
S1    =  topography factor 
S2    =  ground roughness, building size and height above ground    
                                            factor 
S3    =  a statistical factor 
V    =  basic wind speed 
Vs    =  design wind speed 
w    =  width of building  
1
w    =  bay width in multi‐bay buildings 
α    =  wind angle (from a given axis) 
    =  aerodynamic solidity ratio 
ημ    =  shielding factor 
v    =  kinematic viscosity 
Ø    =  geometric solidity ratio 
 
5.9.4      Procedure for calculating Wind Loads on Structures 
(1)  The wind load on a structure should be calculated for: 
a)   the structure as a whole; 
         b) individual structural elements such as roofs and walls; 
c) individual cladding units and their fixings. 
(2) In the case of partially completed structures, the wind load will depend on the  
      method and sequence of construction and may be critical. In calculating the 
      temporary  higher  wind  loads,  the  maximum  design  wind  speed  Vs  may  be 
assumed  not  to  occur  during  the  short  construction  period  and  a  reduced 

23 

 
factor  S3  used.  It  is  recommended  that  the  graphs  of  Fig.5.6  should  not  be 
extrapolated for periods less than two years.  
(3) The assessment of wind load should be made as follows: 
a) The basic wind speed V appropriate to the area where the structure 
is to be erected is determined as specified in 5.9.5(2) 
b) The basic wind speed is multiplied by factors S1, S2 and S3 to give the 
design wind speed Vs (see 5.9.5(3)). 
 
Vs = V S1 S2 S3 
 

c) The design wind speed is converted to dynamic pressure q = kVS.2 
          Table 5.11 gives corresponding values of q and Vs 
d) The  design  external  pressure  or  suction  at  any  point  on  the  surface 
of the building is given by: 
p = Cpq 
A  negative  value  of  Cp  indicates  suction.  The  resultant  load  on  an 
element  or  cladding  depends  on  the  algebraic  difference  of  the 
external  pressure  or  suction  and  the  internal  pressure  or  suction 
may be calculated from: 
F = (Cpe – Cpi)qA 
A negative value of F indicates that the resultant force is outwards. 
The  total  wind  load  on  a  structure  may  be  obtained  by  a  vectorial 
summation of the loads on all the surfaces. 
 
e) Where  a  value  of  force  coefficient,  Cf,  is  available,  the  total  wind 
load on the building as a whole is more conveniently obtained from: 
               F = CfqAe 
Pressure coefficients are given in Tables 5.14 and 5.20 for a range of 
building  shapes.  Force  coefficients  are  given  in  Tables  5.21  to  5.25 
for unclad structures. 
 
 
 
 
24 

 
5.9.5  Design Wind Speed, VS 
 

(1) General: The design wind speed Vs should be calculated from  
Vs = VS1 S2 S3 
The basic wind speed table is specified in 5.9.5(2) and the factors S1, S2, S3 
in 5.9.5(3). 
 
            (2) Basic Wind Speed: 
 a)  The  basic  wind  velocity  is  the  maximum  3‐second  gust  speed  at  a 
height     of  10m  above  ground  likely  to  be  exceeded  on  the  average 
not more    than  once  in  50years,  in  open  country.  The  values  are 
shown by   isophleths (line of equal wind speed) on the map in Fig. 
5.1. Table 5.8   gives  basic  wind  speeds  to  be  used  in  some  major 
towns in Ghana. 
b) It should be assumed the wind may blow from any direction. 
 
Table 5.8 ‐   Basic Wind Speed (in metres per second) 
for some major towns 
 
                                                       m/s 
1. Accra                          29 
2. Takoradi              29 
3. Kumasi              36 
4. Tamale              34 
5. Ada                34 
6. Saltpond              29 
7. Axim                          29 
8. Ho                29 
9. Akuse                         34 
10. Kete – Krachi                      38 
11. Wenchi              38 
12. Yendi              45 
13. Wa                44 
14. Navrongo                        35 
15. Bole                          36 
25 

 
 
 
    

Fig. 5.1: Wind Speeds (m/sec)

26 

 
 
  (3) Wind Speed Factors 

         (a)Topography  Factor,  S1:  The  basic  wind  speed,  V,  takes  account  of  the 
  general     level  of  site  above  sea  level.  This  does  not  allow  for  local 
  topographic(orographic) features such as hills, valleys, cliff escarpments or 
  ridges, which can significantly affect the wind speed in their vicinity. 
            The factor S1  is a measure of the enhancement that occurs in wind speeds 
  over hills, cliffs and escarpments. 
  The  effect  of  topography  is  to  accelerate  wind  near  the  summit  of  hills  or 
  crests of cliffs, escarpments or ridges and decelerate the wind in valleys or 
  near the foot of cliffs, steep escarpments or ridges. 
  Table 5.9 gives recommended values of S1 
 
Table 5.9 ‐   Topography Factor S1 
Topography  Description Value of S1 
category 
1  All cases except in 2 and 3 below  1.0 
2  • Very  exposed  hillslopes  and   
crests  where  acceleration  of   
wind is known to occur.   
   
• Valleys shaped so that funneling  1.1 
of wind may occur.   
 

 
• Sites  that  are  known  to  be 
abnormally  windy  due  to  some 
local influence. 
3  Steep sided enclosed valleys, sheltered  0.9 
from all winds. 
 
 
 

27 

 
(i)Effect of a Cliff or Escarpment on the Equivalent Height above ground. 
        The value of S1 in Table 5.9 can be explicitly calculated for the effect of a cliff or  
         escarpment at a site. 
         The effect of topography will be significant at a site when the upward slope (θ)      
  is greater than 3°( or 0.05 slope), and below that, the value of S1 may be taken 
  to  be  equal  to  1.0.  The  value  of  S1  varies  between  1.0  and  1.36  for  slopes  
  greater than 3°. 
 
         The  influence  of  the  topographic  feature  is  considered  to  extend  1.5Le  upwind  
        and 2.5Le downwind of the summit or crest of the feature, where Le is the  
        effective horizontal length of the hill depending on the slope as indicated in  
        Fig. 5.2. The values of Le for the various slopes are given in Table 5.10. 
        If the zone downwind from the crest of the feature is relatively flat (θ < 3°) for a  
        distance exceeding Le, then the feature should be treated as an escarpment.  
        Otherwise, the feature must be treated as a hill or ridge. 
        The topography factor is given by: 
S1 =  1+ C .s 
         where C has values appropriate to the height H above mean ground level and 
        the distance x  from the summit or crest relative to the effective length Le as 
        given in Table 5.11. 
          The factor, s, is determined from Fig. 5.3 for cliffs and escarpments and Fig.5.4 
        for ridges and hills.  
 

Table 5.11 – Variation of effective horizontal length of hill Le  and factor C,  
with slope, θ 
Slope,θ  Effective horizontal length,  Factor, C 
Le 
3°< θ≤ 17  L  1.2(Z/L) 
>17°  Z/0.3  0.36 
           Note: L is the actual length of the upwind slope in the wind direction, and Z is the effective 
           height of the feature. 

 
 

28 

 
 
 

Fig. 5.2a: Topographical dimensions – General notations

29 

 
 

 
 
Fig. 5.2: Topographical dimensions – (a) Hill and Ridge, (b) Cliff and 
Escarpment

30 

 
 
 
 
 

 
 
 
 
 
 
 

31 

 
 
 
 

Category 1                                      Category 2                                        Category 3 

Fig. 5.5: Categories of Ground Roughness


 

32 

 
 (b) Ground Roughness, Building Size and Height above ground, Factor S2 
           The  effect  of  wind  on  a  building,  structure  or  part  thereof  depends  on   
  ground  roughness  variation  of  wind  with  height  above  ground  and  size  of 
  building or component under consideration. The factor S2 takes account of  the 
  influences on wind effect listed above. 

 
 (i) Ground Roughness 
      The ground roughness has been divided into three categories and buildings  
      and their elements into three classes as follows: 
      Ground Roughness 1:   Open, level or nearly level country with no obstructions. 
      Examples are most of the coastal region outside major urban and sub‐urban  
      areas, air fields and areas surrounding the Volta Lake. 
      Ground Roughness 2:   Open country with few trees and houses. Examples are farmland and 
       most of the areas of the North and Upper Regions outside major urban centres. 
      Ground Roughness 3:   Areas covered by large obstructions. Examples are forest areas,  
        towns and their suburbs. Fig. 5.5 shows areas of the country outside major towns and suburbs 
        where the different categories should be generally applicable. 
 
 (ii)Cladding and Building size 
        Natural winds are turbulent and continually fluctuating. There is evidence available that for   
        buildings and components of buildings more susceptible to the action of wind, the 3‐second  
        gust speed should be used in design while for other buildings a longer averaging time could be 
        used. As a consequence of this, 3 classes have been selected. 

                Class A: All units of cladding, glazing and roofing and their immediate fixings and individual                
  members of unclad structures. 

               Class B: All buildings and structures where neither the greatest horizontal dimension nor the  
  greatest vertical dimension exceeds 50m. 

               Class C: All buildings and structures whose greatest horizontal dimension or greatest vertical   
  dimension exceeds 50m. 

The value of S2 for variation for wind speed with height above ground for various ground roughness 
categories  and  building  size  classes  are  given  in  Table  5.12.  The  height  to  be  used  for  the 

33 

 
determination of S2 should be taken as the height from the mean ground level adjoining the building 
to the top of the building. Alternatively, the structure may be divided into convenient parts and wind 
load on each part calculated, using S2 factor that corresponds to the height above ground of the top 
of  the  part.  The  dynamic  pressure  should  be  assumed  to  act  uniformly  over  the  structure  or  part 
respectively. 

(c) Factor for building life, S3 

The  factor  S3  takes  into  account  the  intended  life‐span  of  the  building  or  structure  and  the 
acceptable calculated risk. There is always an element of risk that a given design wind speed may be 
exceeded in a storm of exceptional violence. The greater the life‐span of the structure, the greater 
the risk.  Fig. 5.6 shows values of S3 equivalent to a period of exposure of 50 years plotted against 
intended life span or design life in years. 

Normally,  wind  loads  on  completed  structures  and  buildings  should  be  calculated  at  S3  =  1  except 
for: 

(i) temporary structures;  
(ii) structures where a longer period of exposure to wind may be required; 
(iii) structures where greater than normal safety is required. 

The period of exposure should never be taken as less than 2 years. 

Example:  Calculate  the  design  speed  for  a  tower  20m  high,  situated  in  a  well  wooded  area  ( 
roughness category 3) and for 100‐year probable life near an abrupt escarpment of height 35m. The 
tower is located around Ho. The crest of the escarpment  is  10m  effective distance from the plains. 
The tower is located on the downwind side, 5m from the crest. 

Tan θ = 10/35 = 0.2857, θ = 15.74 

X = +5     Le = 10m   H = 20m    X/Le = +5/10 = +0.5       H/Le = 20/10 = 2  

Basic wind speed for Ho, V = 29m/s ( Fig. 5.1, Table 5.8) 

S3 factor for 100 yr probable life with probability level of 0.63 = 1.05 (Fig. 5.6) 

S2  factor  for  20m  for  a  well  –wooded  area  (ground  roughness  category  3)(Class  B)  =  0.90  (Fig. 
5.5,Table 5.12) 

S1 factor for topography: 

For X/Le = +0.5 and H/Le = 2 ( Fig. 5.2);  s  factor from Fig. 5.3 is = 0.05 

34 

 
From Table  5.11, factor C = 1.2Z/Le = 1.2x20/10 = 2.4 

→ S1 = 1 + C x s =  1+ 0.05 x 2.4 = 1.12 

→Design wind speed = Vs = V x S1 x S2 x S3 

                                                = 29 (1.12)(0.9)(1.05) = 30.7m/s 

Note on Fig. 5.6 

For example, using the graph for probability level 0.63 for a period of exposure equal to 100 years say, S3 = 1.05 i.e. there 
is the probability level of 0.63 that a speed which is 1.05 times the once in 50 years wind speed obtained from  Fig. 5.1 
will be exceeded at least once in 100 years. 

 
5.9.6   Dynamic Pressure of the Wind 

Using  the  value  of  the  design  speed  Vs  obtained  from  section  5.9.5,  the  dynamic  pressure  of  the 
wind q above atmospheric pressure may be calculated from 

 
where:  k = 0.613  in SI units( N/m and m/s) 
 

Table 5.13 gives corresponding values of Vs and q. 
35 

 
Table 5.12 ‐   Ground Roughness, Building size and Height above ground,   Factor S2 

  1. Open Country with no  2. Open Country with few  3. Towns, Suburbs, Forest 


  obstructions  trees and houses  areas 
Class  Class Class 

(m)  A  B  C A B C A B  C
3 or less  0.83  0.78  0.73 0.72 0.67 0.63 0.64  0.60  0.55
5  0.88  0.83  0.78  0.79  0.74  0.70  0.70  0.65  0.60 
10  1.00  0.95  0.90  0.93  0.88  0.83  0.78  0.74  0.69 
15  1.03  0.99  0.94  1.00  0.95  0.91  0.88  0.83  0.78 
20  1.06  1.01  0.96  1.03  0.98  0.94  0.95  0.90  0.85 
30  1.09  1.05  1.00  1.07  1.03  0.98  1.01  0.97  0.92 
40  1.12  1.08  1.03  1.10  1.06  1.01  1.05  1.01  0.96 
50  1.14  1.10  1.06  1.12  1.08  1.04  1.08  1.04  1.00 
60  1.15  1.12  1.08  1.14  1.10  1.06  1.10  1.06  1.02 
80  1.18  1.15  1.11  1.17  1.13  1.09  1.13  1.10  1.06 
100  1.20  1.17  1.13  1.19  1.16  1.12  1.16  1.12  1.09 
120  1.22  1.19  1.15  1.21  1.18  1.14  1.18  1.15  1.11 
140  1.24  1.20  1.17  1.22  1.19  1.16  1.20  1.17  1.13 
160  1.25  1.22  1.19  1.24  1.21  1.18  1.21  1.18  1.15 
180  1.26  1.23  1.20  1.25  1.22  1.19  1.23  1.20  1.17 
200  1.27  1.24  1.21  1.26  1.24  1.21  1.24  1.21  1.18 

Table 5.13 ‐   Values of q in SI Units (N/m2) 

V s         

(m/s)  0  1.0  2.0  3.0  4.0  5.0  6.0  7.0  8.0  9.0 

10  61  74  88  104 120 138 157 177  199  221
20  245  270  297  324  353  383  414  447  481  516 
30  552  589  628  668  709  751  794  839  885  932 
40  981  1030  1080  1130  1190  1240  1300  1350  1410  1470 
50  1530  1590  1660  1720  1790  1850  1920  1990  2060  2130 
60  2210  2280  2360  2430  2510  2590  2670  2750  2830  2920 
70  3000 
(Note: To determine q for a speed of say 33 m/s look under 3  along the row corresponding to 30 which gives q = 668 
N/m2). 

 
36 

 
5.9.7  Pressure Coefficients and Force Coefficients 

   (1) General:  The force on a building or structure or part thereof is obtained by multiplying the  
        dynamic pressure by a coefficient that is dependent on the shape of the building or structure  
        and by the area of the building or structure or part thereof. 
        The two types of coefficients are: 
(a) pressure coefficient Cp which refers to a particular surface or part of building; 
(b) force  coefficient  Cf  which  refers  to  the  building  as  a  whole.  The  values  of  these 
coefficients  are  given  in  Tables  5.14  to  5.23.  These  tables  may  be  used  for  other 
buildings of generally similar shape.  
 
(2)  Pressure Coefficients:  The average values given in the tables are for critical wind directions in  
      one or more quadrants. In order to determine the maximum wind load on a building the total  
      load should be calculated from each of the surfaces or parts of the surfaces of the building. 
      Coefficients of local effects are also given. These are to be used in calculating loads for local areas 
      but not for calculating the load on entire structural elements such as roof and walls. In such  
      locations, the construction must be adequate to resist the local forces (additional nailing,  

     anchoring etc.). 
     Furthermore, it should be noted that these local forces can act in a shaking manner and  
     result in fatigue failures. 
     The net design load due to wind on individual cladding and their fixings, roofs and walls should be 
     the algebraic difference of the external pressure or suction and the design internal pressure or  
     suction from: 
 
F = ( Cpe – Cpi ) qA 
 
      Values of Cpe are given in Tables 5.14, 5.15, 5.16 and values of Cpi  in  section 5.9.7(3). 
 
 (3)  Internal Pressure Coefficient:  It is normally difficult to estimate the internal pressure coefficient   
       for  a building as the coefficient depends on permeability through windows, ventilation louvres,  
      leakage gaps around doors and windows and cladding. It is recommended that for wall and roof  
     loading the internal pressure coefficient should be determined as follows: 
 

37 

 
      (a)  Where  there  is  only  negligible  probability  of  dominant  opening  occurring  during  a  severe 
  storm,    should  be  taken  as  +0.2  or  ‐0.3  whichever  produces  the  greater  effect  on  the 

  building or member concerned. 
      (b) Where a dominant opening is likely to occur,   should be taken as 7.5% of the value of    

            outside the opening. 
 
(4) Force Coefficients: Force coefficients vary for the wind acting on different faces of a building or  
      structure.  In determining the critical load, the total wind load should be calculated for each wind  
     direction . The total wind load on a particular building or structure is given by: 
 
F = Cf q Ae 
The direction of the force is specific in the table. 
Where the wind load is calculated by dividing the area into parts, the value of Cf applied to each part 
should be that for the building as a whole. 
 
(6) Frictional Drag: For certain types of buildings it is necessary to take into account a frictional 
drag  in  addition  to  the  wind  load  calculated  from  5.9.7(2)  and  5.9.7(4).  The  frictional  drag 
may be neglected for rectangular clad buildings where the ratio d/h or d/b is greater than 4. 
The frictional drag in the direction of the wind is given by the following: 
 
if  h ≤ b,    F’ = Cf’q b(d‐4h)    +  Cf’q 2h (d – 4h) 
or 
if  h ≥ b,    F’ = Cf’q b(d – 4b) +  Cf’q 2h (d – 4h) 
 
The first term in each formula represents the drag on the roof and the second the drag on 
the walls. 
          = 0.01 for smooth surfaces without corrugations or ribs across the wind direction. 
 
          = 0.02 for surfaces with  ribs across the wind direction. 
 
        0.  = 0.04  surfaces with ribs across the wind direction. 
 
For  other  buildings  the  frictional  drag  will  be  indicated,  where  necessary,  in  tables  of 
pressure coefficients and force coefficients. 

38 

 
Table 5.14: Pressure coefficient Cpe for walls of Rectangular clad buildings 
BUILDING   BUILDING   ELEVATION  PLAN WIND  Cpe for surface  Local Cpe

HEIGHT  PLAN  ANGLE A B C D 


RATIO  RATIO 
Ѳ° 

C 0 +0.7 ‐0.2 ‐0.5  ‐0.5  ‐0.8

1<l/w≤ 3/2  90  ‐0.5  ‐0.5  +0.7  ‐0.2 

h/w ≤ ½   

  C 0 +0.7 ‐.25 ‐0.6  ‐0.6  ‐1.0


3/2<l/w≤ 4 
90  ‐0.5  ‐0.5  +0.7  ‐0.1 

  C 0 +0.7 ‐.25 ‐0.6  ‐0.6  ‐1.1

1<l/w≤ 3/2 
90  ‐0.6  ‐0.6  +0.7  ‐0.25 

1/2<h/w≤3/2 
  C 0 +0.7 ‐0.3 ‐0.7  ‐0.7  ‐1.1

3/2<l/w≤ 4 
90  ‐ 0.5  ‐0.5  +0.7  +0.1 

  C 0 +0.8 ‐.25 ‐0.8  ‐0.8  ‐1.2

1<l/w≤ 3/2 
90  ‐0.8  ‐0.8  +0.8  +0.25 

3/2<h/w≤6 
  C 0 +0.7 ‐0.4 ‐0.7  ‐0.7  ‐1.2

3/2<l/w≤ 4  90  ‐0.5  ‐0.5  +0.8  ‐0.1 

   C 0 +0.95 ‐1.85 ‐0.9  ‐0.9  ‐1.25


  l/w =  3/2 
90  ‐0.8  ‐0.8  +0.85  ‐0.85 

0 +0.95 ‐1.25 ‐0.7  ‐0.7 


h/w > 6  l/w =  1  ‐1.25 
90  ‐0.8  ‐0.7  +0.95  ‐1.25 

0 +0.85 ‐0.75 ‐0.75 ‐0.75  ‐1.25


l/w = 2 
90  ‐0.75  ‐0.75  ‐0.85  ‐0.75 

Note: h is the height to eaves or parapet, l is the greater horizontal dimension of a building and w is the lesser horizontal dimension of a building 

39 

 
Fig.  5.15:  External  pressure  coefficients  (Cpe)  for  Pitched  roofs  of  rectangular  clad 
buildings 

40 

 
 

     

41 

 
Table 5.16: Pressure coefficient Cfe for monopitch Roofs of rectangular clad buildings  

with h/w < 2 

42 

 
Table 5.17: Force coefficients (Cf) for Rectangular clad (acting in the direction of the wind) 

43 

 
Table 5.18: Pressure coefficients (Cpe) for Pitched Roofs of Multi‐span buildings  

(all spans equal) with h ≤ w 

 
44 

 
Table 5.19: Pressure coefficients (Cpe) for Saw‐tooth Roofs of multi‐span buildings  

(all spans equal) with h ≤ w 

45 

 
Table 5.20: Pressure coefficients (Cp) for Canopy Roofs with 1/2 ≤ h/w < 1 

46 

 
Table 5.21: Force coefficient (Cf) for clad buildings of uniform section 

(acting in direction of wind) 

47 

 
Table 5.21 (cont.) 

48 

 
Table 5.21 (cont.) 

49 

 
Table 5.22: Pressure distribution around Cylindrical structures 

For the purpose of calculating the wind forces that act in a way as to deform a cylindrical structure 
the  values of  Cpe in  Table  5.22  may  be  used.  They  apply only  in  supercritical  flow  (i.e.  they  should 
only be used where D > 0.3m). They may be used for wind blowing normal to the axis of cylinders 
having their axis normal to the ground plane (i.e. chimneys, silos) and to cylinders having their axis 

50 

 
parallel with the ground plane (i.e. horizontal tanks) provided the clearance between the tank and 
the ground is not less than D. 

h is the height of a vertical cylinder or length of a horizontal cylinder. Where there is a free flow of 
air around both ends, h is to be taken as half the length when calculating h/D. Interpolation may be 
used for intermediate values of h/D. 

In  the  calculation  of  the  load  on  the  periphery  of  the  cylinder,  the  value  Cpi  shall  be  taken  into 
account. 

For open ended cylinders where h/D  0.3;     Cpi may be taken as ‐0.8. 

For open ended cylinders where h/D  0.3;    Cpi may be taken as ‐0.5 

 
5.9.8 Force Coefficients for Unclad Structures 
(1) General: This section applies to permanently unclad structures and structural frameworks 
while temporarily unclad. 
Structures that because of their size and the design wind velocity, are in the supercritical 
flow regime may need further calculation to ensure that the greatest loads do not occur at 
some wind speed below the maximum when the flow will be subcritical. 
 
(2) Force  coefficients  of  individual  members:  The  coefficients  refer  to  members  of  infinite 
length.  For  members  of  finite  length,  the  coefficients  should  be  multiplied  by  a  factor  K 
that  depends  on  the  ratio  l/ja,  where  l  is  the  length  of  the  member  and  ja  is  the  width 
across the direction of the wind. Values of K are given in Table 5.23. 
Where any member abuts onto a plate or wall in such a way that free flow of air around 
that end of the member is prevented, the ratio l/ja should be doubled for the purpose of 
determining K. When both ends of a member are so obstructed, the ratio should be taken 
as infinity. 
 
 
 
 
 

51 

 
Table 5.23 ‐   Values of Reduction Factor K for members of finite length 
 and slenderness 
 
l/ja   or  l/D  2  5 10 20 40 50 100  ∞ 
Circular cylinder, subcritical flow  0.58  0.62 0.68 0.74 0.82 0.87 0.98  1.0 
                 
Circular cylinder, supercritical flow  0.80  0.80  0.82  0.90  0.98  0.99  1.0  1.0 
                 
Flat plate perpendicular to wind  0.62  0.68  0.69  0.81  0.87  0.90  0.95  1.0 

 
 

5.9.8(3)(a)    Flat–sided  members:    The  force  coefficient  in  Table  5.24  are  given  for  two  mutually‐
perpendicular directions relative to a reference axis on the structural member. They are designated 
Cfn  and Cft  and give the forces normal and transverse, respectively, to the reference plane as will be 
apparent from the diagrams. 
Force coefficients are for wind normal to the longitudinal axis of the member. 
Normal force:           F = Cfn qklj 
Transverse force:    F = Cft qklj 
 

(b) Circular sections: For circular sections, the force coefficients Cf, which are dependent upon values 
of  DVs,  are  given  in  Table  5.25.  The  values  of  Cf  given  in  this  table  are  suitable  for  all  surfaces  of 
evenly distributed roughness of height less than 1/100 diameter i.e. for all normal surface finishes 
and for members of infinite length. 
Force, F   =  Cfqkld 
 
 
 
 
 
 
 
 
 
 
 
 
 

52 

 
Table 5.24: Force coefficients Cfn and Cft for individual structural members (flat sides) of 
infinite length 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

53 

 
Table 5.25 ‐ Force Coefficients Cf for individual structural members of  
                                            Circular Section and Infinte Length 
 
Flow regime    Force coefficient Cf 

Subcritical flow  DVs   6m2/s 

Re   4.1 x 105  1.2 

  6  DVs   12m2/s   

4.1 x 105  Re   8.2 x 105  0.6 


 
Supercritical flow  12  DVs   33m2/s   

8.2 x 105  Re   22.6 x 105  0.7 

DVs   33m2/s   

Re   22.6 x 105  0.8 

Reynolds number, Re > =   

    where:  D is the diameter of the member 
                   Vs is the design wind speed, and  
           v  is the Kinematic viscosity of the air, which is 1.6 x 10‐5 m2/s at 15oC and standard        
          atmospheric pressure. 
 
(c)  Wires and cables: The force coefficients for wires and cables given in Table 5.26 are dependent 
upon values of DVs. 
 

Table 5.26 ‐ Force Coefficients Cf for Wires and Cables (1/D >100) 
Flow Regime  Smooth  Moderately  wire  Fine  stranded  Thick  stranded 
surface wire  (galvanized  or  cables  cables 
painted) 
DVs   0.6m2/s  ‐  ‐  1.2  1.3 
DVs   0.6m2/  ‐  ‐  0.9  1.1 

DVs   6m2/s  1.2  1.2  ‐  ‐ 

DVs   6m2/s  0.5  0.7  ‐  ‐ 

 
 
 
 
54 

 
(4) Single frames: In general, the most unfavourable wind load on a single frame occurs when 
the     wind is at right angles to the frame. 
The wind load acting on a single frame should be taken as  
F = Cf q Ae 
where;  Ae is the effective area of frame normal to the wind direction. 
The force coefficients for a single frame consisting of (a) flat‐sided members or (b) circular 
section members in which all the members of the frame have DVs value less or greater than 
6m2/s are given in Table 5.27. 
 
Table 5.27 ‐ Effective Force Coefficients Cf for Single Frames 
  Force coefficient Cf for: 
Solidity ratio Ø  Flat – sided members  Circular Sections 
Subcritical flow Supercritical flow
2
DVs   6m /s  DVs   6m2/s 
0.1  1.9 1.2 0.7 
0.2  1.8  1.2  0.8 
0.3  1.7  1.2  0.8 
0.4  1.7  1.1  0.8 
0.5  1.6  1.1  1.4 
0.75  1.6  1.5  1.4 
1.0  2.0  2.0  2.0 
 

The solidity ratio Ø is equal to the effective area of a frame normal to the wind direction divided by 
the area enclosed by the boundary of the frame normal to the wind direction. 

(5) Multiple frame structures: This section applies to structures having two or more parallel frames 
where the windward frame may have a shielding effect upon the frames to leeward. The wind 
load on the windward frame and any unsheltered parts of other frames should be calculated as 
in  5.9.8(3),  but  wind  load  on  the  parts  of  frames  that  are  sheltered  should  be  multiplied  by  a 
shielding factor n, which is dependent upon the solidity ratio of the windward frame, the type of 
member comprising the frame and the spacing ratio of the frames. The values of the shielding 
factor are given in Table 5.28. 
       Where there are more than two frames of similar geometry and spacing, the wind load on the 
       third and subsequent frames should be taken as equal to that on the second frame. 
 
 
 

55 

 
Table 5.28 ‐   Shielding Factor,  n 

    Value of n for an aerodynamic solidity ratio of:   
  Spacing  0.1  0.2  0.3  0.4  0.5  0.6  0.7  0.8 & 
  Ratio 
over 
 
Up to 1.0  1.0  0.96  0.90 0.80 0.68 0.54 0.44  0.37
   
2.0  1.0  0.97  0.91  0.82  0.71  0.58  0.49  0.43 
 
 
3.0  1.0  0.97  0.92  0.84  0.74  0.63  0.54  0.48   
   
4.0  1.0  0.98  0.93  0.86  0.77  0.67  0.59  0.54 
 
 
5.0  1.0  0.98  0.94  0.88  0.80  0.71  0.64  0.60 
6.0 and over  1.0  0.99  0.95  0.90  0.83  0.75  0.69  0.66 

The spacing ratio is equal to the distance, centre to centre, of the frames, beams or girders divided 
by the least overall dimension of the frame, beam or girder measured at right angles to the direction 
of the wind. 

Aerodynamic solidity ratio,    = solidity ratio (Ø) x  a constant  

where the constant is: 

1.6    for flat‐sided members; 

1.2      for  circular  sections  in  the  subcritical  range  and  for  flat‐sided  members  in  conjunctions 
       with such circular sections; 

         0.5    for circular sections  in the  supercritical range  and for flat‐sided members  in conjunction   


      with circular sections.  

(6) Lattice Towers: 

(a)  Lattice  towers  of  square  and  equilateral  triangular  sections  constitute  special  cases  for 
which  it is convenient to use overall force coefficient in the calculation of wind load. The wind 
load  should be calculated for the condition when the wind blows against any face.  

