Professional Documents
Culture Documents
PCS-221G X Instruction Manual en Overseas General X R1.01 (En ZNKZ0041.0086.0002)
PCS-221G X Instruction Manual en Overseas General X R1.01 (En ZNKZ0041.0086.0002)
Merging Unit
Instruction Manual
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR Electric Co., Ltd. is dispatched separately from
manufactured goods and may not be received at the same time. Therefore this guide is provided
to ensure that printed information normally present on equipment is fully understood by the
recipient.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual and read relevant chapters carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
The information in this chapter of the equipment documentation is intended to ensure that
equipment is properly installed and handled in order to maintain it in a safe condition.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason only qualified personnel may work on or operate the equipment.
z Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
z Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
z Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
DANGER means that death, severe personal injury, or considerable equipment damage will
occur if safety precautions are disregarded.
WARNING means that death, severe personal, or considerable equipment damage could occur
if safety precautions are disregarded.
CAUTION means that light personal injury or equipment damage may occur if safety
precautions are disregarded. This particularly applies to damage to the device and to
resulting damage of the protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
z Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high
voltage generated is dangerous
z Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
z Earthing
z Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
z Ratings
Before applying AC voltage and current or the power supply to the equipment, check that they
conform to the equipment ratings.
Do not attach and remove printed circuit boards when the power supply to the equipment is
on, as this may cause the equipment to malfunction.
z External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check
the supply voltage used in order to prevent the connected circuit from overheating.
z Connection cable
Copyright
We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.
The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.
Table of Contents
Preface .....................................................................................................I
1 Introduction .........................................................................................1
1.1 Overview.............................................................................................................. 1
1.2 Functions ............................................................................................................ 1
1.3 Features............................................................................................................... 2
2.3 Certification......................................................................................................... 8
4 Supervision........................................................................................ 11
4.1 Overview.............................................................................................................11
4.2 Self-supervision.................................................................................................11
4.2.1 Module Supervision ............................................................................................................. 11
5 Hardware ............................................................................................13
5.1 Overview............................................................................................................ 13
5.2 Basic Enclosure................................................................................................ 14
5.3 Main DSP Module (NR1136A/NR1136E) .......................................................... 14
5.4 Sampling DSP module (NR1123R)................................................................... 15
5.5 Analog Input Module (NR1401)........................................................................ 16
5.6 Data Transmission Module (NR1211A) ........................................................... 17
5.7 Voltage Transfer Module (NR1538A) ............................................................... 17
5.8 Binary Input and Output Module (NR1525A) .................................................. 18
5.9 Power Supply Module (NR1303E) ................................................................... 19
5.10 Human Machine Interface Module................................................................. 20
7 Settings ..............................................................................................37
7.1 Overview............................................................................................................ 37
7.2 Device Settings................................................................................................. 37
7.3 Channel Parameters ......................................................................................... 39
8 Installation .........................................................................................41
9 Commissioning .................................................................................49
10 Maintenance.....................................................................................55
11.2 Disposal........................................................................................................... 57
1 Introduction
1.1 Overview
The traditional electromagnetic transformers are widely applied in present power grid. But the
wiring modes of the traditional electromagnetic transformers have many disadvantages, and
mainly include following aspects.
1. The wiring modes of the traditional electromagnetic transformers are very complicated, and
many electrical cables are applied, which makes the maintenance is not so easy.
2. The signals (secondary voltages, secondary currents and binary signals etc.) are easy to be
disturbed by external electromagnetic environment in traditional substations or power plants.
In recent years, as the rapid development of the electronic technology and optical communication
technology, the traditional electrical cables are replaced by the optical fibers for transmitting the
signals (voltages, secondary currents and binary signals etc.). The advantages of this method
include following aspects.
1. The optical signals are not disturbed by external electromagnetic environment, so the system
has strong capability for resisting the external electromagnetic disturbance.
2. The adoption of the optical fibers can save the electrical cables greatly, and make the system
be easy to wire and maintain.
The PCS-221G is a merging unit (MU) for traditional electromagnetic transformers. This device is
suitable for mounted near to the traditional primary equipment. It can sample the AC analog values
locally, and then it can transmit these sampled values (SV) to the protection devices, the bay
control unit (BCU) devices or the electric meters through optical communication channels which
are based on the IEC61850-9-2 protocol or IEC60044-8 protocol.
1.2 Functions
z GMRP function
1.3 Features
z The high performance multi-DSP hardware structure is adopted in this device, and so this
device can process real time data with high speed and high precision.
z Modularized hardware design makes this device be easily upgraded or repaired by a qualified
service person.
z Various function optional modules can satisfy various situations according to the different
requirements of the users.
z Adoption of high precision 16 bits A/D converter ensures the measurement calculation with
high precision. Two A/D converters are for an AC sampled channel, and the sampling rate is
80 samples per fundament wave cycle. The real time data calculation can be finished within
one sampling period.
z A human machine interface (HMI) is provided for the user to view the status of this device very
friendly and conveniently.
z Various methods of GPS time synchronization are contained in this device, including
message (IEEE1588), pulse per second (PPS) and IRIG-B synchronization.
z This device can support several communication protocols which are adopted in the modern
digital substation: IEC61850-9-2, IEC60044-8 and IEC61850-8 (GOOSE).
z Perfect event recording function: 128 latest binary bit change reports, 128 latest device self
supervision reports.
