Professional Documents
Culture Documents
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and
benefits afforded under P.R. China and international copyright and patent laws in its products,
including but not limited to software, firmware and documentation. NR Engineering Co., Ltd. is
licensed to use this document as well as all intellectual property rights owned or held by NR
Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how,
trade secrets, trademarks and trade names, service marks, design rights, database rights and
rights in data, utility models, domain names and all similar rights.
The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.
To the extent required the products described herein meet applicable IEC and IEEE standards,
but no such assurance is given with respect to local codes and ordinances because they vary
greatly.
Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered
sufficiently for your purposes, please do not hesitate to contact us.
Preface
Preface
For these calculation results of settings for each function, they are calculated based the
parameters provided by primary equipment manufacturer and system parameters from the field.
All equipment parameters and system parameters needed to be confirmed based on on-site
specific application should be affirmed and checked further.
The guide is not involving of the functions′ configuration and principle, and the detailed description
of relevant contents can be found in the corresponding technical manual and application manual.
Before carrying out any setting work on the device, the user should be familiar with the contents of
this guide, and this guide must be thoroughly read and understood.
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment
(module or device). However, it comprises important information that must be followed for
personal safety, as well as to avoid material damage. Information is highlighted and illustrated as
follows according to the degree of danger:
Indicates that property damage can result if the measures specified are
not taken.
Contact with instrument terminals can cause electrical shock that can result
in injury or death.
Use of this equipment in a manner other than specified in this manual can
impair operator safety safeguards provided by this equipment.
Have only qualified personnel service this equipment. If you are not
qualified to service this equipment, you can injure yourself or others, or
cause equipment damage.
DO NOT connect power to the relay until you have completed these
Document Conventions
⚫ Menu path is connected with the arrow "→" and bold.
For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1
⚫ Binary input signals, binary output signals, analogues, LED lights, buttons, and other fixed
meanings, should be written in double quotes and bold.
Symbols
⚫ AND Gate
⚫ OR Gate
⚫ Comparator
BI xxx
⚫ Signal input
SIG xxx
⚫ Setting input
SET xxx
⚫ Enable input
EN xxx
⚫ Timer
Timer
t
t
⚫ Timer
10ms 2ms
⚫ Timer
[Tset1] 0ms
⚫ Timer
0ms [Tset2]
⚫ Timer
[Tset1] [Tset2]
⚫ Generator
⚫ Transformer
⚫ Reactor
⚫ Motor
⚫ Capacitor
⚫ Busbar
⚫ Circuit breaker
52
⚫ Current transformer
3CT
*
⚫ Voltage transformer
3VT
⚫ Disconnector
⚫ Earth
Example
Ia, Ib, Ic, I0 IL1, IL2, IL3, IN IR, IY, IB, IN
Ua, Ub, Uc VL1, VL2, VL3 UR, UY, UB
Uab, Ubc, Uca VL12, VL23, VL31 URY, UYB, UBR
U0, U1, U2 VN, V1, V2 UN, U1, U2
Warranty
This product is covered by the standard NR 10-year warranty. For warranty details, please consult
the manufacturer or agent for warranty information.
Document Structure
This manual provides detailed instructions for setting the PCS-931S, which covers all functions,
such as protection, control, supervision, measurement, etc., and general device setup. Read the
sections that pertain to your application to gain valuable information about using the PCS-931S.
To concentrate on the target sections of this manual as your job needs and responsibilities dictate.
1 Introduction
Introduces summarizes functions and full view about the settings in the device.
2 Global Settings
Describs the access path, settings list (name, range, unit and step) of global settings, including
system setting, device setting, communication setting, disturbance fault recording setting, label
setting and clock synchronization setting supervision setting, and some important setting
principles are also provided.
3 Protection Settings
Describes the access path, settings list (name, range, unit and step) of protection settings. The
detailed setting calculation guidelines and the recommended value of some settings are also
provided. Some application examples are provided to help familiarize and understand the
calculation process, and to assist you with your own protection settings calculations.
4 Control Settings
Describes the access path, settings list (name, range, unit and step) of control settings. The
detailed setting calculation guidelines and the recommended value of some settings are also
provided.
5 Measurement Settings
Describes the access path, settings list (name, range, unit and step) of measurement settings. The
detailed setting calculation guidelines and the recommended value of some settings are also
provided.
8 Supervision Settings
Describes the access path, settings list (name, range, unit and step) of supervision settings. The
detailed setting calculation guidelines and the recommended value of some settings are also
provided.
9 Logic Links
Describes the access path, settings list (name, range, unit and step) of logic links. The detailed
setting calculation guidelines and the recommended value of some settings are also provided.
Corresponding Version
Release Date Description of change
Document Software
1 Introduction
1
Table of Contents
List of Figures
Figure 1.1-1 Typical application of single circuit breaker (single busbar) ............................ 1-1
Figure 1.1-2 Typical application of single circuit breaker (double busbars) ........................ 1-1
1.1 Overview
PCS-931S protect overhead and underground lines, feeders, and cables on all voltage levels with
1
highest possible selectivity. The availability of various protection and automation functions permits
its utilization in all domains of line protection. The devices contain all important auxiliary functions
that are necessary today for safe network operation. This includes control, measurement and
monitoring functions. The large number of communication interfaces and communication protocols
satisfies the requirements of communication-based selective protection and automation operation.
Its modular structure permits line protection devices always to be adapted flexibly to the individual
requirements.
3CT 3CT
52 * * 52
3VT 3VT
CH1 CH1
PCS-931S Optical fibre channel PCS-931S
CH2 CH2
1VT 1VT
Communication channel via direct dedicated fibre or MUX
3CT 3CT
52
* * 52
1VT 1VT
CH1 CH1
PCS-931S Optical fibre channel PCS-931S
CH2 CH2
3VT 3VT
PCS-931S is a high-speed transmission line differential relay featuring single-pole & three-pole
tripping and reclosing with synchronism check. The device features extensive metering & data
recording including high-resolution data capture and reporting. PCS-931S features expanded
control equation programming for easy and flexible implementation of custom protection and
control schemes.
A simple and robust hardware design features efficient digital signal processing. Combined with
extensive self-testing, these features provide device reliability and enhance relay availability.
PCS-931S can be configured to support single circuit breaker application or double circuit
breakers application by PCS-Studio. If the device is applied to double circuit breakers mode, all
protection functions related to the number of circuit breaker will be affected.
52 52
1VT 1VT
1 3CT 3CT
*
*
3VT 3VT
CH1 CH1
52 52
PCS-931S Optical fibre channel PCS-931S
CH2 CH2
3CT 3CT
*
*
1VT 1VT
52 52
The PCS-931S is widely adopted not only for conventional substations, but also for digital
substations. It supports IEC 61850 Editions 1 and 2 and provides GOOSE and SV network
interfaces with high real-time performance. The process level network supports peer-to-peer (P2P)
mode and networking mode, including single network mode and dual network mode. The station
level network could also receive and send MMS messages (such as interlocking signals) or
process level GOOSE messages (such as circuit breakers or disconnectors positions and trip
signals).
1.2 Functions
Busbar
3VT
52 1
85 21 67P 67G 67Q 32R 49P 50DZ 46BC 62P D 50BF 37 PMU 59P
3CT
*
78 FL
81O 27P
81U 81R
Line
1 Protection
⚫ CT saturation detection
protection scheme
⚫ Up to 6 zones
zone
zone
distance element
current check
50DZ Dead zone protection ⚫ Clear the dead zone faults between CT and the circuit breaker
conductor.
1
⚫ Initiated by three auxiliary contacts of phase-segregate circuit
breaker
62PD Pole discrepancy protection
⚫ Optional auxiliary criterion (zero-sequence current element or
lines
2 Control
⚫ Voltage selection
3 Synchrophasor measurement
⚫ Calculate synchronized phasors, including: Ua, Ub, Uc, U1, U2, U0, Ia, Ib, Ic, I1, I2, I0
⚫ Calculate analog values, including: active power (P), reactive power (Q), frequency,
ROCOF (df/dt)
⚫ Transmit binary status of the IED to PDC (Phasor Data Concentrator) according to IEEE
1 C37.118 standard
⚫ Realize high accurate measurement of the phasors and analogs according to the IEEE
C37.118.1-2011 and IEEE C37.118.1a-2014 standard.