             The wind load acting in the direction of the wind should be taken as: 

F = Cf qAe 

              The overall force coefficient Cf is given in Tables 5.29, 5.30 and 5.31. 
56 

 
Table 5.29 ‐   Overall Force Coefficient Cf  for Towers composed of 

Flat‐sided members 

Solidity ratio  Force coefficient of for: 
Square towers Equilateral triangular towers 
0.1  3.8  3.1 
0.2  3.3  2.7 
0.3  2.8  2.3 
0.4  2.3  1.9 
0.5  2.1  1.5 
 

               For square lattice towers the maximum load occurs when the wind blows on to a corner. 

               It may be taken as 1.2 times the load for the face–on wind. 

               For  triangular  lattice  towers  the  wind  load  may  be  assumed  to  be  constant  for  any 
  inclination of the wind to face.  

(b)  Since  it  is  only  in  very  few  cases  with  lattice  towers  composed  of  members  of  circular 
section        that  all  the  members  of  a  lattice  tower  are  entirely  in  either  subcritical  or 
supercritical  flow,  wind  force  calculations  should  be  carried  out  as  described  in  5.9.8(4)  for 
single frames, due  account being taken of the shielding factors in 5.9.8(5). 

              When  it  can  be  shown  that  all  the  members  of  the  tower  are  wholly  in  the  same  flow 
  regime the overall force coefficients Cf  given in Tables 5.29 and 5.30 may be used.  

             Solidity ratio of a frame = Ø. For lattice steel towers, Ø typically varies between about 0.1 and  
  0.3 

57 

 
Table 5.30 ‐ Overall Force Coefficient Cf for Square Towers composed of  

Rounded Members 

Solidity ratio of front  Force coefficient Cf for: 
face, Ø  Subcritical flow Supercritical flow 
2
  DVs < 6m /s (45ft mile/h)  DVs ≥  62/s (45ft mile/h) 
onto face onto corner onto face onto corner 
0.05  2.4  2.5  1.1  1.2 
0.1  2.2  2.3  1.2  1.3 
0.2  1.9  2.1  1.3  1.6 
0.3  1.7  1.9  1.4  1.6 
0.4  1.6  1.9  1.4  1.6 
0.5  0.4  1.9  1.4  1.6 
 

Table 5.31 ‐ Overall Force Coefficient Cf for Equilateral Triangular Towers 

composed of Rounded members 

 
 Solidity ratio of front  Force coefficient of for: 
face, Ø   Subcritical flow  Supercritical flow   
2
  DV < 6m  /s(45ft mile/h)  DV≥ 62/s (45ft mile/h) 
all wind directions  all wind directions   
0.05  1.8 0.8 
0.1  1.7  0.8 
0.2  1.6  1.1 
0.3  1.5  1.1 
0.4  1.5  1.1 
0.5  1.4  1.2 
 
 

58 

 
5.10  EFFECTS OF EARTHQUAKES 

5.10.1    SCOPE AND FIELD OF APPLICATION 

5.10.1.1  This  Code  sets  down  minimum  design  requirements  to  be  met  when  dealing  with            
seismic  situations  i.e.  situations  in  which  the  earthquake  action  is  considered  as  a  critical 
action in conjunction with other dead loads or live loads.  It applies to: 

(1)  Reinforced  and  Prestressed  concrete  buildings  for  ordinary  uses,  having  structural 
resisting systems belonging to one of three types defined below: 

(a)  Frame  System:  A  system  in  which  both  vertical  loads  and  lateral  forces  are        
resisted by space frames. 

(b) Wall System: A system in which both vertical loads and lateral forces are resisted 
by structural walls either single or coupled. 

(c) Dual System: A system in which support for vertical load is essentially provided 
by a space frame.  Resistance to lateral action is contributed to, in part, by the frame 
system and also in part by structural walls, isolated or coupled. 

5.10.2 DEFINITIONS AND NOTATIONS 
Definitions 

Cross‐tie:  A   continuous  bar  with  a  minimum  diameter  of  6mm,   having  a  1350   hook with  a 
ten‐diameter extension at one end,  and a 900  hook with a six diameter extension at the other end.  
The hooks shall engage hoop bars and be secured to longitudinal bars.   

Hoop:  A closed tie or continuously would tie with a minimum diameter of 6mm the ends of which 
have 1350 hooks with ten‐diameter extensions that encloses the longitudinal reinforcement.  

Boundary elements:  Portions  along  the  edges  of  walls  and  diaphragms  strengthened  by 
longitudinal  and  transverse  reinforcement.    Boundary  elements  do  not  necessarily  require  an 
increase  of  thickness  of  the  wall  or  diaphragms.  Edge  openings  within  walls  and  diaphragms  may 
also have to be provided with boundary elements.  

59 

 
Notations  

A         =     peak ground acceleration  

Ac        =     confined area measured to outside peripheral transverse reinforcement. 

Ag        =     gross sectional area of concrete 

Cd        =    design seismic coefficient  

Cg  =    centre of mass  

Ck  =    centre of stiffness  

E  =    design seismic action (symbolic)  

I  =    importance factor  

Mu,d      =  ultimate moment of a concrete section, evaluated with factored values of concrete and 
steel strengths 

 M+u,d   =  ultimate moment of a concrete section, evaluated with characteristic values of concrete 
and steel strengths. 

Nd        =  design axial force under the most unfavourable load combination including the seismic 
action. 

K  =    behaviour factor 

S  =    site coefficient  

Si  =    soil type index  

Vcd  =    shear force carried by concrete in beam or column sections 

a       = plan dimension of the building in the direction orthogonal to that of seismic action                         

bw  =   web width of a concrete section 

h,b  =   height and width of beams,  major and minor sides in columns 

h’, b’  =   distance between reinforcement bars located at the ends of sides in and b, respectively, 
measured to outside the peripheral bars 

60 

 
d     =   distance from centre of stiffness and centre of gravity of the generic floor  

Sh       =    spacing of transverse reinforcement in beams, columns and walls. 

fcd       =    design concrete strength 

h         =    height of a floor 

lw        =    horizontal wall length 

hw  =  total height of a wall 

hn  =  vertical distance between floors in walls 

α  =  spectral amplification factor  

β  =  parameter of the elastic response spectrum  

γi  =  distribution factor  

γn  =  over‐capacity factor 

Δel  =  elastic interstorey drift under the seismic actions   

ζ  =  ratio between maximum and minimum shear force at a beam end       

Θ  =  deformability index  

ξ  =  amplification factor for torsional effects  

w  =  dynamic magnification factor  

τRd  =  shear design stress of concrete  

 
61 

 
5.10.3  DESIGN CRITERIA 

5.10.3.1 Reliability Differentiation 

 Structures shall be classified under the following reliability levels: 

(1)  Class  I:  Buildings  that  are  required  to  remain  functional  and  to  suffer  reduced         
damage  after  a  strong  seismic  attack  (e.g.  essential  rescue  facilities  such  as         
hospitals, fire and police stations, electricity stations etc. buildings with likely large 
number of occupants such as schools, audience or spectacle halls, etc). 

(2)  Class II: Buildings not included in 5.10.3.1 (1) 

(3)  The  different  reliability  levels  proper  to  each  Class  shall  be  obtained  by  amplifying 
the design action with a factor I, called importance factor. 

5.10.3.2 Ductility Levels 

                Structural  systems  covered  by  the  Code  may  be  designed  to  possess  different  ‘ductility’ 
levels according to the following classification: 

(1)  Ductility Level I (DL I) ‐ is that proper to structures proportioned in accordance to BS 
8110 (1985) with additional requirements on detailing contained in 5.10.8. 

This ductility level, I is suitable for low rise buildings. 

(2)  Ductility Level II (DL II)‐ for this level seismic provisions are to be adopted, enabling 
the  structure  to  enter  the  inelastic  range  of  response  under  repeated  reversed 
loading, while avoiding premature brittle‐type failures.  

(3)  Ductility Level III (DL III) ‐ special procedures for the evaluation of design action and 
for the proportioning and detailing of the elements are to be adopted to ensure the 
development of selected stable mechanisms associated with large energy dissipation 
capacities.  DL III structures should be preferred whenever large uncertainties exist 
(e.g.  Local amplification effects of difficult evaluation etc). 

 
62 

 
5.10.4  METHODS OF ASSESSMENT 

5.10.4.1 Basic data 

5.10.4.1.1 Material Characteristics 

5.10.4.1.1 (1) Concrete 

     Normal concrete grades shall satisfy the following requirements (Table 5.10.4.1) 

                 Table 5.10.4.1 

Ductility Level  Minimum Grades 
DL I  C20

DL II  C20 

DL III  C25 

5.10.4.1.1(2)  Steel 

(a)  DL I and DL II Structures 

The reinforcing steel is defined by its characteristic strength. 

(b)  DL III Structures 

The following additional requirements shall be satisfied. 

(i)  It  must  be  proven  the  steel  used  possesses  adequate  ductility  under 
repeated  reversed deformations. 

(ii)  Steel  grades  with  characteristic  strengths  higher  than  S400  (400N/mm2) 
shall not be used, unless it is demonstrated that the use of higher grades in 
special section arrangements does not affect unfavourably the ductility. 

(iii)  The actual yield stress shall not exceed its normal values by more than 15%. 

63 

 
(iv)       The  ratio of the  mean value of the ultimate strength to actual yield stress 
shall not be less than 1.25 for S220 and 1.15 for S400 

(v)  Only  high  bond  steel  shall  be  used  for  flexural  reinforcement,  unless 
adequate provisions are taken to ensure bond and anchorage. 

5.10.4.1.2 Material Safety Factor,  γm

Design  values  of  strength  for  concrete  and  steel  shall  be  obtained  from  their  respective 
characteristic values by using the factors: 

Concrete  γ c  = 1.5 

Steel  γ s  = 1.15 

5.10.4.1.3 Structure Behaviour Factors   

(1)  The  values  of  the  behaviour  factor  K,  defining  the  intensity  of  the  design  action 
(section  5.10.5.3)  as  a  function  of  the  structural  type  and  of  the  selected  ductility 
level, are given in Table 5.10.4.2 

         Table 5.10.4.2 DESIGN BEHAVIOUR FACTORS 

Ductility  Ductility  Ductility 


Structural System 
Level I  Level II  Level III 

Frame  2 3.5 5

Wall and Dual  2  3  4 

(2)  The values of K in Table 5.10.4.2 for wall and dual structures apply if, at least 50% of 
the lateral force in both directions is resisted by coupled walls. 

(3)  If  condition  5.10.4.1.3(2)  is  not  satisfied,  the  K  values  for  wall  and  dual  structures 
shall be reduced by a factor of 0.7. 

(4)  Ductility  Level  I  is  permitted  only  for  Class  II  structures  in  areas  of  moderate 
seismicity. 

64 

 
(5)  Class I structures to be built in high seismicity areas shall be preferably designed for 
ductility level III.  If appropriate, K values relative to DL II could be used in this case. 

5.10.4.1.4  Design Load Combination 

The fundamental combination of load effects to be used for limit states verification (Section 
5.10.7.4) is 

Sd = S (G + P + E + ∑ψi Qik)                                        ... 5.10.4.1.1 

where  G   =  all permanent loads at their normal value 

P   =  the long‐term prestressing force 

E   =  the design seismic action as defined in Sect .5.10.5.3.4 

Qik =  fractile  values  of  extreme  distributions  of  all  live  loads  whose  duration  of 
application is long enough for the probability of their joint occurrences with 
earthquake action to be considered. 

ψ I  =  factors required to change the fractile values Qik to the average values of Qik 
in their instantaneous distribution (See Table 5.10.4.3) 

S   =    Site Co‐efficient 

       Table 5.10.4.3:  COMBINATION FACTOR   ψ I FOR LIVE LOADS 

Live loads from persons and equipment  0.3 

Live loads from persons at places with likelihood of 
0.5 
large number of occupants (halls) 

Long term storage (warehouse, libraries)  0.9 

Live loads on staircases and corridors  1.0 

 
65 

 
5.10.4.2 Structural analysis   

5.10.4.2.1  Building Configuration 

A building shall be classified as regular when the following conditions are satisfied, regarding 
both plan and vertical configuration. 

(a) Plan Configuration 

(i)  The  building  has  an  approximately  symmetrical  plan  configuration  with 
respect  to,  at  least  two  orthogonal  directions  along  which  the  earthquake 
resisting elements are oriented. When re‐entrant corners are present, they 
do not exceed 25 percent of the building external dimension. 

(ii)  At any storey the distance (measured in the direction orthogonal to that of 
the  seismic  action)  between  the  centre  of  mass  and  that  of  the  stiffness 
does not exceed l5% of the ‘resistance radius’ defined as the square root of 
the ratio of storey torsional and translation stiffnesses. 

(b)   Vertical Configuration      

(i)  The  stiffness  and  mass  properties  are  approximately  uniform  along  the 
building height. 

(ii)  In  frame  structures,  the ratio  between actual  shear capacity  (sum  of shear 


forces  contributed  by  all  vertical  elements  at  their  design  strengths)  and 
design  shear  does  not  differ  more  than  20  percent,  for  any  two  storeys  of 
the building. 

(iii)  In the case of a gradual setback along its height, the setback at any floor is 
not greater than l0% of the plan dimension in the direction of the setback.  
This clause need not be complied with if the setback occurs within the lower 
l5% of the total height of the building. 

5.10.4.2.2 Application of Seismic Action   

(1)  Horizontal Action 

(i)  The  seismic  actions  shall  be  applied  to  the  building  in  the  directions 
producing in each element the most unfavourable effect. 
66 

 
(ii)  In buildings having one axis of symmetry, the seismic action can be assumed 
as acting separately along this axis and its orthogonal direction 

(2)  Vertical Action 

(i)  The  vertical  component  of  the  seismic  action  shall  be  considered  in  the 
design of non‐vertical cantilevers and of prestressed beams. 

5.10.4.2.3 Analytical Model 

(1)  The  determination  of  the  seismic  effects  on  the  structure  shall  be  based  on  an 
idealized  mathematical  model  which  is  adequate  for  representing  the  actual 
behaviours;  the  model  shall  also  account  for  all  non‐structural  elements  that  can 
influence the response of the main resisting system. 

(2)  For the  purpose  of the  present  code, the  determination  of the  load effects  due to 
design forces may be based on a linear elastic model of the structural system. 

(3)  Regular  buildings  can  be  designed  according  to  the  simplified  method  of  analysis 
(indicated as equivalent static analysis) described in 5.10.4.2.4 provided their height 
does not exceed 80m, and the fundamental period is shorter than 2 secs. 

(4)  If conditions in 5.10.4.2.3.(3) are not satisfied or if the building is of irregular type, 
the dynamic method in 5.10.4.2.5 shall be applied. 

5.10.4.2.4  Equivalent Static Analysis 

(1)  Horizontal Design Forces 

(a)  The  design  lateral  force  to  be  applied  at  each  floor  level  in  the  direction 
being analysed, shall be given by: 

F = Cd .  γ i . W                                                  .... 5.10.4.2.1 


i

where Cd  = design seismic co‐efficient, equal in value to the design response 
spectrum, as given in Section 5.10.5.3.4 

γ    = 
i distribution  factor,  depending  on  the  height  of  the  floor, 
measured from the building base 
67 

 
Wi   =  total gravity load at floor i 

(b)  In cases where the period T is not calculated from methods of mechanics Cd 
shall be taken as: 

1
C = I . A . S .α .
                                                                                                                                       ... 5.10.4.2.2 
d
K
(c)  γi
The distribution factor  γi    is given by the following expression 

∑W i
                                                                                           ... 5.10.4.2.3 
γ i = hi  
∑ W i hi
 

where hi is the height of floor i  from the foundation level. 

