You are on page 1of 2

Reference Drawings

Drwg. No. Title


Revisions

Name Date Notes


□ Approval □ Approved as noted □ Returned □ Approval
for correction

DATE: SIGNITURE

GOVERNMENT OF THE REPUBLIC OF THE SUDAN


NATIONAL ELECTRICITY CORPORATION(NEC)
KHARTOUM - SUDAN
CONTRACTOR SUBCONTRACTOR

Dongula - Wadi Halfa 220 kV Transmission Line Project


H P E - D W - L 1 3 T L G - N T 0 0 7
Name Date
Prepared May.28,2009
Drawn May.29,2009 Design data - OPGW ACS 89
Checked May.30,2009
Approved May.31,2009
Scale: Size A4 NIEPC Reg No: REV. 0
HPE DONGLA – WADI HALFA 220kV T/L PROJECT

DESIGN DATA – OPGW ACS 89 
DESCRIPTION UNITS GUARANTEED
Appropriate IEC/ VDE/ DIN/ ASTM Standards and
Recommendations
Code Name: ACS 89
Cross section area mm² 88.8
Stranded overall diameter of conductor mm 12.6
Number an diameter of ACS wires mm 1/2.6+17/2.5
Number an diameter of steel tube mm 1/2.5
Direction of outer layer Right hand
Elasticity modulus N/mm² 140000
Mass of conductor per m kg 0.558
Min. bending radius mm 189
Rated Tensile Strength kN 91.1
Maximum tension of earthwire conductor:
Suspension Towers Newton 26029
Tension Towers Newton 26029
Earthwire of downleads Newton 11000
Assumed equivalent coefficient of linear expansion of OPGW per °C 0.0000134
Standard length of unjointed conductor on drum m 5000
Number of vibration dampers per span
• Span up to 400m
• Span over 400m
Dimension from clamp mouth to vibration damper
• First damper mm
• Second damper when required mm
Ambient temperature range °C 0 to + 55
Rated mode field diameter at 1310 nm µm 9,2 ±0,5
Mode field diameter at 1550nm µm 10.2 ±1.0
Attenuation coefficient at 1310nm dB/km ≤0.34
Attenuation coefficient at 1550nm dB/km ≤0.20
Chromatic Dispersion at 1310nm ps/nm.km ≤3.5
Chromatic Dispersion at 1550nm ps/nm.km ≤18
Electrical resistance of earth wire at 20°C Ohm/ km 0.733 (max.)
Short circuit current (minimum) kA 47.5

Page: 1 of 1

You might also like