4 Measurement
⚫ Energy metering (active and reactive energy are calculated in import respectively export
direction)
⚫ Power (Apparent/Real/Reactive)
⚫ Power factor
⚫ Frequency
5 Recording
⚫ Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs.
⚫ 64 travelling wave fault location (TWFL) records (The file format of disturbance recorder is
compatible with international COMTRADE file.)
6 Supervision
⚫ VT circuit supervision
⚫ CT circuit supervision
⚫ Self diagnostic
8 Communication interface
9 Communication protocol
⚫ IEC 60870-5-103
⚫ DNP3.0
⚫ Modbus
10 Digital application
⚫ IEC 61850-9-2LE SV
11 Clock synchronization
1 ⚫ IRIG-B: IRIG-B via RS-485 differential level, TTL level or BNC
⚫ PPS: Pulse per second (PPS) via RS-485 differential level, binary input or BNC
⚫ IEEE 1588: Clock message based on IEEE 1588 via Ethernet network
⚫ SNTP: Unicast (point-to-point) & broadcast SNTP mode via Ethernet network
⚫ Clock messages: IEC 60870-5-103 protocol, Modbus protocol and DNP3.0 protocol
12 Cyber security
⚫ NERC CIP
⚫ IEC 62351
⚫ IEC 62443
⚫ IEEE 1686
13 User interface
⚫ Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and
set-point adjustment
⚫ Push buttons for open/close, switch for selection between local and remote control, and
user's login and logout authority management
⚫ Configuration tool—PCS-Studio
14 Miscellaneous
Settings
Device Settings
Communication Settings
IEC61850 Settings
IEC103 Settings
DNP Settings
Modbus Settings
DFR Settings
Label Settings
ClockSyn Settings
Superv Settings
FD Settings
Line Settings
Function Settings
Syn Settings
Control Settings
Interlocking Settings
TWFL Settings
PMU Settings
Logic Links
Function Links
SV Recv Links
2 Global Settings
Table of Contents
List of Tables
⚫ LCD
Active_Grp 1~20 1
Opt_SysFreq 50, 60 Hz
ABC
Opt_PhSeq
ACB
Prot.CB1.I1n 0~60000 1 A
Prot.CB1.I2n 1 or 5 A
Prot.CB2.I1n 0~60000 1 A
Prot.CB2.I2n 1 or 5 A
3I0Adj.I1n 0~9999 1 A
3I0Adj.I2n 1 or 5 A
Disabled
Prot.CB1.En_RevCT
Enabled
Disabled
Prot.CB2.En_RevCT
2 Enabled
Disabled
3I0Adj.En_RevCT
Enabled
Disabled
Prot.En_VT
Enabled
NoVoltSel
DblBusOneCB
CB1.VoltSel.Opt_CBConfig
3/2BusCB
3/2TieCB
NoVoltSel
DblBusOneCB
CB2.VoltSel.Opt_CBConfig
3/2BusCB
3/2TieCB
1. Active_Grp
It is used to set the number of active setting group, and several setting groups (20 at most) can be
configured for protection settings and measurement & control settings, but only one is active at a
time.
The settings in different group can be changed to suit the needs of actual application. The default
settings have been chosen according to established practice but will usually require adjustment to
suit the requirements of individual applications.
2. PrimaryEquip_Name
It is used to set the name of the protected primary equipment, such as busbar, transformer, line,
capacitor, etc. It will be displayed in the printed result and the DFR (Disturbance Fault Recording)
file.
This setting is case sensitive, and its maximum permissible length of this setting is 20 characters.
A a B b C c D d E e F f
G g H h I i J j K k L l
M m N n O o P p Q q R r
S s T t U u V v W w X x 2
Y y Z z _ 0 1 2 3 4 5 6
7 8 9
3. Opt_SysFreq
It is used to set the system frequency. It can be set to either 50Hz or 60 Hz according to the
system frequency.
4. Opt_PhSeq
It is used to inform the device of the actual system phase sequence, either "ABC" or "ACB". CT
and VT inputs on the device, labeled as A, B and C, must be connected to system phase A, B and
C for correct operation. This will affect positive/negative-sequence quantities calculated by the
device and will also affect functions that are dependent on phase quantities.
5. Prot.U1n
It is used to set primary rated voltage of VT (protection voltage), and it should be set based on
phase-to-phase value.
6. Prot.U2n
It is used to set secondary rated voltage of VT (protection voltage), and it should be set based on
phase-to-phase value.
7. Prot.CB*.I1n
It is used to set primary rated value of CT corresponding to circuit breaker * (protection current,
*=1 or 2).
8. Prot.CB*.I2n
It is used to set secondary rated value of CT corresponding to circuit breaker 1 (protection current,
*=1 or 2).
9. UB1.Syn.U1n
It is used to set primary rated voltage of busbar No.1 VT (synchronism voltage), and it should be
10. UB1.Syn.U2n
It is used to set secondary rated voltage of busbar No.1 VT (synchronism voltage), and it should
be set based on phase-to-phase value.
11. UL2.Syn.U1n
2 It is used to set primary rated voltage of line No.2 VT (synchronism voltage), and it should be set
based on phase-to-phase value.
12. UL2.Syn.U2n
It is used to set secondary rated voltage of line No.2 VT (synchronism voltage), and it should be
set based on phase-to-phase value.
13. UB2.Syn.U1n
It is used to set primary rated voltage of busbar No.2 VT (synchronism voltage), and it should be
set based on phase-to-phase value.
14. UB2.Syn.U2n
It is used to set secondary rated voltage of busbar No.2 VT (synchronism voltage), and it should
be set based on phase-to-phase value.
15. 3I0Adj.I1n
It is used to set primary rated value of CT. (residual current for mutual coupling compensation)
16. 3I0Adj.I2n
It is used to set secondary rated value of CT. (residual current for mutual coupling compensation)
17. Prot.CB*.En_RevCT
18. 3I0Adj.En_RevCT
19. Prot.En_VT
It is used to enable/disable VT connect to the device, which is used for protection calculation.
20. CB*.VoltSel.Opt_CBConfig
It is used to select the configuration mode of circuit breaker *, and it should be set as "NoVoltSel" if
no voltage selection is adopted. (*=1 or 2)
3/2BusCB: bus side circuit breaker for one and a half breakers
2
3/2TieCB: line side circuit breaker for one and a half breakers
⚫ LCD
⚫ PCS-Studio
Disabled
En_DebugPort
Enabled
Disabled
En_TelnetPort
Enabled
Disabled
En_VirtualLCDPort
Enabled
Ctrl_Password 000~999 1
Disabled
En_NoCtrlPwd
Enabled
Disabled
En_PopupRecord_Blkd
Enabled
Un_BinaryInput 24~250 1 V
DC
Opt_Pwr_BI AC50Hz
AC60Hz
Num_Blk_Jitter 2~500000 1
Num_Reblk_Jitter 1~500000 1
Disabled
En_Jitter_Blk
Enabled
Disabled
En_BICheckInstP
Enabled
1. En_DebugPort
It is used to enable/disable the debugging port of this device, which is used for debugging tool
connection, program download, variable debugging, etc. via PCS-Studio configuration tool.
If all the unnecessary ports (including the debugging port) are required to be disabled to ensure
cyber security, please configure this setting as "Disabled".
2. En_TelnetPort
If the Telnet port needs to be used, please configure this setting as “Enabled”.
If all the unnecessary ports (including the Telnet port) are required to be disabled to ensure cyber
security, please configure this setting as "Disabled"'.
3. En_VirtualLCDPort
The virtual LCD port is used to simulate a virtual HMI to acquire device information via PCS-Studio
configuration tool. If all the unnecessary ports (including the virtual LCD port) are required to be
disabled to ensure cyber security, please configure this setting as "Disabled".
4. Ctrl_Password
It is used to set the password when executing the control operation via the device's LCD.
Only digits from "000" to "999" can be accepted. If the setting [En_NoCtrlPwd] is configured as
"Enabled", this setting will be invalid even if it is configured.
5. En_NoCtrlPwd
It is used to determine whether it is necessary to input the password when executing the control
2
operation via the device's LCD.
Disabled: it is necessary to input the password when executing the control operation via the
device's LCD.
Enabled: the control operation to switchgear (CB or DS) via the device's LCD can be directly
executed without the password verification.
