PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (MCA)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

Pickup Current: - 0.95 X IN

51 Curve: - IEC EI

50:5A Time Multiplier Setting - 0.62

Pickup Current: - 17 X IN
50
MCA-1 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR TX AT14)
Pickup Current: - 2 X IN

51N Curve: - IEC SI

50:5A Time Multiplier Setting - 0.12

Pickup Current: - 4 X IN
50N
Time Delay: - 0.10

Pickup Current: - 0.95 X IN

51 Curve: - IEC EI

50:5A Time Multiplier Setting - 0.62

Pickup Current: - 17 X IN
50
MCA-2 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR TX AT15)
Pickup Current: - 2 X IN

51N Curve: - IEC SI

50:5A Time Multiplier Setting - 0.12

Pickup Current: - 4 X IN
50N
Time Delay: - 0.10

Pickup Current: - 1.7 X IN

51 Curve: - IEC EI

50:5A Time Multiplier Setting - 0.12

Pickup Current: - 16 X IN
50
MCA-3 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR TX AT30)
Pickup Current: - 2 X IN

51N Curve: - IEC SI

50:5A Time Multiplier Setting - 0.07

Pickup Current: - 4 X IN
50N
Time Delay: - 0.10

Pickup Current: - 1.7 X IN

51 Curve: - IEC EI

50:5A Time Multiplier Setting - 0.12

Pickup Current: - 16 X IN
50
MCA-4 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR TX AT29)
Pickup Current: - 2 X IN

51N Curve: - IEC SI

50:5A Time Multiplier Setting - 0.07

Pickup Current: - 4 X IN
50N
Time Delay: - 0.10

Pickup Current: - 0.3 X IN

51 Curve: - IEC EI

20:5A Time Multiplier Setting - 0.50

Pickup Current: - 2 X IN
50
MCA-5 Time Delay: - 0.10
(FEEDER FOR PENSTOCK ALSTOM P122
FLOODLIGHTS) Pickup Current: - 0.1 X IN

51N Curve: - IEC SI

20:5A Time Multiplier Setting - 0.06

Pickup Current: - 0.2 X IN


50N
Time Delay: - 0.10

Pickup Current: - 0.95 X IN

51 Curve: - IEC EI

200:5A Time Multiplier Setting - 0.07

Pickup Current: - 7 X IN
50
MCA-7 Time Delay: - 0.10
(FEEDER FOR 1MW HYDRO ALSTOM P122
UNIT) Pickup Current: - 0.5 X IN

51N Curve: - IEC SI

200:5A Time Multiplier Setting - 0.07

Pickup Current: - 1 X IN
50N
Time Delay: - 0.10

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 1 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (MCA)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

Pickup Current: - 0.62 X IN

51 Curve: - IEC EI

50:5A Time Multiplier Setting - 0.12

Pickup Current: - 6 X IN
50
MCA-8 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR TX AT17)
Pickup Current: - 2 X IN

51N Curve: - IEC SI

50:5A Time Multiplier Setting - 0.07

Pickup Current: - 4 X IN
50N
Time Delay: - 0.10

Pickup Current: - 0.38 X IN

51 Curve: - IEC EI

2000:5A Time Multiplier Setting - 1.30

Pickup Current: - 16 X IN
50
MCA-9 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR MCB)
Pickup Current: - 0.05 X IN

51N Curve: - IEC SI

2000:5A Time Multiplier Setting - 0.07

Pickup Current: - 0.1 X IN


50N
Time Delay: - 0.10

Pickup Current: - 1.15 X IN

51 Curve: - IEC EI

2000:5A Time Multiplier Setting - 0.58

Pickup Current: - DISABLE


50
MCA-10 Time Delay: - DISABLE
MICOM P122
(MCA INCOMER)
Pickup Current: - 0.06 X IN

51N Curve: - IEC SI

2000:5A Time Multiplier Setting - 0.14

Pickup Current: - DISABLE


50N
Time Delay: - DISABLE

Pickup Current: - 1.4 X IN

51 Curve: - IEC EI

300:5A Time Multiplier Setting - 0.52

Pickup Current: - 20 X IN
50
MCA-11 Time Delay: - 0.10
(FEEDER FOR ALSTOM P122
POWERHOUSE II ) Pickup Current: - 0.33 X IN