(2)  Torsional Effects 

(a)  At each floor of the building, the lateral design force shall be assumed to be 
displaced  from its nominal location at  the distances e1 and  e2 illustrated in 
Figure  5.10.4.1,  which  ever  is  most  unfavourable  for  every  member  to  be 
checked. 

           Fig. 5.10.4.1 ‐ Torsional Effects 

(b)  The expressions for e1 and e2 are: 

            e1 =  0.5 d + 0.05 a            ... 5.10.4.2.4 

e2  =  0.05 a             ... 5.10.4.2.5 

68 

 
(c)  The  total  shear  force  and  torsional  moment  at  the  generic  floor  shall  be 
distributed  to  the  various  resisting  elements  below  that  floor  with  due 
consideration  of  their  relative  stiffness  as  well  as  of  the  stiffness  of  the 
diaphragm. 

(d)  Symmetrical  Cases: When complete symmetry of stiffness  and  mass  about 


one  axis  parallel  to  the  direction  of  the  seismic  excitation  exists,  torsion 
effects can be accounted for by means of the following simplified procedure: 

(i)  the lateral design force shall be applied at the floor centre of gravity, 
to be distributed to the various elements as above; 

(ii)  the actions in each of the elements shall be further multiplied by a 
factor  ξ defined as: 

                                                                     ... 5.10.4.2.6 
x
ξ = 1 + 0.6
a
             

where  x    is  the  distance  of  the  element  from  the  floor  centre  of  gravity, 
measured perpendicularly to the direction of seismic action. 

(3)  Second Order Effects   

(a)  Second‐order effects on storey shears and moments need not be considered 
when the following condition is satisfied at every floor: 

            W . Δe l . K
Θ= ≤ 0.10
V .h
 

where  Θ  = deformability index 

 V  = seismic design shear force acting across the storey considered 

∆el  = elastic interstorey drift due to design action 

K   = behaviour factor 

h   = floor height 

W  = total gravity load above the considered storey   
69 

 
(b)  The deformability index, Θ shall not in any case exceed the value 0.20; 

(c)  For 0.10 < Θ < 0.20 second order effects shall be accounted for by means of 
one of the statistical methods indicated in BS 8110 (1985). 

5.10.4.2.5  Modal Analysis Procedure   

(1)  Modelling 

(a)  If  the  building  can  vibrate  in  two  orthogonal  directions  without  significant 
coupling,  it can be analysed by means of  two separate  planar  models,  one 
for  each orthogonal direction 

(b)  The  condition  stated  in  5.10.4.2.5(1)  (a)  shall  be  assumed  to  occur  when 
5.10.4.2.1(a) (ii) is satisfied. 

(c)  When  5.10.4.2.1(a)(ii)  is  not  satisfied  the  model  shall  account  for  the  non‐
planar motion of the structure 

(2)  Modes   

(a)  In the case of planar models, the analysis shall include for each of the two 
orthogonal axes at least the lowest three modes of vibration, or all modes of 
vibration with periods greater than 0.4 secs., whichever is greater. 

(b)  For non‐planar models the analysis shall include for each direction of seismic 
action,  at  least  four  modes,  two  of  them  predominantly  translational  and 
two predominantly rotational, or all modes of vibration with periods greater 
than 0.4 secs., whichever is greater. 

(c)  The  mode  considered  shall  be  those  with  the  greatest  participation 
coefficients for the direction under consideration 

(3)  Combination of Modal Responses   

The  response  quantities  (force,  displacements  etc)  separately  obtained  for  each 
mode under the effect of the design response spectrum given in Section 5.10 5.3.4 
shall be combined to obtain their corresponding design values by taking the square 
root of the sum of the squares of modal values. 

70 

 
(4)  Torsional Effects 

(a)  At  each  floor  of  the  building  the  mass  contributing  to  inertia  forces  shall  be 
assumed  to  be  displaced  from  its  nominal  location  by  the  amount  "0.05a” 
whichever is more unfavourable for the element to be checked, ‘a’ being the 
dimension  of  the  building  in  the  direction  orthogonal  to    that  of  the 
considered seismic action. 

(b)  When  the  building  is  analysed  by  means  of  planar  models  (Clause  5.10.4.2.5 
(1)), torsional effects can be accounted for by increasing the action effects due 
to the translational oscillations of the building by the factor ξ defined as: 

ξ = 1 + 0.6 x/a 

where x is the distance of the planar element considered from the floor centre 
of gravity, measured perpendicular to the direction of the seismic action. 

(5)  Second ‐ order effects  

Clause 5.10.4.2.4 (3) applies. 

71 

 
5.10.5  SEISMIC ACTION 

5.10.5.1  Seismic Zones 

For the application of this Code, a seismic risk map (Fig 5.10.5.1) has been used to discretize 
the  area  of  Ghana  into  a  number  of  zones.    Within  each  zone  the  normalized  ground 
acceleration is assigned a constant value as shown in Table 5.10.5.1. 

Fig. 5.10.5.1 ‐ Seismic Risk Map Of Ghana 

72 

 
                Table 5.10.5.1:  DEFINITION OF SEISMIC ZONES 

Assigned Horizontal Design 
Seismic  Ground Acceleration: A 
Zone 
(g units of gravity) 

0  0 

1  0.15 

2  0.25 

3  0.35 

5.10.5.2  Characteristics of Seismic Actions 

(1)  For  the  purpose  of  the  code,  the  ground  motion  shall  be  adequately  described  by 
means of: 

(a)  the peak  ground  acceleration  Amax, treated as  a random variable of  known 


distribution;   

(b)  one  or  more  response  spectra  for  horizontal  motion,  having  a  form  
appropriate for the area and firm soil conditions, normalized to Amax = 1 and 
probabilistically characterized; 

(c)  one  or  more  response  spectra  for  vertical  motion,  scaled  to  2/3  of  the 
correspondence horizontal motion response spectra. 

(2)  For particular zones, for instance, where geological evidence indicates the possibility 
of  ‘near  field’  type  of  shocks  (for  which  the  response  spectrum  concept  is 
inadequate) or where there is extensive and deep soil layering (for which selective 
amplification  can  occur)  the  expected  characteristics  of  ground  motion  shall  be 
determined by special studies. 

 
73 

 
5.10.5.3  Design Seismic Action 

5.10.5.3.1  Normalized Elastic Response Spectrum 

For  the  purpose  of  this  Code,  the    shape  of  the  ‘standard’  (rocky  or  firm  soil  condition) 
elastic response spectrum normalized to a unit peak ground acceleration shall be idealized 
as shown in Fig. 1.4.2. 

Fig. 5.10.5.2 ‐ Normalised Elastic Response Spectrum 

5.10.5.3.2  Site Effects 

When  more  detailed  knowledge  of  the  effects  of  local  soil  conditions  and  on  the 
characteristics of ground  motions arriving at the site from possibly different sources is not 
available the procedure in Clause 5.10.5.3.2 (1) and (2), and 5.10.4.4.3 shall be applied. 

(1)  Soil Profile Types 

The effects of site conditions on building response shall be established based on the 
soil profile types defined as follows: 

i  SOIL PROFILE S1: 

Rock of any characteristic either shale‐like or crystalline (such material may be 
characterized by a shear wave velocity greater than 800mm/sec); or stiff soil 
conditions  where  the  soil  depth  is  less  than  60m  and  the  soil  type  overlying 
rock are stable deposits of sands gravel or stiffer clays. 

74 

 
ii  SOIL PROFILE S2: 

Deep  cohesionless  or  stiff  clay  soil  conditions,  including  sites  where  the  soil 
depth  exceeds  60m  and  the  soil  types  overlying  rock  are  stable  deposits  of 
sands, gravels or stiff clay. 

iii  SOIL PROFILE S3:  

            Soft‐to‐medium  stiff  clays  and  sands,  characterized  by  l0m  or  more  of  soft‐
medium  stiff  clay  with  or  without  intervening  layers  of  sand  and  other 
cohesionless soils. 

In locations where soil properties are not known in sufficient detail to determine the soil profile type 
or where the profile does not fit any of the three types, soil profile S2 shall be used. 

(2)  Site Co‐efficient 

The site co‐efficient S is used to modify the standard elastic response spectrum to account for the 
site condition.  Its values are given in Table 5.10.5.2 

                       Table 5.10.5.2:  SITE COEFFICIENT 

Soil Coefficient  Soil Profile Type

  S1  S2  S3 

S  1.0  1.2  1.5 

5.10.5.3.3 Site ‐ Dependant Normalized Elastic Response Spectrum 

The  site‐dependant  normalized  elastic  spectra  for  the  three  soil  profiles  are  shown  in  Fig 
5.10.5.3, their ordinates being defined as the smallest from the following expressions: 

R as = 1 + (α – 1). T/T1 

R as = α  for soil types S1, S2, S3 

= 0.8α for soil S3 if A, as defined in Clause 5.10.5.3.4, is greater than 0.3g 

R as = S. α. ( T/T1)β 

75 

 
In case of lack of specific site‐related information the following can be assumed 

T1       =     0.12 secs     T2  = 0.4 secs 

  α  =  2.5               β   = 2/3 

However, for soil type S3 the value T1 = 0.25 secs. can be adopted. 

 Spectra for vertical motions may be determined with sufficient accuracy by multiplying the 
ordinates of the spectra for horizontal motions by a factor of 2/3. 

Fig 5.10.5.3 ‐ Site Dependent Normalized Elastic Spectra 

5.10.5.3.4  Design Response Spectrum 
 
The  ordinates  of  design  response  spectrum  are  given  by  the  smallest  of  the  following 
expressions:  

 
1
R a (T) = I . A .α . ( )
           
K   for soil type S1, S2 and S3, or  

1
R a (T) = 0. 8 . I . A . α . ( )      for soil type S3 if A > 0.3g 
K

T2 β 1
R a (T) = I . A . α . S . ( ) .( )  
T K

76 

 
Where: 

I  is the importance factor defined in Section 5.10.3.1(3) (see Table 5.10.5.3) 

A  is the peak ground acceleration to be adopted for the seismic zone of interest (% of g ‐ 
Table 5.10.5.1) 

S  is the site coefficient as given in Table 5.10.5.2 

K  is the behaviour factor given in Table 5.10.4.1.3 

In the case of lack of specific site‐related information α, β and T2 are assigned the following 
values:  

               α = 2.5,     β =  2/3,    T2  = 0.4 secs. 

    Table 5.10.5.3:   IMPORTANCE FACTOR 

Class  Factor 

I  1.4 

II  1.0 

5.10.6  DESIGN ACTIONS 

5.10.6.1  General 

Structural elements shall be dimensioned and verified (see section 5.10.7) for design actions 
as defined in this section. 

5.10.6.2   Ductility Level I:  DL I 

DL I structures shall be dimensioned directly on the basis of the results of structural analysis, 
with a possible redistribution of action effects in accordance with BS.8110 (1985) 

5.10.6.3  Ductility Level II:  DL II 

(1)  Elements subject to bending ( N d ≤ 0 . 1 . A g . f cd ) 

     (a) Bending moments: 

77 

 
The  design  bending  moments  shall  be  those  obtained  from  linear  analysis  of  the 
structure  for  the  load  combination  given  by  equation  5.10.4.1.1.  Redistribution 
according to BS.8110 (1985) is permitted. 

      (b) Shear Forces: 

(i)  The  design  shear  forces  shall  be  determined  from  the  condition  of  static 
equilibrium of the element subjected to the relevant transverse load, if any, 
and a rational combination of the end moments. 

(ii)  The  end  moments  shall  correspond  to  the  design  flexural  strengths  of  the 
end actions based on actual reinforcement provided. 

(iii)  The algebraic ratio between the maximum and minimum values of shear at 
each end section shall be denoted by  ζ .  The value of ζ should not be taken 
less than minus one (Fig. 5.10.6.1). 

                 A  VA,d  (I)          B              A  ζVA,d      (II)             B 

     

    VA,d =  VA,d + MA + M1B                           ζVA,d =  VA,d  ‐  M1A   + MB 

                                 L                                     L               

Fig 5.10.6.1 - DESIGN SHEAR FORCES


 

78 

 
(2)  Elements Subject to bending and axial force ( N d > 0 . 1 Ag . f cd ) 

    (a)  Axial forces and bending moments 

(i)  For regular structures, three storeys and higher, to which equivalent static analysis 
has been applied, the column moment due to lateral forces alone shall be multiplied 
by the dynamic amplification factor w as given by the following expressions: 

Planar Frames 

w = 0.6 T1 + 0.85 (1.3 < w < 1.8)        .... 5.10.6.1 

Spatial Frames 

w = 0.5 T1 + 1.10 (1.5 < w < 1.9)      .... 5.10.6.2 

where T1 is the fundamental period of the structure. 

(ii)  The values of the dynamic factor w given in 5.10.6.3(2)(a)(i) are applicable to storeys 
within the upper two‐thirds of the building height.  Below this level a linear variation 
of w should be assumed: the value at first floor level should be taken as 1.3 and 1.5 
for planar and spatial frame respectively (Fig 5.10.6.2). 

Fig. 5.10.6.2 ‐   Values of Dynamic Factor at Various Floors 

79 

 
(iii)  Column  moments  in  addition  shall  satisfy  the  condition  on  the  relative  strength  between 
columns and beams framing into a joint as specified in Clause 5.10.7.1(3). 

(b)  Shear Forces 

(i)  In  evaluating  the  design  shear  forces  from  the  condition  of  static  equilibrium  the 
design end moments shall be those producing maximum shear force obtained from 
analysis, modified if appropriate by the dynamic magnification factor. 

(3)  Structural Walls 

(a)  The  design  actions  shall  be  those  obtained  from  a  linear  analysis  of  the  building 
modified as appropriate in accordance with Clauses 5.10.6.3(1)(b) to 5.10.6.3(3)(c). 

(b)  Redistribution 

      (i)  The distribution of the total force to the various walls, as obtained from the elastic 
analysis  may  be  modified  provided  the  global  equilibrium  is  maintained  and  the 
maximum value of the action in any wall is not reduced by more than 30%  

    (ii)  In a coupled wall, the elastic shear force in the coupling beams can also be modified 
with  a  maximum  reduction  of  20%  provided  that  corresponding  increases  in  the 
shear capacities of beams at other floors are made. 

(c)  Bending Moment Design Envelope 

The  design  moments  along  the  height  of  the  wall  shall  be  those  given  by  a  linear 
envelope of the calculated moment diagram, vertically displaced by a distance equal 
to the horizontal length of the wall.  (Fig. 5.10.6.3) 

80 

 
 

Fig5.10.6.3 ‐  BENDING MOMENT DESIGN ENVELOPE 

(d)  Earthquake Induced Axial Load in Coupled Walls 

(i)  The design axial load in the walls due to the lateral action shall be computed using 
the shear strengths of the coupling beams above the section considered, calculated 
by using characteristic values of concrete and steel strength. 