6. En_PopupRecord_Blkd
If all the event records (including disturbance records, supervision events, IO events, control
events, etc.) are forbidden to pop up in the main graph of local LCD automatically, i.e.: they can
only be viewed by entering corresponding menus, please configure this setting as "Enabled".
7. Un_BinaryInput
It must be the same as the voltage level of the binary inputs which are connected to this device.
8. Opt_Pwr_BI
Three options are available: DC, AC50Hz and AC60Hz. It must be the same as the power supply
mode of the binary inputs which are connected to this device.
9. U_Pickup_BI
This setting is expressed as a percentage value. It must be smaller than the minimum normal
binary input voltage of the binary inputs connected to this device. Base on engineering experience,
it is recommended to be configured as "63.0%".
10. U_Dropoff_BI
This setting is expressed as a percentage value. It must be smaller than the value of the setting
[U_Pickup_BI] in this device. Base on engineering experience, it is recommended to be configured
as "55.0%".
11. Mon_Window_Jitter
In the time span defined by this setting, the state changes of binary input will be recorded. If the
binary input jitter processing is required, this setting must be configured as a value greater than 0.
When the setting [En_Jitter_Blk] is set as "Disabled", this setting will be unnecessary to be
2 configured.
12. Num_Blk_Jitter
It is used to set the times threshold to block the state changes of binary input due to jitter.
If the binary input jitter processing is required, this setting must be configured as a value greater
than 0. If the setting [Mon_Window_Jitter] is modified to a bigger value, the setting
[Num_Blk_Jitter] is recommended to be modified to a bigger value, too. When the setting
[En_Jitter_Blk] is set as "Disabled", this setting will be unnecessary to be configured.
13. Blk_Window_Jitter
In the time span defined by this setting, the state changes of binary inpu will be recorded. If the
binary input jitter processing is required, this setting must be configured as a value greater than 0.
When the setting [En_Jitter_Blk] is set as "Disabled", this setting will be unnecessary to be
configured.
14. Num_Reblk_Jitter
It is times threshold to initiate immediately another blocking window of the state changes of binary
input due to continuous jitter.
If the binary input jitter processing is required, this setting must be configured as a value greater
than 0. If the setting [Blk_Window_Jitter] is modified to a bigger value, the setting
[Num_Reblk_Jitter] is recommended to be modified to a bigger value, too. When the setting
[En_Jitter_Blk] is set as "Disabled", this setting will be unnecessary to be configured.
15. En_Jitter_Blk
It is used to enable/disable the jitter processing function in case of binary input voltage variation.
If binary input jitter processing is required, please configure this setting as "Enabled".
16. En_BICheckInstP
If the binary input the rated voltage of binary input is 110Vdc or above is applied to acquire the
mechanical signal, for example, the binary signal from winding temperature relay, oil temperature
relay or Buchholz relay. The conducting mode of each binary input is switched into the high-power
mode to improve the anti-interference ability when the setting [En_BICheckInstP] is set as
"Enabled". The binary input will not be considered as being energized unless the instantaneous
active power rises to a certain value and during time is larger than 20ms, so as to avoid mistaken
signal.
This conducting mode is only available in the device equipped with some certain BI plug-in
modules (NR6604A or NR6611A) and the rated voltage of binary input is 110Vdc or above.
Otherwise, this conducting mode will be unavailable and this setting will be hidden.
When the setting [En_BICheckInstP] is set as "Enabled", and the debouncing time should be
larger than the during time (20ms) of the instantaneous active power.
2
2.3 Communication Settings
⚫ LCD
⚫ PCS-Studio
IP_LAN1 0.0.0.0~255.255.255.255
Mask_LAN1 0.0.0.0~255.255.255.255
Disabled
En_LAN1
Enabled
IP_LAN2 0.0.0.0~255.255.255.255
Mask_LAN2 0.0.0.0~255.255.255.255
Disabled
En_LAN2
Enabled
IP_LAN3 0.0.0.0~255.255.255.255
Mask_LAN3 0.0.0.0~255.255.255.255
Disabled
En_LAN3
Enabled
IP_LAN4 0.0.0.0~255.255.255.255
Mask_LAN4 0.0.0.0~255.255.255.255
Disabled
En_LAN4
Enabled
2 Gateway 0.0.0.0~255.255.255.255
4800
9600
19200
Baud_Printer bps
38400
57600
115200
Disabled
En_AutoPrint
Enabled
IEC103
Protocol_RS485-1
Modbus
IEC103
Protocol_RS485-2
Modbus
4800
9600
19200
Baud_RS485-1 bps
38400
57600
115200
4800
9600
19200
Baud_RS485-2 bps
38400
57600
115200
Addr_RS485-1 1~254 1
Addr_RS485-2 1~254 1
Cfg_NetPorts_Bond 0~255
Normal 2
1-2:Normal, 3-4:HSR
1-2:Normal, 3-4:RSTP
1-2:PRP, 3-4:PRP
IP_SyslogServer01 0.0.0.0~255.255.255.255
IP_SyslogServer02 0.0.0.0~255.255.255.255
IP_SyslogServer03 0.0.0.0~255.255.255.255
IP_SyslogServer04 0.0.0.0~255.255.255.255
Disabled
En_IP_Whitelist
Enabled
IP**_Whitelist 0.0.0.0~255.255.255.255
1. IP_LAN*
It is used to set IP address of Ethernet port * in the CPU plug-in module (*=1, 2, 3, 4).
This setting adopts dotted-decimal notation of IPv4. If the setting [En_LAN*] is configured as
"Disabled", this setting will be unnecessary to be configured. Please configure this setting
according to actual requirements.
2. Mask_LAN*
It is used to set subnet mask of Ethernet port * in the CPU plug-in module (*=1, 2, 3, 4).
This setting adopts dotted-decimal notation of IPv4. If the setting [En_LAN*] is configured as
"Disabled", this setting will be unnecessary to be configured. Please configure this setting
according to actual requirements.
3. En_LAN*
It is used to enable/disable Ethernet port * in the CPU plug-in module (*=1, 2, 3, 4).
4. Gateway
If there is no gateway, please configure this setting as "0.0.0.0". This setting adopts dotted-decimal
notation of IPv4.
5. Baud_Printer
2 It is used to set the baud rate of printer port.
It must be the same as the baud rate of the printer that is connected to this device.
6. En_AutoPrint
When the setting is set as "Enabled", they will be printed automatically when the event records
(such as, disturbance records, supervision events, IO events, etc.) are generated.
7. Protocol_RS485-1, Protocol_RS485-2
It must be the same as corresponding setting value of the communication client (for example, local
SCADA system, etc.).
8. Baud_RS485-1, Baud_RS485-2
It is used to set baud rate of rear RS-485 serial port 1 (2) in the CPU plug-in module.
It must be the same as corresponding setting value of the communication client (for example, local
SCADA system, etc.).
9. Addr_RS485-1, Addr_RS485-2
It is used to set communication address of rear RS-485 serial port 1 (2) in the CPU plug-in module.
It must be the same as corresponding setting value of the communication client (for example, local
SCADA system, etc.).
10. Cfg_NetPorts_Bond
It is used to set the Ethernet ports that are used as hot standby each other.
The setting is used to configure dual-networks switching, and it means that no dual-networks
switching is created when the setting is set as "0". The device supports a bond between any two
Ethernet ports, and the bond among three or above Ethernet ports is impermissible.
The devices communicate with SAS by station level network. In order to ensure reliable
communication, dual networks (i.e., network 1 and network 2) are adopted. Another special
communication mode based on dual networks is that Ethernet port 1 and Ethernet port 2 of the
device own the same IP address and MAC address, and network 1 and network 2 are used as hot
standby each other. When both network 1 and network 2 are normal, any of them is used to
communicate between the device and SAS. The device will automatically switch to the other
healthy network when one network is abnormal, which will not affect normal communication.
Taking a CPU module with four Ethernet ports as an example, each bit is corresponding with an 2
Ethernet port, i.e., Bit0, Bit1, Bit2 and Bit3 are corresponding with Ethernet port 1, Ethernet port 2,
Ethernet port 3 and Ethernet port 4 respectively. If a bond between Ethernet port 1 and Ethernet 2
is created, the setting [Cfg_NetPorts_Bond] is set as "3". The specific setting is shown as in
following figure.
Ethernet port 1
Port 4 Port 3 Port 2 Port 1 Setting Port 4 Port 3 Port 2 Port 1 Setting
Binary Bonding Bonding Binary
Bit 3 Bit 2 Bit 1 Bit 0 Value Bit 3 Bit 2 Bit 1 Bit 0 Value
0 0 1 1 0011 3 1 0 0 1 1001 9
Ethernet port 2
Port 4 Port 3 Port 2 Port 1 Setting Port 4 Port 3 Port 2 Port 1 Setting
Binary Bonding Bonding Binary
Bit 3 Bit 2 Bit 1 Bit 0 Value Bit 3 Bit 2 Bit 1 Bit 0 Value
0 1 0 1 0101 5 0 1 1 0 0110 6
Ethernet port 3
Port 4 Port 3 Port 2 Port 1 Setting Port 4 Port 3 Port 2 Port 1 Setting
Binary Bonding Bonding Binary
Bit 3 Bit 2 Bit 1 Bit 0 Value Bit 3 Bit 2 Bit 1 Bit 0 Value
1 0 1 0 1010 10 1 1 0 0 1100 12
Ethernet port 4
CPU Module
Take the device's Ethernet ports 1 & 2 for example and assume that Port 1 and Port 2 are bonded,
and Port 1 is connected to NET 1 while Port 2 is connected to NET 2.
⚫ After the device is powered on, only Port 1 is activated when both NET 1 and NET 2 are
normal.
⚫ If NET1 is abnormal, Port 2 cannot be activated if NET 2 is also abnormal. The device will
keep trying on Port 1.
⚫ If Port 2 is working, the device will maintain this state even if NET 1 has been restored to
normal. It will be switched to Port 1 only if NET 2 is abnormal.
11. B01.Opt_NetMode
It is used to select the network method of the CPU module located in slot No.1
Five options are available, please configure this setting according to actual requirements.
1) Normal
If this option is selected, all Ethernet ports of the CPU module adopt "Normal" mode. In the
2) 1-2:Normal, 3-4:HSR
If this option is selected, Ethernet port 1 and Ethernet port 2 of the CPU plug-in module adopt
"Normal" mode, and Ethernet port 3 and Ethernet port 4 of the CPU plug-in module adopt "HSR"
mode (IEC 62439-3 High-availability Seamless Redundancy) to realize data redundancy.
2 In the "HSR" mode, the principle of parallel operation to a single ring is applied to realize data
redundancy. For each message sent, the node sends two frames, one through each port. Both the
2 frames circulate in opposite directions over the ring. Every node forwards the frames it receives
from one port to another to reach the next node. When the originating sender node receives the
frame it sent, the sender node discards the frame to avoid loops.
3) 1-2:Normal, 3-4:PRP
If this option is selected, Ethernet port 1 and Ethernet port 2 of the CPU plug-in module adopt
"Normal" mode, and Ethernet port 3 and Ethernet port 4 of the CPU plug-in module adopt "PRP"
mode (IEC 62439-3 Parallel Redundancy Protocol) to realize data redundancy.
In the "PRP" mode, the data redundancy is realized in this way: the communication is performed in
parallel, i.e., the same data package is transmitted on both channels simultaneously. The received
package identity from one channel is compared with data package identity from the other channel.
If they are the same, the last package will be discarded.
4) 1-2:Normal, 3-4:RSTP
If this option is selected, Ethernet port 1 and Ethernet port 2 of the CPU plug-in module adopt
"Normal" mode, and Ethernet port 3 and Ethernet port 4 of the CPU plug-in module adopt "RSTP"
mode (Rapid Spanning Tree Protocol).
In the "RSTP" mode, the data redundancy is realized in this way: RSTP serves for the
reorganization of the network structure in case of network path error. In other words, RSTP
reroutes the data to another path after the failure of a network path.
5) 1-2:PRP, 3-4:PRP
If this option is selected, Ethernet port 1 and Ethernet port 2 of the CPU plug-in module adopt
"PRP" mode (IEC 62439-3 Parallel Redundancy Protocol) to realize data redundancy, and
Ethernet port 3 and Ethernet port 4 of the CPU plug-in module adopt "PRP" mode (IEC 62439-3
Parallel Redundancy Protocol) to realize data redundancy.
In the "PRP" mode, the data redundancy is realized in this way: the communication is performed in
parallel, i.e., the same data package is transmitted on both channels simultaneously. The received
package identity from one channel is compared with data package identity from the other channel.
If they are the same, the last package will be discarded.
12. IP_SyslogServer**
It is used to set IP address of syslog server ** (**=01, 02, 03, 04), and the device can upload audit
log to syslog server. The setting is invalid unless cyber security is configured in the device. This
Syslog is a communication protocol for message logging, it is used for security auditing in this
device.
13. En_IP_Whitelist
A whitelist is a list of IP addresses that are granted access to a certain system or protocol. When a
2
whitelist is used, all IP addresses are denied access, except those included in the whitelist. Please
configure this setting according to actual requirements
14. IP**_Whitelist
It is used to set No. ** IP address of the whitelist. (**=01...16) This setting is effective only when
the setting [En_IP_Whitelist] is enabled.
This setting adopts dotted-decimal notation of IPv4. Please configure this setting according to
actual requirements.
⚫ LCD
⚫ PCS-Studio
IEDNAME
Disabled
En_Send_MMS_Qual_Chg
Enabled
IEC61850
Opt_DualNetMode_MMS
GB32890
Disabled
En_IEC62351_TCP_Port
Enabled
Disabled
En_IEC61850_TCP_Port
Enabled
It cannot be an empty string and shall be unique within an SCL file. Its length should be less than
20 characters comprising letters or digits or underline ( _ ). The setting must start with an alpha
character and it is case sensitive.
A a B b C c D d E e F f
G g H h I i J j K k L l
M m N n O o P p Q q R r
S s T t U u V v W w X x
Y y Z z _ 0 1 2 3 4 5 6
7 8 9
If this setting is modified, the IED name in the CID file of this device will be changed
simultaneously and vice versa.
As shown in the following figure, the length of the setting [IEDNAME] is also limited by the length
of "LDName":
Length of LDName
In IEC 61850 Ed1: the length of "LDName" is not more than 32 characters.
In IEC 61850 Ed2: the length of "LDName" is not more than 64 characters.
2. En_Send_MMS_Qual_Chg
When the setting is set as "Enabled", and the "quality-change" attribute of "TrgOps" is enabled, 2
once any IEC 61850 MMS quality changes, this device will send the new quality spontaneously to
the communication client.
3. Opt_DualNetMode_MMS
It is used to select the MMS network communication mode with SCADA via network A and B of the
device.
IEC61850: Network mode with IEC 61850 protocol. In this mode, the instances of Report Control
Block (RCB) cannot be shared, so different clients should use different report instances to send
reports. The "IEC61850" mode is preferred overseas.
GB32890: Network mode with GB32890 standard. In this mode, for different clients meeting the
redundancy conditions of A and B networks, if one client enables an RCB instance, the device will
only send a report to the enabled client. When the enabled client is interrupted, another redundant
client will cancel and re-enable the RCB instance, and the device will send a report to the
re-enabled redundant client. The "GB32890" mode is a special mode widely used in China, which
needs to be used with clients supporting.
4. Pcnt_Deadband
It is used to set the change detection threshold for suddenly sending measurement value to the
SCADA via the device's Ethernet port using IEC 61850.
Only when the measurement value change which is greater than this setting will be sent to the
communication client (e.g.: local SCADA system, etc.) via the device's Ethernet port by using IEC
61850. It is expressed as a percentage value.
If the measurement values sent to the communication client changed within a small range too
frequently, but the communication client needs to ignore these frequent changes, please set this
setting to a bigger value.
If the measurement values sent to the communication client are required to be more precise,
please set this setting to a smaller value.
2 5. Threshold_ZeroDrift
For any measurement value which is sent to the communication client (for example, local SCADA
system, etc.) via the device's Ethernet port by using IEC 61850, if it is smaller than this setting, it
will be processed as "0".
If the measurement values sent to the communication client are relatively big, please set this
setting to a big value, so as to eliminate influence of zero drift.
If the measurement values sent to the communication client are relatively small, please set this
setting to a small value, so as to avoid too many measurement values being processed as "0"
mistakenly.
