You are on page 1of 1

PROTECTIVE DEVICE SETTINGS SUMMARY

CBK POWER PROJECT (MCB)

PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS

Pickup Current: - 0.92 X IN

49/51 Curve: - IEC EI

2500:5A Time Multiplier Setting - 0.50

Pickup Current: - DISABLE


50
MCB2A Time Delay: - DISABLE
MICOM P122
(MCB INCOMER)
Pickup Current: - 0.06 X IN

51N Curve: - IEC SI

2500:5A Time Multiplier Setting - 0.07

Pickup Current: - DISABLE


50N
Time Delay: - DISABLE

Pickup Current: - 1.3 X IN

51 Curve: - IEC EI

300:5A Time Multiplier Setting - 0.57

Pickup Current: - 23 X IN
50
MCB-4A Time Delay: - 0.10
(FEEDER TO MICOM P122
POWERHOUSE II) Pickup Current: - 0.33 X IN

51N Curve: - IEC SI

300:5A Time Multiplier Setting - 0.04

Pickup Current: - 0.5 X IN


50N
Time Delay: - 0.10

Pickup Current: - 1.3 X IN

51 Curve: - IEC EI

300:5A Time Multiplier Setting - 0.57

Pickup Current: - 23 X IN
50
MCB-4B Time Delay: - 0.10
(FEEDER TO MICOM P122
POWERHOUSE II) Pickup Current: - 0.33 X IN

51N Curve: - IEC SI

300:5A Time Multiplier Setting - 0.04

Pickup Current: - 0.5 X IN


50N
Time Delay: - 0.10

Pickup Current: - 1 X IN

51 Curve: - IEC SI

200:5A Time Multiplier Setting - 0.10

Pickup Current: - 20 X IN
50
MCB-5A Time Delay: - 0.10
MICOM P122
(FEEDER FOR +AT7)
Pickup Current: - 0.5 X IN

51N Curve: - IEC SI

200:5A Time Multiplier Setting - 0.07

Pickup Current: - 1 X IN
50N
Time Delay: - 0.10

Pickup Current: - 1 X IN

51 Curve: - IEC VI

200:5A Time Multiplier Setting - 0.19

Pickup Current: - 10 X IN
50
MCB-5B Time Delay: - 0.20
MICOM P122
(DIESEL GENERATOR)
Pickup Current: - 0.5 X IN

51N Curve: - IEC SI

200:5A Time Multiplier Setting - 0.04

Pickup Current: - 1 X IN
50N
Time Delay: - 0.20

Archie F. Balmes, PEE


Email: afb.engg@gmail.com / archiebalmes@gmail.com
Cellphone: 09174947912 1/1

You might also like