You are on page 1of 13

Air System Sizing Summary for MULTIPURPOSE HALL

Project Name: Tugasan Pertama Perdana Hall 12/21/2020


Prepared by: MALAYSIA FRANCE INSTITUTE 12:43PM

Air System Information


Air System Name ................. MULTIPURPOSE HALL Number of zones .......................................................... 1
Equipment Class .......................................... CW AHU Floor Area ................................................................ 46.5 m²
Air System Type .............................................. SZCAV Location .................................. Kuala Lumpur, Malaysia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s ......................... Sum of space airflow rates Calculation Months ....................................... Jan to Dec
Space L/s ..................... Individual peak space loads Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ....................................................... 27.0 kW Load occurs at ................................................ Aug 1500
Sensible coil load ................................................. 22.6 kW OA DB / WB ................................................... 34.4 / 25.6 °C
Coil L/s at Aug 1500 ............................................ 1906 L/s Entering DB / WB ........................................... 25.3 / 18.9 °C
Max block L/s ...................................................... 1906 L/s Leaving DB / WB ........................................... 15.4 / 14.8 °C
Sum of peak zone L/s .......................................... 1906 L/s Coil ADP .................................................................. 14.3 °C
Sensible heat ratio .............................................. 0.837 Bypass Factor ........................................................ 0.100
m²/kW ..................................................................... 1.7 Resulting RH .............................................................. 55 %
W/m² .................................................................. 580.2 Design supply temp. ................................................ 14.4 °C
Water flow @ 5.6 °K rise ...................................... 1.16 L/s Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0.0 °K

Central Heating Coil Sizing Data


No central heating coil loads occurred during this calculation.

Supply Fan Sizing Data

Actual max L/s ..................................................... 1906 L/s Fan motor BHP ........................................................ 0.00 BHP
Standard L/s ........................................................ 1901 L/s Fan motor kW .......................................................... 0.00 kW
Actual max L/(s-m²) ............................................ 41.02 L/(s-m²) Fan static ...................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s .................................................. 139 L/s L/s/person ................................................................ 2.78 L/s/person
L/(s-m²) ................................................................ 2.99 L/(s-m²)
Zone Sizing Summary for MULTIPURPOSE HALL
Project Name: Tugasan Pertama Perdana Hall 12/21/2020
Prepared by: MALAYSIA FRANCE INSTITUTE 12:27PM

Air System Information


Air System Name ................. MULTIPURPOSE HALL Number of zones ........................................................... 1
Equipment Class .......................................... CW AHU Floor Area ................................................................ 46.5 m²
Air System Type .............................................. SZCAV Location .................................. Kuala Lumpur, Malaysia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates Calculation Months ....................................... Jan to Dec
Space L/s ..................... Individual peak space loads Sizing Data ................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 21.7 1906 1906 Aug 1500 0.0 46.5 41.02

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
MULTIPORPUSE HALL 1 21.7 Aug 1500 1906 0.0 46.5 41.02
Ventilation Sizing Summary for MULTIPURPOSE HALL
Project Name: Tugasan Pertama Perdana Hall
Prepared by: MALAYSIA FRANCE INSTITUTE

