Professional Documents
Culture Documents
BYBU - XR715 - Fire-Resistance Ratings - ANSI - UL 1709 - UL Product Iq - BOTTOM COLUMN AVI - GCP2020 PDF
BYBU - XR715 - Fire-Resistance Ratings - ANSI - UL 1709 - UL Product Iq - BOTTOM COLUMN AVI - GCP2020 PDF
https://iq.ulprospector.com/en/profile?e=17500 1/3
8/1/2021 BYBU.XR715 - Fire-resistance Ratings - ANSI/UL 1709 | UL Product iQ
1. Spray-Applied Fire Resistive Material* — See table below for appropriate thicknesses. Applied by mixing with water
according to instructions printed on each bag of mixture and spraying in one or more coats, as necessary, to column surfaces
which must be clean and free of dirt, loose scale and oil. Min average density of 40 pcf, with min individual value of 36 pcf for
Avikote AV 650, Z-146, Z-146PC and Z-146T cementitious mixture. Min average density of 50 pcf, with min individual value of
45 pcf for Avikote AV 800, Z-156, Z-156PC and Z-156T. For method of density determination, See Design Information Section
General, Coating Materials. Types AV 650, AV 800, Z-146, Z-146 NPP, Z-146PC, Z-146T, Z-156, Z-156T and Z-156PC
investigated for UL 2431 Classification Category I-A and Exterior Environmental Purpose.
ARABIAN VERMICULITE INDUSTRIES — Types Avikote AV 650, AV 800, Z-146, Z-146 NPP, Z-146PC, Z-146T, Z-156, Z-156PC and Z-156T
https://iq.ulprospector.com/en/profile?e=17500 2/3
8/1/2021 BYBU.XR715 - Fire-resistance Ratings - ANSI/UL 1709 | UL Product iQ
GCP APPLIED TECHNOLOGIES INC — Type Z-146, Z-146 NPP, Z-146PC, Z-146T, Z-156, Z-156PC and Z-156T cementitious mixture
GCP KOREA INC — Type Z-146, Z-146 NPP, Z-146PC, Z-146T, Z-156, Z-156PC and Z-156T cementitious mixture
2. Metal Lath — 3.4 lb per sq yd galv or painted expanded steel lath. Lath shall be lapped 1 in. and tied together with No. 18
SWG galv steel wire spaced vertically every 6 in.
Where steel pin fixings (not shown) are utilized to assist in holding metal lath to column, either welded fixing or high
temperature adhesive referenced "HTA Adhesive" (supplied by HTA Ltd), fixing of pins to steel column are permitted.
4. Corner Bead — (Optional, Not Shown) — 26 SWG galv steel corner bead placed at flange tips and mechanically fastened to
the steel column or to the metal lath cage.
5. Batts and Blankets — (Optional, Not Shown) — Rock wool/Mineral wool fiber as an optional in-fill material for the web
areas of steel column when box application is utilized.
* Indicates such products shall bear the UL or cUL Certification Mark for
jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
Last Updated on 2020-05-20
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following
format: "© 2021 UL LLC"