OPzV Type Test Report OPzV Testing Acc. to IEC 60896-21/22, DIN 40742 & DIN
40744
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5Page 1 by 53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
INDEX
OPzV Type Test Report ..................................................................................................... 3
1 Discharge Capacity. ............................................................................................. 4
1.1 2V - OPzV 50Ah Plate ....................................................................................... 5
1.2 6V - OPzV 50Ah Plate ..................................................................................... 10
1.3 12V - OPzV 50Ah Plate .................................................................................... 15
1.4 70Ah Plate .................................................................................................... 20
1.5 100Ah Plate ................................................................................................... 25
1.6 125Ah Plate. .................................................................................................. 30
2 Short Circuit Current & DC Internal Resistance.......................................................35
3 High Current Tolerance .......................................................................................36
4 Recharge Behaviour............................................................................................37
5 Protection against Ground Short Propensity ...........................................................38
6 Charge Retention during Storage .........................................................................39
7 Gas Emission .....................................................................................................40
8 Material Identification .........................................................................................43
9 Valve Operation .................................................................................................43
10 Intercell Connector Performance ..........................................................................44
11 Endurance in Cycles (Float Service with Daily Discharges) .......................................45
12 Impact of a Stress Temperature of 60 °C (Accelerated Test of Operational Lifetime) ...46
13 Service life at an operating temperature of 40 °C ...................................................47
14 Abusive over-discharge .......................................................................................47
15 Thermal Runaway Sensitivity ...............................................................................48
16 Low Temperature Sensitivity................................................................................49
17 Dimensional Stability at Elevated Internal Pressures and Temperatures ....................50
18 Stability against mechanical abuse of units during installation ..................................51
19 Content and durability of required markings ..........................................................52
20 Protection against internal ignition from external spark sources ...............................52
21 Flammability rating of materials ...........................................................................52
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5Page 2 by 53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
Table 1 shows the relation between the test type and the number of cells acc. to IEC60896-21.
The selection of the cell type Vs the test type was made in order to be able to extrapolate the
results to the whole OPzV range. In most cases, the selection was made by the possible worst
case scenario.
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5Page 3 by 53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
1 Discharge Capacity.
The purpose of this test is to confirm the capacity of the cells/batteries to a specific end-voltage
at the selected discharge rate. One cell type per 50Ah, 70Ah, 100Ah and 125Ah plate has been
selected. Regarding the 50Ah plate, the tests have been separated into two categories:
2V cells
Monoblock batteries
The reason for this categorization is the difference of the separator for these two types (the
plate remains the same but the monoblock batteries are using thinner separator comparing to
the 2V cells).
Each cell type was tested at the following rates (the following rates are according to IEC60896-
21):
Rate C0,25 C1 C3 C8 C10 C20 C48 C120
Temperature (o C) 20 20 20 20 20 20 20 20
Final Voltage (V/cell) 1,6 1,6 1,7 1,75 1,8 1,8 1,8 1,85
The most common applications for the Sunlight OPzV batteries are:
Deviation according to IEC: cells have been submitted initially to two C10 discharges (IEC
mentions that the cells shall not have been previously submitted to any discharges). In any
case, the results from the two initial discharges were successful with the actual capacity to be
≥95% of the rated capacity.
