Manual 37615B SPM-D2-10 - Synchronizing Unit

Reference Point
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡

Reference point

0
Figure 4-5: Reference point

Terminal Description Amax


Reference point: Neutral point of the three-phase system (3Ph4W) or
neutral terminal of the voltage transformer (Measuring reference
0 Sold.lug
point);
 with three-conductor systems (3Ph3W), do not connect

Power Supply
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
24 Vdc (+/-25 %)
Standard
0 Vdc

2
Power supply
24 Vdc

1
Figure 4-6: Power supply (24 Vdc)

Terminal Description Amax


Standard
1 +24 Vdc, 10 W 2.5 mm²
2 0 V reference potential 2.5 mm²

90 to 250 Vac / 120 to 375 Vdc


Wide-range power supply
25 +/L
27 PE Power supply
29 -/N

Figure 4-7: Power supply (90 to 250 Vac and 120 to 375 Vdc, N & XN Packages)

Terminal Description Amax


N & XN Packages - wide range power supply
25 90 to 250 Vac / 120 to 375 Vdc, max. 10 W 2.5 mm²
27 PE 2.5 mm²
29 0 Vac 2.5 mm²

Page 14/68 © Woodward