0 No Irregularities check is observed on the report as well on analysis file as per clause 7 especially
-Regular and irregular configuration
- Soft story
- Mass Irregularity
- irregular mode of oscillation in two principal plan direction -first three mode should contribute
more than 65% mass participation
2.0 eccentricity is taken 0% for both direction… Calculate eccentricity and apply on dynamic case using
clause 7.8.1
3.0 Provide (Wall load+plaster)/floor finish load calculation on the report
4.0 No Partition wall load observed on future possible change-minimum 1 or calculated which ever is
critical…calculated partion load applied only in few place.
5.0 No staircase void is observed. true representation of staircase load in modelling is missing
6.0
8.0
-
Please provide Calculated data for section in detailing.
17.
Up to what length stirrups provided… + extra bar length???? Provide proper data.. not formula
18. No Soil Pressure on Retaining wall is observed… pl provide proper soil pressure on wall and…
effect of this should be reflected on raft foundation design
19. design building as per clause 7.2.7 for dual system.
20.
Mass source 0.25 for all live load? … check the code and revise design
21. Time period calculated is 36 m height use for 30m excluding basement floor.
22. Design the retaining wall manually to verify the thickness and reinforcement.
ALL THESE COMMENTS ARE PROVIDED BASED ON SURFACIAL OBSERVATION ONLY BECAUSE OF
TIME LIMITATIONS.
PLEASE TAKE THIS COMMENTS AS REPRESENTATIVE COMMENTS FOR ALL OTHER BLOCKS.
BECAUSE OF TIME LIMITATION STILL WE ARE GOING THROUGH THE DESIGN.
YOUR COORDINATION FOR OTHER THINGS WHICH ARE NOT INCLUDED HERE, (BUT YOU THINK IT
AS IMPORTANT) ARE ALWAYS WELCOME. OUR COMMON MOTIVE IS TO MAKE BUILDING SAFER
AND STRONGER. THANK YOU FOR YOUR UNDERSTANDING.