Professional Documents
Culture Documents
TABLE OF CONTENTS
Chapter 1 – Introduction
Chapter 4 - Terminology
I. General
II. Parts of Safety Relief Devices
III. Dimensional Characteristics - Safety Relief Valves
IV. Operational Characteristics - Safety Relief Devices
V. System Characteristics
Chapter 6 - Appendix
I. Required Sizing Data
II.Safety Relief Valve Specification Sheet
The primary purpose of a safety Relief valve is to protect life and property by venting process fluid
from an over pressurized vessel. Proper sizing, selection, manufacture, assembly, testing,
installation, and maintenance of a safety Relief Valve are all critical for optimal protection of the
vessel or system.
I. Introduction
This section will provide the sizing formulae, guidelines and calculation of Safety Relief Valve for
various different cases of LPG Mobile tankers and static vessels.
Required external surface Area of pressure vessel/mobile tanker is calculated using NFPA-58, 2004.
Total surface area Aw of vessel is computed by following formula.
Required Minimum Relieving Capacity of safety relief Valve of pressure vessel/mobile tanker is
calculated using NFPA-58, 2004.
Required Minimum Discharge capacity of safety Relieve valve in SCFM standard cubic feet per
minute is calculated using following formula.
Where Aw is in Ft2
I. As per Annexure E.2.2, it is advised that spring loaded pressure relief valves should be used
for above ground and road tanker vessels.
II. The minimum rate of discharge for spring loaded pressure Relief valves should be based on
outside surface area of the vessel/container on which the valves are installed.
III. Figure A.3.3.72.5.4 for NFPA-58 2004, Annexure - A recommended internal spring
type pressure relief valve typical picture.
III. API-520 Guide Lines and recommended Practice
Required Minimum Relieving Area and Diameter of safety relief Valve of pressure
vessel/mobile tanker is calculated using API520.
Minimum required discharge/relieving Area in square inches for set pressure ≥ 15 psig is
calculated using below formula.
A= V*(MTZ) 0.5/6.32*C*K*P1*Kb*Kc
V : Required Relieving capacity in SCFM
M : Molecular weight
T : Absolute relieving temperature in degree Rankine, ◦R= ◦F+460
Z : Compressibility Factor
C : Gas constant based on specific heat ratio Cp/Cv
K : Coefficient of discharge or nozzle discharge coefficient, ratio of actual
discharge to theoretical discharge= (0.975*0.9)
P1 : Relieving pressure = Set pressure*1.1 + 14.7 psia
Kb : Back pressure correction factor
Kc : combination factor if rapture disc is used, if no rapture disc then Kc=1.0
Note: the volumetric flow equation uses SCFM, since capacity is equivalent Air, so use M=29,
T=60+460, Z=1.0
IV. Sizing calculation Examples
Step One: External surface area calculation for the vessel in (ft2) for non hemispherical dished end
= (5.680+0.3*1.980)*1.980*3.1416
= 39.0 M2
= 39.0*10.7639
= 420.0 ft2
V = 53.632*(Aw) 0.82
= 53.632*(420) 0.82
= 7591.22 SCFM
A = V*(MTZ) 0.5/6.32*C*K*P1*Kb*Kc
= 7591.22*(29*520*1.0)^0.5/6.32*356*0.975*0.9*262.2*1.0*1.0
= 1.8 (inch2)
D = (4*A/3.1416)0.5
= 1.51 inch
2. Study Case 2 For 12 MT LPG capacity vessel(Mobile Tanker)
Vessel specification
Design Pressure: 14.5 Kg/cm2 + 3G effect = 15.35 kg/cm2
LPG capacity: 12 MT
Water capacity: 25530 liters
Dish end: Hemispherical head
Shell internal Dai: 2320 mm
Shell outside Dai: 2340 mm
Overall length of vessel: 6832 mm
Thickness of shell: 10 mm with wear and tear Allowance.