51N Curve: - IEC SI

300:5A Time Multiplier Setting - 0.07

Pickup Current: - 0.70 X IN


50N
Time Delay: - 0.10

Pickup Current: - 0.4 X IN

51 Curve: - IEC EI

2000:5A Time Multiplier Setting - 0.20

Pickup Current: - 2.5 X IN


50
MCA-12 Time Delay: - 0.35
(FEEDER TO E-MCA AND ALSTOM P122
MCAE1/E2) Pickup Current: - 0.05 X IN

51N Curve: - IEC SI

2000:5A Time Multiplier Setting - 0.07

Pickup Current: - 0.2 X IN


50N
Time Delay: - 0.10

Pickup Current: - 1.4 X IN

51 Curve: - IEC EI

300:5A Time Multiplier Setting - 0.52

Pickup Current: - 20 X IN
50
MCA-13 Time Delay: - 0.10
(FEEDER FOR ALSTOM P122
POWERHOUSE II ) Pickup Current: - 0.33 X IN

51N Curve: - IEC SI

300:5A Time Multiplier Setting - 0.07

Pickup Current: - 0.70 X IN


50N
Time Delay: - 0.10

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 2 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (MCA)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

Pickup Current: - 1 X IN

51 Curve: - IEC SI

200:5A Time Multiplier Setting - 0.10

Pickup Current: - 20 X IN
50
MCA-15 Time Delay: - 0.10
ALSTOM P122
(FEEDER TO AT7)
Pickup Current: - 0.05 X IN

51N Curve: - IEC SI

200:5A Time Multiplier Setting - 0.07

Pickup Current: - 1 X IN
50N
Time Delay: - 0.10

Pickup Current: - 0.62 X IN

51 Curve: - IEC EI

50:5A Time Multiplier Setting - 0.12

Pickup Current: - 6 X IN
50
MCA-19 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR TX AT16)
Pickup Current: - 2 X IN

51N Curve: - IEC SI

50:5A Time Multiplier Setting - 0.07

Pickup Current: - 4 X IN
50N
Time Delay: - 0.10

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 3 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (EMCA)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

Pickup Current: - 0.87 X IN (87%)

51 Curve: - IEC EI

600:5A Time Multiplier Setting - 0.22 (2.2)

Pickup Current: - 10 X IN
50
EMCA-E1 Time Delay: - 0.10
FUJI F-MPC30
(POWERHOUSE-1)
Pickup Current: - 0.12 X IN (12%)

51N Curve: - IEC SI

600:5A Time Multiplier Setting - 0.05 (0.5)

Pickup Current: - 0.3 X IN


50N
Time Delay: - 0.10

Pickup Current: - 0.87 X IN (87%)

51 Curve: - IEC EI

600:5A Time Multiplier Setting - 0.22 (2.2)

Pickup Current: - 10 X IN
50
EMCA-E2 Time Delay: - 0.10
FUJI F-MPC30
(POWER HOUSE-1)
Pickup Current: - 0.12 X IN (12%)

51N Curve: - IEC SI

600:5A Time Multiplier Setting - 0.05 (0.5)

Pickup Current: - 0.3 X IN


50N
Time Delay: - 0.10

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 4 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (PMB)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

Pickup Current: - 0.92 X IN

49/51 Curve: - IEC EI

2500:5A Time Multiplier Setting - 0.50

Pickup Current: - DISABLE


50
PMB1 Time Delay: - DISABLE
MICOM P122
(PMB INCOMER)
Pickup Current: - 0.06 X IN

51N Curve: - IEC SI

2500:5A Time Multiplier Setting - 0.07

Pickup Current: - DISABLE


50N
Time Delay: - DISABLE

Pickup Current: - 1 X IN (100%)

49/51 Curve: - IEC EI

2000:5A Time Multiplier Setting - 0.5 (5)

Pickup Current: - 7 X IN
50
PMB2 FUJI ELECTRIC Time Delay: - 0.20
(PONY MOTOR-1) F-MPC30
Pickup Current: - 0.05 X IN (5%)

51N Curve: - IEC SI

2000:5A Time Multiplier Setting - 0.05 (0.5)

Pickup Current: - 0.10 X IN


50N
Time Delay: - 0.20

Pickup Current: - 1 X IN (100%)

49/51 Curve: - IEC EI

2000:5A Time Multiplier Setting - 0.5 (5)

Pickup Current: - 7 X IN
50
PMB3 FUJI ELECTRIC Time Delay: - 0.20
(PONY MOTOR-2) F-MPC30
Pickup Current: - 0.05 X IN (5%)

