A‐PAT‐SALES140901‐DIV‐NDC‐Ind00

Dimensioning of Hydraulic and 
Aerolic Loops

Cerro Panama Power Plant

Written By F. TROUCHE
Date 30/06/2015
Index 00

1 sur 8
A‐PAT‐SALES140901‐DIV‐NDC‐Ind00

I‐Heating Water circuit

Liquid Glycol water 37%
Flow 43,1 m3/h

Dimensioning of 3 way valves

3 Ways Valves Variable flow element Maxi back pressure Theorical kvs Chosen Kvs Back pressure valve Autority


Cooler 3 ways valve Cooler 0,36 bar 70,5518299 80 0,30 bar 0,451
Warm up 3 ways valve 0,00 bar ‐ 0 0,00 bar ‐

Diameter Dimensioning

Chosen Diameter DN 100
Speed Limit 2 m/s
Speed with Chosen 
1,52 m/s
Diameter

Inventory of back pressure

Element Quantity Temperature Lenght DN Back pressure


V3V 2 75 °C ‐‐ ‐‐ 0,30 bar
Genset 1 75 °C ‐‐ ‐‐ 1,30 bar
Rounded berd 10 75 °C ‐‐ 100 0,02 bar
T path 1 75 °C ‐‐ 100 0,0012 bar
Divergent reduced sleeve 1 75 °C ‐‐ 80 0,0007 bar
Convergent reduced 
1 75 °C ‐‐ 100 0,0005 bar
sleeve
Cooler 1 75 °C ‐‐ ‐‐ 0,26 bar
Straight pipe 1 75 °C ‐‐ 100 0,04 bar
Control valve 1 75 °C ‐‐ 100 0,07 bar

Total  (+20%) 2,4 bar

2 sur 8
A‐PAT‐SALES140901‐DIV‐NDC‐Ind00

Back pressure distribution Control valve V3V


Straight pipe 4% 15%
2%

Cooler

Rounded berd
1%

Genset
65%

3 sur 8
A‐PAT‐SALES140901‐DIV‐NDC‐Ind00

Expansion Vessel Volume

Volume of glycol 1070 Litres


Density at 25°C 1046,2 kg/m3
Density at 90°C 1018,2 kg/m3
Expension coefficient 2,755%
Expending coefficient 29 Litres
Blowing valve pressure 6,0 bar
Static pressure 1,7 bar
Pressure factor 0,614
Safety factor 1,50
Expansion Vessel volume 72 liters
Expansion Vessel chose 100 liters

4 sur 8
A‐PAT‐SALES140901‐DIV‐NDC‐Ind00

II‐ Exhaust gas Loop

Chimney Height 10,00 m
Exhaust gas exit 
507 °C
temperature
Exhaust gas temperature 
507 °C
after turbocharger

Outside Temperature 38 °C
Exhaust gas mass flow 
15388 kg/h
rate wet
Maximal back pressure 50 mbar
Static draw 0,559 mbar
Dilatation thermic 
7,66 mm/m
coefficient at 627°C
Ejecting nominal 
diameter ( for a ejection 
DN 600
speed higher than 25 
m/s)

Element Quantity Lenght DN Back pressure


Straight duct 1 11,00 m 600 0,61 mbar
Rounded Berd 3 ‐‐ 600 1,12 mbar
Silencer 1 ‐‐ ‐‐ 10,00 mbar

Available back pressure 
TOTAL  12 mbar 38 mbar 76,5%

5 sur 8
A‐PAT‐SALES140901‐DIV‐NDC‐Ind00

III‐ Air loop

Heat to be dissipated 206 kW
Inlet Temperature 38 °C
Outlet Temperature 45 °C
Air flow (oversized +25%) 130 000 m3/h
Outlet Flow 120 000 m3/h
Speed limit in the air loop 7 m/s
Admittion surface 11,18 m²
Expulsion surface 10,32 m²

Back 
Element Quantity Position Lenght
Pressure
Straight pipe 1 aspi 3,50 m ~ <0,01 Pa
Rounded berd 2 aspi ‐‐ 4,0 Pa
Straight pipe 1 aspi 4,00 m ~ <0,01 Pa
Straight pipe 1 aspi 5,00 m ~ <0,01 Pa
Rounded berd 1 aspi ‐‐ 0,4 Pa
Rounded berd 1 aspi ‐‐ 1,7 Pa
Straight pipe 1 aspi 3,00 m ~ <0,01 Pa
Acoustic trap 1 aspi ‐‐ 50,0 Pa
Grid 1 aspi ‐‐ 100,0 Pa
Filter 1 aspi ‐‐ 250,0 Pa
Acoustic trap 1 refoul ‐‐ 50,0 Pa
Grid 1 refoul ‐‐ 100,0 Pa

TOTAL
Vacuum 406,1 Pa
Expulsion 150,0 Pa
Total 556,1 Pa

6 sur 8
A‐PAT‐SALES140901‐DIV‐NDC‐Ind00

IV‐ Oil Loop

Flow 2 m3/h
Liquid Oil pegasus 710 Viscosity 0,533 Pa.s
Static back 
Static back pressure after  pressure after 
0,12557 bar 0,15696 bar
fresh oil pump Waste oil 
pump
Static back 
Static back pressure  pressure 
0,00000 bar 0,00000 bar
before fresh oil pump before Waste 
oil pump
Pression de 
Molar 0,018 kg/mol vapeur  0,0213 bar
saturante
Latent heat 2260000,000 J/kg Volumic Mass 896 kg/m3

Daily tank 
Temperature 15 °C minimum  176 Litres
volume

Element Quentity Position Lenght DN Back Pressure


Straight pipe 1 aspi 45,70 m 50 0,882167 bar
Berd 14 aspi ‐‐ 50 0,000856 bar
Ball valve 1 aspi ‐‐ 50 0,000050 bar
T path 3 aspi ‐‐ 50 0,000108 bar
Berd 7 refoul ‐‐ 25 0,006846 bar
Ball valve 6 refoul ‐‐ 25 0,004818 bar
Straight pipe 1 refoul 9,60 m 25 0,670410 bar
Filter 1 refoul ‐‐ 25 0,030989 bar
Chek valve 2 aspi ‐‐ 25 0,008149 bar
Filter 1 aspi ‐‐ 25 0,030989 bar

TOTAL       TOTAL 
Fresh Oil Waste Oil
Before pump 0,84 bar 1,08 bar
After pump 0,92 bar 0,71 bar
Total 1,76 bar 1,79 bar
NPHS available 0,7 mCE 3,0 mCE
NPHS  0,7 mCE
Chosen back pressure 
2,15 bar
(+20%):

7 sur 8
A‐PAT‐SALES140901‐DIV‐NDC‐Ind00

V‐ Gas Loop

Flow  1931 m3/h
Selected 
Flow for 3 engines 5792 m3/h
DN
Delivrery gas pressure 0,15 bar  Engine   DN 250
Max speed 12 m/s Feeder DN 450
Temperature 40 °C

Element Quantity Temperature Lenght DN Back pressure


Straight pipe 1 40 °C 77,00 m 450 2,14 mbar
Rounded berd 1 40 °C ‐‐ 450 0,06 mbar
Rounded berd 1 40 °C ‐‐ 450 0,03 mbar
Straight pipe 1 40 °C 35,00 m 300 0,86 mbar
Rounded berd 15 40 °C ‐‐ 300 0,59 mbar
Valve 10 40 °C ‐‐ 300 0,88 mbar
Straight pipe 1 40 °C 3,00 m 150 1,03 mbar
Valve 2 40 °C ‐‐ 150 1,41 mbar
Rounded berd 3 40 °C ‐‐ 150 1,67 mbar
Feeder nipel 1 40 °C ‐‐ 150 2,61 mbar
Feeder nipel 1 40 °C ‐‐ 300 0,01 mbar
Feeder nipel 1 40 °C ‐‐ 250 0,02 mbar
Rounded berd 7 40 °C ‐‐ 250 0,50 mbar
Valve 1 40 °C ‐‐ 250 0,08 mbar
Jonction 90° 1 40 °C ‐‐ 250 0,16 mbar
Feeder nipel 1 40 °C ‐‐ 150 0,04 mbar
Carbon Tanks 3 ‐‐ ‐‐ ‐‐ 60,00 mbar
Filter 1 ‐‐ ‐‐ ‐‐ 11,60 mbar

TOTAL
84 mbar

8 sur 8