(ii)  The  shear  strength  of  the  beams  calculated  in  5.10.6.3(3)(d)(i)  shall  be  further 
amplified by a factor of 1.25 

(e)  Dynamic Magnification Factors 

(i)  Where the equivalent static analysis is adopted, the shear forces in the walls shall be 
magnified by the dynamic amplification factor w  as  given by the  expression below 
for buildings up to 5 storeys high 

w = 0.1N + 0.9.........     1.5.3 

                              

                            where N is the number of storeys 

(ii)  For  walls  taller  than  five  storeys,  w,  shall  be  linearly  increased  up  to  the  value  of 
    w =1.8 for N = 15 

81 

 
 

5.10.6.4  Ductility Level III  : DL III 

(1)  Elements subject to bending ( N d ≤ 0 . 1 . A g . f cd ) 

(a)  Bending moments: The design bending moments shall be those obtained from linear 

analysis of the structure.  Redistribution according to BS 8110 (1985) is permitted. 

(b)  Shear Forces: 

      (i)  The design shear forces shall be determined from the conditions of equilibrium of the 

element subjected to the relevant transverse loads, if any, and to a rational adverse 

combination of end moments, as specified in 5.10.6.4(1)(b)(iii) 

     (ii)  The end moments shall correspond to the design flexural strengths of the end sections 

based on actual reinforcement provided, multiplied by the factor   γ n = 1.25  

     (iii)  The algebraic ratio between the maximum and minimum values of shear force at a  

section shall be denoted by  ζ .  For the purposes to follow, the value of ζ should 

not be taken smaller than minus one.(Fig 5.10.6.4) 

      A  VA,d   (1)         B      A   ζVA,d   (11)    B 

                             VA,d =  VA,d +  MA + M1B      ζVA,d =  VA,d ‐ M1A + MB 

L L

Fig 5.10.6.4 DESIGN SHEAR FORCES 

82 

 
 

(2)  Elements subject to bending and axial force ( Nd > 0 .1. Ag . f cd  ) 

(a)  Axial forces and bending moments 

 (i)  The  axial  forces  and  bending  moments  to  be  used  for  column  design  shall  be  determined               
from a linear analysis of structures, eventually redistributed according to BS 8110 (1985). 

(ii)For  regular  structures,  three  storeys  and  higher,  to  which  equivalent  static  analysis  has  been 
applied,  the  column  moment  due  to  the  lateral  forces  alone,  shall  be  multiplied  by  the  dynamic 
magnification factor, w, as given by the following expressions: 

Planar frames: 

     w = 0.6  T + 0.85
    (1.3 ≤  w ≤ 1.8
  )       5.10.6.4 
1

                             Spatial frames: 

   
w = 0.5 T 1 + 1.10 (1.5 ≤ w ≤ 1.9 )
                  5.10.6.5 

where T1, is the fundamental period of the structures. 

(iii)  The  values  of  the  dynamic  factor,  w  as  given  in  5.10.6.4(2)(a)(ii)  are  applicable  to  storeys 
within the upper two‐thirds of the building height.   Below this level a linear variation of, w, 
should be  assumed; the  value  at first floor  level  should be  taken as  1.3  and  1.5  for  planar 
and spatial frames respectively. (Fig 5.10.6.5) 

83 

 
 

Fig. 5.10.6.5 ‐ Values of Dynamic Factor 

(iv) Column moments shall satisfy the condition on the relative strength between columns and 
beams framing into a joint (see 5.10.7.1 (3)) 

(b)  Shear forces 

(i)          In evaluating the design shear forces from the conditions of static equilibrium the design end 
moments shall be the most adverse ones as obtained from the analysis of the structure. 

(ii)      The end moments as calculated above shall be further amplified, if appropriate by the dynamic 
magnification factors, and by the  γ n  factor:   γ n = 1.10  

(3)  Beam ‐ Column Joints 

(a)  The design actions shall be those induced in the joint when the design ultimate 

moments of the beam or beams multiplied by a factor  γn, equal to 1.25 are developed, 

except in cases when hinges are permitted to form in the columns (see Clause 5.10.7.1 (3)) 

The axial force in the column shall be the minimum corresponding to the design 

seismic actions. 

 
84 

 
(b)  Horizontal Shear Force (Vjh) 

(i)  Interior Joint (see Fig. 5.10.6.6) 

The  shear  force  Vjh  across  a  typical  interior  joint  without  prestressing  may  be  calculated 
from: 

                 
V jh = γ n ( As1 + As2 ) f yd - V col
              ........  5.10.6.6 

where                 

Vcol =2 l1 .M1   + l2   M2      / ( lc + l’c)                            .........    5.10.6.7 

                  l1n             l2n     

with   

                             l1, l2     = centre to centre span of adjacent beams 

                            l1n ,l2n   = clear spans of adjacent beams 

                            lc, l'c     = centre to centre upper and lower column heights 

                              M1, M2 = design end moments of beams multiplied by  γ n = 1.25  for spans l1  and l2    

                                  respectively.                       

                            As1, A s2 = top and bottom steel in beam 

85 

 
 

            Fig. 5.10.6.6  Design Shear Actions at Beam – Column Joints 

(ii)  External joints 

For external joints equation 1.5.6 still applies while equation 5.10.6.7becomes 

       
⎛ l ⎞
 
V col = 2 ⎜⎜ 1 . M 1 ⎟⎟ / ( l c + l ′c )
⎝ l 1n ⎠

                           5.10.6.8 

               (c)        Vertical Shear Force (Vjv) 

The vertical shear force may be approximately as follows: 

  bb
V jv = V jh .
hc
                            5.10.6.9 

 where 

bb = depth of beam 

hc = width of column 

86 

 
(d)  When two non co‐planar frames have common joints, verification of these joints 

may be considered in each direction separately. 

(4)  Structural Walls 

(a)  The design actions shall be those obtained from a linear analysis of the building 

modified as appropriate in accordance with clause 5.10.6.4(b) ‐ (f) 

(b)  Redistribution 

(i)  The distribution of the total force to the various walls, as obtained from the 

                             elastic analysis, may be subsequently modified, provided the global equilibrium is            

                            maintained and the maximum value of the action in any wall is not reduced by   

                            more than 30% 

               (ii)  In a coupled wall, the elastic shear forces in the coupling beams can also 

be modified with a maximum reduction of 20% provided corresponding 

increases in the shear capacities of beams at other floors are made 

(c)  Bending Moment Design Envelope 

The  design  moments  along  the  height  of  the  wall  shall  be  those  given  by  a  linear 
envelope of the calculated moment diagram, vertically displaced by a distance equal 
to the horizontal length of the wall. (Fig5.10.6.7) 

87 

 
 

Fig5.10.6.7 BENDING MOMENT DESIGN ENVELOPE 

(d)      Earthquake induced Axial Load in Coupled Walls 

The design axial load in the walls due to the lateral action shall be computed using 
the  shear  strengths  of  the  coupling  beams  above  the  section  considered  which 
should  be  calculated  from  the  characteristic  values  of  concrete  and  steel  strength. 
The  shear  strength  of  the  beams  thus  calculated  shall  be  further  amplified  by  a 
factor of 1.25 

 (e)  Dynamic Magnification Factor 

Where the equivalent static analysis has been adopted, the shear forces in the walls 
shall be increased by the dynamic amplification factors w as given by the expression 
below, for buildings up to 5 storeys high: 

                            
w = 0.1 N +  0.9           5.10.6.10 

where N is the number of storeys. 

88 

 
For walls taller than 5 storeys w shall be linearly increased up to the value of  

w = 1.8 for N = 15 

(f)  Shear Forces 

(i)  The design shear forces in walls shall be compatible with the actual flexural strength 
that can possibly be developed at the base of the walls 

(ii)  The design shear forces shall be obtained by multiplying the shear forces due to the 
Code loading by the following  γ n  factor, 

                  
+
γ n = M                   
u, d
        5.10.6.11    
M d
 

where 

Md          is the design moment obtained from the analysis, and  

M+u,d  is  the  flexural  strength  of  the  section  on  the  basis  of  actual 
reinforcement  provided  calculated  by  using  the  characteristic  values  of 
concrete and steel strengths. 

In evaluating the flexural strength of the base section the appropriate axial load shall 
also be considered. 

(iii)  The factor  γ n  need not be taken greater than 4      

89 

 
5.10.7  DIMENSIONING AND VERIFICATION 

5.10.7.1  Linear Elements (General) 

(1)  Design Strengths 

The design strengths of the structural elements in bending, bending with axial force, 
shear and torsion shall be evaluated in accordance with BS 8110 except as modified 
by this Section 5.10.7 

     (2)           Limiting Axial Load 

The  design  axial  compression  load  under  the  most  severe  load  combination 
including seismic action shall not exceed the following limit 

  0.5 A g . f  
ck

               (3)           Beam ‐ Column Strength Ratio 

(a)Except for cases where hinge formation in column is permitted (see 5.10.7.1 (3) 
(b)  (iii)  at  any  beam  ‐  column  joint  the  sum  of  the  absolute  values  of  the  design 
ultimate moments of the columns (under the most unfavourable value of the axial 
force) shall not be less than the  sum of the absolute values of the design ultimate 
moments of the beams framing into the joint  (Fig.5.10.7.1) 

Fig.5.10.7.1 ‐  Beam – Column Strength Ratio 

90 

 
(b)  DL III Structure 

(i)  For columns of DL III Structures, the design bending moments shall account for 
possible increase in strength of the beams framing into the joint. 

(ii)  Unless otherwise justified, the global strength increase can be assumed as: 

γn = 1.15            5.10.7.1 

and is applicable to all storeys, including column bases in the first storey. 

(iii)  Development of plastic hinges in columns and of columns hinge mechanism 
(i.e. exemption from the prescription on beam – column ratio) is permitted 
in the following cases:‐ 

‐  for  frames  having  four  or  more  columns,  hinging  is  permitted  to 
occur in one column for every three others remaining elastic. 

‐  column  hinge  mechanisms are permitted in  single  and  two –storey 


buildings and in the top storey of multi‐storey building. 

  

(4)  Resistance to Shear 

(a)  Contribution of Concrete 

The magnitude of the term Vcd, expressing design resistance contributed 

by concrete shall be taken as follows: 

(i)  When  Nd ≤ 0.1 Ag fcd , Vcd shall be assumed to be zero in all regions 
where stirrup‐ties are required in accordance with Clause 5.10.8.2.3 
(with the exception of Case (c)) 

(ii)  When  Nd > 0.1 Ag fcd ,  Vcd  shall be computed by the expression 

Vcd = 2τRd bw d β1                    5.10.7.2   

where  the  values  of  τRd  are  given  in  Table  1.6.1  as  functions  of 
concrete grades and β 1 is given by 5.10.7.4 

91 

 
    
M
β 1 = 1+ o ≤ 2  
              Md                 5.10.7.3 

           

where Mo and Md are decompression moment and design moment 
respectively. Mo shall be computed by the expression 

Mo = Nd h/2                           5.10.7.4 
   

Table 5.10.7.1: DESIGN CONCRETE SHEAR STRESS

  Concrete grade

25  30  35 

τRd (Mpa)  0.30  0.34  0.38 

(b)  Transverse Reinforcement 

(I)  Nd ≤ 0.1 Ag  fcd   

(i).  ζ > 0.  

           The resistance to shear provided by the reinforcement: Vwd shall be given by 

        Vwd = 0.87 h Asw . fyk                   5.10.7.5   
                           s . γs 

where,    

               h is the effective depth,  

Asw  the  individual  cross‐sectional  area  of  a  mat  of  transverse 


reinforcement, and 

92 

 
s  the spacing of the mats of transverse reinforcement measured 
parallel to the axis of the beam. 

(ii)  ζ< 0.  For Vsd not exceeding the limit value, VRd1 where 

      VRd1 = 3( 2 + ζ ) τRd .bw . d                                5.10.7.6   

same requirement as in( i) above applies. 

‐  For Vsd exceeding the limit value VRd2 where 

      VRd2 = 6( 2 + ζ ) τRd .bw . d                               5.10.7.7 
       

the entire shear shall be resisted by diagonal reinforcement across the web, 
that  is,  steel  bars  inclined  in  two  directions  shall  equilibrate  with  their 
compression and tension components the shear forces of opposite sign Vsd 
and  ζ.Vsd occurring at the section. 

‐  For  VRd1 < Vsd < VRd2  

one  half  of  the  maximum  shear  force  shall  be  carried  by  doubly  diagonal 
bars, the other half by transverse reinforcement. 

(II)  Nd > 0.1 Ag fcd    

The resistance to shear shall be checked as for Case (I) (i) 

5.10.7.2      Beam ‐ Column Joints (DL III only) 

(1)  Horizontal Joint Shear 

(a)  Nominal Horizontal Shear Stress 

        (i)  The nominal horizontal shear stress in the joint as given by the following expression 

         V         5.10.7.8  
τ
jh
jh =
b j hc
 

shall not exceed the value 20 τRd   

       
93 

 
        (ii)  The effective joint width bj shall be taken as: 

‐ when ( bc > bw ) 

either   bj = bc                   5.10.7.9 

or  bj = bw + 0.5hc     

whichever is smaller  (Fig. 5.10.7.2) 

‐ when  bc < bw        

either bj = bw      

or  bj = bc + 0.5hc                          5.10.7.10 

whichever is smaller 

         Fig.5.10.7.2 ‐ Effective Joint Width and Effective Joint Areas 

(b)  Shear Force carried by Concrete 

The value of shear force carried by the concrete strut Vch shall be assumed zero except for 
the following: 

(i) When  minimum  average  compression  stress  σ cm   on  gross  concrete  area  of  the 

column above the joint including prestress where applicable, exceeds 0.1 fck  
 

94 

 
 
V ch = (2 τ Rd ( σ cm - 0.1 f ck ) ) b j h c  
                      5.10.7.11 

(ii)  When beams are prestressed through the joint: 

  Vch = 0.7 Pcs               5.10.7.12 

where Pcs is the permanent force in the prestressing steel that is located within the 
central third of the beam depth. 

(iii)  When the design precludes the formation of any beam plastic hinge at the joint, or 
when  all  beams  at  the  joint  are  detailed  so  that  the  critical  section  of  the  plastic 
hinge is located at a distance from the column face not less than hb, or for external 
joints where flexural steel is anchored outside the column core in a beam stub. 

   

  Vch = A’s . Vjh     1 +      Nd          5.10.7.13 

          As         2         0.4Agfck         

where  the  ratio  A's/As  of  the  compression  to  the  tension  longitudinal  beam 
reinforcement  shall  not  be  taken  larger  than  1.0.    When  the  axial  column  load 
results in tensile stresses over the gross concrete area exceeding 0.2  f ck the entire 

joint shear shall be resisted by reinforcement. 

For axial tension smaller than this limit, the value of Vch may be linearly interpolated 
between zero and the value given by equation 5.10.7.13 with Nd taken as zero. 

(iv)        When parts Aa1   and Aa2 of the column tensile reinforcement and As1 and As2 of the 
adjacent beams are bent vertically and anchored in the tensile face of the column 

                 
f yk
        V ch  = Aa           5.10.7.14 
γs
 

where Aa is the smaller of Aa1 and Aa2. 

