STANDBY Key

▼ Returns to the first screen in the series

MENU RESET Highlighted Text indicates adjustable fields


MAIN MENU MAIN MENU
1)Control 4)Faults
2)Adjust
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼

CONTROL CTRL TEST TEST START/STOP TEST START/STOP


1)Test Transition Type: Transition Type:
2)Ext Parallel 1)Start/Stop Hard Closed Trans Confirm? Hard Closed Trans
3)Ld Demand 2)Settings Test With Load: Test With Load:
4)Ld Add Shed Disabled Disabled
(1) (2) (3) (4) (1) (2) START YES NO STOP

TEST SETTINGS
Transition Type:
Hard Closed Trans
Test With Load:
Disabled
ADJUST

CTRL EXT PARALL EXTPAR START/STP EXTPAR START/STP


1)Start/Stop kW Load Cntl: kW Load Cntl:
Genbus % Level Genbus % Level
2)Settings kVAR Load Cntl: kVAR Load Cntl:
Utility Bus PF Utility Bus PF
(1) (2) START STOP

CTRL EXT PAR SET Genset Bus % Level Genset Bus kW Genset kW w/Util Const Utility Bus kW
Vary kW Const kW Vary kW Const kW Vary kW Const kW Const kW Vary kW
1)kW Control
2)kVAR Control -65535 kW -65535 kW -65535 kW -65535 kW -65535 kW -65535 kW -65535 kW -65535 kW
100 % -65535 kW -65535 kW -65535 kW -65535 kW

(1) (2) ADJUST ADJUST ADJUST ADJUST

Genset Controls Genset Bus % Level Genset Bus PF (OL) Genset Bus kVAR Genset Bus PF (CL) Utility Bus kVAR Utility Bus PF
Vary kVAR Const kVAR Vary kVAR Const kVAR Vary PF Const PF Vary kVAR Const kVAR Vary PF Const PF Const kW Vary kW Vary PF Const PF

-65535 kVAR -65535 kVAR -1.0 PF -1.0 PF -65535 kVAR -1.0 PF -1.0 PF -65535 kVAR -65535 kVAR -1.0 PF -1.0 PF
-65535 kVAR -65535 kVAR 100 % -1.0 PF -1.0 PF -65535 kVAR -1.0 PF
-65535 kVAR -65535 kVAR

ADJUST ADJUST ADJUST ADJUST ADJUST ADJUST ADJUST

CNTRL LD DEMAND GEN STATUS LD Gen NOW NEW Gen NOW HRS NEXT GEN THRESH CNTRL LD DEMAND Notes:
Ld Enable: 1 NoExist Run A Gen1 Gen4 A Gen1 4 Off Gen2 12345kW Total Online Cap The Gen NOW NEW screen is not available when CNTRL LD DEMAND Ld Type is
Disabled 2 Offline Stop B Gen2 Gen3 B Gen2 3
2 On None 0kW 1234 kW
Ld Type: 3 Online Run C Gen3 Gen2 C Gen3 2 set to Run Hours.
Gen Tot 12345kW Spare Online Cap
Run Hours 4 Waiting Run D Gen4 Gen1 D Gen4 1 2345 kW The Gen NOW HRS screen is not available when CNTRL LD DEMAND Ld Type is
ADJUST ▼ ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ▼ ▲ ▲ set to Fixed Sequence Adjust.

CTRL LD ADD SHED CTRL LD ADD SHED CTRL LD ADD SHED CTRL LD ADD SHED Notes:
Add Levels Shed Levels Total Online Cap
Load Add Shed 1: Add 4: Off 0: Off 3: Off The CTRL LD ADD SHED CTRL button is only available when Load Add/Shed Control is set to Manual.
2345kW
Control: Manual
Manual 2: Add 5: Off 1: Shed 4: Off Spare Online Cap
3: Add 6: Off 2: Shed 5: Off 1245kW
ADJUST ▼ CTRL CAP ▼ ▲ CTRL CAP ▲ BACK

CTRL LD ADD SHED CTRL LD ADD SHED


Add Levels Shed Levels
1 Add
1: 4 Off
4: 0: Off 3 Off
3:
2:
2 Add 5:
5 Off 1 Shed
1: 4:
4 Off
3:
3 Add 6:
6 Off 2 Shed
2: 5 Off
5:
→ Add ▼ ▲ → Shed ▼ ▲

Control
STANDBY

▼ Returns to the first screen in the series

MENU RESET

MAIN MENU MAIN MENU ENTER PASSWORD


1)Control 4)Faults
2)Adjust Password: XXX
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼ View → – +

ADJUST ADJUST ADJUST ADJUST ADJUST


1)ACMeter Adjust 4)Communication 7)PTC 10)System 13)Ld Demand
2)ACMeter Setup 5)Config Output 8)Sync Check 11)Scheduler 14)Ld Add Shed
3)Breakers 6)Load Control 9)Sync Adjust 12)LCD Display 15)Gen Bus Overld
▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) (6) ▼ (7) (8) (9) ▼ (10) (11) (12) ▼ (13) (14) (15) ▼

AC METER ADJUST ACMETER GEN ACMETER GEN


1) Genset L1L2: 19 V L1: 25 Amps
L2L3: 9 V L2: 24 Amps
2) Utility
L3L1: 21 V L3: 19 Amps
(1) (2) ADJUST ▼ ADJUST ▲

