10 Minimum spacing of rows of seats from back to back for a public assembly building. 0.83 mtr.
Maximum travel distance between room door intended as exit access and exit with
39 30 mts.
sprinkler system for institutional use.
40 Maximum travel distance from the door of any room to exit for hotels with sprinkler. 30 mts.
Maximum travel distance from the main entrance door to exit for apartments with
41 31 mts.
sprinkler.
42 Minimum increase in width for an aisle per linear meter. 2.5 cms.
Minimum width of an aisle serving an occupant of 60 or more serving one side for a
43 91 cms.
public assembly building.
Minimum width of an aisle serving an occupant of 60 or more serving two sides for a
44 1.00 mtr.
public assembly building.
Armories with an occupant load of more than 100 are classified under what classification
54 Assembly
of occupancy
56 Rooms where baled, bundled or piled materials segregated into desired sizes or groups. Picking rooms.
An air compartment or chamber to which 1 or more ducts are connected and which form
59 Plenum
part of an air distribution system.
147 Any room for sleeping in institutional occupancies if subdivided shall have a maximum
465 sqm.
area of how many square meters?
148 Includes buildings or groups of building under the same management in which there are
Hotel
more than 15 sleeping accommodations for hire.
149 Includes buildings containing three or more living units independent cooking and bathroom
facilities, whether designed as rowhouse, apartment house, tenement, garden apartment, Apartment Buildings
or by any other name.
150 Minimum number of stories of apartment buildings requiring fire alarm system. 3
151 Minimum number of apartment units requiring fire alarm system. 12