2 Technical Data
Standard IEC60255-6:1988
Rated frequency (fn) 50Hz, 60Hz
Nominal range fn ± 5Hz
Phase rotation ABC
Rated voltage (Un) 100V ~ 130V (phase-to-phase voltage) 200V (open-delta voltage)
Linear to 170V 340V
Thermal continuously 200V 220V
withstand 10s 260V 380V
capability 1s 300V 420V
Burden (@ Un) < 0.20VA/phase < 0.80VA/phase
Medium Parameters
Connector type LC (IEC61850-9-2) or ST (IEC60044-8)
Transmission Rate 100Mbps (IEC61850-9-2) or 10Mbps (IEC60044-8)
Transmission standard 100Base-FX
Optical Fiber Type Multi-mode
Wavelength 1310nm (IEC61850-9-2) or 850nm (IEC60044-8)
Optical Ethernet
Transmission distance < 2000m
Protocol IEC61850-9-2 or IEC60044-8
Transmission Power Min. -20.0dB
Reception Power Min. -30.0dB
System Backup Min. +3.0dB
Medium Parameters
Port number 1
Connector type ST
Optical RS-485 (EIA)
Transmission distance < 2000m
Timing standard PPS, IRIG-B
Port number 1~2
Connector type LC
Optical Ethernet
Transmission distance < 2000m
Timing standard IEEE1588
2.3 Certification
z ISO9001: 2000
z ISO14001:2004
z OHSAS18001: 1999
z ISO10012:2003
z CMMI L4
3 Operation Theory
The PCS-221G is a merging unit (MU) for traditional electromagnetic transformers. This device
can locally sample the AC analog values and synchronize these values, and then it can transmit
these sampled values (SV) to the protection devices, the bay control unit (BCU) devices or the
electric meters through optical communication channels which are based on the IEC61850-9-2
protocol or IEC60044-8 protocol.
Busbar
To BCU, Protection
3
or Metering Devices
1
GPS signal
IRIG-B, PPS, IEEE1588
3 PCS-221G
3
Busbar Voltages
Electrical Cable Per IEC60044-8
Line
Optical Fiber
The PCS-221G can locally sample 12 AC analog values: 5 currents for protection, 3 currents for
metering and 4 voltages. It also can receive voltage values from a busbar MU, and support the
voltage transfer function.
The sampled frequency is 4kHz, and the output sampled value codes of the currents and voltages
are as below: the rated voltage code is “2D41H”, the rated current code for protection is “01CFH”,
and the rated current code for metering is “2D41H”.
This merging unit can provide the voltage transfer function if the voltage transfer function is
selected according to the technique contract. There are two methods for realizing the voltage
transfer function.
In the first method, this device can detect the disconnector positions through the GOOSE
communication or the local binary inputs, and get two groups of busbar voltages from a busbar MU
through the IEC60044-8 communication. Then this device will transfer the voltages according to
the disconnector positions and output the selected active voltages.
The demonstration of the first method of the voltage transfer function is shown in Figure 3.2-1.
In the second method, this device this device can detect the disconnector positions through the
GOOSE communication or the local binary inputs, and then it will transfer the voltages according
to the disconnector positions and output the selected active voltages through a special voltage
transfer module NR1538A (See Section 5.7).
The demonstration of the second method of the voltage transfer function is shown in Figure 3.2-2.
4 Supervision
4.1 Overview
When this device is in energizing process before the LED “HEALTHY” is on, this device needs to
be checked to ensure there are no errors. Therefore, the automatic supervision function, which
checks the health of this device during startup and normal operation procedure, is very important.
This device based on the microprocessor operations has the capability for implementing this
automatic supervision function.
In case a fatal fault is detected during automatic supervision, this device will be blocked out. It
means that this device is out of service. Therefore you must re-energize this device or even
replace a module to make this device back into service.
4.2 Self-supervision
If this device detects the optical reception light intensity is very low, the LED indicators “ALARM”
and “LIGHT INTENSITY ALARM” will be on.
If this device detects the GOOSE reception is incorrect, the LED indicators “ALARM” and
“GOOSE ALARM” will be on.
5 Hardware
5.1 Overview
The modular design of this device allows this device to be easily upgraded or repaired by a
qualified service person, and the back-plugging structure design makes it easy to repair or replace
any modules.
There are several types of hardware modules in this device; each module takes a different part in
this device. These modules can be selected according to the practical engineering demands.
NOTE! The module NR1211A and module NR1538A are optional according to the
The following two figures show the front panel and the rear panel of this device.
1
HEALTHY
MERGING UNIT
2
ALARM
3
IN MAINTENANCE
4
SYNCHRO ALARM
5
BI PWR ALARM
6
SAMPLE ALARM
7
LIGHT INTENSITY ALARM
8
GOOSE ALARM
9
ON BB1
10
ON BB2
The basic enclosure for this device is an electronic equipment rack (see Figure 5.2-1) with an
adequate number of slots for all these modules. The basic rack is equipped with a back plane
(mother board), and the back plane provides some back plane lines for distributing signals within
the enclosure.
The rack, back plane and the slot allocation of this device is shown as below.
Figure 5.2-1 Rack, back plane and slot allocation of this device
There are 8 slots in the rack of this device, which can be populated with up to 7 modules:
NR1136A/NR1136E, NR1123R, NR1401, NR1211A, NR1538A, NR1525A and NR1303E.
The main DSP module is am important part of this device, and contains a powerful microchip
processor and some necessary electronic elements. This powerful processor performs some
functions of this merging unit: the device management function, the GOOSE communication
function, sampled value (SV) transmission function, time synchronization function and event
record function etc.
The main DSP module can communicate with other module through the inner bus of this device.
This module provides several optical Ethernet ports, and it supports the protocol of IEC61850-9-2
over point-to-point link or ISO/IEC 8802-3 link and the protocol of IEC61850-8 (GOOSE) over
ISO/IEC 8802-3 link through these optical Ethernet ports. Each optical Ethernet port can support
IEEE1588 time synchronization protocol.
There are two kinds of main DSP module: NR1136A and NR1136E. The NR1136A module
provides 8 optical Ethernet ports. The NR1136E module provides 7 optical Ethernet ports and an
optical time synchronization port, and the optical time synchronization port can receive IRIG-B
signal or PPS signal to correct the local clock in this module.
The front view of the main DSP module is shown in Figure 5.3-1.
The sampling DSP module can sample up to 12 channels of AC analog values from the analog
input module and synchronize the sampled values, and then it can transmit these synchronized
values to other modules through the inner bus of this device. To ensure the validity of the sampled
values, the dual-channel sampling technique is adopted in this module.
This module can transmit the sampled values per the protocol of IEC60044-8 over point-to-point
link through the optical Ethernet ports “TX1” and “TX2” respectively. It also can receive several
busbar voltage sampled values per the protocol of IEC60044-8 over point-to-point link from a
busbar merging unit through the optical Ethernet ports “TX1” and “TX2” respectively.
The front view of the sampling DSP module is shown in Figure 5.1-2.
The analog input module can transform high AC input values to relevant low AC output values,
which are suited to the analog inputs of the sampling DSP module. The transformers are used
both to step-down the currents and voltages to levels appropriate to the electronic circuitry of this
device and to provide effective isolation between this device and the power system. A low pass
filter circuit is connected to each transformer (CT or VT) secondary circuit for reducing the noise of
each analog AC input signal.
NOTE! The rated value of the current transformer is optional: 1A or 5A. The rated value
of the CT must be definitely declared in the technical scheme and the contract.
NOTE! Because the rated value of the current transformer is optional, it is necessary to
check whether the rated value of the current transformer inputs is according to the
demand of the engineering scheme before the device is put into operation.
The front view of the analog input module is shown in Figure 5.1-2.
A 24-pin connector is fixed on the front side of this module. The terminal definition of the connector
is described as below.
21 Uc
The input of the voltage of the C phase.
22 Ucn
23 Usy
The input of the synchro-check voltage.
24 Usyn
DANGER! Never allow the current transformer (CT) secondary circuit connected to this
equipment to be opened while the primary system is live. Opening the CT circuit will
produce a dangerously high voltage. If this safety precaution is disregarded, personal
death, severe personal injury or considerable equipment damage will occur.
The data transmission module can provide 8 optical Ethernet ports for output the sampled values.
The communication protocol is strictly compatible with the protocol of IEC60044-8 over
point-to-point link.
The front view of the data transmission module is shown in Figure 5.1-2.
NOTE! The data transmission module NR1211A is optional according to the requirement
The voltage transfer module is used for the second method of the voltage transfer function. See
Section 3.2 for the details of the voltage transfer function. It provides 7 voltage transfer channels,
and provides two binary outputs.
The main DSP module detects the disconnector positions through the GOOSE communication or
the local binary inputs, and the voltage transfer module get the disconnector positions from the
main DSP module through inner bus. Then this module can transfer the voltages according to the
disconnector positions and output the selected active voltages.
NOTE! The voltage transfer module NR1538A is optional according to the requirement of
The theory demonstration of anyone of the voltage transfer channels is shown in Figure 5.7-1.
DS: Disconnector
NR1538A
NR1136 Busbar DS positon X: 1~7
The front view of the voltage transfer module is shown in Figure 5.1-2.
A 30-pin connector is fixed on the front side of this module. The terminal definition of the connector
is described as below.
The binary input and output module provides 13 binary inputs and 4 binary outputs. This module
can communicate with other DSP module (main DSP module or sampling DSP module) through
the inner bus.
The front view of the binary input and output module is shown in Figure 5.1-2.
A 24-pin connector is fixed on the front side of this module. The terminal definition of the connector
is described as below.
NOTE! The binary inputs and outputs can be configured according to the requirement of
The power supply module is a power supply converter with electrical insulation between input and
output, and it can provide the suitable output voltage for other modules of this device. The power
supply module has an input voltage range as described in Section 2.1.1.1. The tolerances of the
output voltages are continuously monitored.
The power supply module also provides one group of binary outputs which are used to send out
failure and alarm signals of this device.
The use of an external miniature circuit breaker is recommended. The miniature circuit breaker
must be in the on position when the device is in operation and in the off position when the device is
in cold reserve.
The front view of the power supply module is shown in Figure 5.1-2.
Four LED indicators of this module are used to indicate the status of the power supply module.
A 12-pin connector is fixed on the front side of this module. The terminal definition of the connector
is described as below.
The human machine interface (HMI) module is installed on the front panel of this device. It is used
to observe the running status through the LED indicators, and help the user to view the status of
this device. For the relevant information about the LED indicators, please see Section 4.2.
The view of the human machine interface module is shown in Figure 5.1-1.
This chapter will describe the device HMI and the virtual HMI terminal software.
This device has a human machine interface (HMI) module which is described in Section 5.10. The
view of the human machine interface module is shown in Figure 5.1-1.
This device has 10 LED indicators to show the operation status of this device and a RS-232 serial
port for communicating with the virtual HMI terminal software.
The LED indicators and their description are listed in following table.
The RS-232 serial port is used for communicating with the virtual HMI terminal software through a
dedicated communication cable which is provides by the manufacturer.
The dedicated communication cable is shown as below. The RS-232 terminal is to connect with a
computer, and the RJ45 terminal is to connect with this device.
The virtual HMI terminal software is dedicated to simulate a practical HMI for the user to access
this device through a computer.
