Reclosing Single phase and three phase auto Not Mentioned Conformation
reclosing Required
Thermal Rating of Auxiliary 10A at 220V DC 15A-Contineous
Contacts 7.5A-at 264V DC.
Noise level at base and up to 140 dB Maximum Confirmed
50M from breaker
Type tests for performance As per IEC Not Mentioned Conformation
verification Required
Phase discrepancy Control If the position of all three breaker Not Mentioned Conformation
poles control after switching is not Required
the same then an opening
command shall be initiated to all
poles after a definite set time
delay. Signal shall be given to
control room for alarm ‘Phase
Discrepancy Trip’
Accessories:
On/Off Indicator Mechanical as well as electrical Not Mentioned Conformation
Required
Emergency tripping Mechanical Not Mentioned Conformation
mechanism Required
Termination suitability with ACSR/ ALUMINIMUM TUBE Not Mentioned Conformation
connectors Required
Anti pumping relay Shall be provided Not Mentioned Conformation
operation , counter, local Required
control panel , local/remote
selector switch
Continuous operating voltage 303kV rms Confirmed without Temp. Conformation with
at 500C temp is required
Maximum switching surge
residual voltage(1KA)
Minimum switching surge 780 kV peak
residual voltage(1KA) Confirmed
730kV peak
Long duration of discharge 3 Confirmed
class
Maximum discharge 8 kJ/kV Confirmed
capability
Partial discharge at 1.05 COV Maximum 50 pc Not Mentioned Conformation
Required
One minute power frequency 630 kV Confirmed
dry & wet withstand test
voltage for arrestor housing
Full wave impulse voltage +/- 1425 kV peak Confirmed
(1.2/50 micro sec.) for
arrestor housing
Switching impulse withstand +/-1050kV Peak Confirmed
voltage
(250/2500microsecond) dry
and wet for arrestor house
Maximum radio interference 1000 micro volt Confirmed with less than
voltage for frequency between 1000 microvolt and at
0.5-2 MHz at 156 kV 266kv rms.
Insulation level-Rated +/- 1425 KV Confirmed
lightning impulse peak
withstand voltage (1.2/50
micro second impulse)
between line terminal and
ground
Partial discharge Maximum 10 pc As per IS 11322(1985) Supporting
Documents
required to be
Submit.
One minute power frequency 5 kV Not Mentioned Conformation
withstand voltage between Required
secondary terminal and earth
Number of terminals All terminals of are wired up to Not Mentioned Conformation
marshalling box plus 20% Required
terminals exclusively for purchaser
use
Insulation level-Rated one 630 KV Confirmed
minute power frequency wet
and dry withstand voltage
Temperature Rise - Oil top of As per IEC 44-1. 40 deg C Not Mentioned Conformation
housing (measured by Required
thermometer
Temperature Rise - Winding 50 deg C Not Mentioned Conformation
(measured by increase in Required
resistance method
Voltage ratio 400/ 3 KV : 0.11 /3 KV Confirmed with Two Two winding is not
: 0.11/ 3 KV : 0.11/ 3 KV Winding acceptable
Star – Star – Star – Star
Rated burden to be not less As per Enclosed list Confirmed for Two Two winding is not
than Winding acceptable