Step One: External surface area calculation for the vessel in (ft2)
= 6.832*2.340*3.1416
= 50.224 M2
= 50.224*10.7639
= 540.6 ft2
V = 53.632*(Aw) 0.82
= 53.632*(540.6) 0.82
= 9340.9 SCFM
A = V*(MTZ) 0.5/6.32*C*K*P1*Kb*Kc
= 9340.9*(29*520*1.0)^0.5/6.32*356*0.975*0.9*262.2*1.0*1.0
= 2.21 (inch2)
D = (4*A/3.1416)0.5
= 1.68 inch
3. Study Case 3 For 18 MT LPG capacity vessel(Mobile Tanker)
Vessel specification
Design Pressure: 14.5 Kg/cm2 + 3G effect = 15.75 kg/cm2
LPG capacity: 18 MT
Water capacity: 38300 liters
Dish end: Hemispherical head
Shell internal Dai: 2350 mm
Shell outside Dai: 2374 mm
Overall length of vessel: 9631 mm
Thickness of shell: 12 mm with wear and tear Allowance.
Step One: External surface area calculation for the vessel in (ft2)
= 9.631*2.374*3.1416
= 71.82 M2
= 71.82*10.7639
= 773.16 ft2
V = 53.632*(Aw) 0.82
= 53.632*(773.16) 0.82
= 12525.86 SCFM
A = V*(MTZ) 0.5/6.32*C*K*P1*Kb*Kc
= 12525.86*(29*520*1.0)^0.5/6.32*356*0.975*0.9*262.2*1.0*1.0
= 2.96 (inch2)
D = (4*A/3.1416)0.5
= 1.94 inch
4. Study Case 4 For 21 MT LPG capacity vessel(Mobile Tanker)
Vessel specification
Design Pressure: 14.5 Kg/cm2 + 3G effect = 16.0 kg/cm2
LPG capacity: 21 MT
Water capacity: 44700 liters
Dish end: Hemispherical head
Shell internal Dai: 2340 mm
Shell outside Dai: 2364 mm
Overall length of vessel: 11180 mm
Thickness of shell: 12 mm with wear and tear Allowance.
Step One: External surface area calculation for the vessel in (ft2)
= 11.180*2.364*3.1416
= 83.03 M2
= 83.03*10.7639
= 893.7 ft2
V = 53.632*(Aw) 0.82
= 53.632*(893.7) 0.82
= 14106.4 SCFM
A = V*(MTZ) 0.5/6.32*C*K*P1*Kb*Kc
= 14106.4*(29*520*1.0)^0.5/6.32*356*0.975*0.9*262.2*1.0*1.0
= 3.34 (inch2)
D = (4*A/3.1416)0.5
= 2.06 inch
5. Study Case 5 For 50 MT LPG capacity (static vessel)
Vessel specification
Design Pressure: 14.5 Kg/cm2 + Static head = 14.81 kg/cm2
LPG capacity: 50 MT
Water capacity: 106000 liters
Dish end: Hemispherical head
Shell internal Dai: 3100 mm
Shell outside Dai: 3132 mm
Overall length of vessel: 11977 mm
Thickness of shell: 16 mm with wear and tear Allowance.
Step One: External surface area calculation for the vessel in (ft2)
= 11.977*3.132*3.1416
= 117.84 M2
= 117.84*10.7639
= 1268.5 ft2
V = 53.632*(Aw) 0.82
= 53.632*(1268.5) 0.82
= 18798.45 SCFM
A = V*(MTZ) 0.5/6.32*C*K*P1*Kb*Kc
= 18798.45*(29*520*1.0) ^0.5/6.32*356*0.975*0.9*262.2*1.0*1.0
= 4.45 (inch2)
D = (4*A/3.1416)0.5
= 2.38 inch
6. Study Case 6 For 30 MT LPG capacity (static vessel)
Vessel specification
Design Pressure: 14.5 Kg/cm2 + Static head = 15.35 kg/cm2
LPG capacity: 30 MT
Water capacity: 64000 liters
Dish end: Hemispherical head
Shell internal Dai: 2800 mm
Shell outside Dai: 2832 mm
Overall length of vessel: 11400 mm
Thickness of shell: 16 mm with wear and tear Allowance.