Three command buttons on the main interface are used to configure the LED indicators, configure
the RS-232 port of a computer and exit the software.
z LED configuration
1. Click the button “LED Config.” to popup the LED configuration interface;
2. Click the button “More…” to show all the changeable item of the LED configuration;
3. Select the device type in the item “Device Type”, and select the LED number in the item
“LED Number”;
4. Double click on a LED in the item “Current LED”, and then the attribute (name and color)
of the selected LED will be shown;
5. Change the LED name in the item “LED Name”, and change the LED color in the item
“LED Color”;
6. After finishing the LED configuration, click the button “OK” to confirm the modification;
and the newest LED definition will be shown on the main interface of the virtual HMI
terminal software.
Figure 6.2-2 LED configuration interface of the virtual HMI terminal software
z Communication configuration
1. Click the button “COMM Config.” to popup the communication configuration interface;
2. Select the port sequence number in the item “Port No.” according to the practical
communication connection of the computer;
3. Set the reception and transmission intervals of the virtual HMI terminal software;
4. After finishing the communication configuration, click the button “OK” to confirm the
modification.
Figure 6.2-3 Communication configuration interface of the virtual HMI terminal software
z The 10 LED indicators are used to show the operation status of this device. For further details
about these LED, see Section 6.1.
The default display on the LCD is shown as below when the device is in normal situation.
The first line shows the current time of this device, and the current time format of this relay is
“yyyy-mm-dd hh:mm:ss”. The middle part of the LCD shows the some operation information of this
device. The last line shows the current address of this device.
When the default display is being shown, press key “Up” to enter the main menu of this device.
The following figure shows the menu tree structure of this device.
Press key “Up”, “Down”, “Right” or “Left” to select a submenu and the press key “ENT” to show
the details.
Purpose:
This menu is used to modify the operation environment of this device, such as default language.
Access approach:
Move cursor to the item “EnvironmentSet” and press key “ENT” to enter its submenu after
entering the main menu of this device.
Operating steps:
1. Press key “Up” to enter the main menu in the default displaying situation.
2. Press key “Up” or “Down” to locate the cursor on the submenu “EnvironmentSet” and press
key “ENT” to enter this submenu.
5. After finishing the language modification, press key “ENT” to confirm the modification.
Purpose:
Access approach:
Move cursor to the item “ProgramVersion” and press key “ENT” to enter its submenu after
entering the main menu of this device.
Operating steps:
1. Press key “Up” to enter the main menu in the default displaying situation.
2. Press key “Up” or “Down” to locate the cursor on the submenu “ProgramVersion” and press
key “ENT” to enter the program version information interface.
NOTE! It is only an example for explaining the program version menu. The practical
Purpose:
Access approach:
Move cursor to the item “SetTimer” and press key “ENT” to enter the clock modification interface
after entering the main menu of this device.
Operating steps:
1. Press key “Up” to enter the main menu in the default displaying situation.
2. Press key “Up” or “Down” to locate the cursor on the submenu “SetTimer” and press key
“ENT” to enter the clock modification interface.
3. Press key “Up” or “Down” to locate the cursor on a selected item and press key “+” or “-” to
modify the selected item.
4. After finishing the clock modification, press key “ENT” to confirm the modification.
Purpose:
This menu is used to operate this device locally, such as signal resetting and clearing the history
statistic counter.
Access approach:
Move cursor to the item “LocalCommand” and press key “ENT” to enter its submenu after
entering the main menu of this device.
Operating steps:
1. Press key “Up” to enter the main menu in the default displaying situation.
2. Press key “Up” or “Down” to locate the cursor on the submenu “LocalCommand” and
press key “ENT” to enter this submenu.
3. Press key “Up” or “Down” to locate the cursor on the submenu “ResetSignalOut” and
press key “ENT” to restore all the signals and relevant outputs of this device.
z Clear Status
Operating steps:
1. Press key “Up” to enter the main menu in the default displaying situation.
2. Press key “Up” or “Down” to locate the cursor on the submenu “LocalCommand” and
press key “ENT” to enter this submenu.
3. Press key “Up” or “Down” to locate the cursor on the submenu “ClearStatus” and press
key “ENT” to clear the history statistic counter.
Purpose:
The menu is used to view and modify the settings and parameters of this device. Please read
Chapter 7 for the details about the all the settings.
Access approach:
Move cursor to the item “ModifyConstantValue” and press key “ENT” to enter its submenu after
entering the main menu of this device.
z View Settings
Here take viewing the device settings as an example to introduce the operating steps of
viewing the setting.
Operating steps:
1. Press key “Up” to enter the main menu in the default displaying situation.
2. Press key “Up” or “Down” to locate the cursor on the submenu “ModifyConstantValue”
and press key “ENT” to enter this submenu.
3. Press key “Up” or “Down” to locate the cursor on the submenu “DEVICE-SETTINGS”
and press key “ENT” to enter this submenu and then press key “ENT” to show the device
settings.
Operating steps:
1. Refer the above description to locate the cursor on the expected setting, and then press
key “ENT” to enter the setting modification state.
2. Press key “+” or “-” to modify a selected setting, and press key “ENT” to return to the
setting interface (see Figure 6.2-10) after the selected setting modification is finished.
3. Repeat Step “1” and “2” to modify other settings which need to be modified.
4. After finishing the setting modification, press key “ESC” to prompt the user whether to
save the settings. Select “Yes” to confirm to save the modified settings. Then the
password input interface is shown on the LCD. Input the correct password and press key
“ENT” to confirm the modification. If the modification is given up, press key “ESC” to exit
the modification operation.
5. After confirming the setting modification, it will show “Saving Settings Now…” on the LCD.
Then the device will restart, and the new settings will be in service.
Purpose:
This menu is used to view all kinds of history reports: the supervision alarm reports and the binary
state change reports.
Access approach:
Move cursor to the item “ShowReports” and press key “ENT” to enter its submenu after entering
the main menu of this device.
The history supervision alarm report stores the alarm elements and alarm time.
