Stability Improvement of Power System Using Thyristor Controlled Series


Capacitor (TCSC)

Article · April 2013

CITATIONS READS

4 319

4 authors, including:

Hafiz Tehzeeb Ul Hassan Irfan Khan


University of Engineering and Technology Texas A&M University - Galveston
48 PUBLICATIONS   134 CITATIONS    48 PUBLICATIONS   147 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Optimal Load Shedding View project

Power Systems View project

All content following this page was uploaded by Irfan Khan on 14 December 2018.

The user has requested enhancement of the downloaded file.


International Journal of Engineering & Computer Science IJECS-IJENS Vol:13 No:02 30

Stability Improvement of Power System Using


Thyristor Controlled Series Capacitor (TCSC)
1
H.T.Hassan, 2 Usman Farooq Malik, 3 Irfan Ahmad Khan, 4 Talha Khalid
1
Associate Professor, the University of Lahore tehzibulhasan@gmail.com
2
Assistant Manager, NTDC WAPDA usman_malik724@hotmail.co m
3
Assistant Professor, the University of Lahore irfankhan184@gmail.co m
4
Assistant Engineer,NTDC WAPDA talha_ee@yahoo.com

Abstract-- TCS C are used to improve power handling capability compensation techniques but FACTS not only increase the
and reduce line losses in power systems. An additional feature of power transfer capability [4] but its dynamic features act to
TCS C is its dynamic performance of power oscillation damping reduce power oscillations, increasing angular and voltage
by varying the power flow in accordance with power oscillations. stability [5],[6] and thus the reliability of the entire system.
This behavior can be used to improve the stability of the system Transmission compensation can be series or shunt. Both types
following a disturbance. In this paper eigenvalue -based methods
for analysis have been studied and the stability improvement- of compensation have been further categorized and discussed
steady state as well as transient stability of the system is in [7]. Since we are studying TCSC which is in fact a series
improved using TCS C. FACTS device so we shall only high-lighten the effects of
series compensation. The steady state advantage of TCSC is to
Index Term-- Eigen-values, Power system oscillations, provide series compensation which acts to reduce the
S teady-S tate S tability, TCS C, Transient S tability. electrical length of the line and hence increases the power
transfer capability of the line by decreasing impedance and
I. INT RODUCT ION losses as is clear from the following relation (1).
With the increase in electrical equipment worldwide, the EG  EM
electric supply industry is undergoing remarkable P sin (1) [8]
transformation. Transmission systems are becoming more XT
heavily loaded and are being operated in ways not originally An excellent study of various stages /phases for the
anticipated. Transmission systems must be flexible to react to deployment of FACTS devices in system has been discussed
more diverse generation and load patterns. For industrialized in [9].
countries economic utilization of transmission systems assets AT the same time,one of the things to be taken care of while
is necessary to compete, whereas for developing countries applying these devices in the system is the determination of
optimum use of these assets is essential to meet the rapid optimal location so to extract maximum ou of them.There
increase in generation demand. have been various algorithms proposed to determine optimal
An increased demand of generation requires an increase location of Facts devices [10],[11],[12].
power transfer through lines which is limited by the thermal,
voltage and stability of lines [1]. As the lines are operated near
to their critical limits of power angles or voltage limits; any II. TCSC
disturbance in such a system can result in instability like The dynamic applications of TCSCs, various control
power system oscillation [2] and may lead to generator techniques and designs have been proposed for damping
outages and ultimately blackout. A solution is to develop new power oscillations to improve system dynamic response,
lines, but this requires a high system cost, complexity of whereas for steady state control, the main interest of users
protection system design, time requirements and and researchers has been the use of the this controller for
environmental issues etc. These restrictions on the power flow control in transmission lines, usually considering
construction of new transmission lines have persuaded the optimal scheduling.
power system designers to look for some alternative solutions A typical TCSC module consists of a fixed series capacitor
to increase the power system stability and efficiently transmit (FC) in parallel with a thyristor controlled reactor (TCR). It is
power over the transmission lines. All these problems of connected in series with the transmission line and is used to
environmental and regulatory concerns, and reliability and control the real power flow by controlling the electrical length
stability issues are mitigated by a new class of Power of transmission line along with providing increased SSR
electronic devices named as Flexible AC Transmission stability. There may be one or more TCSC modules in series
Systems which brings us to the second option and that is in a practical TCSC construction.
implementation of FACTS devices. The economical
prospective of FACTS device has been discussed in [3].
Although there is an another option to use the traditional

136102-4848-IJECS-IJENS © April 2013 IJENS


IJ EN S
International Journal of Engineering & Computer Science IJECS-IJENS Vol:13 No:02 31
1) TCR Therefore by varying the conduction angle the fundamental
A TCR consists of a fixed reactor in series with a bidirectional reactance of the TCSC can be controlled and can be made
thyristor controlled switch which is fired with a phase angle α either inductive or capacitive.
ranging between 90º and 180º with respect to the voltage. Putting the value of XL(α) in the above relation (3), the
following result equation (4) is obtained.