1. Summary
Ventilation Sizing Method .................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................. 139 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Require
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor A
Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of suppl
Zone 1
MULTIPORPUSE HALL 1 46.5 50.0 1905.5 2.50 0.30 0.0 0
Totals (incl. Space Multipliers) 1905.5
Air System Design Load Summary for MULTIPURPOSE HALL
Project Name: Tugasan Pertama Perdana Hall 12/21/2020
Prepared by: MALAYSIA FRANCE INSTITUTE 12:27PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.4 °C / 25.6 °C HEATING OA DB / WB 21.7 °C / 15.2 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 626 m² 17549 - 626 m² 0 -
Roof Transmission 47 m² 1368 - 47 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 14 m² 213 - 14 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 325 W 242 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 50 2297 1760 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 21669 1760 - 0 0
Zone Conditioning - 20902 1760 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1906 L/s 0 - 1906 L/s 0 -
Ventilation Load 139 L/s 1659 2629 139 L/s -93 0
Supply Fan Load 1906 L/s 0 - 1906 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 22561 4389 - -93 0
Central Cooling Coil - 22561 4391 - 0 0
Central Heating Coil - 0 - - 0 -
>> Total Conditioning - 22561 4391 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads
Zone Design Load Summary for MULTIPURPOSE HALL
Project Name: Tugasan Pertama Perdana Hall 12/21/2020
Prepared by: MALAYSIA FRANCE INSTITUTE 12:27PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.4 °C / 25.6 °C HEATING OA DB / WB 21.7 °C / 15.2 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 626 m² 17549 - 626 m² 0 -
Roof Transmission 47 m² 1368 - 47 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 14 m² 213 - 14 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 325 W 242 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 50 2297 1760 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 21669 1760 - 0 0
Space Design Load Summary for MULTIPURPOSE HALL
Project Name: Tugasan Pertama Perdana Hall 12/21/2020
Prepared by: MALAYSIA FRANCE INSTITUTE 12:27PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' MULTIPORPUSE HALL '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.4 °C / 25.6 °C HEATING OA DB / WB 21.7 °C / 15.2 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 626 m² 17549 - 626 m² 0 -
Roof Transmission 47 m² 1368 - 47 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 14 m² 213 - 14 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 325 W 242 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 50 2297 1760 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 21669 1760 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' MULTIPORPUSE HALL '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 626 1.409 - 17549 - 0
DOOR 14 1.703 - 213 - 0
E EXPOSURE
ROOF 47 0.685 - 1368 - 0
Hourly Air System Design Day Loads for MULTIPURPOSE HALL
Project Name: Tugasan Pertama Perdana Hall 12/21/2020
Prepared by: MALAYSIA FRANCE INSTITUTE 12:27PM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.1 1906 13.0 14.7 0.0 0.0 0.0 0.0 0.0 0.0
0100 26.6 1906 11.6 12.9 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.2 1906 10.5 11.6 0.0 0.0 0.0 0.0 0.0 0.0
0300 25.8 1906 9.9 11.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.5 1906 9.1 10.1 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.4 1906 8.2 9.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.6 1906 7.9 8.7 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.1 1906 7.4 8.1 0.0 0.0 0.0 0.0 0.0 0.0
0800 26.9 1906 7.1 7.6 0.0 0.0 0.0 0.0 0.0 0.0
0900 28.1 1906 9.0 11.5 0.0 0.0 0.0 0.0 0.0 0.0
1000 29.4 1906 10.7 13.4 0.0 0.0 0.0 0.0 0.0 0.0
1100 30.9 1906 13.5 16.7 0.0 0.0 0.0 0.0 0.0 0.0
1200 32.4 1906 16.2 19.7 0.0 0.0 0.0 0.0 0.0 0.0
1300 33.5 1906 19.2 23.1 0.0 0.0 0.0 0.0 0.0 0.0
1400 34.2 1906 21.1 25.3 0.0 0.0 0.0 0.0 0.0 0.0
1500 34.4 1906 21.2 25.4 0.0 0.0 0.0 0.0 0.0 0.0
1600 34.2 1906 20.3 22.8 0.0 0.0 0.0 0.0 0.0 0.0
1700 33.5 1906 19.7 22.2 0.0 0.0 0.0 0.0 0.0 0.0
1800 32.6 1906 18.7 20.9 0.0 0.0 0.0 0.0 0.0 0.0
1900 31.4 1906 17.6 19.7 0.0 0.0 0.0 0.0 0.0 0.0
2000 30.2 1906 17.3 19.5 0.0 0.0 0.0 0.0 0.0 0.0
2100 29.2 1906 16.1 18.1 0.0 0.0 0.0 0.0 0.0 0.0
2200 28.3 1906 15.1 17.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 27.6 1906 13.9 15.6 0.0 0.0 0.0 0.0 0.0 0.0
Hourly Zone Loads for MULTIPURPOSE HALL
Project Name: Tugasan Pertama Perdana Hall 12/21/2020
Prepared by: MALAYSIA FRANCE INSTITUTE 12:27PM