Operating steps:
1. Press key “Up” to enter the main menu in the default displaying situation.
2. Press key “Up” or “Down” to locate the cursor on the submenu “ShowReports” and
press key “ENT” to enter this submenu.
3. Press key “Up” or “Down” to locate the cursor on the submenu “SelfCheckUpReports”
and press key “ENT” to enter this submenu. If there is no report in the selected submenu,
it will show “No Report!” on the LCD.
4. Press key “+” or “-” to view the expected history supervision alarm report.
The first line shows the report title and the sequence number of the history alarm report, and the
second line shows the alarm time of the history alarm report. Other lines show the alarm elements
and state change information one by one.
The history binary state change report stores the binary signal name and state change time.
Operating steps:
1. Press key “Up” to enter the main menu in the default displaying situation.
2. Press key “Up” or “Down” to locate the cursor on the submenu “ShowReports” and press key
“ENT” to enter this submenu.
3. Press key “Up” or “Down” to locate the cursor on the submenu “BitChangeReport” and press
key “ENT” to enter this submenu. If there is no report in the selected submenu, it will show “No
4. Press key “+” or “-” to view the expected history binary state change report.
The first line shows the report title and the sequence number of the history binary input state
change report, and the second line shows the binary state change time of the history binary state
change report. Other lines show the binary state change information one by one.
Purpose:
This menu is used to view the state of the analog measurement values, binary input status,
supervision alarm elements and sampled value (SV) information of this device.
Access approach:
Move cursor to the item “DeviceStatus” and press key “ENT” to enter its submenu after entering
the main menu of this device.
z View status
Here take viewing the status of the binary inputs as an example to introduce the operating
steps of viewing the status.
Operating steps:
1. Press key “Up” to enter the main menu in the default displaying situation.
2. Press key “Up” or “Down” to locate the cursor on the submenu “DeviceStatus” and
press key “ENT” to enter this submenu.
3. Press key “Up” or “Down” to locate the cursor on the submenu “ContactInput” and press
key “ENT” to enter this submenu.
The following tables show all the operation state information of this device.
The two busbar disconnectors are closed at the same time for longer
25 Alm_OpSimul_VoltSwitch
than 60s.
26 Alm_InputMode_Usyn The input mode of the synchro-check voltage is not correct
27 Alm_ReadF01_B02 The No.1 reception channel of the No.2 board has error
28 Alm_Ch1Send44-8_B02 The No.1 transmission channel of the No.2 board has error
29 Alm_Ch2Send44-8_B02 The No.2 transmission channel of the No.2 board has error
Anyone of the GOOSE function block disconnection, the GOOSE
30 GAlm_General
configuration file error and the GOOSE network storm is happened
31 GAlm_NetADisc_1 The network A of the No.1 GOOSE connection is disconnected
32 GAlm_NetBDisc_1 The network B of the No.1 GOOSE connection is disconnected
33 GAlm_Config_1 The configuration of the No.1 GOOSE connection is not correct
34 GAlm_NetADisc_2 The network A of the No.2 GOOSE connection is disconnected
35 GAlm_NetBDisc_2 The network B of the No.2 GOOSE connection is disconnected
36 GAlm_Config_2 The configuration of the No.2 GOOSE connection is not correct
37 GAlm_NetAStorm The network storm is occurred of the GOOSE network A
38 GAlm_NetBStorm The network storm is occurred of the GOOSE network B
24 Alm_State_DS_BB1 Please check the normal close contact of the relevant disconnector.
25 Alm_State_DS_BB2 Please check the normal open contact of the relevant disconnector.
26 Alm_InputMode_Usyn Please check the input voltage of the synchro-check voltage.
27 Alm_ReadF01_B02 Please inform the manufacturer to deal with it.
28 Alm_Ch1Send44-8_B02 Please inform the manufacturer to deal with it.
29 Alm_Ch2Send44-8_B02 Please inform the manufacturer to deal with it.
30 GAlm_General Please check the GOOSE related configuration and GOOSE network.
31 GAlm_NetADisc_1 Please check the GOOSE network.
32 GAlm_NetBDisc_1 Please check the GOOSE network.
33 GAlm_Config_1 Please check the GOOSE configuration file.
34 GAlm_NetADisc_2 Please check the GOOSE network.
35 GAlm_NetBDisc_2 Please check the GOOSE network.
36 GAlm_Config_2 Please check the GOOSE configuration file.
37 GAlm_NetAStorm Please check the GOOSE network.
38 GAlm_NetBStorm Please check the GOOSE network.
The first line shows the alarm report title, and then shows the alarm elements one by one
according to the time sequence. The alarm report will keep being displayed on LCD until the
relevant alarm situation is restored to normal state. It means that this device does not detect any
alarm situation.
If the input password is correct, the modification operation can be done; otherwise, it will show the
input interface on the LCD to prompt the user to input the password again.
The password for device setting modification is fixed, and it is press key “+”, “Left”, “Up” and “-” in
sequence. The password for channel parameter modification is fixed, and it is “114”.
The following figure shows the password input interface of this device.
7 Settings
7.1 Overview
The device settings are used to determine the operation mode, communication mode and other
functions of this merging unit (MU). It is necessary to configure the device settings according to the
practical requirements before this merging unit is put into service.
The channel parameters are used to regulate the angle difference and ratio difference of each
sampled channel respectively.
NOTE! If a main DSP module is replaced, it is necessary to configure all the settings
again according to the configuration of the main DSP module which is replaced.
NOTE! The channel parameters are not permitted to be configured unless the analog
input module is replaced. If the analog input module is replaced, the channel parameters
must be configured according to the label which is on the new analog input module.
The device settings (in the submenu “DEVICE-SETTINGS”) are used to determine the operation
mode, communication mode and other functions of this merging unit (MU).