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5Page 4 by 53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
5 OPzV 250
Rate C0,25 C1 C3 C8 C10 C20 C48 C120
Current (A) 371,0 174,6 76,6 34,8 28,0 15,73 7,33 3,02
Final Voltage (V) 1,6 1,6 1,7 1,75 1,8 1,8 1,8 1,85
Test Temperature (o C) 20 20 21 22 23 24 25 26
Nominal Capacity (Ah) 92,8 174,6 229,9 278,4 280,0 314,7 352,0 362,7
Measured Capacity (Ah) 126,67 180,97 250,05 287,87 290,05 329,72 359,69 366,42
Nominal Capacity (50 Ah Plate) 18,6 34,9 46,0 55,7 56,0 62,9 70,4 72,5
Measured Capacity (50 Ah Plate) 25,33 36,19 50,01 57,57 58,01 65,94 71,94 73,28
Result (%) 136,6% 103,7% 108,8% 103,4% 103,6% 104,8% 102,2% 101,0%
Summary of test results: Tests were successful. In all the rates the following was
applied Ca ≥ 95 % Crt
1,85
1,80
Voltage (V/cell)
1,75
1,70
136,6%
1,65
1,60
100%
1,55
0 5 10 15 20 25
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5Page 5 by 53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
1,95
1,90
1,85
Voltage (V/cell)
1,80
1,75
1,70
103,7%
1,65
1,60
100%
1,55
0 10 20 30 40 50 60 70
Time (min)
2,00
1,95
1,90
Voltage (V/cell)
1,85
1,80
108,8%
1,75
1,70
100%
1,65
0 15 30 45 60 75 90 105 120 135 150 165 180 195 210
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5Page 6 by 53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2,05
2,00
1,95
Voltage (V/cell)
1,90
1,85
103,4%
1,80
1,75
100%
1,70
0 60 120 180 240 300 360 420 480 540
Time (min)
2,05
2,00
Voltage (V/cell)
1,95
1,90
103,6%
1,85
1,80
100%
1,75
0 60 120 180 240 300 360 420 480 540 600 660
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5Page 7 by 53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2,05
2,00
Voltage (V/cell)
1,95
1,90
104,8%
1,85
1,80
100%
1,75
0 120 240 360 480 600 720 840 960 1080 1200 1320
Time (min)
2,10
2,05
2,00
Voltage (V/cell)
1,95
1,90
102,2%
1,85
1,80
100%
1,75
0 240 480 720 960 1200 1440 1680 1920 2160 2400 2640 2880 3120
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5Page 8 by 53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2,10
2,05
Voltage (V/cell)
2,00
1,95
101%
1,90
1,85
100%
1,80
0 720 1440 2160 2880 3600 4320 5040 5760 6480 7200 7920
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5Page 9 by 53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
6V - 6 OPzV 300
Rate C0,25 C1 C3 C8 C10 C20 C48 C120
Current (A) 402,7 200,7 87,3 38,8 30,9 17,1 7,85 3,18
Final Voltage (V) 4,8 4,8 5,1 5,25 5,4 5,4 5,4 5,55
Test Temperature (o C) 20 20 21 22 23 24 25 26
Nominal Capacity (Ah) 100,7 200,7 261,8 310,6 309,0 342,5 376,7 381,3
Measured Capacity (Ah) 146,60 217,37 282,66 321,00 326,99 359,55 390,17 389,83
Nominal Capacity (50 Ah Plate) 16,8 33,4 43,6 51,8 51,5 57,1 62,8 63,5
Measured Capacity (50 Ah Plate) 24,43 36,23 47,11 53,50 54,50 59,93 65,03 64,97
Result (%) 145,6% 108,3% 108,0% 103,4% 105,8% 105,0% 103,6% 102,2%
Summary of test results: Tests were successful. In all the rates the following was
applied Ca ≥ 95 % Crt
5,40
5,25
Voltage (V/cell)
5,10
145,6%
4,95
4,80
100%
4,65
0 5 10 15 20 25
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 10 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
5,70
5,55
5,40
Voltage (V/cell)
5,25
5,10
108,3%
4,95
4,80
100%
4,65
0 10 20 30 40 50 60 70
Time (min)
6,15
6,00
5,85
Voltage (V/cell)
5,70
5,55
5,40
108%
5,25
5,10
100%
4,95
0 15 30 45 60 75 90 105 120 135 150 165 180 195