51N Curve: - IEC SI

2000:5A Time Multiplier Setting - 0.05 (0.5)

Pickup Current: - 0.10 X IN


50N
Time Delay: - 0.20

Pickup Current: - 1 X IN (100%)

51 Curve: - IEC EI

600:5A Time Multiplier Setting - 0.37 (3.7)

Pickup Current: - 8 X IN
50
PMB4 FUJI ELECTRIC Time Delay: - 0.35
(SERVING EMCA1/EMCA2) F-MPC30
Pickup Current: - 0.17 X IN (17%)

51N Curve: - IEC SI

600:5A Time Multiplier Setting - 0.07 (0.7)

Pickup Current: - 0.3 X IN


50N
Time Delay: - 0.10

Pickup Current: - 1 X IN (100%)

51 Curve: - IEC EI

600:5A Time Multiplier Setting - 0.37 (3.7)

Pickup Current: - 8 X IN
50
PMB5 FUJI ELECTRIC Time Delay: - 0.35
(SERVING EMCA1/EMCA2) F-MPC30
Pickup Current: - 0.17 X IN (17%)

51N Curve: - IEC SI

600:5A Time Multiplier Setting - 0.07 (0.7)

Pickup Current: - 0.3 X IN


50N
Time Delay: - 0.10

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 5 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (MCB)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

Pickup Current: - 0.92 X IN

49/51 Curve: - IEC EI

2500:5A Time Multiplier Setting - 0.50

Pickup Current: - DISABLE


50
MCB2A Time Delay: - DISABLE
MICOM P122
(MCB INCOMER)
Pickup Current: - 0.06 X IN

51N Curve: - IEC SI

2500:5A Time Multiplier Setting - 0.07

Pickup Current: - DISABLE


50N
Time Delay: - DISABLE

Pickup Current: - 0.20 X IN

51 Curve: - IEC EI

2000:5A Time Multiplier Setting - 0.57

Pickup Current: - 3.5 X IN


50
MCB-4A Time Delay: - 0.10
(FEEDER TO MICOM P122
POWERHOUSE II) Pickup Current: - 0.05 X IN

51N Curve: - IEC SI

2000:5A Time Multiplier Setting - 0.04

Pickup Current: - 0.07 X IN


50N
Time Delay: - 0.10

Pickup Current: - 0.20 X IN

51 Curve: - IEC EI

2000:5A Time Multiplier Setting - 0.57

Pickup Current: - 3.5 X IN


50
MCB-4B Time Delay: - 0.10
(FEEDER TO MICOM P122
POWERHOUSE II) Pickup Current: - 0.05 X IN

51N Curve: - IEC SI

2000:5A Time Multiplier Setting - 0.04

Pickup Current: - 0.07 X IN


50N
Time Delay: - 0.10

Pickup Current: - 0.1 X IN

51 Curve: - IEC SI

2000:5A Time Multiplier Setting - 0.10

Pickup Current: - 2 X IN
50
MCB-5A Time Delay: - 0.10
MICOM P122
(FEEDER FOR +AT7)
Pickup Current: - 0.05 X IN

51N Curve: - IEC SI

2000:5A Time Multiplier Setting - 0.07

Pickup Current: - 0.1 X IN


50N
Time Delay: - 0.10

Pickup Current: - 0.1 X IN

51 Curve: - IEC VI

2000:5A Time Multiplier Setting - 0.19

Pickup Current: - 1 X IN
50
MCB-5B Time Delay: - 0.20
MICOM P122
(DIESEL GENERATOR)
Pickup Current: - 0.05 X IN

51N Curve: - IEC SI

2000:5A Time Multiplier Setting - 0.04

Pickup Current: - 0.1 X IN


50N
Time Delay: - 0.20

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 6 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (MDB-AC)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

LONG TIME LTPU - FIXED

LTD - -

STPU - 4 X IN
SHORT TIME
STD - -

MDB-AC1 SQIUARE D PAF 2000A (SENSOR) I2T - -


(FOR MDB AC LOADS) 2000 (PLUG-IN)
INSTANTANEOUS I-PU - -

TD - -

GPU - -
GROUND
GTD - -

I2T - -

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 7 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (PCD)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

