Zone L/s ......................... Sum of space airflow rates Calculation Months ....................................... Jan to Dec
Space L/s ..................... Individual peak space loads Sizing Data ................................................... Calculated
Total coil load ....................................................... 27.0 kW Load occurs at ................................................ Aug 1500
Sensible coil load ................................................. 22.6 kW OA DB / WB ................................................... 34.4 / 25.6 °C
Coil L/s at Aug 1500 ............................................ 1906 L/s Entering DB / WB ........................................... 25.3 / 18.9 °C
Max block L/s ...................................................... 1906 L/s Leaving DB / WB ........................................... 15.4 / 14.8 °C
Sum of peak zone L/s .......................................... 1906 L/s Coil ADP .................................................................. 14.3 °C
Sensible heat ratio .............................................. 0.837 Bypass Factor ........................................................ 0.100
m²/kW ..................................................................... 1.7 Resulting RH .............................................................. 55 %
W/m² .................................................................. 580.2 Design supply temp. ................................................ 14.4 °C
Water flow @ 5.6 °K rise ...................................... 1.16 L/s Zone T-stat Check ................................................. 1 of 1 OK
Max zone temperature deviation ................................ 0.0 °K
Actual max L/s ..................................................... 1906 L/s Fan motor BHP ........................................................ 0.00 BHP
Standard L/s ........................................................ 1901 L/s Fan motor kW .......................................................... 0.00 kW
Actual max L/(s-m²) ............................................ 41.02 L/(s-m²) Fan static ...................................................................... 0 Pa
1. Summary
Ventilation Sizing Method .................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate .................................................................. 139 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' MULTIPORPUSE HALL '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.4 °C / 25.6 °C HEATING OA DB / WB 21.7 °C / 15.2 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 626 m² 17549 - 626 m² 0 -
Roof Transmission 47 m² 1368 - 47 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 14 m² 213 - 14 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 325 W 242 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 50 2297 1760 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 21669 1760 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' MULTIPORPUSE HALL '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 626 1.409 - 17549 - 0
DOOR 14 1.703 - 213 - 0
E EXPOSURE
ROOF 47 0.685 - 1368 - 0
Hourly Air System Design Day Loads for MULTIPURPOSE HALL
Project Name: Tugasan Pertama Perdana Hall 12/21/2020
Prepared by: MALAYSIA FRANCE INSTITUTE 12:27PM
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 27.1 24.2 69 1905.5 12731.1 12563.6 0.0 0.0 0.0
0100 26.6 24.4 72 1905.5 11747.5 11229.2 0.0 0.0 0.0
0200 26.2 24.5 74 1905.5 10817.8 10169.4 0.0 0.0 0.0
0300 25.8 24.2 75 1905.5 9950.6 9662.9 0.0 0.0 0.0
0400 25.5 24.2 77 1905.5 9147.0 8901.5 0.0 0.0 0.0
0500 25.4 24.3 79 1905.5 8407.7 7993.2 0.0 0.0 0.0
0600 25.6 24.1 80 1905.5 7736.1 7671.7 0.0 0.0 0.0
0700 26.1 24.1 81 1905.5 7142.8 7089.1 0.0 0.0 0.0
0800 26.9 24.1 82 1905.5 6803.8 6599.5 0.0 0.0 0.0
0900 28.1 24.2 80 1905.5 8663.6 8364.3 0.0 0.0 0.0
1000 29.4 24.2 77 1905.5 10177.4 9799.0 0.0 0.0 0.0
1100 30.9 24.3 71 1905.5 12809.4 12410.0 0.0 0.0 0.0
1200 32.4 24.6 66 1905.5 15803.9 14924.7 0.0 0.0 0.0
1300 33.5 24.5 61 1905.5 18408.5 17658.5 0.0 0.0 0.0
1400 34.2 24.5 58 1905.5 20143.5 19435.1 0.0 0.0 0.0
1500 34.4 24.8 57 1905.5 20894.9 19633.8 0.0 0.0 0.0
1600 34.2 24.4 57 1905.5 19296.8 18715.8 0.0 0.0 0.0
1700 33.5 24.5 58 1905.5 18850.5 18217.4 0.0 0.0 0.0
1800 32.6 24.6 60 1905.5 18209.0 17326.7 0.0 0.0 0.0
1900 31.4 24.7 61 1905.5 17490.3 16490.9 0.0 0.0 0.0
2000 30.2 24.3 61 1905.5 16716.6 16357.5 0.0 0.0 0.0
2100 29.2 24.4 63 1905.5 15813.8 15324.9 0.0 0.0 0.0
2200 28.3 24.3 65 1905.5 14800.8 14457.5 0.0 0.0 0.0
2300 27.6 24.3 67 1905.5 13757.2 13329.7 0.0 0.0 0.0
System Psychrometrics for MULTIPURPOSE HALL
Project Name: Tugasan Pertama Perdana Hall 12/21/2020
Prepared by: MALAYSIA FRANCE INSTITUTE 12:27PM
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.9 W/(L/s)
Site Altitude = 21.9 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2939.9 W/(L/s)
Site Altitude = 21.9 m
20
Load ( kW )
15
10
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Hourly Zone Design Day Loads for MULTIPURPOSE HALL
Project Name: Tugasan Pertama Perdana Hall 12/21/2020
Prepared by: MALAYSIA FRANCE INSTITUTE 12:27PM
Zone: Zone 1
Data for July
20000
18000
16000
14000
12000
W
10000
8000
6000
4000
2000
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Location: Kuala Lumpur, Malaysia
Altitude: 21.9 m.
Data for: August DESIGN COOLING DAY, 1500
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0.018
5. Room Air
0.016
2 0.012
34 5
0.010
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )