Professional Documents
Culture Documents
MCCB and MCB
MCCB and MCB
PROTECTIVE DEVICE TYPE SENSOR / CT RATIO DEVICE FUNCTION SETTING PARAMETERS UNIT / RANGE SETTING CALCULATIONS
51 Curve: - IEC EI
Pickup Current: - 23 X IN
50
MCB-4A Time Delay: - 0.10
(FEEDER TO MICOM P122
POWERHOUSE II) Pickup Current: - 0.33 X IN
51 Curve: - IEC EI
Pickup Current: - 23 X IN
50
MCB-4B Time Delay: - 0.10
(FEEDER TO MICOM P122
POWERHOUSE II) Pickup Current: - 0.33 X IN
Pickup Current: - 1 X IN
51 Curve: - IEC SI
Pickup Current: - 20 X IN
50
MCB-5A Time Delay: - 0.10
MICOM P122
(FEEDER FOR +AT7)
Pickup Current: - 0.5 X IN
Pickup Current: - 1 X IN
50N
Time Delay: - 0.10
Pickup Current: - 1 X IN
51 Curve: - IEC VI
Pickup Current: - 10 X IN
50
MCB-5B Time Delay: - 0.20
MICOM P122
(DIESEL GENERATOR)
Pickup Current: - 0.5 X IN
Pickup Current: - 1 X IN
50N
Time Delay: - 0.20