 
95 

 
The values of Vch obtained from equations (5.10.7.11, 5.10.7.12, 5.10.7.14) may be 
added where applicable.    (See Fig 5.10.7.3) 

                    Fig. 5.10.7.3 ‐Shear Force carried by Concrete 

(c)  Horizontal Shear Reinforcement 

(i)  The  horizontal  shear  reinforcement  shall  be  capable  of  carrying  the  design  joint 
shear force: 

          Vsh = Vjh ‐ Vch             5.10.7.15 


   

across  a  corner‐to‐corner  potential  failure  plane.    The  effective  total  area  of  the 
horizontal  reinforcement  that  crosses  the  critical  diagonal  plane  and  is  situated 
within the effective joint width bj shall not be less than: 

 
V sh
A jh =
          yk /  γ s
f         5.10.7.16 

(ii)  Horizontal  sets  of  stirrup  ties  shall  be  distributed  as  uniformly  as  practicable 
between layers of the top and bottom beam reinforcement. 

(2)  Vertical Joint Shear 

(a)  The vertical shear reinforcement shall be able to resist a vertical shear force 

96 

 
          Vsv = Vjv – Vcv                      5.10.7.18 
                 

where the value Vcv shall be determined from 

  Vcv =   A’sc . Vj    0.6 +     Nd                  5.10.7.18 

            Asc                                Agfck 

where  A'sc  and  Asc  are  the  areas  of  longitudinal  compression  and  tension 
reinforcement in columns respectively, with the following exceptions: 

(i)  Where  axial  load  results  in  tensile  stress  over  the  column  section,  the  value  of  Vcv 
shall be linearly interpolated between the value of Vcv given by equation (5.10.7.18) 
with Nd taken as zero when the axial tension over the gross concrete area is 0.2 fck; 

(ii)  Where  plastic  hinges  are  expected  to  form  in  the  column  above  or  below  a  joint, 
part of  the primary  seismic  energy  dissipating  mechanism, Vcv  shall  be  assumed to 
be zero for any value of the axial load on the column. 

(b)  The  required  area  of  vertical  joint  shear  reinforcement  within  the  effective  joint 
width bj shall be determined from: 

 
V sv
A jv =
                 f yk / γ s
        5.10.7.19 

(c)  The  vertical  joint  shear  reinforcement  shall  consist  of  intermediate  column  bars 
placed  in  the  plane  of  bending  between  corner  bars,  or  of  vertical  stirrup  ties  or 
special vertical bars, placed in the column and adequately anchored to transmit the 
required tensile forces within the joint. 

(d)  The spacing of vertical joint reinforcement in each plane of any beam framing into a 
joint  shall  not  exceed  200mm,  and  in  no  case,  shall  there  be,  less  than  one 
intermediate bar in each side of the column in that plane. 

 
97 

 
(3)  Eccentric Beam ‐ Column Joints 

All  design  provisions  of  this  section  apply  except  that  in  case  of  an  eccentricity  of  a  beam 
relative  to  the  column  into  which  it  frames,  as  measured  by  the  distance  between  the 
geometric centre lines of the two members, the effective joint width bj shall not be taken as 
larger than: 

                              0.5( bw + bc + 0.5hc) – e                                  5.10.7.20 

5.10.7.3  Structural Walls 

(1)  General 

The design strengths of walls and coupling beams shall be evaluated as for linear elements 
(Section 5.10.7.1) except as modified by provisions in section 1.6.3 

(2)  Resistance to Shear 

(a)  Maximum Allowable Shear Stress 

The  maximum  nominal  design  shear  stress  in  a  wall  section,  evaluated  by  means  of  the 
expression 

              τd  =  Vd / Ag             5.10.7.21 

where Vd is the design force computed in accordance with Clauses5.10.6.3 (3) or 5.10.6.4 (4) 
shall not exceed the following limit 

              τd   ≤ 10τRd                          5.10.7.22 

(b)  Contribution of Concrete to Shear Strength 

(i)  In the potential plastic zone, as defined in Clause 5.10.8.5.3(2), the contribution of concrete 
to  shear  resistance  is  assumed  to  be  zero,  unless  the  minimum  axial  load  produces  an 
average compression stress over the gross concrete area of the wall equal at least to: 

                           0.1 fcd.                                                                                                         5.10.7.23 

98 

 
In which case the shear contributed by concrete shall be computed by: 

    τcd = 2.5 τRd .β1            5.10.7.24     

 (ii)  Outside the potential hinge zone, and when the average compressive stress is less than 0.1 
fcd, the shear stress contributed by concrete shall be taken as: 

    τcd = 2 τRd                        5.10.7.25 

while in case the average stress is greater than 0.1 fcd the value is taken as: 

    τcd = 2.5 τRd .β1                         5.10.7.26 

(c)  Web Reinforcement 

Horizontal bars fully anchored at the extremities of the wall section, shall be provided in the 
amount: 

    ρv =  Ah  = τd ‐ τcd          5.10.7.27 

        b.sv        fyd 

while the vertical reinforcement ratio shall be: 

    ρv =  Av  =   τd ‐ τcd ‐ Nd / Ag        5.10.7.28 

        b.sh               fyd 

The vertical shear reinforcement can be assumed to fully contribute to the required flexural 
strength. 

(3)  Coupling Beams 

(a)  Symmetrical flexural reinforcement, (ρ = ρ'), shall be adopted in case of usual arrangement. 

(b)  Design for flexure and shear shall be carried out as for ordinary beams unless the following 
limits are exceeded   τd  ≥  6.τRd  

ρ  = l√ (8fck) / (4.h.fyk),           (fck, fyk in Mpa)                5.10.7.289 

99 

 
(ρ  =  longitudinal  reinforcement  ratio,  top  or  bottom)  in  which  case  all  flexural  and  shear 
actions shall be resisted by diagonal reinforcement in both directions. 

5.10.7.4     Verifications 

(1)  Collapse Verification 

(a)  For  the  purpose  of  the  present  code,  a  structure  shall  be  deemed  to  satisfy  the 
safety requirement against collapse if the following conditions are met  

(i)  the strength and stability verifications are satisfied; 

(ii)  the elements are dimensioned and detailed in accordance with rules given in 
Sections  5.10.7  and  5.10.8  relative  to  the  appropriate  structural  type  and 
intended ductility level. 

(2)  Strength Verification 

The following condition must be satisfied for every element: 

      Sd ≤ Rd             5.10.7.30 

where Sd is the design load effect on the element considered, evaluated according 

 to Section 5.10.6. 

                             Rd is the design strength of the same element, evaluated according to Section 5.10.7 

(3)  Stability Verification 

The stability verification shall be considered satisfied if: 

(i)  the deformability index Θ formula 5.10.4.2.7 is less than 0.1, 

(ii)  for 0.1 < Θ < 0.2, the second order effects are calculated and added to the 
design forces. 

(iii)  the stability verification cannot be satisfied if   

                                            Θ > 0.20. 

100 

 
(4)  Serviceability Verification 

(a)  The elastic drift, Δel resulting from the application of the horizontal forces specified 
in 5.10.4.2.4 or from the dynamic procedure in 5.10.4.2.5, shall at any storey satisfy 
the condition: 

0.010             5.10.7.31   
Δ el ≤ .h
K
         

where h is the clear height of the floor. 

(b)  For  Class  II  buildings,  the  indicated  limits  may  be  increased  by  50%  if  it  can  be 
demonstrated that the finishes adopted are not brittle ‐ type and can accommodate 
without significant damage to those limits. 

(c)  When  the  limits  in  (a)  and  (b)  are  exceeded,  separation  of  the  non‐structural 
elements  is  required,  of  an  amount  adequate  for  permitting  an  inter  storey  drift 
equal at least to: 

Δ =  0.35 Δ el . K           5.10.7.32 

to take place without restraint. 

(d)  In no case shall inter‐storey drift  Δel  exceed the limit : 

  
0.025
Δ max = .h
  K            5.10.7.33 

(5)  Maximum Expected Displacements 

The  maximum  expected  displacements  of  the  building  shall  be  obtained  by 
multiplying the displacements produced by the system of horizontal forces specified 
in  5.10.4.2.4  or  those  obtained  from  dynamic  analysis  as  in  5.10.4.2.5  by  the 
appropriate values of the behaviour factor K. 

 
101 

 
5.10.8  DETAILING, EXECUTION, USE 

5.10.8.1   General 

When no explicit distinction is made, the provisions in this section apply to both DL II and DL 
III structures. Provisions applicable to DL I structures are always explicitly stated. 

5.10.8.2  Elements Subject to Bending ( N d ≤ 0 . 1 . A g . f cd ) 

5.10.8.2.1 Geometrical Constraints 

 DL II and DL III Structures 

Unless special proofs for exemption are given, the following dimensional limitations shall be 
satisfied 

(i)  The width shall not be less than 200mm or more than the width of the supporting 
column, plus lengths, on each side of this member not exceeding one fourth of the 
depth of the column cross section. 

(ii)  The ratio b/h shall not be less than 0.25 

(iii)  The ratio  l/h  shall not be less than  4  (This requirement does not apply to coupling 


beams in wall structures, Clause 5.10.7.3(3).(Fig 5.10.8.1) 

(iv)  The  eccentricity  of  any  beam  relative  to  the  columns  into  which  if  frames  as 
measured  by  the  distance  between  geometrical  centre  lines  of  the  two  members 
shall not exceed 1/4 bc   (Fig5.10.8.2)          

102 

 
 

                                           Fig. 5.10.8.1 

                                           Fig. 5.10.8.2 

(a)  Maximum eccentricity of beams

(b)  Example of bad  structural layout for this  and  analogous cases, if  they 


cannot  be  avoided,  special  detailing  shall  be  provided  to  ensure 
continuity with ductile behaviour. 

103 

 
5.10.8.2.2  Longitudinal Reinforcement 

(1)  DL II and DL III Structures 

(a)  At any section of the member the tensile reinforcement ratio for top or the bottom 

reinforcement shall not be less than: 

  1.4
ρ min = ( f yk
i n Mpa )
f yk
                5.10.8.1 

nor greater than 

  7
ρ max =  
f yk
                5.10.8.2 

with ρ min and  ρ max  referred to the gross concrete area, Ag. 

(b)  At least two 12mm bars shall be provided both top and bottom throughout the length of the 
members. 

(c)  Within any potential plastic hinge region, the compression reinforcement ratio ρ'    

shall not be less than one half of the tension reinforcement ratio at the same section. 

(d)  At  least  one  quarter  of  the  larger  of  the  top  reinforcement  required  at  either  end  of  the 
member shall be continued throughout its length. 

(e)  In  T  and  L  beams  built  integrally  with  slabs,  the  effective  reinforcement  to  be  considered 
near column faces in addition to all longitudinal bars placed within the web width of beam, 
shall be as follows: 

(i)  At interior columns when a transverse beam of similar dimensions frames into the 
column,  all  reinforcement  within  that  part  of  the  slab  which  extends  a  distance  4 
times the slab thickness from each side of the column. (Fig 5.10.8.3a) 

     

104 

 
(ii) At  interior columns where  no  transverse beam  exists all  reinforcement within that 
part of the slab which extends a distance of 2.5 times the thickness of the slab from 
each side of the column. (Fig 5.10.8.3b) 

(iii)  At  exterior  columns  where  a  transverse  beam  of  similar  dimensions  frames  into 
column  and  where  the  beam  reinforcement  is  to  be  anchored  all  reinforcement 
  within that part of the slab which extends a distance of twice the slab thickness from 
each side of the column. (Fig5.10.8.3c) 

(iv)  At exterior columns where no transverse beam exists, all reinforcement within the 
width of the column. (Fig.5.10.8.3d) 

                            Fig. 5.10.8.3 ‐ Areas of Effective Reinforcement 

(v)  In all cases, at least 75% of the reinforcement in each face providing the required 

flexural capacity, must pass through or be anchored in the column core. 

105 

 
(2)  DL I Structures 

Clause5.10.8.2.2. (1) (a) only needs to be satisfied. 

5.10.8.2.3 Minimum Transverse Reinforcement 

(1)  Transverse reinforcement as specified in this section shall be provided unless a 

larger amount is required to resist shear (section 5.10.7.1.(4) ) . Portions of the beams 

to be considered as ‘critical’ regions are: 

(a)  Twice the member depth, measured from the face of the supporting column, 

or beam, towards midspan at both ends of the beam. 

(b)  Twice the member depth on both sides of a section where yielding may occur. 

(c)  Wherever compression reinforcement is required. 

(2)  DL II Structures 

In the critical regions as defined in 5.10.8.2.3 (1), stirrup ties of not less than 6mm 

diameter shall be provided, with maximum spacings not exceeding the smaller of: 

    (a)  h/4 

    (b)  eight times the minimum diameter of the longitudinal bars 

    (c)  24 times the diameter of the hoop bars 

    (d)  200mm 

The first hoop shall be located not more distant than 50mm from the face of the  

supporting member. 

 
106 

 
(3)  DL III Structures 

In the critical regions as defined in 5.10.8.2.3 (1) stirrup ties of not less than 6mm 

diameter shall be provided, with maximum spacing not exceeding the smaller of: 

   (a)  h/4 

   (b)  six times the diameter of the longitudinal bars 

   (c)  150 mm 

The minimum area of one leg of the transverse reinforcement shall be: 

 
∑ Ab . f yk S
As, min = .
        16  f ykt   100           5.10.8.3 

ΣAb =  Sum  of  the  areas  of  longitudinal  bars  at  the  section  considered  to  be 
restrained by the transverse leg  

    fyk   =  yield strength of longitudinal bars 

   fykt    =  yield strength of stirrups 

   S     =  spacing of stirrups in mm 

The  first  hoop  shall  be  located  not  more  than  50mm  from  the  face  of  the  supporting 
member. (Fig 5.10.8.4) 

       Fig. 5.10.8.4 Regions and Spacing of Transverse Reinforcement 

107 

 
5.10.8.3 Elements Subject to Bending and Axial Force ( N d > 0 . 1 . A g . f cd ) 

5.10.8.3.1 General 

Corner columns should be detailed according to DL III requirements. 

5.10.8.3.2  Geometric Constraints 

(1)  DL II Structures 

(a)  The minimum cross ‐ sectional dimension shall not be less than 250mm 

(b)  The ratio l/b shall not exceed 25 

(2)  DL III Structures 

(a)  The minimum cross‐section shall not be less than 300mm 

(b)  The ratio l/b shall not exceed the value of 16 for columns having moments of 

opposite sign at the two extremities; 10 for cantilever columns. 

5.10.8.3.3 Longitudinal Reinforcement 

(1)  General 

(a)  The reinforcement ratio shall not be less than 0.01 or larger than 0.06 including the 
region of lap splices. 

(b)  For S400 steel, the reinforcement ratio outside the splices shall not be greater  

than 0.045. 

(c)  The bars shall not be spaced further apart between centres than 200mm. 

(2)  DL I Structures 

The provisions in 5.10.8.3.3 (1) apply to DL I Structures. 

108 

 
5.10.8.3.4  Transverse Reinforcement 

(1)  General 

(a)  A basic amount of reinforcement shall be provided all over the height of the column while 
special  reinforcement  shall  be  placed  in  the  column  critical  regions  defined  in  Clause 
5.10.8.3.4 (2) 

(b)  The  amount  of  reinforcement  required  by  5.10.8.3.4  shall  be  provided  unless  a  larger 
amount is required to resist shear according to Clause 5.10.7.1 (4) 

(2)  Column Critical Regions 

 (a)  For  usual  cases,  critical  regions  are  considered  to  be  the  regions  at  each  end  of  a  column 
above and below connections over a length from the faces of the connection of not less than 
the larger of: 

(i)  the longer column cross‐section dimension in the case of a rectangular 

cross‐section, or the diameter of the section in case of a circular column. 