Step One: External surface area calculation for the vessel in (ft2)
= 11.400*2.832*3.1416
= 101.4 M2
= 101.4*10.7639
= 1091.7 ft2
V = 53.632*(Aw) 0.82
= 53.632*(1268.5) 0.82
= 16621.9 SCFM
A = V*(MTZ) 0.5/6.32*C*K*P1*Kb*Kc
= 16621.9*(29*520*1.0) ^0.5/6.32*356*0.975*0.9*262.2*1.0*1.0
= 3.93 (inch2)
D = (4*A/3.1416)0.5
= 2.23 inch
7. Study Case 7 For 20 MT LPG capacity (static vessel)
Vessel specification
Design Pressure: 14.5 Kg/cm2 + Static head = 15.35 kg/cm2
LPG capacity: 20 MT
Water capacity: 42000 liters
Dish end: Non Hemispherical head
Shell internal Dai: 2340 mm
Shell outside Dai: 2364 mm
Overall length of vessel: 10907 mm
Thickness of shell: 12 mm with wear and tear Allowance.
Step One: External surface area calculation for the vessel in (ft2)
= 10.907*2.364*3.1416
= 81 M2
= 81*10.7639
= 872 ft2
V = 53.632*(Aw) 0.82
= 53.632*(872) 0.82
= 13824 SCFM
A = V*(MTZ) 0.5/6.32*C*K*P1*Kb*Kc
= 13824*(29*520*1.0) ^0.5/6.32*356*0.975*0.9*262.2*1.0*1.0
= 3.27 (inch2)
D = (4*A/3.1416)0.5
= 2.04 inch
8. Study Case 8 For 10 MT LPG capacity (static vessel)
Vessel specification
Design Pressure: 14.5 Kg/cm2 + Static head = 14.8 kg/cm2
LPG capacity: 10 MT
Water capacity: 21000 liters
Dish end: Non Hemispherical head
Shell internal Dai: 2150 mm
Shell outside Dai: 2182 mm
Overall length of vessel: 5932 mm
Thickness of shell: 16 mm with wear and tear Allowance.
Step One: External surface area calculation for the vessel in (ft2) for non hemispherical dished end
= (5.932+0.3*2.182)*2.182*3.1416
= 45.15 M2
= 69.9*10.7639
= 486 ft2
V = 53.632*(Aw) 0.82
= 53.632*(486) 0.82
= 8559.84 SCFM
A = V*(MTZ) 0.5/6.32*C*K*P1*Kb*Kc
= 8559.84*(29*520*1.0) ^0.5/6.32*356*0.975*0.9*262.2*1.0*1.0
= 2.02 (inch2)
D = (4*A/3.1416)0.5
= 1.60 inch
V. Discharge Capacity table-I for LPG mobile tankers and static Vessel
Required Minimum rate of discharge in SCFM of air at 120% of the maximum permitted start to
discharge pressure for pressure relief valve to be used on ASME vessels (from NFPA -58)
This section will provide highlights on global codes, standards and recommended practices
referenced in sizing the safety relief valve in this report.
II. National Fire Protection Agency, NFPA 58 - Liquefied Petroleum Gas Code (2014 Edition)
The US-based organization established over 100 years ago to provide fire prevention guidance via
recommended practices, codes, and standards. Since external fire or heat input is often a source of
overpressure for vessels and equipment. There are several of these NFPA codes that may be used to
size and select pressure relieving devices. This code (NFPA-58) can apply to tanks and piping that
are used to provide propane, or similar hydrocarbon having a vapor pressure not exceeding that of
propane. The scope also applies to road transportation, many marine terminals and onshore
pipeline storage tanks that handle this type of liquid petroleum. Where storage vessels are built for
use at 15 psig (1.03 barg) and above, then these vessels are to be designed per ASME Section VIII or
other similar codes. These vessels are to have pressure relief valves designed to open on vapor
service. Direct acting spring loaded valves are required up to a vessel volume of 40,000 gallons
(151 m3) of water capacity. Above this volume, either direct acting or pilot operated pressure relief
devices are allowed. There are also requirements for the use of thermal relief valves for piping
systems. For non-refrigerated tanks, isolation valves are not allowed unless two or more pressure
relief valves are installed on a manifold and only one pressure relief valve can be isolated. The
remaining active pressure relief valve must have adequate capacity to meet the requirements.