6. En_IEC62351_TCP_Port
To realize the station level IEC 62351 cyber security communication, please enable this setting
and configure certificate, private key, etc. of this device and corresponding IEC 62351 client.
If station level IEC 62351 cyber security communication is not required, please configure this
setting as "Disabled" to close the listening port of IEC 62351 protocol.
7. En_IEC61850_TCP_Port
If station level IEC 61850 communication is not required, please configure this setting as
"Disabled" to close the MMS listening port of IEC 61850 protocol.
⚫ LCD
⚫ PCS-Studio
Current_Language
Opt_Caption_103 Fixed_Chinese
Fixed_English
Disabled
En_Broadcast_LAN1
Enabled
Disabled
En_Broadcast_LAN2
Enabled
Disabled
En_Broadcast_LAN3
Enabled
Disabled
En_Broadcast_LAN4
Enabled
DisturbData
Format_Wave_Sent
File
Period_Measmt_Net 0~65535 1 s
Disabled
En_IEC103_TCP&UDP_Port
Enabled
1. Opt_Caption_103
It is used to select the language of group caption of IEC 60870-5-103 protocol and NR network
103 protocol.
The standard application of IEC 60870-5-103 protocol adopts a twisted pair EIA-485 connection
over a distance up to 500m. This device also supports the NR network 103 protocol that is an
alternative to IEC 60870-5-103 and is applicable through Ethernet network.
2. En_Broadcast_LAN*
Disabled: the device does not send UDP (User Datagram Protocol) messages through Ethernet
port * (*=1, 2, 3, 4) of the CPU plug-in module.
Enabled: the device sends UDP messages through Ethernet port * (*=1, 2, 3, 4).
3. Format_Wave_Sent
It is used to set the data format for sending waveform list using NR network 103 protocol.
If both ASDU23 mode and ASDU222 mode are supported onsite, it is recommended to configure
this setting as "File", because the waveform list can be transmitted faster.
4. Pcnt_Deadband_Net
It is used to set the change detection threshold for suddenly sending measurement value to the
SCADA via the device's Ethernet port using IEC 60870-5-103
Only when the measurement value change which is greater than this setting will be sent to the
communication client (for example, local SCADA system, etc.) via the device's Ethernet port using
NR network 103 protocol. It is expressed as a percentage value.
If the measurement values sent to the communication client changed within a small range too
frequently, but the communication client needs to ignore these frequent changes, please set this
setting to a bigger value.
If the measurement values sent to the communication client are required to be more precise,
please set this setting to a smaller value.
If the measurement value change is not required to be sent to the communication client, please
configure this setting as "0".
5. Period_Measmt_Net
It is used to set the time period for sending the measurement value to the communication client
(for example, local SCADA system, etc.) via the device's Ethernet port by using NR network 103 2
protocol.
If this device is not required send all measurement values to the communication client
spontaneously based on the integrity period, please configure this setting as "0".
6. En_IEC103_TCP&UDP_Port
It is used to enable/disable the TCP port and the UDP port when using NR network 103 protocol.
If NR network 103 communication is not required, please configure this setting as "Disabled" to
close the listening port of NR network 103 protocol.
When using NR network 103 protocol (network mode), al the settings in the
submenu MainMenu→Settings→Global Settings→Comm
Settings→IEC103 Settings need to be configued.
⚫ LCD
⚫ PCS-Studio
Disabled
En_TCP1_DNP
2 Enabled
Addr_Slave_TCP1_DNP 0~65519 1
Addr_Master_TCP1_DNP 0~65519 1
IP_Master_TCP1_DNP 0.0.0.0~255.255.255.255
Opt_Map_TCP1_DNP 0~4 1
t_AppLayer_TCP1_DNP 1~5 1 s
t_KeepAlive_TCP1_DNP 0~7200 1 s
Disabled
En_UR_TCP1_DNP
Enabled
Disabled
En_MsgCtrlUR_TCP1_DNP
Enabled
Num_URRetry_TCP1_DNP 2~10 1
t_UROfflRetry_TCP1_DNP 1~5000 1 s
Class_BI_TCP1_DNP 0~3 1
Class_AI_TCP1_DNP 0~3 1
t_Select_TCP1_DNP 0~240 1 s
t_TimeSynIntvl_TCP1_DNP 0~3600 1 s
1-BISingleBit
Obj01DefltVar_TCP1_DNP
2-BIWithStatus
1-BIChWoutT
Obj02DefltVar_TCP1_DNP 2-BIChWithAbsTime
3-BIChWithRelTime
1-AI32Int
Obj30DefltVar_TCP1_DNP 2-AI16Int
3-AI32IntWoutF
4-AI16IntWoutF
5-AI32Flt
1-AI32IntEvWoutT
Obj32DefltVar_TCP1_DNP 2-AI16IntEvWoutT 2
5-AI32FltEvWoutT
1-AO32Int
Obj40DefltVar_TCP1_DNP 2-AO16Int
3-AO32Flt
Disabled
En_TCP2_DNP
Enabled
Addr_Slave_TCP2_DNP 0~65519 1
Addr_Master_TCP2_DNP 0~65519 1
IP_Master_TCP2_DNP 0.0.0.0~255.255.255.255
Opt_Map_TCP2_DNP 0~4 1
t_AppLayer_TCP2_DNP 1~5 1 s
t_KeepAlive_TCP2_DNP 0~7200 1 s
Disabled
En_UR_TCP2_DNP
Enabled
Disabled
En_MsgCtrlUR_TCP2_DNP
Enabled
Num_URRetry_TCP2_DNP 2~10 1
t_UROfflRetry_TCP2_DNP 1~5000 1 s
Class_BI_TCP2_DNP 0~3 1
Class_AI_TCP2_DNP 0~3 1
t_Select_TCP2_DNP 0~240 1 s
t_TimeSynIntvl_TCP2_DNP 0~3600 1 s
1-BISingleBit
Obj01DefltVar_TCP2_DNP
2-BIWithStatus
1-BIChWoutT
Obj02DefltVar_TCP2_DNP 2-BIChWithAbsTime
3-BIChWithRelTime
2 1-AI32Int
2-AI16Int
Obj30DefltVar_TCP2_DNP 3-AI32IntWoutF
4-AI16IntWoutF
5-AI32Flt
1-AI32IntEvWoutT
Obj32DefltVar_TCP2_DNP 2-AI16IntEvWoutT
5-AI32FltEvWoutT
1-AO32Int
Obj40DefltVar_TCP2_DNP 2-AO16Int
3-AO32Flt
Disabled
En_TCP3_DNP
Enabled
Addr_Slave_TCP3_DNP 0~65519 1
Addr_Master_TCP3_DNP 0~65519 1
IP_Master_TCP3_DNP 0.0.0.0~255.255.255.255
Opt_Map_TCP3_DNP 0~4 1
t_AppLayer_TCP3_DNP 1~5 1 s
t_KeepAlive_TCP3_DNP 0~7200 1 s
Disabled
En_UR_TCP3_DNP
Enabled
Disabled
En_MsgCtrlUR_TCP3_DNP
Enabled
Num_URRetry_TCP3_DNP 2~10 1
t_UROfflRetry_TCP3_DNP 1~5000 1 s
Class_BI_TCP3_DNP 0~3 1
Class_AI_TCP3_DNP 0~3 1
t_Select_TCP3_DNP 0~240 1 s
t_TimeSynIntvl_TCP3_DNP 0~3600 1 s 2
1-BISingleBit
Obj01DefltVar_TCP3_DNP
2-BIWithStatus
1-BIChWoutT
Obj02DefltVar_TCP3_DNP 2-BIChWithAbsTime
3-BIChWithRelTime
1-AI32Int
2-AI16Int
Obj30DefltVar_TCP3_DNP 3-AI32IntWoutF
4-AI16IntWoutF
5-AI32Flt
1-AI32IntEvWoutT
Obj32DefltVar_TCP3_DNP 2-AI16IntEvWoutT
5-AI32FltEvWoutT
1-AO32Int
Obj40DefltVar_TCP3_DNP 2-AO16Int
3-AO32Flt
Disabled
En_TCP4_DNP
Enabled
Addr_Slave_TCP4_DNP 0~65519 1
Addr_Master_TCP4_DNP 0~65519 1
IP_Master_TCP4_DNP 0.0.0.0~255.255.255.255
Opt_Map_TCP4_DNP 0~4 1
t_AppLayer_TCP4_DNP 1~5 1 s
t_KeepAlive_TCP4_DNP 0~7200 1 s
Disabled
En_UR_TCP4_DNP
Enabled
Disabled
En_MsgCtrlUR_TCP4_DNP
2 Enabled
Num_URRetry_TCP4_DNP 2~10 1
t_UROfflRetry_TCP4_DNP 1~5000 1 s
Class_BI_TCP4_DNP 0~3 1
Class_AI_TCP4_DNP 0~3 1
t_Select_TCP4_DNP 0~240 1 s
t_TimeSynIntvl_TCP4_DNP 0~3600 1 s
1-BISingleBit
Obj01DefltVar_TCP4_DNP
2-BIWithStatus
1-BIChWoutT
Obj02DefltVar_TCP4_DNP 2-BIChWithAbsTime
3-BIChWithRelTime
1-AI32Int
2-AI16Int
Obj30DefltVar_TCP4_DNP 3-AI32IntWoutF
4-AI16IntWoutF
5-AI32Flt
1-AI32IntEvWoutT
Obj32DefltVar_TCP4_DNP 2-AI16IntEvWoutT
5-AI32FltEvWoutT
1-AO32Int
Obj40DefltVar_TCP4_DNP 2-AO16Int
3-AO32Flt
1. En_TCP*_DNP
It is used to enable/disable TCP port * when using DNP protocol (*=1, 2, 3, 4).
