You are on page 1of 9

RESULT

Sensible Cooling &


Experimen Steam
No Heating Dehumidification
t
Humidificatio
Process
Reading 1.5k n 5
1kW 100 ml
W mins
28.9°
T1 (TAd) 28.1°C 28.7°C 28.9°C 29.0°C 29.3°C
C
25.4°
T2 (TAw) 25.2°C 25.3°C 25.4°C 24.5°C 24.8°C
C
41.4°
T3 (TAd) 28.3°C 39.6°C 32.2°C 29.1°C 29.4°C
C
31.0°
T4 (TAw) 25.8°C 28.6°C 31.3°C 27.0°C 29.0°C
C
32.5°
T5 (TAd) 28.1°C 28.3°C 31.4°C 18.2°C 18.1°C
C
28.2°
T6 (TAw) 25.0°C 27.9°C 30.7°C 15.0°C 18.0°C
C
37.0°
T7 TAd) 28.1°C 27.8°C 31.3°C 17.8°C 17.9°C
C
29.0°
T8 (TAw) 25.0°C 27.5°C 30.8°C 14.0°C 17.8°C
C
T9 (T1) x x x x 19.9°C 19.4°C
T10 (T2) x x x x 69.1°C 78.9°C
T11 (T3) x x x x 40.8°C 41.8°C
T12 (T4) x x x x 3.4°C 3.9°C
Qp (W) x 993.6 980.2 x x x
Qr (W) x 0 521.2 x x x
Qb (W) x x x 3662.8 x x
Pevap (P1) kPa x x x x 179.7 185.8
Pcond (P3) kPa x x x x 966.9 1000
ma (gram/sec) 217.6 217.2 213.6 214.7 221.1 220.9
mr x x x x 0 0
5
Time x x x x 15 mins 40 s
mins
Drain Water
x x x x x 100 ml
(ml)
Table 1: Result table
NO PROCESS

Based on the table:

T₁(TAd) = 28.1ºC
T₂(TAw) = 25.2ºC
M a1 = 0.2176 kg/s
Referring to the Psychometric chart (Appendices), the relative humidity is 79.0%

Pressure gas, Pg:


Based on the table A-4 (Saturated water) attached in Appendices, apply interpolation to find
PgI .
T1= 28.1 °C
Pg 1−3.1698 28.1−25
=
4.2469−3.1698 30−25
Pg 1=3.838 Kpa

Pressure of moist air, Pv


Ø1 = Pv1/Pg
Pv1= Ø1 x Pg
Pv1= 0.79 × 3.838k
Pv1= 3.032 kPa

Specific Humidity, ω1 or Humidity Ratio


Patm= 101.33 Kpa
Pv
ω1= 0.662 ( )
P−Pv
3.032 k
ω1= 0.662
101.33 k−3.032 k
ω1= 0.02042 kgv/kga

Enthalpy, h1
Lets hg=2501.3+1.82T1

h1 = CpT1+ ω1hg

h1= (1.005×28.1) + 0.02042 (2501.3+1.82 (28.1))


h1=80.361 kJ/kga

SENSIBLE HEAT

Based on the table:

T₃(TBd) = 39.5ºC
T₄(TBw) = 29.0ºC
Ma2 = 0.2172 kg/s
Referring to the Psychometric chart (Appendices), the relative humidity is 46%

Pressure gas, Pg:


Based on the table A-4 (Saturated water) attached in Appendices, apply interpolation to find
Pg2.
T3= 39.5 °C
Pg 1−5.6291 39.5−35
=
7.3551−5.6291 40−35
Pg 1=7.183 Kpa

Pressure of moist air, Pv


Ø2 = Pv2/Pg
Pv2= Ø2 x Pg
Pv2= 0.46 × 7.183k
Pv2= 3.304kPa

Specific Humidity, ω or Humidity Ratio


Patm= 101.33 Kpa
Pv
ω2= 0.662 ( )
P−Pv
3. 304 k
ω2= 0.662
101.33 k−3. 304 k
ω2= 0.0223 kgv/kga

Enthalpy, h2
Lets hg=2501.3+1.82T3

h2 = CpT3+ ω2hg
h2= (1.005×39.5) + 0.02042 (2501.3+1.82 (39.5))

h2=92.24 kJ/kga
STEAM HUMIDIFICATION
From the table:

T₅(TCd) = 31.4ºC
T₆(TCw) = 30.7ºC
Ma3 = 0.2147 kg/s

Referring to the Psychometric chart (Appendices), the relative humidity is 94%

Pressure gas, Pg
Based on the table A-4 (Saturated water) attached in Appendices, apply interpolation to find
Pg3.
T6= 30.7°C
Pg 3−4.2469 30.7−30
=
5.6291−4.2469 35−30
Pg 3=4.44 Kpa

Pressure of moist air, Pv


Ø3 = Pv3/Pg
Pv3= Ø3 x Pg
Pv3= 0.94 × 4.44k
Pv3= 4.174 kPa

Specific Humidity, ω or Humidity Ratio


Patm= 101.33 Kpa
Pv
ω3= 0.662 ( )
P−Pv
4.174 k
ω3= 0.662
101.33 k−4.174 k
ω3= 0.0284 kgv/kga

Enthalpy, h3
Let hg=2501.3+1.82T6

h3 = CpT6+ ω3hg

h3= (1.005×30.7) + 0.0284 (2501.3+1.82 (30.7))

h3=103.477kJ/kga
COOLING DEHUMIDIFICATION
From the table:
T₇(TDd) = 17.8ºC
T₈(TDw) = 14.0ºC
Ma4 = 0.2211 kg/s

Referring to the Psychometric chart (Appendices), the relative humidity is 67%

Pressure gas, Pg
Based on the table A-4 (Saturated water) attached in Appendices, apply interpolation to find
Pg4 .
T8= 14.0°C
Pg 4−1.2281 14−10
=
1.7057−1.2281 15−10
Pg 4=1.61 Kpa

Pressure of moist air, Pv


Ø4 = Pv4/Pg
Pv4= Ø4 x Pg
Pv4= 0.67× 1.61k
Pv4= 1.0787 kPa

Specific Humidity, ω or Humidity Ratio


Patm= 101.33 Kpa
Pv
ω4= 0.662 ( )
P−Pv
1.0787 k
ω4= 0.662
101.33 k−1.0787 k
ω4= 0.007123 kgv/kga

Enthalpy, h4
Let hg=2501.3+1.82T8

h4 = CpT8+ ω4hg

h4= (1.005×14.0) + 0.007123 (2501.3+1.82 (14.0))


h4=32.1kJ/kga

Appendices

Table 2: Pyshometric Chart


Table 3:Table A-4

You might also like