There are to be no isolation valves on the outlet piping. The minimum testing interval for non-
refrigerated tanks is ten years.
III. API Standard/Recommended Practice 520 - Sizing, Selection and Installation of Pressure
Relieving Devices: The scope of API 520 deals with pressure vessels with a MAWP of 15 psig (1.03
barg) and above. The relieving devices designed for unfired vessels, such as those listed as ASME
Section VIII and other similar codes. One of the sizing techniques listed in API 520 is utilized
Chapters 2 for SRV sizing calculation.
SMPV (U) Rules, 2016: The role of SMPV (U) rule 2016 is central and main guiding source in
selection and sizing of Safety relief Valve of static and Mobile pressure vessels. Sub Rule 2 of Rule
18 of SMPV (U) Rules 2016, specifies the use of two or more than two pressure relieving devices in
accordance with the provision of the design code referred to in Rule 13.The relief valve shall be
spring loaded and shall be set to discharge and reach full flow conditions as required by the design
code referred to in rule 13.The safety relief valve on any vessel shall be set to start to discharge at a
pressure not exceeding 110 % of the design pressure or maximum working pressure of the vessel
and shall have a total relieving capacity sufficient to prevent the maximum pressure in the vessel of
more than 120% of the design or maximum working pressure.
Chapter 4 - Terminology
This chapter contains common and standardized terminology related to Safety relief Valve.
I. General
Bench Testing
Testing of a safety relief device on a test stand using an external pressure source with or without an
auxiliary lift device to determine some or all of its operating characteristics of the valve.
Safety Valve
A pressure relief valve characterized by rapid opening or closing and normally used to relieve
compressible fluids.
Relief Valve
A pressure relief valve characterized by gradual opening or closing generally proportional to the
increase or decrease in pressure. It is normally used for incompressible fluids.
Safety Relief Valve
A pressure relief valve characterized by rapid opening or closing or by Gradual opening or closing,
generally proportional to the increase or decrease in pressure. It can be used for compressible or
incompressible fluids.
Adjusting Ring: a ring assembled to the nozzle and/or guide of a direct spring valve used to control
the opening characteristics and/or the reseat pressure
Adjustment Screw: a screw used to adjust the set pressure or the reseat pressure of a reclosing
safety relief device.
Body: a pressure retaining or containing member of a safety relief device that supports the parts of
the valve assembly and has provisions(s) for connecting to the primary and/or secondary pressure
source(s).
Seat: the pressure sealing surfaces of the fixed and moving pressure containing components.
Spindle: a part whose axial orientation is parallel to the travel of the disc. It may be used in one or
more of the following functions:
a. assists in alignment,
b. guide disc travel, and
c. transfer of internal or external forces to the seats.
Spring: the element in a pressure relief valve that provides the force to keep the disc on the nozzle.
Stem: see spindle.
Actual Discharge Area: the measured minimum net area which determines the flow through a
valve determines the flow through a valve.
Bore Area: the minimum cross-sectional flow area of a nozzle.
Bore Diameter: the minimum diameter of a nozzle.
Developed Lift: the actual travel of the disc from closed position to the position reached when the
valve is at flow rating pressure.
Discharge Area: see actual discharge area.
Effective Discharge Area: a nominal or computed area of flow through a pressure relief valve used
with an effective discharge coefficient to calculate minimum required relieving capacity.
IV. Operational Characteristics of Safety Relief Devices
Blowdown: the difference between actual set pressure of a safety relief valve and actual reseating
pressure, expressed as a percentage of set pressure or in pressure units.
