CICED2008 Technical Session 2 Power Quality and PowerConservation

82-12 CP1512

Operation Test and Industrial Application of SVC for Mitigation


Flicker from Electric arc Furnaces
zhong-yuan zhao, chi-han chen, xiao-hong wang, shun-xian bao

NARI-RELAYS Electric Company Limited, Power Electronics Center,


Jiangsu 211102, China

Abstract: The situation at electric arc furnace factory is in Zhejiang province.


always severe containing voltage fluctuation and flicker, With the SVC in operation, the compensated power
three-phase imbalance and low power factor. The dynamic var factor at the point of common coupling is better than 0.99.
compensator is a good solution to this condition. The static The SVC also achieves filtering of harmonics caused by the
var compensator (SVC), with its continuously variable operating of the furnaces in the steel plant as well as acts as a
compensation, also safeguards the plant against balancer of the highly unsymmetrical load on the AC supply
overcompensation during furnace outages. The SVC grid represented by the electric arc furnace.
equipment, offered by NARI-RELAYS, presents a phase-wise
2 SVC INTEGRATED PRINCIPLE
open-loop reactive power controller and a three-phase
closed-loop power factor control, which are based on In the deduction process of SVC compensation
high-speed space vector control. The factory system test on susceptances, there are two prerequisites. One condition is that
physical simulator is implemented, and its open-loop response the three-phase system is balanced after compensation, that is to
time is less than 7 milliseconds with closed-loop one less than say, negative sequence component of system line currents must
25 milliseconds. One electric arc furnace plant's engineering equal zero.Accordingly, the equation is as follows:
is illustrated as an example to show the effects with/without 12+12,=0 (I)
SVC function. where 12 is the negative sequence component of
Keywords: SVC, voltage fluctuation and flicker, harmonic system line currents I a, I b and Ie' 12 , is the negative
mitigation, electric arc furnace sequence component of SVC compensation currents.
The other condition is that power factor equal one after
1 INTRODUCTION
compensation, that is to say, the imaginary part of the positive
The use of static var compensator (SVC) can solve sequence component of system line currents equals zero, and
effectively many electric power quality problems such as low the corresponding equation is as follows:
power factor, voltage fluctuation and flicker, three-phase 1m[II + II,] = 0 (2)
imbalance and the dynamic and static instability of power
where II is the positive sequence component of system
system. In fact, as power quality issues are getting more and line currents Ia , I, and Ie' II, is the positive sequence
more into focus in many parts of the world, requirements on component of SVC compensation currents.
the mitigation of flicker and other kinds of current and Based on (I) and (2) above, the SVC three-phase
voltage distortion are being imposed by regulatory bodies at compensation susceptance B;b, B;e .B" can be deduced,
an increasing scale. To meet this, grid owners and operators which are shown as follow:
of process industry are meeting each other in order to work 1
B;b = --(Im[Ia]+ Im[aIb]+ Im[a 2 Ie]
out solutions to common problems which will satisfy the 3U
needs and interests of all concerned. B;e =__1_(_ Im[Ia] + Im[aIb]+ Im[a 2 Ie]
A SVC rated 0-15Mvar, supplied by NARI-RELAYS, 3U
has been in operation at Yishengte's steel making plant(YST) B;a = -_I_(Im[Ia] - Im[aIb]+ Im [a 2 Ie]
3U
CICED2008 Technical Session 2 Power Quality and PowerConservation

where U represents the virtual value of three-phase


balanced voltages, a =ej 2n 13 •
2.1 Main circuit connection
The SVC at YST is operated directly on the 35kV arc
furnace bus. It comprises a Thyristor-Controlled Reactor
(TCR) rated 15Mvar and four parallel Harmonic Filters, also
with an overall rating 15Mvar. I n..--_...11...._ ...

11• ..-....1_
,~

.1001 . . . .. . 011

This control system adopted the phase-wise reactive _ ... -.1 ....

power control by means of fast-acting open-loop controller.


Plus three-phase closed-loop power factor control. The 2nd Figure2. SVC layout
harmonic filter, 3rd harmonic filter,4th harmonic filter and 5th
harmonic filter are installed at AC load side. And all the
protection devices for filters are also supplied by
NARI-RELAYS.
The factory system test is implemented on physical
simulator to meet the requirements from IEC 61000. The
open-loop response time for the controller is less than 7
millisecond. Its closed-loop response time is less than 25
millisecond. Meanwhile, the three-phase imbalanced case is
also done on this SVC.
The whole single-line diagram is offered in Figure\.

Figure3. SVC control & protection cubiclephoto

Figure 1. Single-line diagram

2.2 Main equipment layout


The thyristor-valve is a three-phase, water-cooled valve
with indirect light firing.
On-site layout is shown in Figure 2. The thyristor-valves
and control & protection cubicles in Figure 3 are installed at
the first floor indoor. The water-cooler system uses the pure Figure4. Reactorand capacitorphoto
water as cooling material. The reactors and capacitors for
filters are set down on the second floor, illustrated in Figure 4. 3 OPERATION EFFECTS
The operation waves on site are shown in Figure 5.
Power quality has been improved sharply, and voltage
fluctuation also has been mitigated with var absorbed from
power grid system side being nearly zero, since the SVC was
installed.
The overall power factor of 0.99 is achieved steadily.
The voltage flicker and other harmonic values are better than

2
CICED2008 Technical Session 2 Power Quality and PowerConservation

ones regulated by IEC standard. pp.288-291,Oct.2001.


[2] Ding Ren-jie , Liu Jian , Zhang Juan, and Zhao Yu-wei.
"New Control Method of SVC Based on Instantaneous
Reactive Power Theory", Transactions of China
Electrotechnical Society, vol.21, pp.48-51, May.2006.
[3] Wilsun Xu, Yi Zhang, Luiz C. P. da Silva, et al.
"Valuation of Dynamic Reactive Power Support
Services for Transmission Access", IEEE Transaction
on Power Systems, 16(4), pp. 719-728, 2001.
[4] Wang Mu-hai, and Sun Yuan-zhang, "Application of
Figure5. Operation recordwave Universal Instantaneous Power Theory to Unbalanced
Load Compensation," Proceedings of the Chinese
Society for Electrical Engineering, vol.23, pp.56-59,
4 CONCLUSIONS
2003.
The functions ofSVC can be obtained as follows. [5] Ji Fei-feng, Zhou Li-dan, and Yao Gang, "Static var
• The overall power factor can be kept on 0.99. the compensator based on the method of synchronous
over-compensation and sub-compensation do not occur. symmetrical component ," Proceedings of the Chinese
• Rapid response to voltage fluctuation can be Society for Electrical Engineering, vol.25, pp.27-32,
achieved to mitigate the voltage flicker, and is able to 2005.
stabilize the power supply, as well as to increase the [6] Sun Chi, Wei Guang-hui , and Bi Zeng-jun., "Detection
production quality. for reactive and harmonic currents of unbalanced
• Reducing the harmonic currents generated by arc three-phase systems based on synchronous coordinate
furnace. conversion ," Proceedings of the Chinese Society for
• The situation of three-phase imbalance can Electrical Engineering, vol.23, pp.43-48, 2003.
be effectively improved.
REFERENCES
[1] Li Xing-guang, and Lai Sheng-Ii, "An Approach of
Integrated Compensation for Reactive Power and Three
Phase Unbalance", Power System technology, vol.25,