LONG TIME LTPU - 0.80 X IN

LTD - 2.50

STPU - 1.5 X IN
SHORT TIME
STD - 0.07
MAGRINI GALLILEO
CONTROL B1-35 I2T - OUT
52PCD1 400A (SENSOR)
(JOSLYN OPTI TRIP II RMS)
(INCOMER FOR PCD) 400 (PLUG-IN)
INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.6 X IN
GROUND
GTD - 0.20

I2T - OUT

LONG TIME LTPU - 0.80 X IN

LTD - 2.50

STPU - 1.5 X IN
SHORT TIME
STD - 0.07
MAGRINI GALLILEO
CONTROL B1-35 I2T - OUT
52PCD2 400A (SENSOR)
(JOSLYN OPTI TRIP II RMS)
(INCOMER FOR PCD) 400 (PLUG-IN)
INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.6 X IN
GROUND
GTD - 0.20

I2T - OUT

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 8 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (CCD)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

LONG TIME LTPU - 0.8 X IN

LTD - 0.50

STPU - 4 X IN
SHORT TIME
STD - 0.05

52CCD1 FUJI DH12 400A (SENSOR) I2T - OUT


(INCOMER FOR CCD-B) 400 (PLUG-IN)
INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.6 X IN
GROUND
GTD - 0.50

I2T - OUT

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 9 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (PPCA / PDP)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

LONG TIME LTPU - 0.75 X IN

LTD - 3.00

STPU - 0.9 X IN
SHORT TIME
STD - 0.13
+GDP.A-52A I2T - OUT
ABB E4S SACE PR112 4000A (SENSOR)
4000 (PLUG-IN)
(MAIN INCOMER-1) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.28 X IN
GROUND
GTD - 0.20

I2T - IN

LONG TIME LTPU - 0.75 X IN

LTD - 3.00

STPU - 0.9 X IN
SHORT TIME
STD - 0.13
+GDP.A-52B I2T - OUT
ABB E4S SACE PR112 4000A (SENSOR)
4000 (PLUG-IN)
(MAIN INCOMER-2) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.28 X IN
GROUND
GTD - 0.20

I2T - IN

LONG TIME LTPU - 0.5 X IN

LTD - 3.00

STPU - 0.6 X IN
SHORT TIME
STD - 0.08
+GDP.A-52C I2T - OUT
ABB E4S SACE PR112 4000A (SENSOR)
4000 (PLUG-IN)
(TIE CB) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.2 X IN
GROUND
GTD - 0.15

I2T - IN

LONG TIME LTPU - 0.75 X IN

LTD - CURVE B

STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.A.Q1A I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP UA) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.3 X IN
GROUND
GTD - CURVE A

I2T - OUT

LONG TIME LTPU - 0.75 X IN

LTD - CURVE B

STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.A.Q1B I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP CA) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.3 X IN
GROUND
GTD - CURVE A

I2T - OUT

LONG TIME LTPU - 0.75 X IN

LTD - CURVE B

STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.A.Q2A I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO +DBA) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.3 X IN
GROUND
GTD - CURVE A

I2T - OUT

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 10 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (PPCA / PDP)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

LONG TIME LTPU - 0.75 X IN

LTD - CURVE B

STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.A.Q2B I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP UA) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.3 X IN
GROUND
GTD - CURVE A

I2T - OUT

LONG TIME LTPU - 0.75 X IN

LTD - CURVE B

STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.A.Q3A I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP CA) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.3 X IN
GROUND
GTD - CURVE A

I2T - OUT

LONG TIME LTPU - 0.7 X IN

LTD - CURVE A

STPU - 1 X IN
SHORT TIME
STD - CURVE A

1600A (SENSOR) I2T - OUT


+PDP.UA.52A ABB S7L SACE PR212
1600 (PLUG-IN)
INSTANTANEOUS I-PU - 4 X IN

TD - -

GPU - 0.2 X IN
GROUND
GTD - CURVE A

I2T - OUT

LONG TIME LTPU - 0.7 X IN

LTD - CURVE A

STPU - 1 X IN
SHORT TIME
STD - CURVE A

1600A (SENSOR) I2T - OUT


+PDP.UA.52B ABB S7L SACE PR212
1600 (PLUG-IN)
INSTANTANEOUS I-PU - 4 X IN

TD - -

GPU - 0.2 X IN
GROUND
GTD - CURVE A

I2T - OUT

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 11 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (PPCB / PDP)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