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.1 24.2 69 1905.5 12731.1 12563.6 0.0 0.0 0.0
0100 26.6 24.4 72 1905.5 11747.5 11229.2 0.0 0.0 0.0
0200 26.2 24.5 74 1905.5 10817.8 10169.4 0.0 0.0 0.0
0300 25.8 24.2 75 1905.5 9950.6 9662.9 0.0 0.0 0.0
0400 25.5 24.2 77 1905.5 9147.0 8901.5 0.0 0.0 0.0
0500 25.4 24.3 79 1905.5 8407.7 7993.2 0.0 0.0 0.0
0600 25.6 24.1 80 1905.5 7736.1 7671.7 0.0 0.0 0.0
0700 26.1 24.1 81 1905.5 7142.8 7089.1 0.0 0.0 0.0
0800 26.9 24.1 82 1905.5 6803.8 6599.5 0.0 0.0 0.0
0900 28.1 24.2 80 1905.5 8663.6 8364.3 0.0 0.0 0.0
1000 29.4 24.2 77 1905.5 10177.4 9799.0 0.0 0.0 0.0
1100 30.9 24.3 71 1905.5 12809.4 12410.0 0.0 0.0 0.0
1200 32.4 24.6 66 1905.5 15803.9 14924.7 0.0 0.0 0.0
1300 33.5 24.5 61 1905.5 18408.5 17658.5 0.0 0.0 0.0
1400 34.2 24.5 58 1905.5 20143.5 19435.1 0.0 0.0 0.0
1500 34.4 24.8 57 1905.5 20894.9 19633.8 0.0 0.0 0.0
1600 34.2 24.4 57 1905.5 19296.8 18715.8 0.0 0.0 0.0
1700 33.5 24.5 58 1905.5 18850.5 18217.4 0.0 0.0 0.0
1800 32.6 24.6 60 1905.5 18209.0 17326.7 0.0 0.0 0.0
1900 31.4 24.7 61 1905.5 17490.3 16490.9 0.0 0.0 0.0
2000 30.2 24.3 61 1905.5 16716.6 16357.5 0.0 0.0 0.0
2100 29.2 24.4 63 1905.5 15813.8 15324.9 0.0 0.0 0.0
2200 28.3 24.3 65 1905.5 14800.8 14457.5 0.0 0.0 0.0
2300 27.6 24.3 67 1905.5 13757.2 13329.7 0.0 0.0 0.0
System Psychrometrics for MULTIPURPOSE HALL
Project Name: Tugasan Pertama Perdana Hall 12/21/2020
Prepared by: MALAYSIA FRANCE INSTITUTE 12:27PM

August DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 34.4 0.01705 139 400 1659 2629
Vent - Return Mixing Outlet 25.3 0.01108 1906 1634 - -
Central Cooling Coil Outlet 15.4 0.01030 1906 1634 22561 4391
Central Heating Coil Outlet 15.4 0.01030 1906 1634 0 -
Supply Fan Outlet 15.4 0.01030 1906 1634 0 -
Cold Supply Duct Outlet 15.4 0.01030 1906 1634 - -
Zone Air - 24.5 0.01061 1906 1731 20902 1760
Return Plenum Outlet 24.5 0.01061 1906 1731 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.9 W/(L/s)
Site Altitude = 21.9 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 21669 Cooling 20902 24.5 1906 1731 0 0

WINTER DESIGN HEATING


TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 21.7 0.00810 139 400 93 0
Vent - Return Mixing Outlet 21.2 0.00810 1906 519 - -
Central Cooling Coil Outlet 21.1 0.00810 1906 519 0 0
Central Heating Coil Outlet 21.1 0.00810 1906 519 0 -
Supply Fan Outlet 21.1 0.00810 1906 519 0 -
Cold Supply Duct Outlet 21.1 0.00810 1906 519 - -
Zone Air - 21.1 0.00810 1906 528 0 0
Return Plenum Outlet 21.1 0.00810 1906 528 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.9 W/(L/s)
Site Altitude = 21.9 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 0 Deadband 0 21.1 1906 528 0 0
Hourly Air System Design Day Loads for MULTIPURPOSE HALL
Project Name: Tugasan Pertama Perdana Hall 12/21/2020
Prepared by: MALAYSIA FRANCE INSTITUTE 12:27PM

Data for July

Total Cooling Total Heating


25

20
Load ( kW )

15

10

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Hourly Zone Design Day Loads for MULTIPURPOSE HALL
Project Name: Tugasan Pertama Perdana Hall 12/21/2020
Prepared by: MALAYSIA FRANCE INSTITUTE 12:27PM

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning

20000
18000
16000
14000
12000
W

10000
8000
6000
4000
2000
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Location: Kuala Lumpur, Malaysia
Altitude: 21.9 m.
Data for: August DESIGN COOLING DAY, 1500
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0.018
5. Room Air

0.016

Specific Humidity ( kg/kg )


0.014

2 0.012
34 5
0.010

0.008

0.006

0.004

0.002

0.000
0 5 10 15 20 25 30 35
Temperature ( °C )