ACMETER UTIL ACMETER UTIL


L1L2: 481 V L1: 0 Amps
L2L3: 480 V L2: 277 Amps
L3L1: 485 V L3: 279 Amps
ADJUST ▼ ADJUST ▲

AC METER SETUP ACMETR GEN SETUP ACMETR GEN SETUP ACMETR GEN SETUP
1) Genset Connection Type: PT Primary Volt: CT Primary Curr:
Delta 120 Volts 10000 Amps
2) Utility Nominal Voltage: PT Secondary CT Secondary
120 Volts Volt: 120 Volts Curr: 5 Amps
(1) (2) ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

ACMETR UTL SETUP ACMETR UTL SETUP ACMETR UTL SETUP


Connection Type: PT Primary Volt: CT Primary Curr:
Delta 120 Volts 10000 Amps
Nominal Voltage: PT Secondary CT Secondary
120 Volts Volt: 120 Volts Curr: 5 Amps
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

ADJ BREAKERS BREAKER GENSET BREAKER GENSET


1) Genset CB Fail To Close CB Recharge
Delay: 5.0 sec Delay: 60.00 sec
2) Utility CB Fail To Open Breaker Position
Delay: 5.0 sec Contcts: Single
(1) (2) ADJUST ▼ ADJUST ▲

BREAKER UTILITY BREAKER UTILITY


CB Fail To Close CB Recharge
Delay: 5.0 sec Delay: 60.00 sec
CB Fail To Open Breaker Position
Delay: 5.0 sec Contcts: Single
ADJUST ▼ ADJUST ▲

COMMUNICATIONS COMMUNICATIONS
Modbus Address:
1 Modbus Parity:
Modbus Baud: Even
19200
ADJUST ▼ ADJUST ▲

Adjust 1
STANDBY

▼ Returns to the first screen in the series

MENU RESET

MAIN MENU MAIN MENU ENTER PASSWORD


1)Control 4)Faults
2)Adjust Password: XXX
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼ View → – +

ADJUST ADJUST ADJUST ADJUST ADJUST


1)ACMeter Adjust 4)Communication 7)PTC 10)System 13)Ld Demand
2)ACMeter Setup 5)Config Output 8)Sync Check 11)Scheduler 14)Ld Add Shed
3)Breakers 6)Load Control 9)Sync Adjust 12)LCD Display 15)Gen Bus Overload
▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) (6) ▼ (7) (8) (9) ▼ (10) (11) (12) ▼ (13) (14) (15) ▼

CONFIG OUTPUTS CONFIG OUTPUTS CONFIG OUTPUTS CONFIG OUTPUTS CONFIG OUTPUTS
Config Output 1 Config Output 3 Config Output 5 Config Output 7 Start Gensets
Fault #: 1483 Fault #: 2965 Fault #: 1121 Fault #: 1456 Relay Active
Config Output 2 Config Output 4 Config Output 6 Config Output 8 State:
Fault #: 1457 Fault #: 2328 Fault #: 1916 Fault #: 343 Deenergized
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▲

ADJ LOAD CNTL ADJ LOAD SETUP LOAD CNTL MISC LOAD CNTL MISC LOAD CNTL MISC LOAD CNTL MISC
1)Misc Extend Par kW Extend Par kVAR kW Load Cntl Max
1)Setup Load Cntl Type: Load Cntl Type:
2)Genset % Out: 100.00 % Extend Par Ramp
2)Tuning Gen Bus % Gen Bus % kVAR Ld Cntl Max Ld Time: 90.0 s
3)Utility Level — Open Loop Level — Open Loop % Out: 100.00 %
(1) (2) (1) (2) (3) ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▲

LOAD CNTL GENSET LOAD CNTL GENSET LOAD CNTL GENSET LOAD CNTL GENSET
kW SetPt Source: kW SetPoint: Power Factor
Analog Input 32000 kW SetPt: 1.00 % kVAR SetPoint:
k V A R Se t P t Sr c : kVAR SetPoint: % kW SetPoint: 105 %
Internal 32000 kVAR 100.00 %
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▲

LOAD CNTL UTIL LOAD CNTL UTIL LOAD CNTL UTIL


kW SetPt Source: kW SetPoint: Power Factor
Analog Input 32000kW SetPt: 1.00
kVAR SetPt Src: kVAR SetPoint: kW Constraint
Internal 32000kVAR Level: 100 kW
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

ADJ LOAD TUNING LOAD CNTL TUNING LOAD CNTL TUNING LOAD CNTL TUNING
1)kW kW Kp: 1000 kW Adaptive Gain
2)kVAR kW Adaptive Gain Error Threshold: kW Ki: 255
Slope: 50.000 /% 10.00 %

(1) (2) ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

LOAD CNTL TUNING LOAD CNTL TUNING LOAD CNTL TUNING


kVAR Kp: 1000
kVAR Adaptive
Gain Error Thres: kVAR Ki: 255
kVAR Adapt Gain
50.000 /% 10.00 %
Slope:
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

Adjust 2
STANDBY

▼ Returns to the first screen in the series

MENU RESET

MAIN MENU MAIN MENU ENTER PASSWORD


1)Control 4)Faults
2)Adjust Password: XXX
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼ View → – +

ADJUST ADJUST ADJUST ADJUST ADJUST


1)ACMeter Adjust 4)Communication 7)PTC 10)System 13)Ld Demand
2)ACMeter Setup 5)Config Output 8)Sync Check 11)Scheduler 14)Ld Add Shed
3)Breakers 6)Load Control 9)Sync Adjust 12)LCD Display 15)Gen Bus Overload
▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) (6) ▼ (7) (8) (9) ▼ (10) (11) (12) ▼ (13) (14) (15) ▼

ADJUST PTC ADJ GEN PTC SENS PTC GEN MISC PTC GEN MISC PTC GEN MISC PTC GEN MISC
1)Gen Sensors 1)Misc Volt Sensr Type: Loss Phase Drop. Online Cap Sensr Unloaded Level:
2)Time Delay 2)Undervoltage Line To Neutral Delay: 10.0 s Enable: Disabled 50 kW
3)Overvoltage Loss Phase Sensr Phase Rot Sensor Online Cap Sensr Dead Bus Thresh:
3)Util Sensors 4)Frequency Enable: Disabled Thresh: 32000 kW 50.0 %
Enable: Enabled
(1) (2) (3) (1) (2) (3) (4) ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▲

PTC GEN UNDERVLT PTC GEN UNDERVLT PTC GEN UNDERVLT


Dropout Percent: Dropout Delay:
98.00 % 30.0 s Pickup Threshld:
Pickup Percent: Drpout Threshld: 57 V
100.00 % 65000 V
ADJUST ▼ ADJUST ▼ ▲ ▲

PTC GEN OVERVOLT PTC GEN OVERVOLT PTC GEN OVERVOLT


Sensor Enable: Pickup Percent: Drpout Threshld:
Disabled 5.0 % 65 V
Dropout Percent: Dropout Delay: Pickup Threshld:
135.00 % 20.0 s 60 V
ADJUST ▼ ADJUST ▼ ▲ ▲

PTC GEN FREQ PTC GEN FREQ PTC GEN FREQ PTC GEN FREQ PTC GEN FREQ
Sensor Enable: Drpout Bandwdth: Dropout Delay: Lower Pickup
Disabled 10.0 % 15.0 s Thresh: 99.9 Hz Upper Dropout
Center Frequncy: Pickup Bandwdth: Lower Dropout Upper Pickup Thresh: 99.9 Hz
65.0 Hz 10.0 % Thresh: 99.9 Hz Thresh: 99.9 Hz
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ▼ ▲ ▲

PTC TIME DELAY PTC TIME DELAY PTC TIME DELAY


Start Time Delay Transfer Delay Programmed Trans
(TDES): 2400.0 s (TDNE): 120.0 s (TDPT): 60.0 s
Stop Time Delay Retransfer Delay Max Parallel
(TDEC): 3600.0 s (TDEN): 1800.0 s (TDMP): 1800.0 s
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

Continued on next sheet

Adjust 3
STANDBY

▼ Returns to the first screen in the series

MENU RESET

MAIN MENU MAIN MENU ENTER PASSWORD


1)Control 4)Faults
2)Adjust Password: XXX
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼ View → – +

ADJUST ADJUST ADJUST ADJUST ADJUST


1)ACMeter Adjust 4)Communication 7)PTC 10)System 13)Ld Demand
2)ACMeter Setup 5)Config Output 8)Sync Check 11)Scheduler 14)Ld Add Shed
3)Breakers 6)Load Control 9)Sync Adjust 12)LCD Display 15)Gen Bus Overload
▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) (6) ▼ (7) (8) (9) ▼ (10) (11) (12) ▼ (13) (14) (15) ▼

ADJUST PTC
1)Gen Sensors
2)Time Delay
3)Util Sensors
(1) (2) (3)

ADJ PTC UTL SENS PTC UTIL MISC PTC UTIL MISC PTC UTIL MISC
1)Misc Volt Sensr Type: Loss Phase Drop. Unloaded Level:
2)Undervoltage Line To Neutral Delay: 10.0 s 50 kW
3)Overvoltage Loss Phase Sensr Phase Rot Sensor Dead Bus Thresh:
4)Frequency Enable: Enabled Enable: Disabled 50.0 %
(1) (2) (3) (4) ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

PTC UTIL UNDERVLT PTC UTIL UNDERVLT PTC UTIL UNDERVLT


Dropout Percent: Dropout Delay:
98.00 % 30.0 s Pickup Threshld:
Pickup Percent: Drpout Threshld: 248 V
100.00 % 224 V
ADJUST ▼ ADJUST ▼ ▲ ▲

PTC UTIL OVERVLT PTC UTIL OVERVLT PTC UTIL OVERVLT


Sensor Enable: Pickup Percent: Drpout Threshld:
Disabled 5.0 % 804 V
Dropout Percent: Dropout Delay: Pickup Threshld:
135.00 % 20.0 s 289 V
ADJUST ▼ ADJUST ▼ ▲ ▲

PTC UTIL FREQ PTC UTIL FREQ PTC UTIL FREQ PTC UTIL FREQ PTC UTIL FREQ
Sensor Enable: Drpout Bandwdth: Dropout Delay: Lower Pickup
Disabled 10.0 % 15.0 s Thresh: 99.9 Hz Upper Dropout
Center Frequncy: Pickup Bandwdth: Lower Dropout Upper Pickup Thresh: 99.9 Hz
65.0 Hz 10.0 % Thresh: 99.9 Hz Thresh: 99.9 Hz
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ▼ ▲ ▲