Blowdown Pressure: the value of decreasing inlet static pressure at which no further discharge is
detected at the outlet of a safety relief valve after the valve has been subjected to a pressure equal
to or above the set pressure.
Closing Pressure: the value of decreasing inlet static pressure at which the valve disc re-
establishes contact with the seat or at which lift becomes zero.
Coefficient of Discharge: the ratio of the measured relieving capacity to the theoretical relieving
capacity.
Effective Coefficient of Discharge: a nominal value used with the effective discharge area to
calculate the minimum required relieving capacity of a pressure relief valve.
Leak Test Pressure: the specified inlet static pressure at which a quantitative seat leakage test is
performed in accordance with a standard procedure.
Marked Set Pressure: the value or values of pressure marked on a pressure relief device.
Measured Relieving Capacity: the relieving capacity of a pressure relief device measured at the
flow rating pressure, expressed in gravimetric or volumetric units.
Overpressure: a pressure increase over the set pressure of a pressure relief valve, usually
expressed as a percentage of set pressure.
Popping Pressure: the value on increasing inlet static pressure at which the disc moves in the
opening direction at a faster rate as compared with corresponding movement at higher or lower
pressures.
Primary Pressure: the pressure at the inlet in a pressure relief device.
Relieving Conditions: the inlet pressure and temperature on a pressure relief device during an
overpressure condition. The relieving pressure is equal to the valve set pressure plus the
overpressure. (The temperature of the flowing fluid at relieving conditions may be higher or lower
than the operating temperature.)
Resealing Pressure: the value of decreasing inlet static pressure at which no further leakage is
detected after closing. The method of detection may be a specified water seal on the outlet or other
means appropriate for this application.
Reseating Pressure: see closing pressure.
Seal-Off Pressure: see resealing pressure.
Secondary Pressure: the pressure existing in the passage between the actual discharge area and
the valve outlet in a safety, safety relief, or relief valve
Set Pressure: the value of increasing inlet static pressure at which a pressure relief device displays
one of the operational characteristics as defined under opening pressure, popping pressure or
start-to-leak pressure. (The applicable operating characteristic for a specific device design is
specified by the device manufacturer.)
Simmer: the audible or visible escape of fluid between the seat and disc at an inlet static pressure
below the popping pressure and at no measurable capacity. It applies to safety or safety relief
valves on compressible fluid service.
Start-to-Discharge Pressure: see opening pressure.
Start-to-Leak Pressure: the value of increasing inlet static pressure at which the first bubble
occurs when a pressure relief valve is tested by means of air under a specified water seal on the
outlet.
Theoretical Relieving Capacity: the computed capacity expressed in gravimetric or volumetric
units of a theoretically perfect nozzle having a minimum cross-sectional flow area equal to the
actual discharge area of a pressure relief valve or net flow area of a non-reclosing pressure relief
device.
V. System Characteristics
Accumulation: is the pressure increase over the maximum allowable working pressure (MAWP) of
the process vessel or storage tank allowed during discharge through the pressure relief device. It is
expressed in pressure units or as a percentage of MAWP or design pressure. Maximum allowable
accumulations are typically established by applicable codes for operating and fire overpressure
contingencies.
Design Pressure: is the pressure of the vessel along with the design temperature that is used to
determine the minimum permissible thickness or physical characteristic of each vessel component
as determined by the vessel design rules. The design pressure is selected by the user to provide a
suitable margin above the most severe pressure expected during normal operation at a coincident
temperature. It is the pressure specified on the purchase order. This pressure may be used in place
of the maximum allowable working pressure (MAWP) in all cases where the MAWP has not been
established. The design pressure is equal to or less than the MAWP.
Maximum Allowable Working Pressure: is the maximum gauge pressure permissible at the top
of a completed process vessel or storage tank in its normal operating position at the designated
coincident temperature specified for that pressure. The pressure is the least of the values for the
internal or external pressure as determined by the vessel design rules for each element of the
vessel using actual nominal thickness, exclusive of additional metal thickness allowed for corrosion
and loadings other than pressure. The maximum allowable working pressure (MAWP) is the basis
for the pressure setting of the pressure relief devices that protect the vessel. The MAWP is normally
greater than the design pressure but must be equal to the design pressure when the design rules
are used only to calculate the minimum thickness for each element and calculations are not made to
determine the value of the MAWP.
