COOLING TOWER NOISE LEVEL


PROJECT : PLANTROOM SIZING, PHNOM PENH DATE : 27.09.2020
YOUR REF : - OUR REF : -

L
5 1.5m

4 3 2 1
10.0m 2.0m 10.0m 2.0m

1.5m 1.5m

The measuring point 5 is 45 degrees diagonally above the top edge of fan stack, opposite of motor driver side

Tower Model MEASURING POINT


Longitudinal Direction (L) Width Direction (W) 45°(1.5m )
ECS 1313F3-2B 1 2 3 4 5
82.0 72.5 82.0 72.5 83.5
NOTE:
1) For Extra Low Noise Requirement, there are several simple solutions :
a) Face fans away from potential problem area.
b) Avoid amphitheater type locations.
c) Provide natural sound barriers such as trees, shrubs or a small hill between unit & neighbours.
d) Consult manufacturer for possible alternative selection of a quieter unit.
e) In extreme cases, install a wall-type sound barrier or have manufacturer provide a factory-
build attenuation package.
2) Tolerance on sound values ±2 dB(A)