Professional Documents
Culture Documents
Icolim 2017 07964144 PDF
Icolim 2017 07964144 PDF
Abstract—Following the implementation of the antigalloping Several versions were designed, tested and even used in some
devices for the 400 kV o/h lines with 2 subconductors per phase, minor projects, demonstrating their high capacity to solve the
as explained in our paper presented by the occasion of the risk of the overhead line conductor galloping with usual
ICOLIM 2014 in Budapest, a new antigalloping device of the frequencies in the range 0.4- 0.6 Hz. The parameter describing
same torsional damper and detuner pendulum type was created the damping performance is the transfer function with values in
and already implemented on some of the 400 kV with 3 the range 1.5- 2.5 in the case of the previous versions. The new
subconductors per phase in Romania, in 2015. version transfer functions came to much better values.
The device is characterized by combining the properties of A description of the pendulum parts, tests carried out and the
torsional damping with those of detuning, avoiding the energy final design are presented.
transfer from the torsion to the vertical motion. The torsional
damping leads to a higher critical wind speed at which the The pendulum can be easy mounted in live- line conditions.
galloping instability appears and limits its amplitude, while the
detuning characteristic of the device separates the torsional and Keywords— damper, galloping, live-line, pendulum, test
vertical frequencies.
I. INTRODUCTION
The new device design took the main shape of that used for 2
conductors per phase, the rigid spacers being now triangular and The galloping phenomenon consists of low frequency and
some differences in the dimensions having to be considered. Nine high amplitude wind induced vibration of the single and
alternatives were taken into account for testing. Finally, based on bundled conductors, with a single or a few loops per span. The
the transfer function diagrams, two alternatives were further met frequencies are in the range of 0.1 to 1 Hz and their
developed and manufactured, the Llght (L) and the Heavy(H). amplitudes may vary from 0.1 to 1 times the sag of the
The axonometric drawing and the view one are shown in the conductors in the span. The galloping may occur if a steady
figure. The difference between these two consists of different wind acts upon an asymmetrically iced conductor surface. The
counterweights (H- 10.9 Kg and L- 8.9 Kg) and different distance wind speed is moderate without to may mention an upper limit
between the counterweight axis ( H- 860 mm, respective L- 830 of the speed and the wind direction has to be of more than 450
mm). to the line axis.
The concept of the damping pendulum as torsional damper The impact on the overhead line structural elements
and detuner (TDD) was created and reported in 1993 by its consists of the excessive loads caused by the conductor
authors led by Prof. Jean-Louis Lilien from University of Liege- movement leading to the horizontal and vertical bending, as
Belgium. well as torsional effects. Because of the large amplitudes of the
galloping oscillations, at the conductor attachment points the
breaking loads may be reached for both tower elements and
insulator string hardware. The torsional oscillations of high
amplitudes lead to the frequent conductor outer strands
breaking.
978-1-5090-5132-8/17/$31.00 ©2017 IEEE
Authorized licensed use limited to: George Florea. Downloaded on September 18,2020 at 13:34:35 UTC from IEEE Xplore. Restrictions apply.
2017 12th International Conference on Live Maintenance (ICOLIM)
During the galloping, especially those characterized by very III. THE TORSIONAL DAMPER AND DETUNER
big amplitudes, the flashovers between phases or from phase to DEVELOPMENT
groundwire may appear, causing the arcing damages to the
The TDD-2 was designed by the research group of Prof.
conductor surface and even broken strands in those conductors.
Jean-Luis Lilien (University of Liege, Belgium) in ’80-ies. The
first devices were manufactured and delivered to the Belgian
II. METHODS OF PROTECTION TSO, ELIA, in 1994. New other types were developed (8.1,
Four types of protection methods against galloping are well 3.1, 2.2a, 2.2b, 2.2, 3.1), for different phase structures [2],
known: starting from 2002. The type 2.3 was preliminary designed by
Dr. Alexander A. Vinogradov from ESSP, Russia, to satisfy the
• The removal of the ice on the conductors, by electrical necessity of the Romanian 400 kV overhead lines equipped
or mechanical means or even the ice formation with 2 ACSR 450/75 conductors per phase, in 2011. The
prevention; Romanian team in charge, under Dr. A. Vinogradov
• Installing antigalloping devices on the supervision, improved and detailed the design. 126 pieces were
conductors/phases, diminishing the risk of the galloping manufactured after the type test performance and were installed
from building up or just from attaining big amplitudes; on a section of the 400 kV Isaccea- Tulcea overhead line. In
2014, other 261 pieces of the same type were manufactured
• Adoption of increased clearances between phases or and installed on two other 400 kV lines in Romania.
from phases to the shieldwires, tolerating the galloping;
But, the galloping is a wide phenomenon met in Romania,
• Reconductoring using the special conductors with a especially in the South- East side of the country and the 400 kV
lower risk of galloping incidence. lines with 3 subconductors per phase (ACSR 300/69), crossing
the region, requested such antigalloping devices. Therefore, a
The ice removal is very well known, but very difficult to be new type of torsional damper and detuner had to be designed
applied. The increased clearances may be applied for the new and tested, the TTD 2.3- RO. In the autumn of 2015 the design
lines, during the design stage, but not on the existing lines and and the type tests were ready. 639 pieces are already installed
can not eliminate or even reduce the dynamic loads caused by on the relevant sections of 3 400 kV single circuit lines.
galloping. The reconductoring is a very expensive solution
without to get significant advantages.
