Professional Documents
Culture Documents
CBK2 RelaySettingsSummary Rev2 PDF
CBK2 RelaySettingsSummary Rev2 PDF
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
51 Curve: - IEC EI
Pickup Current: - 17 X IN
50
MCA-1 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR TX AT14)
Pickup Current: - 2 X IN
Pickup Current: - 4 X IN
50N
Time Delay: - 0.10
51 Curve: - IEC EI
Pickup Current: - 17 X IN
50
MCA-2 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR TX AT15)
Pickup Current: - 2 X IN
Pickup Current: - 4 X IN
50N
Time Delay: - 0.10
51 Curve: - IEC EI
Pickup Current: - 16 X IN
50
MCA-3 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR TX AT30)
Pickup Current: - 2 X IN
Pickup Current: - 4 X IN
50N
Time Delay: - 0.10
51 Curve: - IEC EI
Pickup Current: - 16 X IN
50
MCA-4 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR TX AT29)
Pickup Current: - 2 X IN
Pickup Current: - 4 X IN
50N
Time Delay: - 0.10
51 Curve: - IEC EI
Pickup Current: - 2 X IN
50
MCA-5 Time Delay: - 0.10
(FEEDER FOR PENSTOCK ALSTOM P122
FLOODLIGHTS) Pickup Current: - 0.1 X IN
51 Curve: - IEC EI
Pickup Current: - 7 X IN
50
MCA-7 Time Delay: - 0.10
(FEEDER FOR 1MW HYDRO ALSTOM P122
UNIT) Pickup Current: - 0.5 X IN
Pickup Current: - 1 X IN
50N
Time Delay: - 0.10
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
51 Curve: - IEC EI
Pickup Current: - 6 X IN
50
MCA-8 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR TX AT17)
Pickup Current: - 2 X IN
Pickup Current: - 4 X IN
50N
Time Delay: - 0.10
51 Curve: - IEC EI
Pickup Current: - 16 X IN
50
MCA-9 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR MCB)
Pickup Current: - 0.05 X IN
51 Curve: - IEC EI
51 Curve: - IEC EI
Pickup Current: - 20 X IN
50
MCA-11 Time Delay: - 0.10
(FEEDER FOR ALSTOM P122
POWERHOUSE II ) Pickup Current: - 0.33 X IN
51 Curve: - IEC EI
51 Curve: - IEC EI
Pickup Current: - 20 X IN
50
MCA-13 Time Delay: - 0.10
(FEEDER FOR ALSTOM P122
POWERHOUSE II ) Pickup Current: - 0.33 X IN
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
Pickup Current: - 1 X IN
51 Curve: - IEC SI
Pickup Current: - 20 X IN
50
MCA-15 Time Delay: - 0.10
ALSTOM P122
(FEEDER TO AT7)
Pickup Current: - 0.05 X IN
Pickup Current: - 1 X IN
50N
Time Delay: - 0.10
51 Curve: - IEC EI
Pickup Current: - 6 X IN
50
MCA-19 Time Delay: - 0.10
ALSTOM P122
(FEEDER FOR TX AT16)
Pickup Current: - 2 X IN
Pickup Current: - 4 X IN
50N
Time Delay: - 0.10
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
51 Curve: - IEC EI
Pickup Current: - 10 X IN
50
EMCA-E1 Time Delay: - 0.10
FUJI F-MPC30
(POWERHOUSE-1)
Pickup Current: - 0.12 X IN (12%)
51 Curve: - IEC EI
Pickup Current: - 10 X IN
50
EMCA-E2 Time Delay: - 0.10
FUJI F-MPC30
(POWER HOUSE-1)
Pickup Current: - 0.12 X IN (12%)
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
Pickup Current: - 7 X IN
50
PMB2 FUJI ELECTRIC Time Delay: - 0.20
(PONY MOTOR-1) F-MPC30
Pickup Current: - 0.05 X IN (5%)
Pickup Current: - 7 X IN
50
PMB3 FUJI ELECTRIC Time Delay: - 0.20
(PONY MOTOR-2) F-MPC30
Pickup Current: - 0.05 X IN (5%)
51 Curve: - IEC EI
Pickup Current: - 8 X IN
50
PMB4 FUJI ELECTRIC Time Delay: - 0.35
(SERVING EMCA1/EMCA2) F-MPC30
Pickup Current: - 0.17 X IN (17%)
51 Curve: - IEC EI
Pickup Current: - 8 X IN
50
PMB5 FUJI ELECTRIC Time Delay: - 0.35
(SERVING EMCA1/EMCA2) F-MPC30
Pickup Current: - 0.17 X IN (17%)
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
51 Curve: - IEC EI
51 Curve: - IEC EI
51 Curve: - IEC SI
Pickup Current: - 2 X IN
50
MCB-5A Time Delay: - 0.10
MICOM P122