Adjust 4
STANDBY

▼ Returns to the first screen in the series

MENU RESET

MAIN MENU MAIN MENU ENTER PASSWORD


1)Control 4)Faults
2)Adjust Password: XXX
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼ View → – +

ADJUST ADJUST ADJUST ADJUST ADJUST


1)ACMeter Adjust 4)Communication 7)PTC 10)System 13)Ld Demand
2)ACMeter Setup 5)Config Output 8)Sync Check 11)Scheduler 14)Ld Add Shed
3)Breakers 6)Load Control 9)Sync Adjust 12)LCD Display 15)Gen Bus Overload
▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) (6) ▼ (7) (8) (9) ▼ (10) (11) (12) ▼ (13) (14) (15) ▼

SYNC CHECK SYNC CHECK SYNC CHECK SYNC CHECK SYNC CHECK SYNC CHECK
Permissive Freq Permissive Volt Fail To Sync Fail To Sync Dead Util Dead Dead Util Live
Window: 1.000 Hz Window: 10.0 % Time: 900.0 sec Open Transition Gen: Disabled Gen: Enabled
Permissive Phase Permissive Windw Fail Sync Lckout Retransfer Live Util Dead Live Util Live
Window: 20.00 º Time: 5.00 sec Enable: Disable Enable: Disabled Gen: Disabled Gen: Disabled
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▲

ADJ SYNC ADJUST SYNC ADJ MISC SYNC ADJ MISC SYNC ADJ MISC
1)Misc System Frequncy: Slip Frequency: Phase Match Kp:
2)Frequency 65.0 Hz 3.000 Hz 150
Sync Method: Sync Phase Offst: Volt Match Test
3)Voltage Phase Match -50.00 deg Offset: -10.0 %
(1) (2) (3) ▼ ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

SYNC ADJ FREQ SYNC ADJ FREQ SYNC ADJ FREQ


Freq Match Kp: Freq Match Ramp
30 Freq Match Upper
Freq Match Ki: Rate: 60.00 sec
Freq Match Lower Limit: 5.00 Hz
255
Limit: -5.00 Hz
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

SYNC ADJ VOLT SYNC ADJ VOLT SYNC ADJ VOLT


Volt Match Kp: Volt Match Ramp
800 Volt Match Upper
Volt Match Ki: Rate: 60.00 sec
Volt Match Lower Limit: 15.00 %
255 Limit: -15.0 %
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

ADJ SYSTEM SETUP SYS SETUP APP SYS SETUP APP SYS SETUP APP SYS SETUP APP SYS SETUP APP SYS SETUP APP SYS SETUP APP SYS SETUP APP
System Topology: Transition type: Load Demand Typ: Sys Phase Rot: Fail to Sync
1)Application Hard Closed Fixed Sequence L1-L2-L3
Fail To Fail to Sync Open Transition System Frequncy:
Transfer Pair Extended Parall Test With Load: Disconnect Lockout Enable: Retransfer 65.0 Hz
2)kW Ratings Priority Control Enable: Disabled
Enable: Disabled Disabled Disabled Enable: Disabled
Method: Manual
(1) (2) ▼ ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▲

SYS SETUP RATING SYS SETUP RATING SYS SETUP RATING


Gen 01: 1000 kW Gen 05: 0kW Gen 09: 0 kW
Gen 02: 1000 kW Gen 06: 0kW Gen 10: 0 kW
Gen 03: 1000 kW Gen 07: 0kW Gen 11: 0 kW
Gen 04: 970 kW Gen 08: 0kW Gen 12: 0 kW
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

Adjust 5
STANDBY

▼ Returns to the first screen in the series

MENU RESET

MAIN MENU MAIN MENU ENTER PASSWORD


1)Control 4)Faults
2)Adjust Password: XXX
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼ View → – +

ADJUST ADJUST ADJUST ADJUST ADJUST


1)ACMeter Adjust 4)Communication 7)PTC 10)System 13)Ld Demand
2)ACMeter Setup 5)Config Output 8)Sync Check 11)Scheduler 14)Ld Add Shed
3)Breakers 6)Load Control 9)Sync Adjust 12)LCD Display 15)Gen Bus Overload
▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) (6) ▼ (7) (8) (9) ▼ (10) (11) (12) ▼ (13) (14) (15) ▼

ADJ SCHEDULER SCHD SET CLOCK


1)Set Clock
2)Daylite Savng MM/DD/YYYY
12 /31 /2038
3)Programs HH:MM:SS
4)Exceptions 23 :59 : 59
(1) (2) (3) (4) ADJUST

SCHD DAYLITE SAV SCHD DAYLITE SAV SCHD DAYLITE SAV


Daylight Saving Start Month: 12 End Month: 10
Enable: Disabled Start Week: First End Week: Last
Time Adjustment: Start Day: Thur End Day: Sun
60 Minutes Start Hour: 23 End Hour: 02
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

SCHDULE PROGRAMS SCHDULE PROGRAMS SCHDULE PROGRAMS SCHDULE PROGRAMS


System Scheduler Prog Select: 12 Start DAY HH:MM
Enable: Disabled Enable: Disabled Thur 23 : 59 Repeat Interval:
RunCmd: Extd Par Prog Run Mode: Duration HH:MM Second Week
ActiveSch: None Extend Parall 23 : 59 Of Month
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▲