Maximum Operating Pressure: is the maximum pressure expected during normal system
operation.
Chapter 5 - Engineering Support Information (English Units)
I. Introduction
This section will provide highlights on various engineering support information
The following formula equates the ratio of specific heats (k) to the coefficient, C, used in
sizing methods for gases and vapors. Figure 2 and Table -3 provide the calculated
solution to this formula. If k is not known, use C = 315.
Where:
k =Cp/Cv (Ratio of specific heats)
K C K C K C K C K C
1.01 317 1.21 338 1.41 357 1.61 373 1.81 388
1.02 318 1.22 339 1.42 358 1.62 374 1.82 389
1.03 319 1.23 340 1.43 359 1.63 375 1.83 389
1.04 320 1.24 341 1.44 360 1.64 376 1.84 390
1.05 321 1.25 342 1.45 360 1.65 376 1.85 391
1.06 322 1.26 343 1.46 361 1.66 377 1.86 391
1.07 323 1.27 344 1.47 362 1.67 378 1.87 392
1.08 325 1.28 345 1.48 363 1.68 379 1.88 393
1.09 326 1.29 346 1.49 364 1.69 379 1.89 393
1.10 327 1.3 347 1.5 365 1.7 380 1.9 394
1.11 328 1.31 348 1.51 365 1.71 381 1.91 395
1.12 329 1.32 349 1.52 366 1.72 382 1.92 395
1.13 330 1.33 350 1.53 367 1.73 382 1.93 396
1.14 331 1.34 351 1.54 368 1.74 383 1.94 397
1.15 332 1.35 352 1.55 369 1.75 384 1.95 397
1.16 333 1.36 353 1.56 369 1.76 384 1.96 398
1.17 334 1.37 353 1.57 370 1.77 385 1.97 398
1.18 335 1.38 354 1.58 371 1.78 386 1.98 399
1.19 336 1.39 355 1.59 372 1.79 386 1.99 400
1.20 337 1.4 356 1.6 373 1.8 387 2.0
IV. Equivalents and Conversion Factors.
Table –VI (Lpg and Air Properties @ 14.7 psi and 60 Degree )
Properties unit Lpg Air
Molecular Weight M 51 29
Specific heat Ratio Cp/Cv 1.1 1.4
Gas / Vapor constant C 328 356
Compressibility factor Z 0.9 1.0
Latent heat of Vaporization L btu/lb 183.2 -
Chapter 6 – Appendix
II Molecular weight 51
III Viscosity -
2 OPERATING CONDITIONS
3 RELIEVING CONDITION
I Required relieving capacity, Gas/vapor lb/h or gas/vapor (scfm) 13420
Description about Rotary Gauge/Roto Gauge: The Rotogauges are designed to provide an
accurate determination of LP-Gas or anhydrous ammonia container contents. They mount in a
standard 1” NPT coupling on large mobile or stationary containers. To operate the Rotogauges, the
vent valve is opened and the dip tube rotated slowly from the container vapor space to the liquid
space. The difference in appearance of the discharge indicates when the liquid level is reached. Dial
readings then indicate the percentage of product in the container.
End mount or side Mount End mount installation, must know whether tank is hemispherical or
ellipsoidal.