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 11 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
6,15
6,00
5,85
Voltage (V/cell)
5,70
5,55
103,4%
5,40
5,25
100%
5,10
0 60 120 180 240 300 360 420 480 540
Time (min)
6,15
6,00
Voltage (V/cell)
5,85
5,70
105,8%
5,55
5,40
100%
5,25
0 60 120 180 240 300 360 420 480 540 600 660
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 12 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
6,15
6,00
Voltage (V/cell)
5,85
5,70
105%
5,55
5,40
100%
5,25
0 120 240 360 480 600 720 840 960 1080 1200 1320
Time (min)
6,30
6,15
6,00
Voltage (V/cell)
5,85
5,70
103,6%
5,55
5,40
100%
5,25
0 240 480 720 960 1200 1440 1680 1920 2160 2400 2640 2880 3120
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 13 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
6,30
6,15
Voltage (V/cell)
6,00
5,85
102,2%
5,70
5,55
100%
5,40
0 720 1440 2160 2880 3600 4320 5040 5760 6480 7200 7920
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 14 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
Summary of test results: Tests were successful. In all the rates the following was
applied Ca ≥ 95 % Crt
10,80
10,50
Voltage (V/cell)
10,20
109,5%
9,90
9,60
100%
9,30
0 5 10 15 20
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 15 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
11,70
11,40
11,10
Voltage (V/cell)
10,80
10,50
10,20
101,5%
9,90
9,60
100%
9,30
0 10 20 30 40 50 60 70
Time (min)
12,00
11,70
11,40
Voltage (V/cell)
11,10
10,80
109,6%
10,50
10,20
100%
9,90
0 15 30 45 60 75 90 105 120 135 150 165 180 195 210
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 16 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
12,30
12,00
11,70
Voltage (V/cell)
11,40
11,10
102,9%
10,80
10,50
100%
10,20
0 60 120 180 240 300 360 420 480 540
Time (min)
12,30
12,00
Voltage (V/cell)
11,70
11,40
106,6%
11,10
10,80
100%
10,50
0 60 120 180 240 300 360 420 480 540 600 660
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 17 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
12,30
12,00
Voltage (V/cell)
11,70
11,40
106,8%
11,10
10,80
100%
10,50
0 120 240 360 480 600 720 840 960 1080 1200 1320
Time (min)
12,60
12,30
12,00
Voltage (V/cell)
11,70
11,40
102,5%
11,10
10,80
100%
10,50
0 240 480 720 960 1200 1440 1680 1920 2160 2400 2640 2880 3120
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 18 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
12,60
12,30
Voltage (V/cell)
12,00
11,70
103%
11,40
11,10
100%
10,80
0 720 1440 2160 2880 3600 4320 5040 5760 6480 7200 7920
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 19 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2V - 6 OPzV 420
Rate C0,25 C1 C3 C8 C10 C20 C48 C120
Current (A) 567 300,5 132,7 60,7 48,6 27,5 12,95 5,37
Final Voltage (V) 1,6 1,6 1,7 1,75 1,8 1,8 1,8 1,85
Test Temperature (o C) 20 20 21 22 23 24 25 26
Nominal Capacity (Ah) 141,7 300,5 398,1 485,7 486,0 550,8 621,7 643,8
Measured Capacity (Ah) 221,17 313,09 410,12 500,79 497,40 560,67 631,25 656,16
Nominal Capacity (70 Ah Plate) 23,6 50,1 66,3 80,9 81,0 91,8 103,6 107,3
Measured Capacity (70 Ah Plate) 36,86 52,18 68,35 83,46 82,90 93,45 105,21 109,36
Result (%) 156,1% 104,2% 103,0% 103,1% 102,3% 101,8% 101,5% 101,9%
Summary of test results: Tests were successful. In all the rates the following was
applied Ca ≥ 95 % Crt
The measurement curves are shown below:
1,80
1,75
Voltage (V/cell)
1,70
156,1%
1,65
1,60
100%
1,55
0 5 10 15 20 25
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 20 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
1,90
1,85
1,80
Voltage (V/cell)
1,75
1,70
104,2%
1,65
1,60
100%
1,55
0 10 20 30 40 50 60 70
Time (min)
2,00
1,95
1,90
Voltage (V/cell)
1,85
1,80
103%
1,75
1,70
100%
1,65
0 15 30 45 60 75 90 105 120 135 150 165 180 195
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 21 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2,05
2,00
1,95
Voltage (V/cell)
1,90
1,85
103,1%
1,80
1,75
100%
1,70
0 60 120 180 240 300 360 420 480 540
Time (min)
2,05
2,00
Voltage (V/cell)
1,95
1,90
102,3%
1,85
1,80
100%
1,75
0 60 120 180 240 300 360 420 480 540 600 660
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 22 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2,05
2,00
Voltage (V/cell)
1,95
1,90
101,8%
1,85
1,80
100%
1,75
0 120 240 360 480 600 720 840 960 1080 1200 1320
Time (min)
2,10
2,05
2,00
Voltage (V/cell)
1,95
1,90
101,5%
1,85
1,80
100%
1,75
0 240 480 720 960 1200 1440 1680 1920 2160 2400 2640 2880 3120
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 23 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2,10
2,05
Voltage (V/cell)
2,00
1,95
101,9%
1,90
1,85
100%
1,80
0 720 1440 2160 2880 3600 4320 5040 5760 6480 7200 7920
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 24 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2V - 6 OPzV 600
Rate C0,25 C1 C3 C8 C10 C20 C48 C120
Current (A) 682,0 416,8 188,8 86,6 69,0 39,3 18,6 7,81
Final Voltage (V) 1,6 1,6 1,7 1,75 1,8 1,8 1,8 1,85
Test Temperature (o C) 20 20 21 22 23 24 25 26
Nominal Capacity (Ah) 170,5 416,8 566,4 693,1 690,0 785,1 892,3 937,4
Measured Capacity (Ah) 255,5 461,1 589,8 707,2 707,4 800,1 915,1 950,7
Nominal Capacity (100 Ah Plate) 28,4 69,5 94,4 115,5 115,0 130,9 148,7 156,2
Measured Capacity (100 Ah Plate) 42,58 76,86 98,30 117,86 117,90 133,34 152,52 158,46
Result (%) 149,8% 110,6% 104,1% 102,0% 102,5% 101,9% 102,6% 101,4%
Summary of test results: Tests were successful. In all the rates the following was
applied Ca ≥ 95 % Crt
The measurement curves are shown below:
1,80
1,75
Voltage (V/cell)
1,70
149,8%
1,65
1,60
100%
1,55
0 5 10 15 20 25
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 25 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
1,85
1,80
Voltage (V/cell)
1,75
1,70
110,6%
1,65
1,60
100%
1,55
0 10 20 30 40 50 60 70
Time (min)
2,00
1,95
1,90
Voltage (V/cell)
1,85
1,80
104,1%
1,75
1,70
100%
1,65
0 15 30 45 60 75 90 105 120 135 150 165 180 195
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 26 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2,05
2,00
1,95
Voltage (V/cell)
1,90
1,85
102%
1,80
1,75
100%
1,70
0 60 120 180 240 300 360 420 480 540
Time (min)
2,05
2,00
Voltage (V/cell)
1,95
1,90
102,5%
1,85
1,80
100%
1,75
0 60 120 180 240 300 360 420 480 540 600 660
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 27 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2,05
2,00
Voltage (V/cell)
1,95
1,90
101,9%
1,85
1,80
100%
1,75
0 120 240 360 480 600 720 840 960 1080 1200 1320
Time (min)
2,10
2,05
2,00
Voltage (V/cell)
1,95
1,90
102,6%
1,85
1,80
100%
1,75
0 240 480 720 960 1200 1440 1680 1920 2160 2400 2640 2880 3120
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 28 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2,10