SCHDULE EXCEPTN SCHDULE EXCEPTN SCHDULE EXCEPTN


Exceptn Select: Month DD HH:MM
12 12 31 23 : 59 Repeat Interval:
Exceptn Enable: Dur Days HH:MM Every Year
Disabled 44 23 :59
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

LCD DISPLAY LCD DSPLY SCREEN


1)Screen Contrast
2)CRC Brightness
Display Symbols:
3)Lamp Test No
(1) (2) (3) ADJUST

CRC INFO
BOOTLOAD: 0xC57ED6AD
FIRMWARE: 0xAD3D6B6D
SCREENS: 0x28C68F28
FONTS: 0xD84B56D3

LCD DISPLAY LAMP


Lamp Test:
All 6 LEDs
Should be
ON

Adjust 6
STANDBY

▼ Returns to the first screen in the series

MENU RESET

MAIN MENU MAIN MENU ENTER PASSWORD


1)Control 4)Faults
2)Adjust Password: XXX
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼ View → – +

ADJUST ADJUST ADJUST ADJUST ADJUST


1)ACMeter Adjust 4)Communication 7)PTC 10)System 13)Ld Demand
2)ACMeter Setup 5)Config Output 8)Sync Check 11)Scheduler 14)Ld Add Shed
3)Breakers 6)Load Control 9)Sync Adjust 12)LCD Display 15)Gen Bus Overload
▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) (6) ▼ (7) (8) (9) ▼ (10) (11) (12) ▼ (13) (14) (15) ▼

LD DEMAND LD DEMAND LD DEMAND LD DEMAND LD DEMAND Online


Load Demand Min Cap: 32767 kW Init Delay: 60 min GenA: Gen1 Gen1: 460 hrs
Enable: Disable Shutdown: 100 % ShutdwnDly: 60 min GenB: Gen2 Gen2: 480 hrs
Load Demand Typ: Restart: 100 % RestartDly:25.0 s GenC: Gen4 Gen3: 630 hrs
Fixed Sequence Hrs Diff: 500 hrs GenFailTime: 900 s GenD: Gen3 Gen4: 1003 hrs
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▲

LD ADD SHED ADJ LD ADD SHED ADJ LD ADD SHED ADJ LD ADD SHED ADJ LD ADD SHED ADJ LD ADD SHED ADJ LD ADD SHED ADJ LD ADD SHED ADJ LD ADD SHED ADJ
Genset Bus Load Load Add Shed Type Type LVL ADJ Add Shed LVL ADJ Add Shed
Open Transition Add Delay: 60 sec
Ld Add Shed Retransfer Load Load Shed Delay: Required Online Load 1: Breaker Load 4: Breaker Load 1: 1 0 Load 4: 4 3
Enable: Disabled Shed: Disabled
Utility Bus Load 10 sec Capacity: Load 2: ATS Load 5: ATS Load 2: 2 5 Load 5: 5 2
Add Delay: 60 sec 32000 kW Load 3: 3 4 Load 6: 6 1
Load 3: None Load 6: Breaker
ADJUST ▼ ADJUST ▼ ▲ ADJUST 1` ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▲

GEN BUS OVERLD GEN BUS OVERLD


Method: kW Only UnderFreq OverLd
Threshld: 10.0 Hz
%kW OL Thrs: 140 % UnderFreq OverLd
kW OL Delay: 120 s Delay: 20 s
ADJUST ▼ ADJUST ▲

Adjust 7
STANDBY

▼ Returns to the first screen in the series

MENU RESET

MAIN MENU MAIN MENU


1)Control 4)Faults
2)Adjust
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼

MONITOR MONITOR MONITOR MONITOR MONITOR MONITOR


1)AC Meter 4)Breakers 7)Load Control 10)Switch Inputs 13)System Status 16)Gen Bus Overld
2)Analog In 5)Communication 8)Priority 11)Sync Check 14)Ld Demand 17)Scheduler
3)Analog Out 6)PTC 9)Relay Outputs 12)Synchronizer 15)Ld Add Shed
▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) (6) ▼ (7) (8) (9) ▼ (10) (11) (12) ▼ (13) (14) (15) ▼ (16) (17) ▼

MON AC METER MON AC METER GEN MON AC METER GEN


1)Genset 1)Current 4)Phase
2)Utility 2)Energy 5)Power
3)System 3)Frequency 6)Voltage
▼)More Options ▼)More Options
(1) (2) (3) (1) (2) (3) ▼ (4) (5) (6) ▼

ACMETR GEN CURR


L1: 65000 Amps
L2: 65000 Amps
L3: 65000 Amps
Avg: 65000 Amps

ACMETR GEN ENER ACMETR GEN ENER ACMETR GEN ENER ACMETR GEN ENER
Total kWh+: Total kVARh+: Total Net kWh: Total Net kVAh:
47 kWh 308 kVARh 47 kWh 311 kVAh
Total kWh-: Total kVARh-: Total Net kVARh: Reset Gen Energy
0 kWh 0 kVARh 308 kVARh Meters: Nothing
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