(ii)  one‐sixth of the clear height of the column 

(iii)  450mm 

(b)  When a masonry infill wall is in contact with one or both of the two opposite sides 

of  the  column,  over  the  whole  height  or  part  of  it,  the  entire  column  height  shall  be 
considered as a critical region.(Fig 5.10.8.5a) 

109 

 
 

                             Fig. 5.10.8.5 ‐ Solutions to be avoided 

(c)  In case of columns with part of their height restrained due to a connection with a wall the 
free part of the column shall be considered as a critical region. 

(3)   DL II Structures 

 (A)  Critical Regions 

(a)  Special transverse reinforcement having a minimum diameter of 8mm in the form of 
spiral or hoop reinforcement shall be provided. 

(b) Cross ties to restrain longitudinal bars not directly held by hoops shall be used in
accordance with BS 8110
(c)  The maximum spacing between spirals or hoops shall not exceed the smaller of: 

(i)  eight times the minimum diameter of the longitudinal bars 

(ii)  one half the least cross‐sectional dimension of the section 

(iii)  200 mm 

110 

 
(d)  The  transverse  reinforcement  in  the  amount  specified  above  shall  be  continued 
throughout the length of the beam ‐ column joint. 

(B)  Non‐critical regions 

The  minimum  transverse  reinforcement  in  non‐critical  regions  shall  be  in  accordance  with 
Table 5.10.8.1 

                            Table 5.10.8.1: TRANSVERSE REINFORCEMENT ‐ DL II 

Critical Region lc = max   (h,  l/6,  450 mm) 

Spacing  Critical Region   Sh    =   min (8φ L, 1/2b, 200mm) 

  Elsewhere Sh   =    mm (12φL, b, 300mm) 

(See Fig. 5.10.8.6) 

(4)  DL III Structures 
 

(A)  Definition 

(a)  The volumetric ratio is the ratio of volume of spiral or hoop reinforcement to total 
volume of concrete core ( out ‐to‐out of bars) within the spacing, Sh 

(b)  The volumetric ratio ρs for rectangular sections is defined as 

  ρs =Ash / Sh . h’            5.10.8.4 

where Ash is the total area of hoop bars and supplementary cross ties in each of the 
principal directions of cross section, Sh is the spacing and h'  is the distance between 
centres of outer bars. 

111 

 
 

Fig. 5.10.8.6 ‐  Special Transverse Reinforcement. Critical Region and Spacing 

 (B)  Critical Regions 

(a)  The volumetric ratio of transverse reinforcement (spiral or hoops) shall not be less 
than the greater of 

  f ck
ρ s = λ1 .
f yk
                    5.10.8.5 

112 

 
         
⎛ Ag ⎞ f
ρ s = λ2 ⎜ - 1⎟ ck

⎝ Ac ⎠ f yk
                  5.10.8.6 

where,  Ag  =  gross sectional area 

Ac  =  confined area of concrete and the values of  λ1 and λ2 are given in 
Table 5.10.8.2 as functions of the reduced axial force ratio Nd / Ac fck    

                                  Table 5.10.8.2: VALUES OF λ1 AND λ2 

           

Nd /Ac .fck  0.10  0.20  0.30  0.40  0.50 

           

λ1  0.05  0.06  0.07  0.08  0.09 

 
λ2 
0.l8  0.22  0.26  0.30  0.34 

(b)  The minimum diameter of spiral or hoops shall be 8mm. 

(c)  The maximum spacing between spirals or hoops shall not exceed the smaller of: 

(i)  six times the minimum diameter of longitudinal bars; 

(ii)  one fourth of the smallest lateral dimension of the section 

(iii)  l50 mm 

(d)  Each longitudinal reinforcement bar or bundle of bars shall be laterally supported by 
the  corner  of  a  hoop  having  an  included  angle  of  not  more  than  135o        or  by  a 
supplementary  cross  tie  except  that  the  following  bars  are  exempted  from  this 
requirement: 

113 

 
(i)  bars or bundles of bars which lie between two bars supported by the same 
hoop where the distance between the laterally supported bars or bundles of 
bars does not exceed 200mm between centres. 

(ii)  inner layers of reinforcing bars within the concrete core centred more than 
75mm from the inner face of hoops. 

(e) The yield force of the hoop bar or supplementary tie shall be at least one‐sixteenth of 
the yield force of the bar or bars it is to restrain including the contribution from the bar 
or bars exempted under 5.10.8.3.4 (4)(B)(d)(i) 

(f)    Each  end  of  a  supplementary  tie  shall  engage  either  a  longitudinal  bar  or  the 
peripheral hoop besides a longitudinal bar with a bent of at least 1350 and an extension 
beyond the bent of at least 10 tie bar diameters.  Supplementary ties and legs of hoops 
shall not be spaced transversely more than either 200mm or one‐quarter of the column 
section dimension perpendicular to the direction of the transverse steel. (Fig. 5.10.8.7). 
 

114 

 
     

     hoop   

         supplementary       
cross ties 
hoop 
      
 
  
 

(a)      Single  hoop  plus  two    (b)      Single  hoop  plus  two   
supplementary  crossties  bent  supplementary cross ties 
round longitudinal bars  bent round hoop 

   

   

   

   

   

(c)  Two overlapping hoops  (d)  Two  overlapping  hoops 


not preferred detail 
preferred detail 

   

(e)  Three overlapping hoops                          (f)  Four overlapping hoops 

Fig. 5.10.8.7 ‐  Typical details using overlapping hoops 

115 

 
(C)  Non‐critical regions 

The requirements relative to the critical regions of DL II columns apply (see Table 1.7.3). 

             Table 5.10.8.3 TRANSVERSE REINFORCEMENT 

                                                DUCTILITY LEVEL III 

       Critical Region lc = max (h, l/6, 450mm) (Fig. 5.10.8.6) 

Spacing  Critical Region Sh   =  min (6φL,  1/4b,  150mm) 
 
Elsewhere Sh         =  min (8φL,   1/2b ,  200 mm) 
 

             

5.10.8.4 Beam ‐ Column Joints 

5.10.8.4.1 Confinement 

(1)  DL I and DL II Structures 

The horizontal transverse confinement reinforcement in beam ‐ column joints shall not 

be less than that required for the columns. 

(2) DL III Structures 
(a)  The horizontal transverse confinement reinforcement in beam ‐ column joints shall 
not    be  less  than  that  required  for  the  columns  with  the  exception  of  joints 
connecting  beams  at  all  four  column  faces  that  are  designed  according  to  Clause 
5.10.7.2(1)(b)(ii)  or  (iii)  in  which  case  the  transverse  joint  reinforcement  may  be 
reduced to one half of that required for the columns, but in no case  shall the stirrup 
tie  spacing  in  the  joint  core  exceed  ten    times  the  diameter  of  the  column  bar,  or 
200 mm, whichever is less. 

(b)  When the width of the column is larger than the effective joint width specified in in 
Clause  5.10.7.2(1)(a),  all  flexural  reinforcement  in  the  column  that  is  required  to 
interact with the narrow beam shall be placed within the effective joint area, bj.hc. 

116 

 
Additional  longitudinal  column  reinforcement  shall  be  placed  outside this effective 
area. 

5.10.8.5 Structural Walls 

5.10.8.5.1 Geometrical Constraints 

(1)  General  

(i)  Wall thickness shall not be less than 150 mm. 

(ii)  Openings  in  the  walls  not  regularly  arranged  to  form  coupled  walls  shall  be 
preferably  avoided,  unless  their  influence  on  the  behaviour,  of  the  wall  under 
seismic action is either insignificant or accounted for by rational analysis 

(2)  DL III Structures 

In  addition  to  the  requirements  in  5.10.8.5.1  (1)  ‐  DL  III  structures  shall  also  satisfy  the 
following. 

(a)  the height (hw) to width (lw ) ratio shall not be less than 2; 

(b) the  local  thickness  of  a  wall  shall  not  be  less  than  hn/10  (hn  is  storey  height) 
wherever the maximum compressive strain exceeds the value εcu /3, unless  
(i)  the distance of the critical fibre (ie where εcu = εcu  /3 ) from the wall edge is 
smaller than 2b or 0.2 lw,                    

(ii)  the distance of the critical fibre from a transverse wall, or from a flange the 
width  of  which  is  at  least  hn/5  is  smaller  than  3b  (see  Figs.  5.10.8.8  – 
5.10.8.9) 

117 

 
 

Fig. 5.10.8.8 ‐ Minimum Width Requirements 

Fig. 5.10.8.9 ‐ Exemptions from Clause 1.7.5.1 on Minimum Wall Width 

Fig. 5.10.8.10 ‐ Definition of Vertical Reinforcement Ratio 

118 

 
5.10.8.5.2  Longitudinal Reinforcement 

(a)  The  vertical  reinforcement  ratio  in  any  part  of  the  section  shall  not  be  less  than  0.25%  or 
greater than 4% (see Fig. 5.10.8.10). 

(b)  At least two orthogonal grids of reinforcement shall be used one near each side of the wall 

(c)  The diameter of the bars used in any part of a wall shall not exceed b/10 

(d)  The maximum spacing between bars shall be 300mm except where the section is required to 
be confined, in which case the spacing shall not exceed 200 mm. 

(e)  Curtailing: Vertical flexural reinforcement shall be curtailed in accordance with the bending 
moment envelope, allowing for the development lengths of the curtailed bars. 

(f)  Splicing: Splicing of the vertical reinforcement in potential areas of yielding 

(See 5.10.8.5.3(1)) shall be avoided whenever possible. In no case shall more than one third 
of such reinforcement be spliced in those areas. Special care shall be taken for splicing of the 
main (flexural) vertical bars. The splices should be staggered in the longitudinal direction at 
least twice the spliced length. 

(g)  Construction joints: The ratio of vertical reinforcement crossing a construction joint shall be 
such as to provide for the transfer of the entire shear capacity of concrete and is given by 
the expression: 

ρv = (1.3 fctm – 0.7 Nd/Ag) / fyk > 0.0025          5.10.8.7 

where: 

ρv = Ast / b . lw                  

with Ast =  total vertical wall reinforcement, including  that in boundary elements provided 
to resist flexure. 

 Ag   is the gross area of the effective wall section including boundary elements. 

 Nd   is  the  minimum  compression  force  in  the  wall.  Tension  shall  be  taken  as 
negative. 

119 

 
5.10.8.5.3 Transverse Reinforcement 

(1)  General 

The  requirement  for  minimum  reinforcement  ratio,  maximum  diameter  and  maximum 
spacing, shall be as for longitudinal reinforcement (Clause 5.10.8.5.2) 

(2)  Zones with special transverse reinforcement 

      (a)  The  zones of walls requiring special reinforcement as specified  in (b) below  are  defined as 


follows: 

(i)  in the vertical direction, they shall extend from the base over the probable 

plastic  hinge  length,  which  for  the  purpose  is  assumed  to  be  the  greater  of;  the 
length ( lw) or 1/6 of the height  (hw) of the wall. 

(ii)  in  the  plan  section  whenever  the  computed  concrete  strain  exceeds  the  value:  
εcu/3.  The  strain  profile  over  the  section  shall  correspond  to  development  of  its 
flexural strength, under the maximum design axial compression force occurring for a 
load combination including the seismic action (Fig. 5.10.8.11) 

   E 

 
   

    

Fig. 5.10.8.11 
 
 

120 

 
(b)  The  amount  of  special  transverse  reinforcement  to  be  provided  is  a  function  of  the 
computed  depth  of  the  neutral  axis:  x  in  the  base  section  of  the  wall,  and  of  the  selected 
ductility level as follows: 

(i)  DL II Structures 

The  critical  neutral  axis  depth,  computed  for  the  most  adverse,  design  bending 
moment, d, is given by: 

 
( M +u ,d )
χ = 0.2 . lw
    M d            5.10.8.8 

when:  χ ≤ χ      ‐  Transverse  reinforcement  shall  satisfy  the  minimum 

requirements  set  forth  in  Clause  5.10.8.5.3.  Cross  ties  to 


restrain  longitudinal  bars  shall  be  used  in  accordance  with 
BS 8110 (1985) 

             χ > χ     ‐  Transverse  reinforcement  shall  satisfy  the  requirements  of 

Clause  5.10.8.3.4(3)  (Ductility  Level  II  columns  in  critical 


regions). 

(ii)  DL III Structures 

The critical neutral axis depth, computed for the most adverse bending moment Md, 
is  given by: 

  ( M +u ,d )
χ = 0.1 . lw
Md
                 5.10.8.9 

when: 

χ ≤ χ   ‐  Transverse  reinforcement  shall  satisfy  requirements  of  Clause 


5.10.8.3.4(4) (DL III columns in non‐critical regions). 

χ > χ ‐    Transverse  reinforcement  volumetric  ratio  shall  not  be  less 
than the greater of: 

 
121 

 
       f              
ρ s = λ1 . ck

f yk
                                                          5.10.8.10 

or 

 
⎛ A ⎞ f
ρ λ ⎜⎜ - 1 ⎟⎟
g ck
s
= 2  
        ⎝  A c
  ⎠ f  yk     5.10.8.11 

where the values of λ1 and λ2 are given in the following Table 5.10.8.4 as functions 
of neutral axis depth ratio. 

TABLE 5.10.8.4     VALUES OF λ1 AND λ2 IN EQUATIONS 5.10.8.10 AND 5.10.8.11 

x /lw  0.1  0.2  0. 3  0.4  0.50  0.60  0.70 

λ 1  0.07  0.08  0.09  0.105  0.115  0.125  0.135 

λ 2  0.18  0.205  0.23  0.26  0.285  0.31  0.34 

    

The volumetric ratio is defined as 

ρ =    A’sh              5.10.8.12 

             Sh h1       

where   h1  =  dimension of wall concrete core measured perpendicular to the direction 

of hoop bars to outside of peripheral hoops 

A’sh =  total steel area of hoop bars and supplementary cross ties in direction under 
consideration, with spacing Sh 

5.10.8.5.4 Coupling Beams 

(a)  The  diagonal  reinforcement  in  each  direction  shall  be  enclosed  by  rectangular  stirrups, 
hoops or spirals in accordance with Clause 5.10.8.3.4(4), however their spacing or pitch shall 
not exceed l00mm. 

122 

 
(b)  Minimum thickness for diagonally reinforced beams shall be 200 mm. The anchorage length 
of diagonal reinforcement in the adjacent wall be increased by 50% of the lengths prescribed 
in   BS 8110 (1985) (Fig.  5.10.8.12). 

                                                            Fig.  5.10.8.12 

5.10.8.6  Anchorage and Splicing of Reinforcement 

5.10.8.6.1  General 

In addition to the rules of BS 8110 the following requirements shall be satisfied in order to 
ensure reliable behaviour during cyclic loading reversals caused by seismic action: 

(a) All  reinforcement  bars  should  be  considered  to  be  in  insufficient  bond  conditions  except 
when anchorage is made in regions confined by means of special transverse reinforcement 
where good bond condition can be assumed. 
(b)  All  bars  should  be  able  to  develop  their  maximum  strength  (γn)  fyk  when  a  plastic  hinge  is 
formed.            

