Professional Documents
Culture Documents
Esd Cyrus Molinyawe
Esd Cyrus Molinyawe
PROBLEM 1
An accounting office 50 feet by 70 feet is to be illuminated. The ceiling is 10ft high and the
lighting fixtures are to be surface mounted. The walls and ceiling are painted white.
1. Specify the type and number of fixtures you will use.
SINGLE FIXTURE
50ft= 15.24m
70ft= 21.336m
10ft= 3.048m
hc =.08m ; where: hc= height of ceiling to floor
(Assume 1m height of working plane to floor)
So, hcw = 3.048m- 1m= 2.048m; where hcw = height of ceiling to working plane
l xb
ROOM INDEX (R.I.) = where l= length, b= width
hcw(l x b)
15.24 x 21.336
=
2.048(15.24+21.336)
= 4.34
Lumen Required= 325.16m² x 500 = 162,580 lm
For R.I = 4.34 and reflectance code = 752, Utilization Factor = 0.83
For classroom/office maintenance factor= 0.8 (standard)
ExA
N=
F xn xU . F. x M .F .
162,580
=
4100 x 1 x 0.83 x 0.8
N= 59.7 ≈ 60
No. of fixtures to use = 60 fixtures
Where:
N= number of luminaire required for a given area
E= Average luminance over the horizontal working plane
n= Number of lamps in each luminaire
F= lighting design lumens per lamp, i.e. initial bare lamp luminous flux
UF= utilization factor for the horizontal working plane
M.F.= Maintenance Factor
SHR= 0.76
= 60 x 38 = 2280 watts
PROBLEM 2
A first class 10 door apartment has a floor area of 80 square meter for the ground floor
and 70 sq. meter for the second floor. The following load should be provided by an outlet.
1 -8 kVA Electric Range
2-2.5 KVa Water Heater
2-6A Air Condition Unit
2- CO’s at 1500VA
Provide the complete power distribution for the said apartment
Load Current
IL = (Load in VA)/ Supply Voltage
=𝟖𝟎𝟎 𝐕𝐀/𝟐𝟑𝟎= 3.48 𝐀
I = 21160VA/230V = 92 A
Breaker
Use: 1-90 Ampere Trip and 1-100 Ampere Frame Size
Conduit Size
Use: 35mm mm Ø PVC
C. Branch Circuit wire, Conduit, and Breaker for each load
Circuit 1. Lighting Outlet
Design Calculation:
Design Assumption:
System Voltage, 230V, 1-phase, 2W
Demand Factor is assuming to be 100% since the load is one unit only.
Ambient Temperature: less than 40°Ç
kW = kVA since this is a pure resistive load.
Check for PEC Rule (Maximum full load current on the branch circuit shall not exceed 80%)
Hence
15 x 0.8 = 12A > 5.21A
Check for PEC Rule (Maximum full load current on the branch circuit shall not exceed 80%)
Hence
15 x 0.8 = 12A > 10.4349A
Check for PEC Rule (Maximum full load current on the branch circuit shall not exceed 80%)
Hence
15 x 0.8 = 12A > 6.9562A
Check for PEC Rule (Maximum full load current on the branch circuit shall not exceed 80%)
Hence
40 x 0.8 =32A <34.78A
Check for PEC Rule (Maximum full load current on the branch circuit shall not exceed 80%)
Hence
30 x 0.8 = 24A > 21.74A
Circuit 7: 6A ACU
Design Calculation:
Design Assumption:
System Voltage, 230V, 1-phase, 2W
Demand Factor is assuming to be 100% since the load is one unit only.
Ambient Temperature: less than 40°Ç
kW = kVA since this is a pure resistive load.
Check for PEC Rule (Maximum full load current on the branch circuit shall not exceed 80%)
Hence
20 x 0.8 = 16A > 12A
PROBLEM 3
Given the rating of the following motors:
Motor 1: 20 HP, squirrel cage, 460V, 3phase
Motor 2: 30 HP Wound Rotor, 460V, 3phase
Motor 3: 50 HP, squirrel cage, 460V, 3phase
1. Design the Branch Circuit Conductors and Protection and the conduits.
2. Setting of the Overload Relay
3. Size of Main Feeder and Main Protection
Instructions:
Refer to PEC 2017 for the motor tables including section.
Design of the Branch Circuit Conductors and Protection and the conduits
Motor 1.
Branch Circuit Short Circuit and Ground Fault Protection
FLC of 20 HP (19kVA), squirrel cage, 460V, 3phase (See Table 4.30.14.4)
FLC= 27 A
Multiplier of FLC (See PEC 2017 Article 4.30 Table 4.30.4.2 for OCPD.
Inverse time Breaker = 250%
Standard Ampere rating for fuse and inverse time breaker in PEC Article 2.40 table 2.40.1.6(A)
FLC*250%= 67.5 A
Next standard size above 67A is 80A CB
(Use. 80 AT Inverse Time Circuit Breaker)
Motor 2.
Branch Circuit Short Circuit and Ground Fault Protection
FLC of 30 HP (28kVA) Wound Rotor, 460V, 3phase (See Table 4.30.14.4)
FLC= 40 A
Multiplier of FLC (See PEC 2017 Article 4.30 Table 4.30.4.2 for OCPD.
Inverse time Breaker = 150%
Standard Ampere rating for fuse and inverse time breaker in PEC Article 2.40 table 2.40.1.6(A)
FLC*150%= 60 A
Next standard size above 60A is 70A CB
(Use. 70 AT Inverse Time Circuit Breaker)
Motor 3.
Branch Circuit Short Circuit and Ground Fault Protection
Full Load Current of 50 HP (47kVA), Squirrel Cage, 460V, 3phase (See Table 4.30.14.4)
FLC= 65 A
Multiplier of FLC (See PEC 2017 Article 4.30 Table 4.30.4.2 for OCPD.
Inverse time Breaker = 250%
Standard Ampere rating for fuse and inverse time breaker in PEC Article 2.40 table 2.40.1.6(A)
FLC*250%= 162.5 A
Next standard size above 162A is 175A CB
(Use. 175 AT Inverse Time Circuit Breaker)