If network DNP communication is not required, please configure this setting as "Disabled" to close
the listening port of the network DNP protocol.
It is used to set the device's DNP address for the network DNP session * (*=1, 2, 3, 4).
It should be consistent with corresponding setting value of the communication client (for example,
local SCADA system, master station in control center, etc.) for the network DNP session *.
3. Addr_Master_TCP*_DNP
It is used to set the DNP address of the master (i.e., the communication client) for the network
DNP session * (*=1, 2, 3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
4. IP_Master_TCP*_DNP
It is used to set the IP address of the master (i.e., the communication client) for the network DNP
session * (*=1, 2, 3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
5. Opt_Map_TCP*_DNP
It is used to configure the DNP communication point map for the network DNP session * (*=1, 2, 3,
4).
Five options are available, each of them corresponds to a communication point map
pre-configured by the PCS-Studio configuration tool.
6. t_AppLayer_TCP*_DNP
It is used to set the timeout duration of the application layer for the network DNP session * (*=1, 2,
3, 4).
It must be the same as corresponding setting value of the communication client for the network
2 DNP session *.
7. t_KeepAlive_TCP*_DNP
It is used to set the heartbeat time interval for the network DNP session * (*=1, 2, 3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
8. En_UR_TCP*_DNP
It is used to to enable/disable the UR (Unsolicited Response) message function for the network
DNP session * (*=1, 2, 3, 4).
For the network DNP session *, if the communication client requires this device to support sending
UR (Unsolicited Response) messages, please configure this setting as "Enabled".
9. En_MsgCtrlUR_TCP*_DNP
The setting is used to determine the mode of sending Class 1, 2, 3 events from the network DNP
session * to the communication client spontaneously (*=1, 2, 3, 4).
Enabled: the communication client must activate UR reporting by enabling unsolicited application
function (Function code: 20). After activation, the network DNP session * of this device begins to
send Class 1, 2, 3 events to the communication client spontaneously.
Disabled: this device will send Class 1, 2, 3 events spontaneously to the communication client for
the network DNP session *.
10. Num_URRetry_TCP*_DNP
It is used to set the online retransmission number for sending the UR messages to the
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
11. t_UROfflRetry_TCP*_DNP 2
It is used to set the offline retransmission interval for sending the UR messages to the
communication client for the network DNP session * (*=1, 2, 3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
12. Class_BI_TCP*_DNP
It is used to select the default event class generated by the binary input points to the
communication client for the network DNP session * (*=1, 2, 3, 4).
0: If this option is selected, all the binary input points of this device will NOT generate any event to
the communication client for the network DNP session *.
1: If this option is selected, all the binary input points of this device will generate class 1 events to
the communication client for the network DNP session *.
2: If this option is selected, all the binary input points of this device will generate class 2 events to
the communication client for the network DNP session *.
3: If this option is selected, all the binary input points of this device will generate class 3 events to
the communication client for the network DNP session *.
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
13. Class_AI_TCP*_DNP
It is used to select the default event class generated by the binary input points to the
communication client for the network DNP session * (*=1, 2, 3, 4).
0: If this option is selected, all the binary input points of this device will NOT generate any event to
the communication client for the network DNP session *.
1: If this option is selected, all the binary input points of this device will generate class 1 events to
the communication client for the network DNP session *.
2: If this option is selected, all the binary input points of this device will generate class 2 events to
the communication client for the network DNP session *.
3: If this option is selected, all the binary input points of this device will generate class 3 events to
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
14. t_Select_TCP*_DNP
It is used to set the selection timeout duration of the remote control and the remote regulation for
the network DNP session * (*=1, 2, 3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
15. t_TimeSynIntvl_TCP*_DNP
It is used to set the time interval of the time synchronization function for the network DNP session *
(*=1, 2, 3, 4).
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
16. Obj01DefltVar_TCP*_DNP
It is used to select the default variation for object group 1 ("Obj01") for the network DNP session *
(*=1, 2, 3, 4).
If this option is selected, "Object group 1, variation 1" will be adopted to report the current value
of a binary input point. Variation 1 objects contain a single-bit binary input state without status
flags.
If this option is selected, "Object group 1, variation 2" will be adopted to report the current value
of a binary input point. Variation 2 objects contain a status octet that includes the state of the
binary input.
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
17. Obj02DefltVar_TCP*_DNP 2
It is used to select the default variation for object group 2 ("Obj02") for the network DNP session *
(*=1, 2, 3, 4).
If this option is selected, "Object group 2, variation 1" will be adopted to report events related to
a binary input point. Variation 1 objects contain an octet for reporting the state of the input and
status flags.
If this option is selected, "Object group 2, variation 2" will be adopted to report events related to
a binary input point. Variation 2 objects contain an octet for reporting the state of the input and
status flags, and the absolute time when the event occurred.
If this option is selected, "Object group 2, variation 3" will be adopted to report events related to
a binary input point. Variation 3 objects contain an octet for reporting the state of the input and
status flags, and the relative time when the event occurred. A preceding common
time-of-occurrence (CTO) object, group 51, establishes the basis of the relative time.
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
18. Obj30DefltVar_TCP*_DNP
It is used to select the default variation for object group 30 ("Obj30") for the network DNP session *
(*=1, 2, 3, 4).
If this option is selected, "Object group 30, variation 1" will be adopted to report the current value
of an analog input point. Variation 1 objects contain a flag octet and a 32-bit, signed integer value.
If this option is selected, “"Object group 30, variation 2" will be adopted to report the current
value of an analog input point. Variation 2 objects contain a flag octet and a 16-bit, signed integer
value.
If this option is selected, "Object group 30, variation 3" will be adopted to report the current value
2 of an analog input point. Variation 3 objects contain a 32-bit, signed integer value.
If this option is selected, "Object group 30, variation 4" will be adopted to report the current value
of an analog input point. Variation 4 objects contain a 16-bit, signed integer value.
If this option is selected, "Object group 30, variation 5" will be adopted to report the current value
of an analog input point. Variation 5 objects contain a flag octet and a 32-bit single-precision,
floating-point value.
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
19. Obj32DefltVar_TCP*_DNP
It is used to select the default variation for object group 32 ("Obj32") for the network DNP session *
(*=1, 2, 3, 4).
If this option is selected, "Object group 32, variation 1" will be adopted to report events related to
an analog input point. Variation 1 objects contain a flag octet and a 32-bit, signed integer value.
If this option is selected, "Object group 32, variation 2" will be adopted to report events related to
an analog input point. Variation 2 objects contain a flag octet and a 16-bit, signed integer value.
If this option is selected, "Object group 32, variation 5" will be adopted to report events related to
an analog input point. Variation 5 objects contain a flag octet and a 32-bit single-precision,
floating-point value.
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
20. Obj40DefltVar_TCP*_DNP
It is used to select the default variation for object group 40 ("Obj40") for the network DNP session *
(*=1, 2, 3, 4).