2,05
Voltage (V/cell)
2,00
1,95
101,4%
1,90
1,85
100%
1,80
0 720 1440 2160 2880 3600 4320 5040 5760 6480 7200 7920
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 29 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2V - 24 OPzV 3000
Rate C0,25 C1 C3 C8 C10 C20 C48 C120
Current (A) 3171 1967 892 407,5 324 183 85,5 35,40
Final Voltage (V) 1,6 1,6 1,7 1,75 1,8 1,8 1,8 1,85
Test Temperature (o C) 20 20 21 22 23 24 25 26
Nominal Capacity (Ah) 792,6 1967,4 2675,3 3259,7 3240,0 3659,5 4106,2 4248,0
Measured Capacity (Ah) 1025,7 2131,6 2865,6 3349,8 3325,1 3734,2 4245,2 4335,0
Nominal Capacity (125 Ah Plate) 33,0 82,0 111,5 135,8 135,0 152,5 171,1 177,0
Measured Capacity (125 Ah Plate) 42,74 88,82 119,40 139,57 138,55 155,59 176,88 180,62
Result (%) 129,4% 108,3% 107,1% 102,8% 102,6% 102,0% 103,4% 102,0%
Summary of test results: Tests were successful. In all the rates the following was
applied Ca ≥ 95 % Crt
The measurement curves are shown below:
1,80
1,75
Voltage (V/cell)
1,70
129,4%
1,65
1,60
100%
1,55
0 5 10 15 20
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 30 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
1,85
1,80
Voltage (V/cell)
1,75
1,70
108,3%
1,65
1,60
100%
1,55
0 10 20 30 40 50 60 70
Time (min)
1,95
1,90
Voltage (V/cell)
1,85
1,80
107,1%
1,75
1,70
100%
1,65
0 15 30 45 60 75 90 105 120 135 150 165 180 195
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 31 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2,05
2,00
1,95
Voltage (V/cell)
1,90
1,85
102,8%
1,80
1,75
100%
1,70
0 60 120 180 240 300 360 420 480 540
Time (min)
2,05
2,00
Voltage (V/cell)
1,95
1,90
102,6%
1,85
1,80
100%
1,75
0 60 120 180 240 300 360 420 480 540 600 660
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 32 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2,05
2,00
Voltage (V/cell)
1,95
1,90
102%
1,85
1,80
100%
1,75
0 120 240 360 480 600 720 840 960 1080 1200 1320
Time (min)
2,05
2,00
Voltage (V/cell)
1,95
1,90
103,4%
1,85
1,80
100%
1,75
0 240 480 720 960 1200 1440 1680 1920 2160 2400 2640 2880 3120
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 33 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
2,10
2,05
Voltage (V/cell)
2,00
1,95
102%
1,90
1,85
100%
1,80
0 720 1440 2160 2880 3600 4320 5040 5760 6480 7200 7920
Time (min)
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 34 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 35 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
Deviation according to IEC: Test was accomplished by using 2.500A for 1min (instead of
1349.7A for 30sec). The purpose of this test is to certify the durability of the pole – connector at
the specific high current. After the high current discharge, the examination of the cells shows no
defects and signs of melting and the voltage measurements are shown on the table below:
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 36 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
4 Recharge Behaviour
The purpose of this requirement is to define the capacity once more available following a long
duration discharge with both short (24 h) and long (168 h) periods of recharge under float
voltage settings. The result of this test documents the effective available capacity, as a percent
of the original capacity after a recharge for 24 h or 168 h using only the recommended float
voltage.
