Likewise, water chillers have a critical range of flow rates in
which they will safely operate. If the designer chooses to vary the flow through the chiller to save on pumping energy at any con- dition less than full load, the control system must be properly designed to operate safely. Because of these design limitations and safety concerns, chillers are usually designed for constant water flow. However, there is an energy-saving opportunity if the chiller pump is variable flow. Cooling equipment is normally designed for a 10°F tempera- ture difference or delta T (∆T). For example, chillers and cooling coils might be designed to operate with a supply water tempera- ture of 45°F and a return temperature of 55°F, while the cooling tower (tower range) and water-cooled condenser (condenser rise) operate between 85°F and 95°F.
PLANT MAINTENANCE AND OPERATION
Good maintenance and the proper operation of plant equip-
ment cannot be overemphasized. Proper maintenance helps en- sure efficient operation of equipment and systems (thereby reducing energy usage) and helps prolong equipment life. The following maintenance procedures can help in the optimization of chiller plant equipment and determine the cause of any abnor- malities and correct them as needed.
Compressors and Motors
Follow manufacturer’s guidelines for compressor and motor maintenance and observe compressor operation. Frequent stop- ping and starting or continuous running may indicate inefficient operation. It is also important to listen to the compressor. A high noise level may be a sign of a loose drive coupling or excessive vibration. Next, inspect the compressor for oil leaks and use a leak detector to check for refrigerant leaks. Establish normal op- erating pressures and temperatures for the system. Routinely record operating temperatures and oil pressures in a log. Be sure 94 HVAC Fundamentals
to compare readings with manufacturer’s specifications to ensure
normal operation.
Pumps and Motors
Follow manufacturer ’s guidelines for pump and motor maintenance. Observe and listen to the pump operation. Keep the pump and motor properly lubricated; lubricate motor bearings and all moving parts according to manufacturer’s recommenda- tions. Keep pump and motor properly aligned. Water balance pumps for proper flow quantity; change impellers as needed.
Fans and Motors
Follow manufacturer’s guidelines for fan and motor mainte- nance. Lubricate motor and fan bearings and all moving parts according to manufacturer’s recommendations. Keep fan and motor drives properly aligned. Inspect condition of belt(s) and check belt tension. Observe and listen for any unusual noise or vibration.
Condensers and Cooling Towers
Clean tubes on water-cooled condensers and keep condenser coil faces clean on air-cooled condensers. Perform chemical treat- ment to determine if desolved solids concentrations are being maintained at acceptable levels on evaporative condensers and cooling towers. Monitor effectiveness of water treatment pro- gram. Keep the tower clean to minimize drops in air and water pressure. Check overflow pipe clearance for proper operating water level. Clean intake strainer. Determine if there is air re-cir- culation from tower outlet back to tower inlet. Inspect towers for proper nozzle performance.
Plant Retrofit The biggest energy users in chilled-water plants are the motors driving the chiller compressors, pumps, and fans. There- fore, significant energy savings can be achieved by:
(BS en 14511-1 - 2013) - Air Conditioners, Liquid Chilling Packages and Heat Pumps With Electrically Driven Compressors For Space Heating and Cooling. Terms, Definitions and C