Professional Documents
Culture Documents
Duct Insulation
Duct Insulation
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including Conditions of Contract and
Division 1 Specification Sections, apply to this Section.
0.2 SUMMARY
A. This Section includes semirigid and flexible duct, plenum, and breeching insulation;
insulating cements; field-applied jackets; accessories and attachments; and sealing
compounds.
A. Materials shall be compatible and shall not contribute to corrosion, soften, or otherwise
attack surfaces to which they are applied in either the wet or dry state. Materials to be used
on stainless-steel surfaces shall meet ASTM C 795 requirements. Materials shall be
asbestos free.
C. Adhesives, coatings, and sealants shall be nonflammable in their wet state. Adhesives,
coatings, and sealants shall have published or certified temperature ratings suitable for the
entire range of working temperatures normal for the surfaces to which they are to be
applied.
0.4 SUBMITTALS
A. Product Data: Identify thermal conductivity, thickness, and jackets (both factory and field
applied, if any), for each type of product indicated.
B. Shop Drawings: Show fabrication and installation details for the following:
C. Samples: For each type of insulation, adhesives, coatings, and field-applied jacket. Identify
each Sample, describing product and intended use. Submit 300 mm square sections of each
sample material.
1. Manufacturer's Color Charts: Show the full range of colors available for each type of
field-applied finish material indicated.
D. Material Test Reports: From a qualified testing agency acceptable to the Engineer,
indicating, interpreting, and certifying test results for compliance of insulation materials,
sealers, attachments, cements, and jackets with requirements indicated. Include dates of
tests.
E. Installer Certificates: Signed by the Contractor certifying that installers comply with
requirements.
A. Installer Qualifications: Skilled mechanics who have completed successfully a craft training
program certified by an agency acceptable to the Engineer.
C. Mockups: Before installing insulation, build mockups for each type of insulation and finish
listed below to demonstrate quality of insulation application and finishes. Build mockups
according to the following requirements, using materials indicated for the completed Work:
2. Build mockups with cutaway sections to allow observation of application details for
insulation materials, mastics, attachments, and jackets.
3. Build mockups in the location indicated or, if not indicated, as directed by the
Engineer.
4. Notify the Engineer 7 days in advance of dates and times when mockups will be
constructed.
5. Obtain the Engineer's approval of mockups before starting insulation application.
0.7 COORDINATION
0.8 SCHEDULING
A. Schedule insulation application after testing duct systems. Insulation application may begin
on segments of ducts that have satisfactory test results.
PART 2 - PRODUCTS
A. Insulation conductance shall be maximum values, as tested at any point, not an average.
Insulation conductance found by test to exceed the stipulated maximum shall either be
replaced or augmented by an additional thickness to bring it to the required maximum
conductance.
B. Mineral-Fiber Board Thermal Insulation: Glass fibers bonded with a thermosetting resin.
Comply with ASTM C 612, Type IB, without facing and with all-service jacket
manufactured from kraft paper, reinforcing scrim, aluminum foil, and vinyl film.
C. Mineral-Fiber Blanket Thermal Insulation: Glass fibers bonded with a thermosetting resin.
Comply with ASTM C 553, Type II, without facing and with all-service jacket
manufactured from kraft paper, reinforcing scrim, aluminum foil, and vinyl film.
1. Finish and Thickness: Stucco embossed finish, 0.6 mm thick for indoor installation
and 0.8 mm for outdoor installation unless otherwise noted.
C. Stainless-Steel Jacket: smooth surface or deep corrugated sheets of stainless steel with 0.025
mm thick factory-applied heat bonded polyethylene and kraft paper moisture barrier on
inside surface complying with ASTM A 666, Type 304 or 316; 0.4 mm thick; and roll stock
ready for shop or field cutting and forming to indicated sizes.
1. Jacket Bands: Stainless-steel, Type 304, 19 mm wide.
A. Materials shall be compatible and shall not contribute to corrosion, soften, or otherwise
attack surfaces to which they are applied in either the wet or dry state. Materials to be used
on stainless-steel surfaces shall meet ASTM C 795 requirements. Materials shall be
asbestos free and conform to the following.
B. Glass Cloth and Tape: Comply with MIL-C-20079H, Type I for cloth and Type II for tape.
Woven glass-fiber fabrics, plain weave, presized a minimum of 270 g/sq. m.
D. Wire: 2.0 mm, nickel-copper alloy; 1.6 mm, soft-annealed, stainless steel; or 1.6 mm, soft-
annealed, galvanized steel.
E. Adhesive-Attached Anchor Pins and Speed Washers: Galvanized steel plate, pin, and
washer manufactured for attachment to duct and plenum with adhesive. Pin length
sufficient for insulation thickness indicated.
F. Adhesives:
1. Cloth: Adhesives for adhering, sizing, and finishing open-weave glass cloth shall be
pigmented polyvinyl acetate emulsion and shall conform to the requirements of
ASTM C 916, Type I.
2. Cellular Elastomer: Adhesive for cellular elastomer insulation shall be a solvent
cutback chloroprene elastomer conforming to ASTM C 916, Type I, and shall be a
type approved by the manufacturer of the cellular elastomer for the intended use.
G. Coatings:
1. Outdoor and Indoor Non-Vapor-Barrier Finishing: Coatings for outdoor and indoor
non-vapor-barrier finishing of insulation surfaces shall be pigmented polymer
emulsion recommended by the insulation-material manufacturer for the surface to be
coated and shall be applied to the specified dry-film thickness.
2. Cellular Elastomer Insulation: Finish coating for cellular elastomer insulation shall be
a polyvinylchloride lacquer approved by the manufacturer of the cellular elastomer
for the intended use.