X TCSC ( )   X C  C1 (2(   )  sin(2(   )))


 C2 cos 2 (   )( w tan( w(   ))
 tan(   ))
(4)

where,
XC X L
X LC 
XC  X L
XC  X L
C1  [14]
Fig. 1. T hyristor controlled reactor [13]

The overall action of the thyristor controller on the linear X 2
C2  4 LC
reactor is to enable the reactor to act as a controllable  XL
susceptance, in the inductive sense, which is a function of the
firing angle. However, this action is not trouble free, since the XC
TCR achieves its fundamental frequency steady-state w
operating point at the expense of generating harmonic XL
distortion, except for the condition of full conduction. For the range of 0 to 90 of α, XL (α) start vary from actual
First, consider the condition when no harmonic distortion is reactance XL to infinity. This controlled reactor is connected
generated by the TCR, which takes place when the thyristors across the series capacitor, so that the variable capacitive
are gated into conduction, precisely at the peaks of the supply reactance is possible across the TCSC to modify the
voltage. The reactor conducts fully, and one could think of the transmission line impedance.
thyristor controller as being short-circuited. The reactor The impedance characteristic is shown in Fig. 2.
contains little resistance and the current is essentially
sinusoidal and inductive, lagging the voltage by almost 90
(p/2) [13].

2) TCSC Impedance
A TCSC is a parallel combination of TCR and a fixed
capacitor. The TCR reactance as a function of firing angle is
given by (2)

X L ( )  X L (2)
  2  sin 2
(2) [14]
As this variable reactance comes in parallel with the fixed
capacitor so in the equivalent circuit, the capacitance can be
considered to be variable as well [14].
The steady state fundamental impedance of the TCSC is given
by (3) Fig. 2. Impedance diagram of T CSC [14]

X C  X L ( ) 3) Stability Analysis
X TCSC  (3) The system considered for study is the IEEE 14 bus system.
X C  X L ( ) The system is modified by adding Automatic voltage
regulators to all generators. The test system as seen in PSAT is
shown in Fig3.

136102-4848-IJECS-IJENS © April 2013 IJENS


IJ EN S
International Journal of Engineering & Computer Science IJECS-IJENS Vol:13 No:02 32
Eigen value 2 0.737 -8.1012

Fig. 5. steady state stability analysis of test system


Fig. 3. Equivalent circuit as variable capacitor

Bus 13

Bus 14
Bus 10

Bus 12

Bus 09
Bus 11

Bus 07

Bus 06
Bus 08
Bus 04

Bus 05
Bus 01

Bus 02

Bus 03

Fig. 6. generator speeds for base case


Fig. 4. IEEE 14 bus modified system for study [15]
1.075
The Steady state analysis of the system is performed using the VBus 01
1.07
eigen-value analysis available in PSAT. The obtained results VBus 02

1.065
show two positive eigen-values which are of the generator 1
excitation system hence the system is steady state unstable. An 1.06

analysis of generator speeds, power and voltage profile shows 1.055

that the generator 1 is contributing the maximum towards 1.05


power oscillations. The Steady state stability analysis results
1.045
obtained from PSAT are shown in Fig.5. The positive eigen
values are 1.04

1.035

Eigen value 1 0.737 8.1012 1.03


0 5 10 15 20 25 30
time (s)

Fig. 7. voltage profiles of bus1 and bus 2 base cases


T he steady state stability of the system is improved by adding turbine
governor to the generators. The simulations results and eigen value analysis
high-lighten this result.

136102-4848-IJECS-IJENS © April 2013 IJENS


IJ EN S
International Journal of Engineering & Computer Science IJECS-IJENS Vol:13 No:02 33
III. TRANSIENT ST ABILIT Y
Now the line outage 2-5 has been done with the help of circuit
breaker at 1sec. From the above eigen value analysis,
generator speeds and voltage profile, it can be inferred that the
system gets unstable with line outage of 2-5 but as shown in
previous figures system was stable with turbine governor. So
it is concluded that turbine governor is not able to make the
system transiently stable.