ACMETR GEN FREQ


Gen Frequency:
65.000 Hz

ACMETR GEN PHASE ACMETR GEN PHASE ACMETR GEN PHASE


Phase Rotation: L2L3 Phase Diff:
L1-L2-L3 360.00 deg Sync Phase Diff:
L1L2 Phase Diff: L3L1 Phase Diff: -180.00 deg
360.00 deg 360.00 deg
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲

ACMETR GEN POWER ACMETR GEN POWER ACMETR GEN POWER ACMETR GEN POWER ACMETR GEN POWER
L1 kW: -32000 L1 kVAR: -32000 L1 kVA: 65000 L1 PF: -1.00 Total kW : -32000
L2 kW: -32000 L2 kVAR: -32000 L2 kVA: 65000 L2 PF: -1.00 Tot kVAR : -32000
L3 kW: -32000 L3 kVAR: -32000 L3 kVA: 65000 L3 PF: -1.00 Total kVA: 65000
Tot kW: -32000 Tot kVAR: -32000 Total kVA: 65000 Total PF: -1.00 Total PF : -1.00
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

ACMETR GEN VOLT ACMETR GEN VOLT


L1N: 16V L1L2: 15V
L2N: 2V L2L3: 11V
L3N: 10V L3L1: 23V
LN Avg: 9V LL Avg: 16V
ADJUST ▼ ADJUST ▼ ▲

Continued on next sheet Monitor 1


STANDBY

▼ Returns to the first screen in the series

MENU RESET

MAIN MENU MAIN MENU


1)Control 4)Faults
2)Adjust
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼

MONITOR MONITOR MONITOR MONITOR MONITOR MONITOR


1)AC Meter 4)Breakers 7)Load Control 10)Switch Inputs 13)System Status 16)Gen Bus Overld
2)Analog In 5)Communication 8)Priority 11)Sync Check 14)Ld Demand 17)Scheduler
3)Analog Out 6)PTC 9)Relay Outputs 12)Synchronizer 15)Ld Add Shed
▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) (6) ▼ (7) (8) (9) ▼ (10) (11) (12) ▼ (13) (14) (15) ▼ (16) (17) ▼

MON AC METER MON AC METER UTL MON AC METER UTL


1)Genset 1)Current 4)Phase
2)Energy 5)Power
2)Utility 6)Voltage
3)System 3)Frequency
▼)More Options ▼)More Options
(1) (2) (3) (1) (2) (3) ▼ (4) (5) (6) ▼

ACMETR UTL CURR


L1: 65000 Amps
L2: 65000 Amps
L3: 65000 Amps
Avg: 65000 Amps

ACMETR UTL ENER ACMETR UTL ENER ACMETR UTL ENER ACMETR UTL ENER
Total kWh+: Total kVARh+: Total Net kWh: Total Net kVAh:
47 kWh 308 kVARh 47 kWh 311 kVAh
Total kWh-: Total kVARh-: Total Net kVARh: Reset Gen Energy
0 kWh 0 kVARh 308 kVARh Meters: Reset
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

ACMETR UTL FREQ


Gen Frequency:
65.000 Hz

ACMETR UTL PHASE ACMETR UTL PHASE ACMETR UTL PHASE


Phase Rotation: L2L3 Phase Diff:
L1-L2-L3 360.00 deg Sync Phase Diff:
L1L2 Phase Diff: L3L1 Phase Diff: -180.00 deg
360.00 deg 360.00 deg
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲

ACMETR UTL POWER ACMETR UTL POWER ACMETR UTL POWER ACMETR UTL POWER ACMETR UTL POWER
L1 kW: 0 L1 kVAR: 0 L1 kVA: 0 L1 PF: -1.00 Total kW : 135
L2 kW: 67 L2 kVAR: -38 L2 kVA: 77 L2 PF: -0.87 Tot kVAR : -78
L3 kW: 68 L3 kVAR: -40 L3 kVA: 79 L3 PF: -0.86 Total kVA: 156
Tot kW: 135 Tot kVAR: -78 Total kVA: 156 Total PF: -0.87 Total PF : -0.87
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

ACMETR UTL VOLT ACMETR UTL VOLT


L1N: 281 V L1L2: 481 V
L2N: 275 V L2L3: 480 V
L3N: 279 V L3L1: 485 V
LN Avg: 278 V LL Avg: 482 V
ADJUST ▼ ADJUST ▼ ▲
ACMETER SYSTEM
Total kW: 135
Total kVA: 155
Total PF: -0.87
Tot kVAR: -78 Monitor 2
STANDBY

▼ Returns to the first screen in the series

MENU RESET

MAIN MENU MAIN MENU


1)Control 4)Faults
2)Adjust
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼

MONITOR MONITOR MONITOR MONITOR MONITOR MONITOR


1)AC Meter 4)Breakers 7)Load Control 10)Switch Inputs 13)System Status 16)Gen Bus Overld
2)Analog In 5)Communication 8)Priority 11)Sync Check 14)Ld Demand 17)Scheduler
3)Analog Out 6)PTC 9)Relay Outputs 12)Synchronizer 15)Ld Add Shed
▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) (6) ▼ (7) (8) (9) ▼ (10) (11) (12) ▼ (13) (14) (15) ▼ (16) (17) ▼

ANALOG IN ANALOG IN ANALOG IN


kW Load SetPt: PF SetPoint: kVAR Load SetPt:
125.00 % -1.00 125.00 %
Battery Voltage: kVAR Load Share kW Load Share
24.00 Vdc Level: 5.000 Vdc Level: -5.000 Vdc
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲

ANALOG OUT ANALOG OUT


kW Master Load Master Voltage
Cntl: -5.00 Vdc Bias: -5.00 Vdc
Master Freq kVAR Master Load
Bias: -5.00 Vdc Cntl: -5.00 Vdc
ADJUST ▼ ADJUST ▼ ▲

BREAKER BREAKER BREAKER BREAKER


Gen CB Position Gen1 CB Pos: Gen3 CB Pos: Util CB Position
Status: Open Breaker Open Breaker Open Status: Open
Gen CB Inhibit: Gen2 CB Pos: Gen4 CB Pos: Util CB Inhibit:
No Inhibit Breaker Open Breaker Open No Inhibit
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

COMM MODBUS COMM MODBUS COMM MODBUS


Bus Msg Count: No Response CRC Error Count:
650 Count: 65000 65000
Slave Msg Count: Exception Count: Clear Counters:
500 65000 Clear Counters
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▲

MON PTC PTC GEN SENSORS PTC GEN SENSORS PTC GEN SENSORS PTC GEN SENSORS
1)Gen Sensors Gen Availabilty: OverVolt Sensor Loss Phase Sensr Online Cap Sensr
2)PTC Status Not Available Stat: Unknown Stat: Unknown Stat: Unknown
3)Timers UnderVolt Sensor Freq Sensor Phase Rot Sensor Gen Bus Status:
4)Util Sensors Stat: Dropped-Out Stat: Unknown Stat: Unknown Live
(1) (2) (3) (4) ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

PTC STATUS PTC STATUS PTC STATUS PTC STATUS PTC STATUS
PTC State: Gen Availability: Active Transiton ReTransfer Inhib
Not Available Active Transiton
Util Connected Type: Timer: 6500.0 s Sw: No Inhibit
PTC Oper Mode: Utl Availability: Transfer Inhibit Override Sw:
Not Available None
Normal Sw: No Inhibit No Override
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

PTC TIMERS PTC TIMERS PTC TIMERS PTC TIMERS PTC TIMERS PTC TIMERS
Start Timer Stop Timer Transfer Timer ReTtransfer Timer Prgmd Trans Timr Max Parall Timer
Stat: Not Timing Stat: Not Timing Stat: Not Timing Stat: Not Timing Stat: Not Timing Stat: Not Timing
Start Timer: Stop Timer: Transfer Timer: ReTransfer Programmed Trans Max Parallel
6500.0 sec 6500.0 sec 6500.0 sec Timer: 6500.0 sec Timer: 5.0 sec Timer: 20.0 sec
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

PTC UTL SENSORS PTC UTL SENSORS PTC UTL SENSORS PTC UTL SENSORS
Utl Availabilty: OverVolt Sensor Loss Phase Sensr Utl Source Fail
Available Stat: Unknown Stat: Unknown Sw: Inactive
UnderVolt Sensor Freq Sensor Phase Rot Sensor Utl Bus Status:
Stat: Picked-Up Stat: Unknown Stat: Unknown Live
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ Monitor 3
STANDBY

MENU RESET

MAIN MENU MAIN MENU


1)Control 4)Faults
2)Adjust
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼

MONITOR MONITOR MONITOR MONITOR MONITOR MONITOR


1)AC Meter 4)Breakers 7)Load Control 10)Switch Inputs 13)System Status 16)Gen Bus Overld
2)Analog In 5)Communication 8)Priority 11)Sync Check 14)Ld Demand 17)Scheduler
3)Analog Out 6)PTC 9)Relay Outputs 12)Synchronizer 15)Ld Add Shed
▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) (6) ▼ (7) (8) (9) ▼ (10) (11) (12) ▼ (13) (14) (15) ▼ (16) (17) ▼

LOAD CONTROL
kVAR Load Ref:
-32000 kVAR
kW Load Ref:
-32000 kW

PRIORITY
Master Inhibit:
No Inhibit

RELAY OUTPUTS RELAY OUTPUTS RELAY OUTPUTS


Gen CB Close Rly Utl CB Close Rly
Status: Inactive Status: Inactive Start Gensets
Gen CB Open Rly Utl CB Open Rly Relay Status:
Status: Inactive ON
Status: Inactive
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲

SWITCH INPUTS SWITCH INPUTS SWITCH INPUTS SWITCH INPUTS SWITCH INPUTS SWITCH INPUTS SWITCH INPUTS SWITCH INPUTS
Gen1 CB Pos Sw: Gen3 CB Pos Sw: Gen CB Inhibit Util Source Fail Extend Parallel Transfer Inhibit Override Sw: Fault Reset Sw:
Breaker Closed Breaker Closed Sw: No Inhibit Sw: Inactive Start Sw: Start Sw: No Inhibit No Override Not Reset
Gen2 CB Pos Sw: Gen4 CB Pos Sw: Util CB Inhibit Test Start Sw: Auto/Manual Sw: Retransfer Inhib Sync Enable Sw: RS232 DCD Sw:
Breaker Closed Breaker Closed Sw: No Inhibit Start Manual Sw: No Inhibit Inactive Inactive
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