Example: Hemispherical End Mount or side mount tank with 72” ID
“D”= 72” need gauge with “A” length of 71.5”
½ of “D”=36”-0.5” (clearance) =”C”
36”+35.5”=71.5”
Ellipsoidal tank end mount only
Subtract 11” from half of the tank ID
“D”=72”
36”-11”=25”= “B”
Side Mount
Subtract 5” from half of the tank ID
“D”=72”
36”-5”=31”
IV.Roto Gauge Components
S.No Description
1 Body Extension Tube
2 Dial – LPG service
3 O-Ring
4 Packing Sleeve
5 Indicator
6 Cap-Seat Assembly
7 Friction Ring
8 Needle Bearing
9 Lock Nut
10 Lock Nut
11 Seal Nut
12 Set Screw
13 Key
14 Insert
15 Washer
V.Operating principle:
Rotary gauges can be used on stationary or mobile tanks to visually indicate the amount of LP-
Gas in the container. They are also used in filling the tank to the proper liquid level. The Gauge is
operated by opening the small bleed orifice when the tube is in the vapor space of the tank. Moving
the pointer on the dial causes the end of the tube to move until it contacts liquid in the container. At
that point, discharge from the bleed orifice turns from vapor to liquid and the rotary gauge dial
gives the volume percentage of liquid in the tank.
VII.Requirements which apply to liquid-level gauging devices as per SMPV (U) Rules:
The SMPV (U), Rule 2016 details about the liquid level gauging devices under sub Rule 4 of Rule 18,
the abstract of which is as follows.
(i) A vessel used for liquefiable gas or dissolved gas shall be equipped with a liquid level
gauging device to afford ready determination of the amount of liquid in the vessel at
anytime.
(ii) All liquid level indicators shall be suitable for operation at the design pressure of the
vessel.
(iii) Every vessel shall, in addition, be equipped with a fixed maximum level indicating
device depending upon the liquefiable gas or dissolved gas filled in the vessel.
(iv) Gauging devices that require bleeding of the contents of the vessel such as rotary tube,
fixed tube and slip tube shall be designed in such a manner that the same cannot be
completely withdrawn in normal gauging operation.
II. Fixed Tube Gauge Details
The fixed liquid level gauge, also known as the bleeder valve is the one and only gauging device that
accurately depicts the level of LPG/propane in the tank when it is being filled. The bleeder valve is
built so that during the filling process, when the LPG/propane is going into the tank reaches 85
percent, liquid will come out of the opened valve. This allows the delivery driver to know that the
tank has reached its maximum filling capacity. The valve is connected to what is called a dip tube
that goes into the container. The dip tube is fixed and set at length equal to 85 percent liquid level
tank capacity. Simply put, the tip of the dip tube is at the level equal to the container being 85
percent full. The dip tube itself should always be located in the vapor space and never submerged in
liquid LPG/propane.
Basically, the fixed liquid level gauge tells the individual delivering the propane that the tank is at
the maximum safe capacity. When installed by the tank manufacturer, the dip tube is pre-set to
indicate when the tank is legally full during the filling process. Consider it this way: When drinking
a soda through a straw, you will not be able to get soda through the straw if the tip of the straw is
above the level of the soda. When the tip of the straw is in the soda, you are able to drink the soda. A
dip tube works similarly to the straw principle.
The Primary purpose of Fixed Maximum level gauge is Overfill protection. A tank overfill can have
disastrous consequences. A spill can cause explosion and fire that can spread to the surrounding
area. Since the tank contains huge amounts of stored energy, a fire can have far reaching
consequence. Fire caused by overfilling has rendered legal damages amounting to huge money.
From this and many other perspectives, preventing tanker overfilling is extremely important.
V.Requirements which apply to liquid-level gauging devices as per SMPV (U) Rules:
The SMPV (U), Rule 2016 details about the liquid level gauging devices under sub Rule 4 of Rule 18,
the abstract of which is as follows.
(i) A vessel used for liquefiable gas or dissolved gas shall be equipped with a liquid level
gauging device to afford ready determination of the amount of liquid in the vessel at
anytime.
(ii) All liquid level indicators shall be suitable for operation at the design pressure of the
vessel.
(iii) Every vessel shall, in addition, be equipped with a fixed maximum level indicating
device depending upon the liquefiable gas or dissolved gas filled in the vessel.
(iv) Gauging devices that require bleeding of the contents of the vessel such as rotary tube,
fixed tube and slip tube shall be designed in such a manner that the same cannot be
completely withdrawn in normal gauging operation.