NOTE!
1. The setting [En_DualNet_GOOSE] is used to enable or disable the dual-net mode of GOOSE
function. If it is set as “1”, the GOOSE function is with dual-net mode; and if it is set as “0”, the
GOOSE function is with single-net mode.
2. The setting [En_MixNet_GOOSE] is used to enable or disable the mixed mode of GOOSE
function. Only the setting [En_DualNet_GOOSE] is set as “1”, this setting is effective. If it is
set as “1”, the mixed mode (dual-net mode and single-net mode) is in service.
3. The setting [Opt_TimeSyn] is used to select the external time synchronization source: “0” is
PPS signal; “1” is IRIG-B signal; “2” is IEEE1588 protocol.
4. The setting [TimeZone] is used to set the hour offset of the current time zone to the GMT
(Greenwich Mean Time) zone; for example, if a relay is applied in China, the time zone of
China is east 8th time zone, so this setting is set as “8”.
Time zone GMT zone East 1st East 2nd East 3rd East 4th East 5th
Setting 0 1 2 3 4 5
th th th th th
Time zone East 6 East 7 East 8 East 9 East 10 East 11th
Setting 6 7 8 9 10 11
th st nd rd th
Time zone East/West 12 West 1 West 2 West 3 West 4 West 5th
Setting -12/12 -1 -2 -3 -4 -5
th th th th th
Time zone West 6 West 7 West 8 West 9 West 10 West 11th
Setting -6 -7 -8 -9 -10 -11
5. The setting [En_Alm_Syn] is used to enable or disable the synchronism alarm function. When
the clock synchronization source is correct and this setting is set as “1”, if the SV synchronism
is not finished correctly, the relevant alarm signal will be issued.
7. The setting [Opt_InputMode_Ubus] is used to select the input mode of the synchro-check
voltage: “0” means the voltage is sampled directly through the analog input module; “1”
means the voltage is from a busbar merging unit.
8. The setting [Opt_InputMode_Usyn] is used to select the input mode of the busbar voltages:
“0” means the busbar voltages are sampled directly through the analog input module; “1”
means the busbar voltages are from a busbar merging unit.
9. The setting [En_VoltSwitch] is used to enable or disable the voltage transfer function.
10. The setting [Opt_InputMode_DS] is used to select the input mode of the disconnector switch
position.
11. The setting [Opt_Rating_DevicCT] is used to select the rated secondary current value of the
analog input module: “0” is “1A”; “1” is “5A”.
12. The setting [En_GMRP] is used to enable or disable the GMRP (GARP Multicast Registration
Protocol) function of this device.
13. The setting [Un_BinaryInput] is used for selecting the rated voltage of the binary input.
Setting Value 0 1 2 3
Rated Voltage 24V 48V 110V 220V
15. The settings [Baud_Send_44-8] and [Baud_Recv_44-8] are used to set the baudrate of the
communication channels when the IEC60044-8 protocol is adopted.
Setting Value 0 1 2
Baudrate 2.5Mbps 5.0Mbps 10.0Mbps
The channel parameters (in the submenu “CHANNEL-PARAMETER”) are used to regulate the
angle difference and ratio difference of each sampled channel respectively.
4 k_Err_Ch4 The amplitude ratio coefficient of the No.4 channel 0.99~1.01 0.0001
5 k_Err_Ch5 The amplitude ratio coefficient of the No.5 channel 0.99~1.01 0.0001
6 k_Err_Ch6 The amplitude ratio coefficient of the No.6 channel 0.995~1.005 0.0001
7 k_Err_Ch7 The amplitude ratio coefficient of the No.7 channel 0.995~1.005 0.0001
8 k_Err_Ch8 The amplitude ratio coefficient of the No.8 channel 0.995~1.005 0.0001
9 k_Err_Ch9 The amplitude ratio coefficient of the No.9 channel 0.995~1.005 0.0001
10 k_Err_Ch10 The amplitude ratio coefficient of the No.10 channel 0.995~1.005 0.0001
11 k_Err_Ch11 The amplitude ratio coefficient of the No.11 channel 0.995~1.005 0.0001
12 k_Err_Ch12 The amplitude ratio coefficient of the No.12 channel 0.99~1.01 0.0001
13 Phi_Comp_Ch1(') The delay angle of the No.1 channel -30' ~ 30' 1'
14 Phi_Comp_Ch2(') The delay angle of the No.2 channel -30' ~ 30' 1'
15 Phi_Comp_Ch3(') The delay angle of the No.3 channel -30' ~ 30' 1'
16 Phi_Comp_Ch4(') The delay angle of the No.4 channel -30' ~ 30' 1'
17 Phi_Comp_Ch5(') The delay angle of the No.5 channel -30' ~ 30' 1'
18 Phi_Comp_Ch6(') The delay angle of the No.6 channel -10' ~ 10' 1'
19 Phi_Comp_Ch7(') The delay angle of the No.7 channel -10' ~ 10' 1'
20 Phi_Comp_Ch8(') The delay angle of the No.8 channel -10' ~ 10' 1'
21 Phi_Comp_Ch9(') The delay angle of the No.9 channel -10' ~ 10' 1'
22 Phi_Comp_Ch10(') The delay angle of the No.10 channel -10' ~ 10' 1'
23 Phi_Comp_Ch11(') The delay angle of the No.11 channel -10' ~ 10' 1'
24 Phi_Comp_Ch12(') The delay angle of the No.12 channel -30' ~ 30' 1'
8 Installation
8.1 General
This device must be shipped, stored and installed with the greatest care.
Choose the place of installation such that the communication interface and the HMI on the front of
the device are easily accessible.
Air must circulate freely around this device. Observe all the requirements regarding place of
installation and ambient conditions given in this instruction manual.