SYNC CHECK SYNC CHECK SYNC CHECK SYNC CHECK SYNC CHECK SYNC CHECK
Sync Status: Util Avail Stat: Util Bus Stat: Util Phase Rot: Phase Match Err:
Synchronizer Off Available Unavailable L1-L2-L3 -180.00 deg Sync Check Close
Master Inhibit: Gen Avail Stat: Gen Bus Stat: Gen Phase Rot: Time in Window: Allow:
No Inhibit Not Available Dead Not Allowed
L1-L2-L3 650.00 sec
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

SYNCHRONIZER SYNCHRONIZER SYNCHRONIZER SYNCHRONIZER


Sync Status: Freq Match Err: Volt Match Err: Master Volt Bias
-32.000 Hz -100.0 % Cmd: 100.000 %PWM
Synchronizer Off Phase Match Err: Master Freq Bias Sync Enable Sw:
-180.00 deg Cmd: 100.000 %PWM Inactive
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS SYSTEM STATUS
System State: Gen Avail Stat: Auto/Manual Sw: Extend Parallel Total Number Of
Standby Not Available Manual Start Sw: Start Gensets: 4 Total Online
PTC State: Util Avail Stat: Test Start Sw: Sync Status: Total Sys Cap: Cap: 3970 kW
Util Connected Available Start Synchronizer Off 3970 kW
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

Monitor 4
STANDBY

▼ Returns to the first screen in the series

MENU RESET

MAIN MENU MAIN MENU


1)Control 4)Faults
2)Adjust
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼

MONITOR MONITOR MONITOR MONITOR MONITOR MONITOR


1)AC Meter 4)Breakers 7)Load Control 10)Switch Inputs 13)System Status 16)Gen Bus Overld
2)Analog In 5)Communication 8)Priority 11)Sync Check 14)Ld Demand 17)Scheduler
3)Analog Out 6)PTC 9)Relay Outputs 12)Synchronizer 15)Ld Add Shed
▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) (6) ▼ (7) (8) (9) ▼ (10) (11) (12) ▼ (13) (14) (15) ▼ (16) (17) ▼

LOAD DEMAND LOAD DEMAND LOAD DEMAND LOAD DEMAND LOAD DEMAND LOAD DEMAND LOAD DEMAND HRS
Gen Total kW: Nxt Gen Shutdown Gen1Avail: NoExst Gen1Cmd: Run GenA: Gen1 Gen1: 360.000
LD State: Off GenB: Gen2
Nxt ShutDn: None -32767kW Thrshld: -32767kW Gen2Avail: Offlin Gen2Cmd: Run Gen2: 946.000
Nxt Restrt: Gen4 Total LD Online Nxt Gen Restart Gen3Avail: Waitng Gen3Cmd: LD Stop GenC: Gen3 Gen3: 119.000
Cap: -32767kW Thrshld: -32767kW Gen4Avail: Online Gen4Cmd: LD Stop GenD: Gen4 Gen4: 311.000
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

LOAD ADD SHED LOAD ADD SHED LOAD ADD SHED LOAD ADD SHED LOAD ADD SHED LOAD ADD SHED
Add Level Status Shed Level Stat Load Status ATS Load Status ATS Load Status Breaker Load Status Breaker
1: Add 4: Off 0: Off 3: Off 1: Not Avail 4: Source 1 Conn Pos Trip Sta Pos Trip Sta
1: Not Avai Not Avai 4: Not Avai Not Avai
2: Add 5: Off 1: Shed 4: Off 2: Not Avail 5: Source 2 Conn 2: Not Avai Not Avai 5: Not Avai Not Avai
3: Add 6: Off 2: Shed 5: Off 3: No Source Con 6: Paralleled 3: Not Appl Not Appl 6: Not Appl Not Appl
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲ ADJUST ▼ ▲

GEN BUS OVERLD GEN BUS OVERLD GEN BUS OVERLD


kW Stat: NoOverLd UnderFreq OverLd Genset Freq:
kW Thres: 0kW Status: NoOverLd 60.089 Hz
Gen Tot: 0kW UnderFreq OverLd System Freq:
SpareCap: 767kW Thres: 10.0Hz 60.0 Hz
ADJUST ▼ ADJUST ▼ ▲ ADJUST ▼ ▲

SCHEDULER
Run Command:
Extd Parallel
Active Schedule:
None

Monitor 5
STANDBY

▼ Returns to the first screen in the series

MENU RESET

MAIN MENU MAIN MENU


1)Control 4)Faults
2)Adjust
3)Monitor 5)About
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) ▼

FAULTS FAULTS
1)Current Faults 4)Actve Flt Tbl
2)Active Evt Table 5)Flt Hist Tbl
3)Evt Occur Tbl 6)Flt Occur Tbl
▼)More Options ▼)More Options
(1) (2) (3) ▼ (4) (5) (6) ▼

CURRENT FAULT
Fault #: 2396
Util Main
Fail To Close

ACTIVE EVENT TBL


Event #: 2965
Genset Bus
Available
▼ ▲

EVENT OCCUR TBL


Count: 18
Event #: 1916
Sync Check OK
CLR ▼ ▲

ACTIVE FAULT TBL


Fault #: 1328
Gen Main Tripped

RESET ▼ ▲

FAULT HISTORY
COT: 4294967285 s
Fault #: 1457
Fail To Sync
CLR ▼ ▲

FAULT OCCUR TBL


Count: 8
Fault #: 1455
Util Main Pos
Contact Fail
CLR ▼ ▲

Faults