Professional Documents
Culture Documents
Application note 40
55 V
RCD
55 V
Testing RCDs without neutral or earth connections RCD testing voltage limits
Testing 3 phase RCDs without neutral or earth
connections is possible by testing across the RCD if the Voltage limits
rating of the tester is sufficient. Many 3 phase RCDs do To have sufficient voltage for accuracy and not too much
not have a neutral connection. Standard RCD testers are power for the instrument to dissipate there are limits to
usually only designed for single-phase operation. More the minimum and maximum voltages when RCD testing.
advanced models enable other connections to be utilized The limit varies with test current as well as the type of
due to a higher operating voltage. instrument.
RCD
Minimum Maximum
voltage voltage
RCDT310 100 V 280 V
RCDT320/330 50 V 280 V
MFT1500 series 100 V 270 V
MFT1710 48 V 280 V
MFT1720/30 48 V 480 V
CERTIFICATION ISO
UNITED STATES OTHER TECHNICAL SALES OFFICES
Registered to ISO 9001:2008 Cert. no. Q 09250
UK 4271 Bronze Way Valley Forge USA, College Station USA, Sydney Registered to ISO 14001-2004 Cert. no. EMS 61597
Archcliffe Road Dover Dallas TX 75237-1019 USA AUSTRALIA, Täby SWEDEN, Ontario CANADA,
CT17 9EN England T 800 723 2861 (USA only) Trappes FRANCE, Oberursel GERMANY, Aargau RCD_AN40_en_V01
T +44 (0) 1304 502101 T +1 214 333 3201 SWITZERLAND, Kingdom of BAHRAIN, Mumbai www.megger.com
F +44 (0) 1304 207342 F +1 214 331 7399 INDIA, Johannesburg SOUTH AFRICA, Chonburi
Megger is a registered trademark
UKsales@megger.com USsales@megger.com THAILAND
UNITED STATES