Fig. 8. Steady state stability through T urbine governor

Fig. 11. line 2-5 Outage without T CSC

1.0008

1.0006

1.0004
Fig. 9. generator speeds after steady state stability
1.0002

1
It is clear from the figure 9 that for the steady state stable
system both the generators operate at their synchronous speeds 0.9998

and there are no inter area oscillations. 0.9996

0.9994

0.9992 Syn 1
1.064

0.999 
1.062 Syn 2

1.06 0.9988
0 5 10 15 20
time (s)
1.058
Fig. 12. Generator speeds for line outage
1.056
V
Bus 01

1.054 V 1.075
Bus 02
VBus 01
1.052 1.07
VBus 02
1.05 1.065

1.048
1.06
1.046
1.055
1.044
0 5 10 15 20
time (s) 1.05

Fig. 10. Voltage profile for steady state stable system. 1.045

1.04
It is clear from Fig.10 that the turbine governor has restored
the steady state stability of the system. However, in this 1.035

system, for a large disturbance such as the line outage of a 1.03


0 5 10 15 20
critical line like line 2-5, the system is unstable. This transient time (s)
stability is then improved using TCSC.
Fig. 13. Voltage profile for T ransient stability

136102-4848-IJECS-IJENS © April 2013 IJENS


IJ EN S
International Journal of Engineering & Computer Science IJECS-IJENS Vol:13 No:02 34
Now TCSC has been inserted between bus 1 and 5 to improve From the Fig.14, Fig.15 and Fig.16, it is concluded that TCSC
the transient stability. between line 1 and 5 has made the system transiently stable in
spite of the occurrence of fault at 1sec. There are oscillations
15
in the system when line outage occurs but TCSC damps out
these oscillations and make the system stable.
10

REFERENCES
5
[1] H.R.Baghae,M.Jannat,,B.Vahidi,S.H Hosseinain,H.Rastegar ,
“Improvement of Voltage Stability and Reduce Power System
Lossess by GA-based allocation of Multi-Type FACT S Devices”,
Imag

0
IEEE.
[2] W.Du,H.F.Wang and R.Dunn ,“Power System Oscillation Stability
-5
and Control by FACT S and ESS-A Survery” , IEEE
[3] Jospeh Mutale and Goran Strbac , “T rasnmission Network
-10 Reinforcement Versus FACT S: An Economic Assessment” , IEEE
T ransaction on Power System,Vol.15,No.3,August 2000
[4] Ying Xiao,Y.H Song,Chen-Ching Liu and Y.Z.Sun , “ Available
-15
-50 -45 -40 -35 -30 -25 -20 -15 -10 -5 0 T ransfer Capability Enhancement Using FACTS Devices” ,IEEE
Real T ransactions on Power Systems,Vol.18,No.1,February 2003
Fig. 14. T ransiently stable system with T CSC [5] Cuong Vu T he,Khanh La Minh,T uan T ran Quoc,Nguyen Boi
Khue and Lam Du Son, “ FACT S Devices Applications on Power
1.0014 System to Improve the Angle Stability” , 2006 IEEE.
[6] Sandeep Gupta,R.K T ripathi and Rishabv Dev Shukla, “ Voltage
1.0012
Stability Improvement in Power Systems Using Facts
1.001
Controllers:State-of-the-Art Review” , 2010 IEEE
[7] Heinz K.T yll, Frank Schettler, “Historical Overview on Dynamic
1.0008 reactive power compensation solutions from the begin of AC
power transmission towards present applications” , 2009 IEEE.
1.0006
[8] HADI SAADAT , “ Power system analysis”, 2 nd Edition, McGraw,
1.0004
Oct 2007.
[9] John J.Paserba , “ How FACT S Controllers Benefit AC
1.0002 T ransmission Systems-Phases of Power System Studies”2009
IEEE.
1 Syn 1
[10] M.M.EI Metwally,A.A.E.I Emary,F.M.E.I Bendary and
Syn 2
0.9998 M.I.Mosaad , “Optimal Allocation of FACT S Devices in Power
System Using Genetic Algorithms” ,2008 IEEE.
0.9996
0 5 10 15 20
[11] Belkacem Mahdad,T arek Bouktir and Kamel , “ Strategy of
time (s) Location and Control of FACT S Devices for Enhancing Power
Fig. 15. Generator speeds with T CSC Quality” ,2006 IEEE.
[12] Baghaee, H.R Jannati,M.Vahidi,B.Hosseinian,S.H Jazebi,
1.07 “Optimal Multi-Type FACTS Allocation Using Genetic Algorithm
to Improve Power System Security” ,Power System
Conference,2008 . MEPCON 2008.12th International Middle-East
1.065
12-15 March 2000.
[13] Enrique Acha, Claudio R. Fuerte-Esquivel, Hugo Ambriz-Pe ´ rez,
Ce ´sar Angeles-Camacho , “FACTS Modelling and Simulation in
1.06
Power Networks” , page 12-20
[14] S. Meikandasivam, Rajesh Kumar Nema, Shailendra Kumar Jain,
“ Behavioral Study of T CSC Device – A MAT LAB/Simulink
Implementation” .
1.055
[15] PSAT v2.12

VBus 01
1.05
VBus 02

1.045
0 5 10 15 20
time (s)

Fig. 16. Voltage profile with T CSC