5.10.8.6.2 Flexural Members: Anchorage of Longitudinal Reinforcement 

(a)  Flexural  members  framing  into  opposite  sides  of  a  column  shall  have  top  and  bottom 
reinforcement provided at ends of members continuous through the column where possible. 

(b) When  top  or  bottom  reinforcement  cannot  be  continuous  through  the  column  due  to  the 
variations  in  flexural  members  cross  section,  and  in  exterior  columns,  the  reinforcement 
shall be anchored within the beam column connection in accordance with the following: 
 (i)  Reinforcement  shall  be  extended  to  the  far  face  of  the  confined  region  and 
anchored to develop its yield strength. 

123 

 
(ii)  Every bar shall terminate with a standard 90‐degree hook or equivalent anchorage 
device, as near as practicably possible to the far face of the column core. Top bars 
should be bent down and bottom bars bent up. 

(iii) Development length of beam reinforcement shall be computed beginning at a distance


of 10 φ from the near face column.

 (c)  For  DL  III  Structures  when  beams  frame  into  opposite  sides  of  a  column,  the  maximum 
diameter of the longitudinal beam bars which are continuous through the column should not 
exceed the following fractions of the column depth (parallel to the bar) in Table 5.10.8.5 

Table 5.10.8.5

Steel grade  Fraction of hc 

S220 smooth  1/35 

S220 deformed  1/20 

S400 deformed  1/30 

5.10.8.6.3  Columns: Anchorage of Longitudinal Reinforcement 

(a)  The  maximum  diameter  of  longitudinal  column  bars  which  are  continuous  through  a  joint 
shall  not  exceed  the  following  fractions  of  maximum  depth  of  the  beams  framing  into  the 
column.(Table 5.10.8.6) 

                                      Table 5.10.8.6 

Steel Grade  Fraction of hb 

S220 smooth  1/25 

S220 deformed  1/15 

S220 deformed  1/25 

124 

 
When hinges are permitted to form in columns the values indicated in Clause 5.10.8.6.2 shall 
be applied. 

 (b)  The anchorage of a column bar into an inter‐section beam shall be made by a horizontal 90‐
degree standard hook or equivalent device, as near the far face of the beam as practically 
possible. The direction of  the  horizontal  leg  of the standard hook  must always  be towards 
the core of the joint. 

 (c)  When  columns  terminate  at  joints  at  the  top  of  frames  or  at  joints  between  columns  and 
foundation  members,  the  anchorage  of  the  longitudinal  column  bars  into  the  joint  region 
shall be assumed to begin at a distance equal to one half of the depth of the beam, or 10φ, 
whichever is less from the face at which the column bar enters the beam. (Fig 5.10.8.13) 

                                             Fig 5.10.8.13 

5.10.8.6.4 Splices of Longitudinal Reinforcement 
(a)  Splices  are  not  permitted  within  beam‐column  joints  or  within  potential  plastic  hinge 
regions. 

 (b)  If  it  can  be  shown  that  plastic  hinge  cannot  develop,  splices  are  permitted  in  the  end 
sections  of  columns,  provided  that  transverse  reinforcement  spaced  vertically  no  further 
than 6 bar diameters, is present. 

125 

 
(c)  Stirrup‐ties shall be provided over the length of all lap splices of reinforcement in beams and 
columns.  The maximum spacing of the stirrup‐ties shall not exceed 10 times the diameter of 
the bar being spliced. 

For DL III structures the maximum spacing shall also not exceed 150 mm. 

 (d)  Welded  splices  or  approved  mechanical  connections  conforming  with  BS  8110  (1985)  may 
be  used,  provided  that  not  more  than  alternate  bars  in  each  layer  of  longitudinal 
reinforcement are spliced at a section, and the distance between splices of adjacent bars is 
600 mm or more measured along the longitudinal axis of the frame component. 

5.10.8.6.5 Anchorage and Splicing of Transverse Reinforcement 

(a)  Transverse  hoop  reinforcement  shall  be  anchored  by  at  least  a  135o  bent  around  a 
longitudinal bar with a minimum extension at the face end of 10 bar diameters. 

Alternatively, the ends of the hoops can be spliced by welds capable of developing the full 
strength of the bar. 

 (b)  Transverse  reinforcement  shall  not  be  lap‐spliced  in  cover  concrete  with  beam  –column 
joints or within potential plastic hinge regions. Deformed bars shall be used for lap splices. 

 (c)  When the anchorage for a spiral terminates with a 135o bend around a longitudinal bar, the 
extension beyond the bend shall be at least 10 spiral bar diameters. 

 
126 

 
APPENDIX A 

SCHEDULE OF UNIT WEIGHT OF BUILDING MATERIALS 

Weights of concrete                           Table 1A 
 
Non‐reinforced plain or mass concrete  Normal  weight Aggregate: kN/m3 
  limestone   22.6 
                 gravel  21.2 to 23.6 
                 broken brick  22.0 to 23.6 
                 other crushed  19.6(av) 
L i g h t w e ig h ts c o n c r e t e

                stone                22.8 to 24.4 
  Nominal weight  23.6 
Reinforced concrete  Reinforcement: 1%  22.6 to 24.2 
                           2%  23.1 to 24.7 
                           4%  24.0 to 25.6 
 
KN/m2 
Solid slabs – Thickness (floors,  1.80 
walls,     75mm etc.)  2.40 
                           100mm  3.60 
                           150mm  6.00 
                             250mm  7.20 
                           300mm  2.00 
Ribbed slabs      125mm  2.15 
                           150mm  2.75 
                           225mm  3.35 
                           300mm 
  Aggregate or type  Compressive strength N/mm2 kN/ m3 
Lightweights concrete

 
Expanded clay or shale  5.6 to 8.4 9.4 to 11.8 
      ‐ditto ‐ structural  13.8 to 34.5  13.4 to 18.1 
       Vermiculite (expanded mica)  0.5 to 3.5  3.9 to 11.0 
      No‐fines (gravel)        ‐  15.7 to 18.9 
        Cellular (aerated or gas concrete)  1.4   
      Cellular structural   10.3 to 15.5  3.9 (min.) 
14.1 to 15.7 
Concrete block and brick walls  kN/ m3 
con struction with concrete products

  Sandcrete block: solid  17.3 
  Lightweight aggregates: solid  13.2 
Brickwork (nominal)  21.7 
  kN/m2 
 Other products  Paving slabs (flags)   
          
    50mm thick  1.15 
Roofing tiles: plain  0.6 to 0.9 
                         inter‐locking  0.6 
   
To convert values in kN to values in kg. multiply by 102 

 
127 

 
Weights of constructional materials                                  Table 2A 

Concrete Brickwork etc.  See   N/m2  


Table 1A 
  Clay floor tiles   575 
 
KN/m3 
Miscellaneous Materials

  Damp‐proof course  48 
Tarmacadam  22.6    N/m2 mm per 
Macadam (waterbound)  25.1    thickness 
Vermiculite3 (aggregate)  0.8  Felt (insulating)  1.9 
Terracotta  20.8  Paving slabs. (stone)  26.4 
  Glass   26.7  Granite sets  28.3 
Cork: granular  1.2  Asphalt  22.6 
         :compressed  3.8  Rubber paving   15.1 
  Polyvinylchloride  19(av) 
Glass‐fibre (forms)  1.9 
  density  at N/m2 per mm 
  12% moisture  Chipboard  7.5 
  content  Plywood  6.1 
Abura  4.7 to 6.1  Fibreboard  2.8 
Afara or limba  4.7 to 6.1  Wood‐wool  5.7 
African walnut  4.7 to 6.1  Plasterboard  9.4 
Afromosia   6.3 to 7.7  Water boarding                      3.8 
Afzelia  7.9 to 10.2     
Density at 12% 
Timber

Agba  4.7 to 6.1   
Albizzia (A.ferruginea)  6.3 to 7.7    moisture constant  
  KN/m  
3
Alstonia   3.1   
Antiaris  3.1  Gedu nohor  4.7 to 6.1 
Avodire  4.7 to 6.1  Guarea (cedrata)  4.7 to 6.1 
Ayan  6.3 to 7.7  Guarea (thomsonii)  4.7 to 6.1 
Canarium, African   3.1  Idigbo  4.7 to 6.1 
Celtis  3.1  Ilomba   4.7 to 6.1 
Dahoma  4.7 to 6.1  Iroko   6.3 to 7.7 
Danta  6.3 to 7.7  Mahogany, African   4.7 to 6.1 
Ekki  4.7 to 6.1  Makore   4.7 to 6.1 
Esia  6.3 to 7.7  Okwen  4.7 to 6.1 
Mansonia   6.3 to 7.7   Opepe  6.3 to 7.7 
Mubura   6.3 to 7.7  Ptergygota  6.3 to 7.7 
Miangori  10.2  Sapele  4.7 to 6.1 
Obeche  7.9 to 10.2  Stervulia, Brown  6.3 to 7.7 
Odoko  4.7 to 6.1  Sterculia, yellow  6.3 to 7.7 
Ogea  6.3 to 7.7  Utile   6.3 to 7.7 
Okan  4.7 to 6.1 
3.1 to 4.6 
4.7 to 6.1 
4.7 to 6.1 
7.9 to 10.2 
128 

 
 Natural stone (solid)     
Granite   25.1 to 28.7  Stone rubble (packed)  22.0 
Sandstone  22.0 to 23.6  Quarry waste  14.1 
slate  28.3  Hardcore (consolidated)  18.9 
     All‐in aggregate  19.6 

iron: cast  70.7 Structural steel work  Net weight of member + 


           wrought  75.4  Riveted 
10% for cleats, rivets bolts 
steel (see also below)  77.0   
etc  
copper: cast  85.6   
            : wrought  87.7    1 1
+1 %  to  2 %  
Brass  83.3  Welded   4 2
Bronze  87.7   
1
Aluminum  27.2  Rolled sections: beams  for welds etc + 2 %  for 
2
Lead  111.0                      :stanchions 
caps and bases)  
Zinc (rolled)  70.0   
  g/mm2  Plate‐web girders  + 10% for rivets or welds, 
  per metre   
stiffeners etc. 
Steel bars  7.85   
See Table 3A 
Roof trusses 
Steel stairs: industrial   N/m 
Type in wide  820 
Steel tube:   
50mm in bore  45 to 60 
Gas piping: 20mm       18 
 

129 

 
Weight of roofs                              Table 3A 

         
  Weight per m2 of slope of roof 
Material  (N/m2) 
   
Net            including normal laps and fastenings 

Aluminum sheet corrugated 18. S.W.G  37.8 47.9 


Aluminum sheet, corrugated 20 S.W.G  28.7  38.3 
Aluminum sheet corrugated 22. S.W.G  22.0 
28.7 
Aluminum sheet corrugated 24. S.W.G  17.2 
Aluminum sheet, flat  18 S.W.G  33.5  23.9 
claddnin g

Aluminum sheet, flat  20 S.W.G  24.9   
  Aluminum sheet, flat  22 S.W.G  19.6 
 
Aluminum sheet, flat  24 S.W.G  15.3 
Asbestos cement sheets, corrugated 6mm thick  135  160 
Asbestos cement sheets, flat 5mm thick  80   
Asbestos cement sheets, flat 6mm thick  110 
 
Asbestos cement sheets, flat 10mm thick  170 
Asbestos cement sheets, flat 12mm thick  220   
Copper sheeting 16 S.W.G  145   
Copper sheeting 18 S.W.G  110   
Copper sheeting 20 S.W.G  80 
Copper sheeting 22 S.W.G  65   
Copper sheeting 24 S.W.G  50   
Roofing felt, 3‐ply  25   
Roofing felt, 2‐ply  20 
 
Roofing felt, 1.ply  15 
Shingles (excluding battens)    120 
Steel sheet, galvanized, corrugated 18GB  110  135 
Steel sheet, galvanized, corrugated 20GB  90 
105 
Steel sheet, galvanized, corrugated 22GB  70 
Steel sheet, galvanized, corrugated 24GB  55  90 
Steel sheet, galvanized, corrugated 26GB  45  70 
Steel sheet, galvanized, corrugated 28GB  35 
55 
Steel sheet, galvanized, flat  18GB  100 
Steel sheet, galvanized, flat  20GB  80  45 
Steel sheet, galvanized, flat  22GB  60   
Steel sheet, galvanized, flat  24GB  50 
 
Steel sheet, galvanized, flat  26GB  40 
 
         
 
 
 
 
 
 

130 

 
   Table 3A (cont’d) 
Steel sheet, galvanized, flat 28BG   
Thatching, 300mm nominal thickness :dry  30     
                                                                    :wet  410 
Cladding

Roofing, burnt clay Marseilles type  530 
  (excluding battens)   
Tiles, roofing, burnt clay Etruscna type  430 
(excluding battens)   
Tiles, roofing, burnt clay, Broseley type  570 
(excluding battens)   
Tiles, roofing, burnt clay, Italian type  670 
(excluding battens)   
Reinforced concrete slabs, concrete tiles  720 
etc.           See Table 1A 
               Spacing of trusses   3.0m  4.5m
2
Approximate weights of steel roof trusses in N/m of  Span of trusses  7.5m 95  72
plan area of roof  9m  120  72 
Roof trusses

12m  132  84 


15m  144  108 

  18m  203  144 


25m  239  168 

 
131 

 
Weights of stored materials               Tables 4A

Acids: acetic  KN/m3 KN/m3 


            nitric  10.4  Mineral oils: naptha  7.4 
            sulphuric  15.1    Paraffin (kerosene)  7.9 
alcohol (commercial)  18.1  Petrol(gasoline)  6.9 
Li quids and semi -liquids

ammonia  7.9  Petroleum oil  8.6 


beer: in bulk  8.8  Pulp (wood)  7.1 
bottled (in cases)  10.0  Slurry: cement  14.1 
in barrels  4.6               Clay  11.9 
benzene, benzol  5.5  Sewage  9.7 to 11.8 

  bitumen (prepared)  8.6  Tar, pitch  11.8 


methylated spirit  13.7  Turpentine  8.5 
linseed oil milk  8.2  Water: fresh  9.81 
  8.8  Sea –water  10.05 
10.2  Wine: in bulk  9.7 
Bottled (in cases)  5.8 
Brewery’s grains (wet)  5.5  Lime (slated) dry 5.5 
Bricks (stacked)  17.3                         wet  14.9 
Clinker  9.4 to 10.2  Paper (packed)  9.4 
Cotton (in bales)  2.4 to 5.5          Waste(pressed)  5.5 
Flour: in bulk  7.1  Salt: dry  9.4 
In sacks  6.3           Loose  14.1 
Solid and packed ma terials

Hops (in sacks)  1.7  Sawdust  2.4 


Ice  9.0  Slag: basic  17.3 
Bottled goods (in cases)  8.8           Crushed  9.4 to 14.1 
Eggs in bulk  10.7           Foamed  6.3 
Meat   7.1  Sugar (loose)  7.9 
Tinned goods (in cases)  9.4  Tea (in chests)  4.4 
 
   
                        To convert values in kN to values in kg. multiply by 102

 
 
 

132 

You might also like