3. Coating Color: Coating color shall conform to color code specified or as directed by
the Engineer.
PART 3 - EXECUTION
0.1 EXAMINATION
A. Examine substrates and conditions for compliance with requirements for installation and
other conditions affecting performance of insulation application.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
0.2 PREPARATION
A. Surface Preparation: Clean and dry surfaces to receive insulation. Remove materials that
will adversely affect insulation application.
A. Apply insulation materials, accessories, and finishes according to the manufacturer's written
instructions; with smooth, straight, and even surfaces; and free of voids throughout the
length of ducts and fittings.
B. Refer to schedules at the end of this Section for materials, forms, jackets, and thicknesses
required for each duct system.
C. Use accessories compatible with insulation materials and suitable for the service. Use
accessories that do not corrode, soften, or otherwise attack insulation or jacket in either wet
or dry state.
D. Apply multiple layers of insulation with longitudinal and end seams staggered.
E. Seal joints and seams with vapor-retarder mastic on insulation indicated to receive a vapor
retarder.
G. Apply insulation with tight longitudinal seams and end joints. Bond seams and joints with
adhesive recommended by the insulation material manufacturer.
I. Apply insulation over fittings and specialties, with continuous thermal and vapor-retarder
integrity, unless otherwise indicated.
J. Hangers and Anchors: Where vapor retarder is indicated, seal penetrations in insulation at
hangers, supports, anchors, and other projections with vapor-retarder mastic. Apply
insulation continuously through hangers and around anchor attachments.
K. Insulation Terminations: For insulation application where vapor retarders are indicated, seal
ends with a compound recommended by the insulation material manufacturer to maintain
vapor retarder.
N. Install vapor-retarder mastic on ducts and plenums scheduled to receive vapor retarders.
1. Ducts with Vapor Retarders: Overlap insulation facing at seams and seal with vapor-
retarder mastic and pressure-sensitive tape having same facing as insulation. Repair
punctures, tears, and penetrations with tape or mastic to maintain vapor-retarder seal.
2. Ducts without Vapor Retarders: Overlap insulation facing at seams and secure with
outward clinching staples and pressure-sensitive tape having same facing as
insulation.
O. Roof Penetrations: Apply insulation for interior applications to a point even with top of roof
flashing.
P. Interior Wall and Partition Penetrations: Apply insulation continuously through walls and
partitions, except fire-rated walls and partitions.
R. Floor Penetrations: Terminate insulation at underside of floor assembly and at floor support
at top of floor.
1. For insulation indicated to have vapor retarders, taper termination and seal insulation
ends with vapor-retarder mastic.
A. Blanket Applications for Ducts and Plenums: Secure blanket insulation with adhesive and
anchor pins and speed washers.
B. Board Applications for Ducts and Plenums: Secure board insulation with adhesive and
anchor pins and speed washers.
DUCT INSULATION 15081 - Page 7/11
STD-SPC-DCA(A3)-ME-DCA REV A
<Project Title>
4. Cut excess portion of pins extending beyond speed washers or bend parallel with
insulation surface. Cover exposed pins and washers with tape matching insulation
facing.
5. Create a facing lap for longitudinal seams and end joints with insulation by removing
50 mm from one edge and one end of insulation segment. Secure laps to adjacent
insulation segment with 13 mm staples, 25 mm o.c., and cover with pressure-sensitive
tape having same facing as insulation.
6. Provide solid inserts to ductwork insulation where supported by bracket. Create
overlap of vapour barrier through brackets.
7. Apply insulation on rectangular duct elbows and transitions with a full insulation
segment for each surface. Groove and score insulation to fit as closely as possible to
outside and inside radius of elbows. Apply insulation on round and flat-oval duct
elbows with individually mitered gores cut to fit the elbow.
8. Insulate duct stiffeners, hangers, and flanges that protrude beyond the insulation
surface with 150 mm wide strips of the same material used to insulate duct. Secure
on alternating sides of stiffener, hanger, and flange with anchor pins spaced 150 mm
o.c.
A. Flexible elastomeric cellular insulation shall be installed with seams and joints sealed with
rubberized contact adhesive. Insulation with pre-applied adhesive is not permitted. Flexible
elastomeric cellular insulation shall not be used on surfaces greater than 93 degrees C.
Seams shall be staggered when applying multiple layers of insulation. Insulation exposed to
weather and not shown to have jacketing shall be protected with two coats of UV resistant
finish as recommended by the manufacturer after the adhesive is dry. A brush coating of
adhesive shall be applied to both butt ends to be joined and to both slit surfaces to be sealed.
The adhesive shall be allowed to set until dry to touch but tacky under slight pressure before
joining the surfaces. Insulation seals at seams and joints shall not be capable of being pulled
apart one hour after application. Insulation that can be pulled apart one hour after
installation shall be replaced.
0.6 FINISHES
A. Flexible Elastomeric Thermal Insulation: After adhesive has fully cured, apply two coats of
insulation manufacturer's recommended protective coating.
B. Color: Final color as selected by the Engineer. Vary first and second coats to allow visual
inspection of the completed Work.
A. Insulation materials and thicknesses are specified in schedules at the end of this Section.
B. Materials and thicknesses for systems listed below are specified in schedules at the end of
this Section.
D. Items Not Insulated: Unless otherwise indicated, do not apply insulation to the following
systems, materials, and equipment:
1. Fibrous-glass ducts.
2. Metal ducts with duct liner.
3. Factory-insulated flexible ducts.
4. Factory-insulated plenums, casings, terminal boxes, and filter boxes and sections.
5. Flexible connectors.
6. Vibration-control devices.
7. Testing agency labels and stamps.
8. Nameplates and data plates.
9. Access panels and doors in air-distribution systems.