2V - 6 OPzV 420
Rate C10 Rate C10
Current (A) 48 Current (A) 48
Final Voltage (V) 1,8 Final Voltage (V) 1,8
Test Temperature (oC) 20 Test Temperature (oC) 20
Nominal Capacity (Ah) 480 Nominal Capacity (Ah) 480
Measured Capacity (Ah) 523,6 Measured Capacity (Ah) 524,4
Rbf24h 515,3 Rbf168h 520,6
Result 98,4% Result 99,3%
Table 12 – Capacity result after 24h and 168h recharge respectively
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 37 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 38 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
Test procedure: The units were stored at an ambient temperature of 22°C and fully
disconnected from any external circuit. After 180 days of storage the units
were discharged without any prior recharge. Their actual capacity after
storage Cast was determined. The charge retention factor Crf is expressed
as percentage, and is equal to Crf = (Cast × 100) / Ca (%)
2V - 5OPzV250
st
Cell 1 C3 C3 after 180 days at 22o C Crf
Cell 1 107,0% 99,8% 93,3%
Cell 2 107,0% 99,5% 93,0%
Cell 3 107,0% 99,5% 93,0%
Cell 4 108,0% 100,0% 92,6%
Cell 5 107,0% 97,6% 91,2%
Cell 6 107,5% 99,7% 92,7%
2V - 24OPzV3000
st o
Cell 1 C3 C3 after 90 days at 40 C Crf
Cell 1 105,0% 98,5% 93,8%
Cell 2 104,0% 97,3% 93,6%
Table 13 – Capacity result after 180 days at 22oC and 90 days at 40oC
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 39 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
7 Gas Emission
The purpose of this requirement is the determination of gas emission volumes under normal
float (rated float voltage) and overcharge voltage (2.40Vpc) conditions.
Instruction: IEC 60896-21, chapter 6.1
Test items: 6pcs 2V – 24 OPzV 3000
Test Procedure: The cells are fully charged and then float charged for 72h at 2.25Vpc
(report the voltage after 72h at float charge). After the 72h of float
charge, the gas collection process begins and continues for four periods of
168h duration. The cumulative total gas volume collected over the four
periods of time is recorded with the ambient temperature and ambient
pressure at which the each determination of gas volume is made. Then,
the test samples are charged at 2.40Vpc for 24h duration. After the 24h
duration, the gas collection process begins and lasts 48h or till 1000ml of
gas is collected.
The results are shown on the following table (data from table 17):
2V - 24OPzV3000
The cell voltages after 72h of floating charge are the following:
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 40 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
By following the procedure, the following tables present the gas emission (temperature and
ambient pressure were standardized to the below values) at the four 168h periods of time
during float charging (2.25Vpc):
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 41 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
After a 24h charging at 2.40Vpc, the gas emission procedure begins and lasts 48h. The results
are presented on the following table:
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 42 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
8 Material Identification
The purpose of this requirement is to enhance the recycling of material
for environmental protection by ensuring that the plastic materials used for the units are
clearly identified with the ISO 1043-1 material symbol and legible throughout the service life.
Instruction: IEC 60896-21, chapter 6.7
Test items: one cell case
Specification: ISO symbol to be present
Test Result: Pass (ISO symbol present on the outside of the cover or case)
9 Valve Operation
The purpose of this requirement is to ensure that each valve on the unit is opening and
releasing gas before and after the high temperature (55 °C or 60 °C).
Instruction: IEC 60896-21, chapter 6.8
Test items: 6 valves
Test Procedure: The cells are fully charged and then float charged for 72h at 2.25Vpc
Test Result: Pass
Opening Closing
Valve Pressure (mbar) Pressure (mbar)
Valve 1 150 130
Valve 2 145 120
Valve 3 150 125
Valve 4 145 120
Valve 5 150 130
Valve 6 150 125
Table 18 – Valve release and reseal pressure
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 43 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 44 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
Test procedure: The test was performed under the following profile:
a. Capacity test at 10h DIN rate (I10 = 42A – 1.80V/c) every 100 cycles.
b. Discharge cycling settings: discharge with 2.0 x I10 for 3 hours. This
current corresponds to ~4h discharge DIN rate. The 3h discharge out
of 4h nominal yields 75% DoD for each cycle
c. Recharge per cycle: with Imax=2*I10 and Umax = 2.40 V/c for 21h
d. Average temperature: 25oC
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 45 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
140%
Cycling test acc to IEC 896-2 (ch5.3): 6 cells 6OPzV420
120% Capacity evolution through cycles
Capacity (% to the DIN nominal)
100%
80%
60%
40%
20%
0%
0 200 400 600 800 1000 1200 1400 1600 1800
Number of cycles
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 46 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
The determination of the expected service life is extrapolated from results of the accelerated
test at 60oC (see paragraph 1.12, figure 50) and equals to 29.3 years at 20oC and 5.7 years at
40oC.