Take care that the external wiring is properly brought into this device and terminated correctly and
pay special attention to grounding. Strictly observe the corresponding guidelines contained in this
section.
Modules and units may only be replaced by correspondingly trained personnel. Always observe
the basic precautions to avoid damage due to electrostatic discharge when handling this device.
In certain cases, the settings have to be configured according to the demands of the engineering
configuration after replacement. It is therefore assumed that the personnel who replace modules
and units are familiar with the use of the operator program on the service PC.
DANGER! Only insert or withdraw the power supply module while the power supply is
switched off. To this end, disconnect the power supply cable that connects with the power
supply module.
WARNING! Only insert or withdraw other modules while the power supply is switched off.
WARNING! The modules may only be inserted in the slots designated in Section 5.2.
DANGER! Improper handling of this device can cause damage or an incorrect response
WARNING! Industry packs and ribbon cables may only be replaced or the positions of
z Should boards have to be removed from this device installed in a grounded cubicle in an HV
switchgear installation, please discharge yourself by touching station ground (the cubicle)
beforehand.
z Only hold electronic boards at the edges, taking care not to touch the components.
z Only works on boards that have been removed from the cubicle on a workbench designed for
electronic equipment and wear a grounded wristband. Do not wear a grounded wristband,
however, while inserting or withdrawing units.
z Always store and ship the electronic boards in their original packing. Place electronic parts in
electrostatic screened packing materials.
Check that the consignment is complete immediately upon receipt. Notify the nearest NR
Company or agent, should departures from the delivery note, the shipping papers or the order be
found.
Visually inspect all the material when unpacking it. When there is evidence of transport damage,
lodge a claim immediately in writing with the last carrier and notify the nearest NR Company or
agent.
If this device is not going to be installed immediately, store all the parts in their original packing in a
clean dry place at a moderate temperature. The humidity at a maximum temperature and the
permissible storage temperature range in dry air are listed in Section 2.1.3.
The necessary mounting kits will be provided, including screws, pincers and assembly
instructions.
A suitable drill and spanners are required to secure the cubicles to the floor using the plugs
provided (if this device is mounted in cubicles).
The place of installation should permit easy access especially to front of the device, i.e. to the
human machine interface of this device.
There should also be free access at the rear of this device for additions and replacement of
electronic boards.
Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient
conditions, such as:
1. The location should not be exposed to excessive air pollution (dust, aggressive substances).
2. Severe vibration, extreme changes of temperature, high levels of humidity, surge voltages of
high amplitude and short rise time and strong induced magnetic fields should be avoided as
far as possible.
This device can in principle be mounted in any attitude, but it is normally mounted vertically
(visibility of markings).
WARNING! Excessively high temperature can appreciably reduce the operating life of
this device.
This device is made of a single layer 4U height 9.5" chassis. The following figure shows the
dimensions of this device for reference in mounting.
177.00
101.60
268.80
101.60±0.10
177.00
Figure 8.6-1 Dimensions of this device and the cut-out in the cubicle (unit: mm)
NOTE! It is necessary to leave enough space top and bottom of the cut-out in the cubicle
As mentioned in Chapter 5, some modules are installed in the enclosure of this device, and these
modules must be plugged into the proper slots of this device respectively. The safety instructions
must be abided by when installing the boards, please see Section 8.2 for the details.
Figure 8.6-2 shows the installation way of a module being plugged into a corresponding slot.
In the case of equipment supplied in cubicles, place the cubicles on the foundations that have
been prepared. Take care while doing so not to jam or otherwise damage any of the cables that
have already been installed. Secure the cubicles to the foundations.
On the other hand, electronic apparatus can transmit interference that can disrupt the operation of
other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
NOTE! All these precautions can only be effective if the station ground is of good quality.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.
NOTE! If the above conditions are not fulfilled, there is a possibility of the cubicle or parts
of it forming a resonant circuit at certain frequencies that would amplify the transmission
of interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (see Figure 8.7-1).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
NOTE! For metallic connections please observe the voltage difference of both materials
The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip
(braided copper).
There are some ground terminals on some connectors of this device, and the sign is “GND”. All the
ground terminals are connected in the cabinet of this device. So, the ground terminal on the rear
panel (see Figure 8.7-2) is the only ground terminal of this device.
The grounding strips must therefore be of (preferably tinned) braided copper and not round copper
conductors, as the cross-section of round copper would have to be too large.
Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting
them firmly to the items to be connected.
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
z Power supply, binary inputs & outputs: brained copper cable, 1.5mm2 ~ 2.5mm2
Relevant information and sections about the modules and the connectors of this device are
described in Chapter 5. Referring the relevant sections can help to wire correctly and effectively.
Circuit Breaker
9 Commissioning
9.1 General
This device is fully numerical in their design, implementing all functions in software. This device
employs a high degree of self-checking and in the unlikely event of a failure, will give an alarm.
To commission this device, it is only necessary to verify that the hardware is functioning correctly
and the application-specific software settings have been applied to this device.
Before carrying out any work on this device, the user should be familiar with the contents of the
safety and technical data sections and the ratings on this device’s rating label.
WARNING! Hazardous voltages are present in this electrical equipment during operation.
Non-observance of the safety rules can result in severe personal injury or property
damage.
WARNING! Only the qualified personnel shall work on and around this equipment after
becoming thoroughly familiar with all warnings and safety notices of this manual as well
as with the applicable safety regulations.
z The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.
z Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.
z Hazardous voltages can be present in the device even after disconnection of the supply
voltage (storage capacitors!)
z The limit values stated in the technical data (Chapter 2) must not be exceeded at all, not even
during testing and commissioning.