(FEEDER FOR +AT7)
Pickup Current: - 0.05 X IN
51 Curve: - IEC VI
Pickup Current: - 1 X IN
50
MCB-5B Time Delay: - 0.20
MICOM P122
(DIESEL GENERATOR)
Pickup Current: - 0.05 X IN
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
LTD - -
STPU - 4 X IN
SHORT TIME
STD - -
TD - -
GPU - -
GROUND
GTD - -
I2T - -
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
LTD - 2.50
STPU - 1.5 X IN
SHORT TIME
STD - 0.07
MAGRINI GALLILEO
CONTROL B1-35 I2T - OUT
52PCD1 400A (SENSOR)
(JOSLYN OPTI TRIP II RMS)
(INCOMER FOR PCD) 400 (PLUG-IN)
INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.6 X IN
GROUND
GTD - 0.20
I2T - OUT
LTD - 2.50
STPU - 1.5 X IN
SHORT TIME
STD - 0.07
MAGRINI GALLILEO
CONTROL B1-35 I2T - OUT
52PCD2 400A (SENSOR)
(JOSLYN OPTI TRIP II RMS)
(INCOMER FOR PCD) 400 (PLUG-IN)
INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.6 X IN
GROUND
GTD - 0.20
I2T - OUT
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
LTD - 0.50
STPU - 4 X IN
SHORT TIME
STD - 0.05
TD - DISABLE
GPU - 0.6 X IN
GROUND
GTD - 0.50
I2T - OUT
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
LTD - 3.00
STPU - 0.9 X IN
SHORT TIME
STD - 0.13
+GDP.A-52A I2T - OUT
ABB E4S SACE PR112 4000A (SENSOR)
4000 (PLUG-IN)
(MAIN INCOMER-1) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.28 X IN
GROUND
GTD - 0.20
I2T - IN
LTD - 3.00
STPU - 0.9 X IN
SHORT TIME
STD - 0.13
+GDP.A-52B I2T - OUT
ABB E4S SACE PR112 4000A (SENSOR)
4000 (PLUG-IN)
(MAIN INCOMER-2) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.28 X IN
GROUND
GTD - 0.20
I2T - IN
LTD - 3.00
STPU - 0.6 X IN
SHORT TIME
STD - 0.08
+GDP.A-52C I2T - OUT
ABB E4S SACE PR112 4000A (SENSOR)
4000 (PLUG-IN)
(TIE CB) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.2 X IN
GROUND
GTD - 0.15
I2T - IN
LTD - CURVE B
STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.A.Q1A I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP UA) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.3 X IN
GROUND
GTD - CURVE A
I2T - OUT
LTD - CURVE B
STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.A.Q1B I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP CA) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.3 X IN
GROUND
GTD - CURVE A
I2T - OUT
LTD - CURVE B
STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.A.Q2A I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO +DBA) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.3 X IN
GROUND
GTD - CURVE A
I2T - OUT
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
LTD - CURVE B
STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.A.Q2B I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP UA) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.3 X IN
GROUND
GTD - CURVE A
I2T - OUT
LTD - CURVE B
STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.A.Q3A I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP CA) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.3 X IN
GROUND
GTD - CURVE A
I2T - OUT
LTD - CURVE A
STPU - 1 X IN
SHORT TIME
STD - CURVE A
TD - -
GPU - 0.2 X IN
GROUND
GTD - CURVE A
I2T - OUT
LTD - CURVE A
STPU - 1 X IN
SHORT TIME
STD - CURVE A
TD - -
GPU - 0.2 X IN
GROUND
GTD - CURVE A
I2T - OUT
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
LTD - 3.00
STPU - 0.9 X IN
SHORT TIME
STD - 0.13
+GDP.B-52A I2T - OUT
ABB E4S SACE PR112 4000A (SENSOR)
4000 (PLUG-IN)
(MAIN INCOMER-1) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.28 X IN
GROUND
GTD - 0.20
I2T - IN
LTD - 3.00
STPU - 0.9 X IN
SHORT TIME
STD - 0.13
+GDP.B-52B I2T - OUT
ABB E4S SACE PR112 4000A (SENSOR)
4000 (PLUG-IN)
(MAIN INCOMER-2) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.28 X IN
GROUND
GTD - 0.20
I2T - IN
LTD - 3.00
STPU - 0.6 X IN
SHORT TIME
STD - 0.08
+GDP.B-52C I2T - OUT
ABB E4S SACE PR112 4000A (SENSOR)
4000 (PLUG-IN)
(TIE CB) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.2 X IN
GROUND
GTD - 0.15
I2T - IN
LTD - CURVE B
STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.B.Q1A I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP UB) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.3 X IN
GROUND
GTD - CURVE A
I2T - -
LTD - CURVE B
STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.B.Q2B I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP UB) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.3 X IN
GROUND
GTD - CURVE A
I2T - -
LTD - CURVE B
STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.B.Q1B I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP CB) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.3 X IN
GROUND
GTD - CURVE A
I2T - -
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
LTD - CURVE B
STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.B.Q1B I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP CB) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.3 X IN
GROUND
GTD - CURVE A
I2T - -
LTD - CURVE B
STPU - 1 X IN
SHORT TIME
STD - CURVE A
+GDP.B.Q3A I2T - OUT
ABB S7L SACE PR212 1600A (SENSOR)
1600 (PLUG-IN)
(FEEDER TO PDP CB) INSTANTANEOUS I-PU - DISABLE
TD - DISABLE
GPU - 0.3 X IN
GROUND
GTD - CURVE A
I2T - -
LTD - CURVE A
STPU - 1 X IN
SHORT TIME
STD - CURVE A
TD - -
GPU - 0.2 X IN
GROUND
GTD - CURVE A
I2T - OUT
LTD - CURVE A
STPU - 1 X IN
SHORT TIME
STD - CURVE A
TD - -
GPU - 0.2 X IN
GROUND
GTD - CURVE A
I2T - OUT
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
LTD - 0.50
STPU - 2 X IN
SHORT TIME
STD - 0.10
PCA-1 3200A (SENSOR) I2T - OUT
FUJI DH30
3200A
(INCOMER OF PCA) 3200A / 1.0 (PLUG-IN) INSTANTANEOUS I-PU - DISABLE
TD - -
GPU - 0.2 X IN
GROUND
GTD - 0.30
I2T - OUT
LTD - 1.25
STPU - 2 X IN
SHORT TIME
STD - 0.40
PCA-2
3200A (SENSOR) I2T - OUT
FUJI DH30
(OUTGOING FEEDER OF
3200A
PCA) 1600A / 0.50 (PLUG-IN) INSTANTANEOUS I-PU - 2 X IN
TD - -
GPU - 0.1 X IN
GROUND
GTD - 0.20
I2T - OUT
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
LTD - 0.50
STPU - 2 X IN
SHORT TIME
STD - 0.10
PCB-1 3200A (SENSOR) I2T - OUT
FUJI DH30
3200A
(INCOMER OF PCA) 3200A / 1.0 (PLUG-IN) INSTANTANEOUS I-PU - DISABLE
TD - -
GPU - 0.2 X IN
GROUND
GTD - 0.30
I2T - OUT
LTD - 1.25
STPU - 2 X IN
SHORT TIME
STD - 0.40
PCB-2
3200A (SENSOR) I2T - OUT
FUJI DH30
(OUTGOING FEEDER OF
3200A
PCA) 1600A / 0.50 (PLUG-IN) INSTANTANEOUS I-PU - 2 X IN
TD - -
GPU - 0.1 X IN
GROUND
GTD - 0.20
I2T - OUT
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
51 Curve: - IEC EI
Pickup Current: - 12 X IN
50
ST1 Time Delay: - 0.35
MICOM P633
(230KV PRIMARY)
Pickup Current: - 0.2 X IN
51N Curve: - DT
51 Curve: - IEC EI
Pickup Current: - 12 X IN
50
ST2 Time Delay: - 0.35
MICOM P633
(230KV PRIMARY)
Pickup Current: - 0.2 X IN
51N Curve: - DT
51 Curve: - IEC EI
Pickup Current: - 12 X IN
50
ST3 Time Delay: - 0.35
MICOM P633
(230KV PRIMARY)
Pickup Current: - 0.2 X IN
51N Curve: - DT
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
Pickup Current: - 1 X IN
51 Curve: - IEC EI
Pickup Current: - 1 X IN
51 Curve: - IEC EI
Pickup Current: - 1 X IN
51 Curve: - IEC EI
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
51 Curve: - IEC EI
51 Curve: - IEC EI