IV. THE TORSIONAL AND DAMPER PENDULUM FOR 3
Concerning the special antigalloping devices, the CIGRE SUBCONDUCTORS PER PHASE
Brochure no. 322 [1] describes 14 types, mentioning their
The main design parameters are: the torsion rigidity, the
characteristics, advantages and disadvantages. The most used
damping properties of the elastomeric units, the pendulum
devices are: the rigid and flexible interphase spacers, the air
inertial momentum around the fixing point and the distance
flow spoilers and the detuning pendulums. The best behavior
between the pendulum weight center and the phase axis.
was got by the detuning pendulums, with a galloping amplitude
reduction of about 90%. The pendulum design took the main shape of that used for 2
conductors per phase (Fig. 1 and Fig. 2), the rigid spacers being
The detuning pendulum action uses the assumption that the
now triangular and some differences in the dimensions having
torsional movement of the bundle interacts with the vertical
to be considered (Fig. 3 and 4).
motion. The wind energy induces a vertical motion through the
torsional movement. To avoid the frequency coalescence
between torsion and vertical movement, causing the instability,
a separation of the frequencies corresponding to the vertical
movement and the torsion motion is needed, the process being
named the detuning. The detuning changes the conductor
dynamics, preventing the potential aerodynamic instability.
The torsional damper and detuner device (TDD) combines
two types of pendulums, the simple pendulum and the torsion
pendulum. The detuning characteristic of the TDD separates
the torsional and vertical frequencies, increasing the torsional
frequency. The damping characteristic of the torsion pendulum
limits the galloping torsion amplitude. During the gallopings,
especially those characterized by very big amplitudes, the
flashovers between phases or from phase to groundwire may Fig. 1. The torsional damper and detuner for 2 subconductors per phase
(photo)
appear, causing the arcing damages to the conductor surface
and even broken strands in those conductors.
Authorized licensed use limited to: George Florea. Downloaded on September 18,2020 at 13:34:35 UTC from IEEE Xplore. Restrictions apply.
2017 12th International Conference on Live Maintenance (ICOLIM)
V. TYPE TESTS
No standards are issued concerning these pendulums, so the
proposed type tests took into consideration the relevant suitable
tests provided by the IEC standards IEC 61897:1998
“Overhead lines – Requirements and tests for Stockbridge type
Aeolian vibration dampers” and IEC 61854: 1998 “Overhead
lines. Requirements and tests for spacers” [4, 5].
The requirements were fulfilled performing the type tests,
but sample tests, too.
Regarding the reliability the fatigue tests were carried out in
the case of:
Fig. 3. The torsional damper and detuner for 3 subconductors per phase • 0.4 Hz – 1,000,000 oscillations;
(drawing)
• 1.5 Hz - 10.000.000 oscillations;
• 20 Hz – 100.000.000 oscillations.
No welding damages or bolt unscrewing could be observed
after the mentioned cycles.
The damping properties of the pendulum were tested by the
IEC 61854 method (page 37 of the standard, Art. C- Damping
method), resulting the transfer function or the logarithmical
decrement. The results are shown in the diagrams of the Fig. 5
and 6, for the 2 types of pendulums.
10.9 kg x 860 mm
6
5
Fig. 4. The torsional damper and detuner for 3 subconductors per phase
4
(view drawing)
3
2
Without the devices (damper and detuner pendulums), the 1
vertical frequency of the phases are in the range of 0.16- 0.18 0
Hz, the torsional frequency being in the range of 0.19- 0.22 Hz. 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
After the device installation (3 per span and phase), the vertical
10.9 kg x 860 mm
frequency comes into the range of 0.15- 0.17 Hz and the
torsional one in the range of 0.45- 0.47 Hz. So, the major risk
of galloping occurrence appears for the first harmonic of the Fig. 5. Heavy device – initial transfer function
torsional oscillation with the third harmonic of the vertical
motion, this affecting the middle of the span (one loop and The difference between these two consists of different
three loops galloping). Nine alternatives were considered and counterweights (H- 10.9 Kg and L- 8.9 Kg) and different
manufactured for testing, with different weights and distances
Authorized licensed use limited to: George Florea. Downloaded on September 18,2020 at 13:34:35 UTC from IEEE Xplore. Restrictions apply.
2017 12th International Conference on Live Maintenance (ICOLIM)
5
4
3
2
1
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
8,9 kg x 830 mm
A. General Circumstances
For practical works the Procedure NTE 010/11/00 –
Technical Normative Establishing the Requirements for Live
Working in Electrical Networks and working procedures of
Smart should be applied.
The method applied is “bare hand” (the worker finds
himself at the same potential as the conductive elements on
which he is working)
When the works have to be done it is necessary for the
equipment to be in special exploitation regime (RSE) which
consists in: Auto reclosing cancelled, radio or telephone links
Fig. 7. Installation by trolley chariot have to be established between the working area and operative
dispatch centre, The reclosing of the OHL should be done
manually, only when the LW foreman agrees.
Authorized licensed use limited to: George Florea. Downloaded on September 18,2020 at 13:34:35 UTC from IEEE Xplore. Restrictions apply.
2017 12th International Conference on Live Maintenance (ICOLIM)
Authorized licensed use limited to: George Florea. Downloaded on September 18,2020 at 13:34:35 UTC from IEEE Xplore. Restrictions apply.