LONG TIME LTPU - 0.75 X IN

LTD - 3.00

STPU - 0.9 X IN
SHORT TIME
STD - 0.13
+GDP.B-52A I2T - OUT
ABB E4S SACE PR112 4000A (SENSOR)
4000 (PLUG-IN)
(MAIN INCOMER-1) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.28 X IN
GROUND
GTD - 0.20

I2T - IN

LONG TIME LTPU - 0.75 X IN

LTD - 3.00

STPU - 0.9 X IN
SHORT TIME
STD - 0.13
+GDP.B-52B I2T - OUT
ABB E4S SACE PR112 4000A (SENSOR)
4000 (PLUG-IN)
(MAIN INCOMER-2) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.28 X IN
GROUND
GTD - 0.20

I2T - IN

LONG TIME LTPU - 0.5 X IN

LTD - 3.00

STPU - 0.6 X IN
SHORT TIME
STD - 0.08
+GDP.B-52C I2T - OUT
ABB E4S SACE PR112 4000A (SENSOR)
4000 (PLUG-IN)
(TIE CB) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.2 X IN
GROUND
GTD - 0.15

I2T - IN

LONG TIME LTPU - 0.75 X IN

LTD - CURVE B

STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.B.Q1A I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP UB) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.3 X IN
GROUND
GTD - CURVE A

I2T - -

LONG TIME LTPU - 0.75 X IN

LTD - CURVE B

STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.B.Q2B I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP UB) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.3 X IN
GROUND
GTD - CURVE A

I2T - -

LONG TIME LTPU - 0.75 X IN

LTD - CURVE B

STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.B.Q1B I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP CB) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.3 X IN
GROUND
GTD - CURVE A

I2T - -

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 12 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (PPCB / PDP)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

LONG TIME LTPU - 0.75 X IN

LTD - CURVE B

STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.B.Q1B I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP CB) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.3 X IN
GROUND
GTD - CURVE A

I2T - -

LONG TIME LTPU - 0.75 X IN

LTD - CURVE B

STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.B.Q3A I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP CB) INSTANTANEOUS I-PU - DISABLE

TD - DISABLE

GPU - 0.3 X IN
GROUND
GTD - CURVE A

I2T - -

LONG TIME LTPU - 0.7 X IN

LTD - CURVE A

STPU - 1 X IN
SHORT TIME
STD - CURVE A

1600A (SENSOR) I2T - OUT


+PDP.UB.52A ABB S7L SACE PR212
1600 (PLUG-IN)
INSTANTANEOUS I-PU - 4 X IN

TD - -

GPU - 0.2 X IN
GROUND
GTD - CURVE A

I2T - OUT

LONG TIME LTPU - 0.7 X IN

LTD - CURVE A

STPU - 1 X IN
SHORT TIME
STD - CURVE A

1600A (SENSOR) I2T - OUT


+PDP.UB.52B ABB S7L SACE PR212
1600 (PLUG-IN)
INSTANTANEOUS I-PU - 4 X IN

TD - -

GPU - 0.2 X IN
GROUND
GTD - CURVE A

I2T - OUT

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 13 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (PCA)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

LONG TIME LTPU - 1 X IN

LTD - 0.50

STPU - 2 X IN
SHORT TIME
STD - 0.10
PCA-1 3200A (SENSOR) I2T - OUT
FUJI DH30
3200A
(INCOMER OF PCA) 3200A / 1.0 (PLUG-IN) INSTANTANEOUS I-PU - DISABLE

TD - -

GPU - 0.2 X IN
GROUND
GTD - 0.30

I2T - OUT

LONG TIME LTPU - 0.80 X IN

LTD - 1.25

STPU - 2 X IN
SHORT TIME
STD - 0.40
PCA-2
3200A (SENSOR) I2T - OUT
FUJI DH30
(OUTGOING FEEDER OF
3200A
PCA) 1600A / 0.50 (PLUG-IN) INSTANTANEOUS I-PU - 2 X IN

TD - -

GPU - 0.1 X IN
GROUND
GTD - 0.20

I2T - OUT

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 14 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (PCB)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

LONG TIME LTPU - 1 X IN

LTD - 0.50

STPU - 2 X IN
SHORT TIME
STD - 0.10
PCB-1 3200A (SENSOR) I2T - OUT
FUJI DH30
3200A
(INCOMER OF PCA) 3200A / 1.0 (PLUG-IN) INSTANTANEOUS I-PU - DISABLE

