Professional Documents
Culture Documents
ORION controller
Our InD, OutD and HelpD series are designed to complement each
other. InD stands for indoor power systems, while OutD solutions
are created for demanding outdoor use. HelpD is our global support
team; its task is to make everything easy for you.
3791363100_00
www.deltapowersolutions.com Smarter. Greener. Together.
Table of contents
1 UIM – User Interface Module / UIL – User Interface Local ................................ 2
1.1 UIM / UIL keys .......................................................................................... 2
1.2 Default password ..................................................................................... 3
2 General ............................................................................................................... 4
3 Implementation setup ......................................................................................... 5
3.1 Defining event thresholds ......................................................................... 5
3.2 Defining event delays ............................................................................... 5
3.3 Defining battery functions ......................................................................... 6
3.4 Defining rectifier functions ........................................................................ 7
• activate functions
• change parameters
• confirm changes
• move the control one level down on the menu tree
• exit a menu
• break an input
• move the control one level up on the menu tree
• silence an active buzzer for 30 minutes (UIM only)
UIL
2 ORION controller UIM – User Interface Module / UIL – User Interface Local
Press the arrow buttons to:
ORION controller UIM – User Interface Module / UIL – User Interface Local 3
2 General
ORION controller is preconfigured at the Delta Energy Systems factory according to the
system configuration. The following step-by-step instructions show how to modify the
basic configuration from the beginning with UIM/UIL. The configuration order is the
following:
From the 6.6.1 Thresholds menu select the menu that you want to modify.
From Psys high menu select Up Thresh. Define the value (n + x number of rectifiers).
From the LVD [U] menu select Low Thres. Define the LVD open value.
From the PLD1 [U] and / or PLD2 [U] menu select Low Thres. Define the PLDx open
value. Set the hysteresis value so that PLDx will not be closed below 50V.
PLD2 [U]
From the PLD1 [t] and / or PLD2 [t] menu select True for. Define the PLDx open delay
time.
From the MF delay menu select True for. Define the Mains failure alarm delay time.
From the 6.5.1 Float menu select Usys @ 20 °C. Define the value (Float charge level).
From the 6.5.2 Temp Comp menu select Tcoeff. Define the value (Temperature
compensation coefficient).
From the 6.5.2 Temp Comp menu select Start T. Define the value (Temperature
compensation low level).
From the 6.5.2 Temp Comp menu select Stop T. Define the value (Temperature
compensation high level).
From the 6.5.2 Temp Comp menu select Max V. Define the value (Highest compensation
voltage level).
Start T: 0 ºC
Stop T: 45 ºC
Max V: 57.5V
From the 6.5.3 Usys Supervi menu select Ua max (max. voltage of system).
From the 6.5.3 Usys Supervi menu select Ua min (min. voltage of system).
From the 6.5.3 Usys Supervi menu select Us max (+ 1 % of float charge).
From the 6.5.3 Usys Supervi menu select Us min (- 1 % of float charge).
From the 6.5.3 Usys Supervi menu select BoD (Battery on Discharge alarm threshold).
Ua min: 46.00V
Us max: 54.10V
Us min: 52.90V
BoD: 48.00V
Hysteresis: 0.10V
From the 6.5.7 Battery Test menu select Duration (battery test duration).
Duration: 60min
From the 6.5.9 Middle Point menu select Ud chrg (difference with recharge or charge
mode).
From the 6.5.9 Middle Point menu select Ud dichrg (difference with discharge mode).
Ud dichrg: 0.50V
From the 6.2.2 Setup menu select 1. RM NUMBER (define correct number of rectifiers).
5010767800_01
*5010767800*