Remark: The test at 40oC is still running.
14 Abusive over-discharge
The purpose of the requirement is to ensure that units, undergoing abusive over-discharges
during the service life, show a minimum of capacity recovery under specified conditions.
Instruction: IEC 60896-21, chapter 6.17
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 47 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
Test procedure: Unbalanced over-discharge (Caod): four units were tested. One unit was
discharged at 20oC with I10 for 3h and then it was connected to the rest
three units. Afterwards, the string was subjected to a discharge with I10 at
20oC (Vfinal 1.80 Vpc) until the voltage of the three, initially fully charged
units reach a total voltage of Ufinal of 3 × n × 1.70 Vpc where n is the
number of cells in this substring. After the discharge and a 24 h stand in
the discharged state, the four unit string was recharged in series for 168 h
with a current limited to I = 2,0xI10 and a voltage limited to the float
voltage specified by the manufacturer for 20 °C. At the end of the 168 h of
charge, the four units were subjected to a capacity test with a constant
current of I = I3 to a Ufinal of 4 × n × 1,70 Vpc and the capacity Ca
corrected to 20 °C.
Cyclic over-discharge test (Caoc): three units were tested. Units were
discharged with I10 at 20oC till they reach 1.25Vpc. After the discharge,
units stand in the discharge state for 1h and afterwards were recharged
with at float voltage with 2*I10 for 168h. This procedure was repeated 5
times. At the end of the firth period, cells were subjected to a C3 test.
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 48 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
60 60
24OPzV3000 - Thermal Runaway Test at 2,45 V/c Temp 1m away
Temp in the gap
50 50
Temp case
o
Cell case temperature after 168 hours: 31,6 C Float Current
40 40
Temperature (oC)
Curren t(A)
30 30
20 20
10 10
0 0
0 20 40 60 80 100 120 140 160 180
time at float (h)
70 70
24OPzV3000 - Thermal Runaway Test at 2,60 V/c
60 60
Case temperature after 168 hours : 57,5 oC
50 50
Temperature (oC)
Current (A)
40 40
30 30
20 20
10 10
0 20 40 60 80 100 120 140 160 180
time at float (h) Temp 1m away Temp in the gap
Temp case surface Float Current
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 49 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 50 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
Test Procedure: The test unit was adapted with a pressure regulator to maintain a pressure
in all interior cavities equal to the maximum valve opening pressure
(110mbar) present in units and as specified by the manufacturer. This
specified pressure was maintained throughout the test. The pressurized
unit was then placed into a chamber with recirculating air at a temperature
of 50 °C. After 24 h of residence in the test chamber and under pressure,
the maximum outside dimension (width and length) of the cell case
difference was recorded in mm.
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 51 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
leakages caused by two drops each onto a smooth, level concrete floor
from drop height 100 mm. This test proceeded as shown below:
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 52 by
53
OPzV Type Test Report
Acc. to IEC 60896-21 & 22
Test Procedure: Test with water and aliphatic solvent: a) A label or marking was rubbed for
15 s with a piece of cloth soaked with water and again for 15 s with a
piece of cloth soaked with petroleum spirit, dried in air and then inspected
visually.
b) The petroleum spirit used for this test was n-hexane with an initial
boiling point of 65 °C, a dry point of approximately 69 °C, a density of 0,7
kg/l and a maximum aromatic hydrocarbon content of 0,1 % per volume.
Test with neutralizing solutions: A new label was rubbed for 15 s with a
piece of cloth soaked with a saturated solution of sodium carbonate
(Na2CO3) in water, dried in air and then inspected visually.
Report: OPzV Type Test Report Issue date: Error! Reference source not found.5 Page 53 by
53