TD - -

GPU - 0.2 X IN
GROUND
GTD - 0.30

I2T - OUT

LONG TIME LTPU - 0.80 X IN

LTD - 1.25

STPU - 2 X IN
SHORT TIME
STD - 0.40
PCB-2
3200A (SENSOR) I2T - OUT
FUJI DH30
(OUTGOING FEEDER OF
3200A
PCA) 1600A / 0.50 (PLUG-IN) INSTANTANEOUS I-PU - 2 X IN

TD - -

GPU - 0.1 X IN
GROUND
GTD - 0.20

I2T - OUT

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 15 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (ST1 / ST2 / ST3 PRIMARY)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

Pickup Current: - 1.3 X IN

51 Curve: - IEC EI

50:5A Time Multiplier Setting - 0.38

Pickup Current: - 12 X IN
50
ST1 Time Delay: - 0.35
MICOM P633
(230KV PRIMARY)
Pickup Current: - 0.2 X IN

51N Curve: - DT

50:5A Time Multiplier Setting - 0.20

Pickup Current: - DISABLE


50N
Time Delay: - DISABLE

Pickup Current: - 1.3 X IN

51 Curve: - IEC EI

50:5A Time Multiplier Setting - 0.47

Pickup Current: - 12 X IN
50
ST2 Time Delay: - 0.35
MICOM P633
(230KV PRIMARY)
Pickup Current: - 0.2 X IN

51N Curve: - DT

50:5A Time Multiplier Setting - 0.20

Pickup Current: - DISABLE


50N
Time Delay: - DISABLE

Pickup Current: - 1.3 X IN

51 Curve: - IEC EI

50:5A Time Multiplier Setting - 0.38

Pickup Current: - 12 X IN
50
ST3 Time Delay: - 0.35
MICOM P633
(230KV PRIMARY)
Pickup Current: - 0.2 X IN

51N Curve: - DT

50:5A Time Multiplier Setting - 0.20

Pickup Current: - DISABLE


50N
Time Delay: - DISABLE

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 16 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (ST1 / ST2 / ST3 SECONDARY)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

Pickup Current: - 1 X IN

51 Curve: - IEC EI

2500:5A Time Multiplier Setting - 0.61

Pickup Current: - DISABLE


50
ST1 Time Delay: - DISABLE
MICOM P633
(6.5KV SECONDARY)
Pickup Current: - DISABLE

51N Curve: - DISABLE

2500:5A Time Multiplier Setting - DISABLE

Pickup Current: - DISABLE


50N
Time Delay: - DISABLE

Pickup Current: - 1 X IN

51 Curve: - IEC EI

2500:5A Time Multiplier Setting - 0.74

Pickup Current: - DISABLE


50
ST2 Time Delay: - DISABLE
MICOM P633
(6.5KV SECONDARY)
Pickup Current: - DISABLE

51N Curve: - DISABLE

2500:5A Time Multiplier Setting - DISABLE

Pickup Current: - DISABLE


50N
Time Delay: - DISABLE

Pickup Current: - 1 X IN

51 Curve: - IEC EI

2500:5A Time Multiplier Setting - 0.61

Pickup Current: - DISABLE


50
ST3 Time Delay: - DISABLE
MICOM P633
(6.5KV SECONDARY)
Pickup Current: - DISABLE

51N Curve: - DISABLE

2500:5A Time Multiplier Setting - DISABLE

Pickup Current: - DISABLE


50N
Time Delay: - DISABLE

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 17 / 18
PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (ST1 / ST2 / ST3 TERTIARY)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

Pickup Current: - 1.1 X IN

51 Curve: - IEC EI

1600:5A Time Multiplier Setting - 0.16

Pickup Current: - 6 X IN (DISABLE)


50
ST1 Time Delay: - 0.1 (DISABLE)
MICOM P633
(6.5KV PRIMARY)
Pickup Current: - DISABLE

51N Curve: - DISABLE

1600:5A Time Multiplier Setting - DISABLE

Pickup Current: - DISABLE


50N
Time Delay: - DISABLE

Pickup Current: - 1.1 X IN

51 Curve: - IEC EI

1600:5A Time Multiplier Setting - 0.16

Pickup Current: - 6 X IN (DISABLE)


50
ST3 Time Delay: - 0.1 (DISABLE)
MICOM P633
(6.5KV PRIMARY)
Pickup Current: - DISABLE

51N Curve: - DISABLE

1600:5A Time Multiplier Setting - DISABLE

Pickup Current: - DISABLE


50N
Time Delay: - DISABLE

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 18 / 18