You are on page 1of 7

GROUND-3RD FLOOR

FACTORED AXIAL
COLUMN MARK LOAD (kN) DIMENSION

C1 377.892 200 X 200 mm


C2 755.8 250 X 250 mm
C3 377.892 200 X 200 mm
C4 0 X 0 mm
C5 0 X 0 mm
C6 755.8 250 X 250 mm
C7 1511.568 350 X 350 mm
C8 755.8 250 X 250 mm
C9 1107.76 300 X 300 mm
C10 1528.848 350 X 350 mm
C11 1138.86 300 X 300 mm
C12 724.68 250 X 250 mm
C13 724.68 250 X 250 mm
C14 755.8 250 X 250 mm
C15 1511.568 350 X 350 mm
C16 1133.676 300 X 300 mm
C17 1133.676 300 X 300 mm
C18 1133.676 300 X 300 mm
C19 755.8 250 X 250 mm
C20 1580.688 350 X 350 mm
C21 1185.516 300 X 300 mm
C22 1185.516 300 X 300 mm
C23 1580.688 350 X 350 mm
C24 377.892 200 X 200 mm
C25 5704.776 600 X 600 mm
C26 5704.776 600 X 600 mm
C27 5704.776 600 X 600 mm
C28 0 X 0 mm
C29 0 X 0 mm
C30 0 X 0 mm
C31 5704.776 600 X 600 mm
C32 0.00 0 X 0 mm
C33 0.00 0 X 0 mm
C34 596.75 200 X 200 mm
C35 1087.39 300 X 300 mm
C36 1155.23 300 X 300 mm
FORMULA

Ag= Ag =

Ast/Ag Pu f'c fy Ag(mm^2)

0.01 5704.776 27.6 414 400897.59612


0.015 5704.776 27.6 414 374196.24999
0.02 5704.776 27.6 414 350829.62626
0.025 5704.776 27.6 414 330209.73338
0.03 5704.776 27.6 414 311879.14206
0.035 5704.776 27.6 414 295476.65234
0.04 5704.776 27.6 414 280713.25322
0.05 5704.776 27.6 414 255210.2514
0.055 5704.776 27.6 414 244120.96825
0.06 5704.776 27.6 414 233955.24812
0.065 5704.776 27.6 414 224602.32607

COLUMN DIMENSION
governs = 350 X 350
except C25 = 600X600
C26 = 600X600
C27 = 600X600
C31 = 600X600
Ag =

0.65
0.65
0.65
0.65
0.65
0.65
0.65
0.65
0.65
0.65
0.65
F-7 1. Area of Footing
A = 0.747
B = 0.9
Column Size = 250 mm B Used = 0.9
Pu = 186.67 KN e = 0.33417
Mu = 62.38 KN-m H Rec = 0.3
H used = 0.3
Concrete Properties qnet = 215.6
γ Concrete = 24 KN/m³
f'c = 28 MPa Use 0.3m x 0.9m x 0.9m

Steel Properties 2. Bearing Pressure for Strength Design


fy = 414 MPa qumax = 743.8684272
qumin = -282.9548469
Soil Properties
γ Soil = 16 KN/m³ 3. Depth Base Requirement for Two way
qa = 250 Kpa d = 187.5
x = 0.137
Foundation Properties B-x = 0.763
Conc cover = 75 mm qu1 = 587.563
Temp. ba Ø = 25 mm Vu = 82.08275405
Main bar Ø = 25 mm ØVc = 113.8499861
df = 2 m SAFE FOR BEAM SHEAR!
Ø = 0.75
ʎ = 1 4. Depth Required for One Way Shear
D = 200
C+D = 450
Vu = 233.338
ØVc = 471.4728836
SAFE FOR PUNCHING SHEAR!!

Use 0.9m x 0.9m x 0.3m square foo


with 2 - 25mm Ø main bar both ways spaced a
5. Steel Reinforcement
m² x = 0.325 m
m qu₂ = 373.0711 KPa
m Mu₁ = 22.38916 KN-m
m Mu₂ = 6.57234 KN-m 22.389161631
m Use Mu = 22.39KN-m
m R = 0.786 Mpa
kPa ρ = 0.001931
ρmin = 0.003382
m x 0.9m x 0.9m Use ρ = 0.0034
d = 250 mm
re for Strength Design As = 765 mm²
kPa N = 2 pcs
kPa Ab = 490.87 mm²
S = 375 mm
quirement for Two way S = 370 mm
mm Use 2 - 25mm Ø main bar both ways
m spaced at 370 mm O.C. 0.0034
m
Kpa 6. Development Length
KN ℓd = 760 mm
KN 0.06ØbFy = 621 mm
R BEAM SHEAR! Use ℓd = 760mm
ℓAvail = 250 mm
d for One Way Shear Use 760mm Development length
mm with hook
mm 760
KN
Kn
UNCHING SHEAR!!

9m x 0.3m square footing


ar both ways spaced at 370 mm O. C.