Water Cooled Centrifugal Chiller

Job Information
Technical Data Sheet
Job Name VALUETRONICS
Date 9/1/2020 10:15:51 AM
Submitted By Nguyen Song Hao
Software Version HTS1.0.7
Unit Tag
Country of Origin China

Unit Overview
Unit Name Capacity Cooling COP NPLV.IP IPLV(GB) Power Supply Starter Type
kW kW / kW kW / kW kW / kW
HTS 2016 5.578 6.632 - 380 V / 50 Hz SS

Unit
Model HTS087MAU49F/E3012-BE-2/C2612-BL-2
Approval AHRI
Compressor Quantity Capacity Control Refrigerant Refrigerant Quantity
1 Inlet Guide Vanes R134a 505 kg

Evaporator
EWT LWT Fluid Type Actual Fluid Flow Min Fluid Flow Fouling Factor

12.00 °C 7.00 °C Water 96.14 l/s 25.40 l/s 0.0180 °C·m²/kW

Condenser
EWT LWT Fluid Type Actual Fluid Flow Min Fluid Flow Fouling Factor

32.00 °C 37.00 °C Water 114.2 l/s 34.69 l/s 0.0440 °C·m²/kW

Unit Performance
Performance Points Rated with Constant Condenser EWT
Cooling
Evaporator Fluid Condenser Fluid
Point # % of Capacity Input COP RLA
Full kW kW kW/kW A Flow EWT LWT PD Flow EWT LWT PD
Load l/s °C °C kPa l/s °C °C kPa
1 100.0 2016 361.4 5.578 630 96.14 12.00 7.00 117 114.2 32.00 37.00 84.6

2 90.0 1814 313.9 5.779 546 96.14 11.50 7.00 117 114.2 32.00 36.47 84.7

3 80.0 1613 277.2 5.820 482 96.14 11.00 7.00 117 114.2 32.00 35.97 84.8

4 70.0 1411 247.3 5.706 432 96.14 10.50 7.00 117 114.2 32.00 35.49 84.9

5 60.0 1210 221.2 5.469 390 96.14 10.00 7.00 117 114.2 32.00 35.01 85.1

6 50.0 1008 196.5 5.130 350 96.14 9.50 7.00 117 114.2 32.00 34.53 85.2

7 41.2 831.6 174.4 4.768 315 96.14 9.06 7.00 118 114.2 32.00 34.12 85.3

8 0.0 - - - - - - - - - - - -

9 0.0 - - - - - - - - - - - -

10 0.0 - - - - - - - - - - - -

Chiller unable to run at requested load point.

Physical
Evaporator
Length Diameter Passes Tube Material Tube wall Thickness Design Pressure (Waterside)

3.66 m 76.2 cm 2 Cu 0.635 mm 1 MPa

HTS1.0.7 Page 1 of 2
Water Cooled Centrifugal Chiller

Condenser
Length Diameter Passes Tube Material Tube wall Thickness Design Pressure (Waterside)

3.66 m 66.0 cm 2 Cu 0.635 mm 1 MPa

Electrical
Power RLA LRA OutputAmps Power Connection Power Factor MOCP

380 V / 50 Hz 630 A 3942 A - Single Point 0.89 1971 A

Drive
Type Model Location Harmonic Distortion Enclosure Type

SS ASP762 Unit Mounted Standard IP22

Sound
Sound Pressure dB(A)

63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Overall 75% Load 50% Load 25% Load

69.0 67.0 70.0 73.0 78.0 81.0 81.0 76.0 86.5 84.0 84.0 85.0

Sound Pressure (dB) measured in accordance with ANSI/AHRI Standard 575-2008 ('A' weighted)

Options
Basic Unit

Oil Cooler Refrigerant Cooled

AHRI Certification
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating
Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard
551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Notes
1. Above RLA and MOCP values are per Chiller.
2. For variable water flow rate application change should be less than 30% per minute.
3. Surge Point Amps% :50%.

HTS1.0.7 Page 2 of 2

You might also like