DANGER! Current transformer secondary circuits must have been short-circuited before
WARNING! Primary test may only be carried out by qualified personnel, who are familiar
with the commissioning of this device, the operation of the plant and safety rules and
regulations (switching, earthing, etc.).
z Multifunctional dynamic current and voltage injection test set with interval timer.
z Multimeter with suitable AC current range and AC/DC voltage ranges of 0~440V and 0~250V
respectively.
NOTE! Modern test set may contain many of the above features in one unit.
Optional equipment:
z An electronic or brushless insulation tester with a DC output not exceeding 500V (for
insulation resistance test when required).
z A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
These product checks cover all aspects of this device which should be checked to ensure that it
has not been physically damaged prior to commissioning, is functioning correctly and all input
quantity measurements are within the stated tolerances.
This device is fully numerical and the hardware is continuously monitored. Commissioning tests
can be kept to a minimum and need only include hardware tests and conjunctive tests. The
function tests are carried out according to user’s correlative regulations.
The following tests are necessary to ensure the normal operation of this device before it is first put
into service.
z Hardware tests
These tests are performed for the hardware to ensure that there is no hardware defect.
Defects of hardware circuits other than the following can be detected by self-monitoring when
the power supply is energized.
z Function tests
These tests are performed for the following functions that are fully software-based.
z Conjunctive tests
The tests are performed after this device is connected with the primary equipment and other
external equipment.
After unpacking the product, check for any damage to the device case. If there is any damage, the
internal module might also have been affected, contact the vendor. The following listed items are
necessary.
z Device panel
Carefully examine the device panel, equipment inside and other parts inside to see that no
physical damage has occurred since installation.
The rated information of this device should be checked to ensure it is correct for the particular
installation.
z Panel wiring
Check the conducting wire which is used in the panel to assure that their cross section
meeting the requirement.
Carefully examine the wiring to see that they are no connection failure exists.
z Label
Check all the isolator binary inputs, terminal blocks, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.
Check each plug-in module of this device on the panel to make sure that they are well
installed into this device without any screw loosened.
z Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator binary inputs and push buttons
work normally and smoothly.
Insulation resistance tests are only necessary during commissioning if it is required for them to be
done and they have not been performed during installation.
Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:
z DC power supply
Test method:
To unplug all the terminals sockets of this device, and do the Insulation resistance test for each
circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to this device.
Check that the external wiring is correct to the scheme diagram. Ensure as far as practical that
phase rotation appears to be as expected.
Check the wiring against the schematic diagram for the installation to ensure compliance with the
customer’s normal practice.
This device only can be operated under the power supply depending on the nominal power supply
rating. The incoming voltage must be within the operating range specified in Section 2.1.1.1,
before energizing this device, measure the auxiliary supply to ensure it within the operating range.
Other requirements to the power supply are specified in Section 2.1.1.1. See this section for
further details about the parameters of the power supply.
On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that
this device is healthy.
Test other LEDs with the alarm conditions which are described in Section 4.2. For the details about
these LEDs, please see Section 5.10.
This test is for checking the merging unit function of this device.
The following figure shows the demonstration testing system for checking the MU function.
Protection
Device
Multi-function PCS-221G
Tester
1. Inject the currents and voltages to this merging unit through a multi-function tester (such as
OMICRON 256), this merging unit will sample and convert the inputted AC analog values;
2. Observer the protection device or BCU device which is connected to this merging unit, check
whether the values displayed by the protection device or BCU device are correct.
NOTE! In the check process, to ensure the optical communication channels between this
merging unit and the protection device or BCU device are reliably connected.
z Confirm the external wiring to the current and voltage inputs is correct.
However, these checks can only be carried out if there are no restrictions preventing the
tenderization of the plant being protected.
After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been
necessary to disconnect any of the external wiring from this device in order to perform the wiring
verification tests, it should be ensured that all connections are replaced in accordance with the
relevant external connection or scheme diagram.
If this device is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that this device is put into service.
Ensure that all event alarm records have been cleared and the LEDs have been reset before
leaving this device.
10 Maintenance
This device is self-supervised and so requires less maintenance. Most problems will result in an
alarm so that remedial action can be taken. However, some periodic tests should be done to
ensure that this device is functioning correctly and the external wiring is intact.
This device is almost completely self-supervised. The circuits which can not be supervised are
binary input, output circuits and human machine interfaces. Therefore regular testing can be
minimized to checking the unsupervised circuits.
When a failure is detected by supervision, an alarm is issued and the failure is indicated on the
front panel with LED indicators. It is also recorded in the alarm record. Failures detected by
supervision are traced by checking LED.
If the failure is identified to be in the module of this device and the user has spare modules, the
user can recover this device by replacing the failed modules.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name and hardware type-form as the
removed module. Furthermore, the replaced module should have the same software version. And
the replaced analog input module and power supply module should have the same ratings.
WARNING! Units and modules may only be replaced while the supply is switched off and
only by appropriately trained and qualified personnel. Strictly observe the basic
precautions to guard against electrostatic discharge.
earthed wrist band and placing modules on an earthed conductive mat. Otherwise, many
of the electronic components could suffer damage.
DANGER! After replacing modules, be sure to check that the same configuration is set
11.1 Decommissioning
DANGER! Before disconnecting the power supply cables that connected with the power
supply module of this device, make sure that the external miniature circuit breaker of the
power supply is switched off.
DANGER! Before disconnecting the cables that are used to connect analog input module
with the primary CT and VT, make sure that the circuit breaker for the primary CT and VT
is switched off.
11.1.3 Dismantling
The rack of this device may now be removed from the system cubicle, after which the cubicles
may also be removed.
DANGER! When the station is in operation, make sure that there is an adequate safety
11.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
NOTE! Strictly observe all local and national regulations when disposing of the device.