If this option is selected, "Object group 40, variation 1" will be adopted to report the status of an
2
analog output point. Variation 1 objects contain a flag octet and a 32-bit, signed integer value.
If this option is selected, "Object group 40, variation 2" will be adopted to report the status of an
analog output point. Variation 2 objects contain a flag octet and a 16-bit, signed integer value.
If this option is selected, "Object group 40, variation 3" will be adopted to report the status of an
analog output point. Variation 3 objects contain a flag octet and a 32-bit single-precision,
floating-point value.
It must be the same as corresponding setting value of the communication client for the network
DNP session *.
⚫ LCD
⚫ PCS-Studio
Disabled
En_Modbus_TCP_Port
Enabled
1. En_Modbus_TCP_Port
If network Modbus communication is not required, please configure this setting as "Disabled" to
2 ⚫ LCD
⚫ PCS-Studio
SampleRate_SV 0~65535 1
t_Dly_Interp_Net_SV 1500~15000 1 μs
t_Dly_Interp_P2P_SV 600~1500 1 μs
NetMode
Opt_RecvMode_SV P2P
Resv
1. SampleRate_SV
It is used to set sampling rate of the received SV data from the merging units.
It must be the same as the sampling rate of the transmitted SV data of the merging units.
2. t_Dly_Interp_Net_SV
It is used to set the backward time delay of SV interpolation for networking mode. This backward
time delay is used to meet the data quantity & quality requirements by the SV interpolation.
Base on engineering experience, its value is recommended to be kept as the default value
"2000μs". Please consult our engineer if modification is required.
3. t_Dly_Interp_P2P_SV
It is used to set the backward time delay of SV interpolation for peer-to-peer (P2P) mode. This
backward time delay is used to meet the data quantity & quality requirements by the SV
interpolation.
Base on engineering experience, its value is recommended to be kept as the default value "850μs".
4. Opt_RecvMode_SV
If "NetMode" is selected, all the devices must share the same clock source.
Resv: reserved
⚫ LCD
⚫ PCS-Studio
1. RecDur_PreTrigDFR
It is used to set the waveform recorded duration before the trigger element operates.
⚫ If this setting is configured as a too big value, the waveform file size will be too large, and
⚫ If this setting is configured as a too small value, the waveform file may be insufficient for fault
analysis.
2. RecDur_PostFault
2 It is used to set the waveform recorded duration after the DFR trigger element drops off.
If there are 2 or more DFR trigger elements, this setting refers to the waveform recorded duration
after the last trigger element drops off.
⚫ If this setting is configured as a too big value, the waveform file size will be too large, and
more storage space and transmission bandwidth will be required.
⚫ If this setting is configured as a too small value, the waveform file may be insufficient for fault
analysis.
"Edge trigger" (Including falling-edge trigger, rising-edge trigger, bilateral-edge trigger) 1.000s
3. MaxRecDur_PostTrigDFR
It is used to set the maximum waveform recorded duration after the trigger element operates.
If there are 2 or more DFR trigger elements, this setting refers to the maximum waveform recorded
duration after the 1st trigger element operates.
⚫ If this setting is configured as a too big value, the waveform file size will be too large, and
more storage space and transmission bandwidth will be required.
⚫ If this setting is configured as a too small value, the waveform file may be insufficient for fault
analysis.
1. Bxx.Name_**_GCommLink
It is used to set the user-defined part of GOOSE communication link** in the module located in slot
No.xx, and this user-defined part is designed to customize the GOOSE communication link name.
It will determine the corresponding part of the alarm signals, logic link settings, statistic data, etc.
The maximum permissible length of this setting is 30 characters, and this setting is case sensitive.
A a B b C c D d E e F f
G g H h I i J j K k L l
M m N n O o P p Q q R r
S s T t U u V v W w X x
Y y Z z _ 0 1 2 3 4 5 6
7 8 9
2. Bxx.Name_**_SVCommLink
It is used to set the user-defined part of SV communication link** in the module located in slot
No.xx, and this user-defined part is designed to customize the SV communication link name. It will
determine the corresponding part of the alarm signals, logic link settings, statistic data, etc.
A a B b C c D d E e F f
G g H h I i J j K k L l
M m N n O o P p Q q R r
2 S s T t U u V v W w X x
Y y Z z _ 0 1 2 3 4 5 6
7 8 9
⚫ PCS-Studio
Conventional
Opt_TimeSyn SAS 1
NoTimeSyn
OffsetHour_UTC -12~12
OffsetMinute_UTC 0~60
IP_Server_SNTP 0.0.0.0~255.255.255.255
IP_StandbyServer_SNTP 0.0.0.0~255.255.255.255
Enabled
En_ConvModeSNTP
Disabled
DST.En Enabled
Disabled
DST.OffsetMinute 0~255 1
Jan
Feb 2
Mar
Apr
May
Jun
DST.MonthInYear_Start 1
Jul
Aug
Sep
Oct
Nov
Dec
1st
2nd
DST.WeekInMonth_Start 3rd 1
4th
Last
Sunday
Monday
Tuesday
DST.DayInWeek_Start Wednesday 1
Thursday
Friday
Saturday
DST.HourInDay_Start 0~23 1
DST.MonthInYear_End Jan 1
Feb
Mar
Apr
2 May
Jun
Jul
Aug
Sep
Oct
Nov
Dec
1st
2nd
DST.WeekInMonth_End 3rd 1
4th
Last
Sunday
Monday
Tuesday
DST.DayInWeek_End Wednesday 1
Thursday
Friday
Saturday
DST.HourInDay_End 0~23 1
1. Opt_TimeSyn
⚫ Conventional
When the setting [Opt_TimeSyn] is set as "Conventional", the following clock synchronization
signals can be accepted by this device. However, if none of the following signals is received, an
alarm signal named “Alm_TimeSyn” will be issued, and the clock synchronization mode will
change to the "SAS" mode automatically.
IEEE 1588: Clock message based on IEEE 1588 via Ethernet network
⚫ SAS
When the setting [Opt_TimeSyn] is set as "SAS", the following clock synchronization signals can
be accepted by this device. However, if none of the following signals is received, an alarm signal
named "Alm_TimeSyn" will be issued.
SNTP: Unicast (point-to-point) & broadcast SNTP mode via Ethernet network
Clock messages: IEC 60870-5-103 protocol, Modbus protocol and DNP3.0 protocol
⚫ NoTimeSyn
If the clock synchronization function is not required, please select "NoTimeSyn", and the device
will not send time synchronization alarm signal.
The clock message via IEC103 protocol is INVALID when the device
receives the IRIG-B signal through RS-485 port.
2. OffsetHour_UTC
The settings [OffsetHour_UTC] and [OffsetMinute_UTC] cooperate to determine the local time
zone of this device.
3. OffsetMinute_UTC
The settings [OffsetHour_UTC] and [OffsetMinute_UTC] cooperate to determine the local time
zone of this device.
4. IP_Server_SNTP
It is used to set the IP address of the server when SNTP time synchronization mode is selected.
5. IP_StandbyServer_SNTP
2 It is used to set the IP address of the standby server when SNTP time synchronization mode is
selected.
When device failed to connect the SNTP server, it will try to connect the standby SNTP server.
It must be the same as corresponding setting value of the standby SNTP server.
6. En_ConvModeSNTP
It is used to enable/disable receive the SNTP message as the backup clock synchronization
source while hardware-based clock (IRIG-B, IEEE 1588 or PPS) is lost when the setting
[OptTimeSyn] is configured as "Conventional". However, the alarm "Alm_TimeSyn" will still be
issued, so as to indicate the failure of the conventional clock synchronization.
7. DST.En
8. DST.OffsetMinute
It is used to set the minute offset of DST, i.e. the difference between DST time and local time.
9. DST.MonthInYear_Start
10. DST.WeekInMonth_Start
11. DST.DayInWeek_Start
12. DST.HourInDay_Start
2
It is used to set the hour in day when daylight time starts.
13. DST.MonthInYear_End
14. DST.WeekInMonth_End
15. DST.DayInWeek_End
16. DST.HourInDay_End
3 Protection Settings
Table of Contents
List of Tables
For the setting calculation in relation to power system operating conditions, it shall base on the
usual operating conditions as its calculation reference. Usual operating conditions usually refer to
normal operating conditions or the maintenance case that adjacent line or a component protected
is out of service. For the system whose operating mode changes greatly, the operating conditions
which setting calculation refers to should be confirmed by dispatching department according to
specific cases.
For all the calculation equations listed in this instruction manual, the results including current,
voltage and impedance are all expressed in the form of secondary actual value, unless it is 3
specifically mentioned. Setting values of the line protection shall be transformed into secondary
side value before inputting in the relay.
Formulas for converting primary settings to secondary ones are shown as below:
1
⚫ 𝐼SEC = 𝐼PRIM × CT ratio
Where:
I1n
CT ratio = ( I1n : Primary rated current; I2n : Secondary rated current).
I 2n
1
⚫ 𝑈SEC = 𝑈PRIM × VT ratio
Where:
U1n
VT ratio = ( U1n : Primary rated voltage; U2n : Secondary rated voltage)
U 2n
CT ratio
⚫ 𝑍SEC = 𝑍PRIM × VT ratio
Where:
All current settings, voltage settings and impedance settings are secondary
value converted from primary value by CT ratio and VT ratio.
⚫ LCD
⚫ PCS-Studio
Disabled
FD.NOC.En
Enabled
1. FD.DPFC.I_Set
It should be higher than maximum variation of load current and typically 0.2In. For line with heavy
load fluctuation like those for electric railway, rolling mill or aluminum-smelting, the setting should
be increased properly so that frequent pickup of the device could be avoided.
2. FD.ROC.3I0_Set
It should be greater than maximum three phases unbalance current. All protection functions
relevant to zero-sequence current will be controlled by this setting. Therefore, it is the most
sensitive among all zero-sequence overcurrent elements.
The settings of fault detector element at both ends should be set based on
the same primary value.
3
3. FD.NOC.I2_Set
It should be greater than maximum negative-sequence unbalance current. All protection functions
relevant to negative-sequence current will be controlled by this setting. Therefore, it is the most
sensitive among all negative-sequence overcurrent elements.
4. FD.NOC.En
⚫ LCD
⚫ PCS-Studio
FO.LocID 0~65535 1
FO.RmtID 0~65535 1
64
FO.BaudRate kbps
2048
G.703
FO.Protocol
C37.94
FOx.Nx64k_C37.94 1~12 1
Ext
FOx.Opt_ClkSrc
Int
Disabled
3 FOx.En
Enabled
1. FO.LocID
The setting principle is same with the setting [FO.RmtID] which is shown as bellow.
2. FO.RmtID
In order to ensure reliability of the device when digital communication channel is applied, settings
[FO.LocID] and [FO.RmtID] are provided as identity code to distinguish uniquely the device at
remote end using same channel.
Under normal conditions, the identity code of the device at local end should be different with that at
remote end. In addition, it is recommended that the identity code of all devices, i.e., the setting
[FO.LocID], should be unique in the substation. The setting range is from 0 to 65535.
The setting [FO.LocID] should be different between the local device and the remote device.
The local device's [FO.LocID] should be as same as the remote device's [FO.RmtID].
The end with greater [FO.LocID] is chosen as the master end for sampling synchronism, the other
end with smaller [FO.LocID] is slave end.
⚫ Loopback test
The setting [FO.LocID] is packaged in the message frame and transmitted to the remote end.
When the [FO.LocID] of the device at remote end received by local device is same to the setting
[FO.RmtID] of local device, the message received from the remote end is valid, and protection
information involved in message is read. When these settings are not matched, the message is
considered as invalid and protection information involved in message is ignored, corresponding
alarms will be issued.
3. FO.BaudRate
For the dedicated optical fiber connection, both 64kbits/s and 2048kbits/s are suitable. But
2048kbits/s is recommended under this situation.
For the multiple connection with external communication equipment such as PCM or SDH, it
should be set as the requirement of communication equipment.
4. FO.Protocol
C37.94 is the protocol which used to define data frame transferred via optical fiber interfaces.
For the dedicated optical fiber connection, both G.703 and C37.94 are suitable. And C37.94 is
recommended under this situation.
For the multiple connection with external communication equipment such as PCM or SDH, And
G.703 is recommended under this situation. By the way, the MUX equipment should be used as
photoelectric conversion device.
For double channels, if one channel uses dedicated optical fiber and the other channel uses
multiple connection, G.703 is recommended under this situation.
5. FOx.Nx64k_C37.94
It is the times of 64kbits/s, which is an N×64kbits/s standard defined by IEEE C37.94 standard.
6. FOx.Opt_ClkSrc
The device can communicate in two modes via multiplex channel or dedicated optical fibre.
The device transmits and receives messages based on respective clocks, which are called
transmit clock (i.e. clock TX) and receive clock (i.e. clock RX) respectively. Clock RX is fixed to be
extracted from message frame, which can ensure no slip frame and no error message received.
Clock TX has two options:
⚫ Use internal crystal clock, which is called internal clock (master clock)
Depend on the clock used by the device at both ends, there are three modes.
⚫ Mode 3: Master-slave mode (one of them uses internal clock, the other uses external clock)
If the device uses multiplex PCM/SDH channel, the setting [FOx.Opt_ClkSrc] at both ends should
be set accordingly.
3 ⚫ The setting [FOx.Opt_ClkSrc] is recommended set as "Int" when the function, "Retiming", of
the communication equipment is disabled.
⚫ The setting [FOx.Opt_ClkSrc] is recommended set as "Ext" when the function, "Retiming", of
the communication equipment is enabled.
If the device uses dedicated optical fibre channel, mode 1 and mode 3 can be used. Mode 1 is
recommended in considering simplification to user, i.e. the setting [FOx.Opt_ClkSrc] at both ends
should be set as "Int".
7. FOx.En
⚫ PCS-Studio
87L.XC1L (40~60000)/In 1 Ω
87L.XC0L (40~60000)/In 1 Ω
87L.Z_LocReac (40~60000)/In 1 Ω
3
87L.Z_LocGndReac (40~60000)/In 1 Ω
87L.Z_RmtReac (40~60000)/In 1 Ω
87L.Z_RmtGndReac (40~60000)/In 1 Ω
Disabled
87L.En
Enabled
Disabled
87L.En_DPFC1
Enabled
Disabled
87L.En_DPFC2
Enabled
Disabled
87L.En_Biased1
Enabled
Disabled
87L.En_Biased2
Enabled
Disabled
87L.En_Neutral
Enabled
Disabled
87L.En_InterTrp
Enabled
Disabled
87L.En_LocDiff
Enabled
Disabled
87L.En_CapCurrComp
Enabled
Disabled
87L.En_CTS_Blk
Enabled
1. 87L.I_Pkp
It should be greater than the maximum unbalance current under the normal load conditions. If the
3 capacitive current is too big to be ignored, it should be considered. Considering the CT errors and
other measuring errors, additional safety margin should be also added. Normally, the
corresponding primary current is recommended to set as 400A~700A.
When the setting [87L.En_CapCurrComp] is set as "Disabled", the sensitivity will be decreased,
and the setting can be appropriately increased. The corresponding primary current is
recommended to set as 500A~800A.
2. 87L.I_Alm
When the propagation delay of the channel is uncertain, so the currents at both ends cannot
accurately be synchronized. For large load current, larger differential current may be generated so
as to lead to undesired operation of current differential protection. Hence, differential current
needs to be supervised.
According to unbalanced differential current under load conditions, if differential current is greater
than the threshold value, the device will issue an alarm to indicate that differential current is
abnormal.
The threshold of discriminating differential current abnormality needs to cooperate with pickup
setting of current differential protection, at the same time it should be greater than unbalanced
current under normal conditions.
3. 87L.I_Pkp_CTS
When CT circuit fails, this pickup setting of current differential protection will be switched into
[87L.I_Pkp_CTS] if the setting [87L.En_CTS_Blk] is set as "Disabled".
If the setting [87L.En_CTS_Blk] is set as "Enabled", current differential protection will be blocked
even the differential current exceed the setting [87L.I_Pkp_CTS]. Generally, this setting should be
greater than the maximal load current to prevent the possible maloperation under heavy load
condition. It reduces the sensitivity, but the reliability is increased.
4. 87L.K_Cr_CT
If CTs' ratio at two ends of the transmission line is different, the currents be converted to one
reference value. Regarding local end as the referenced end, differential current and restraint
current can be calculated since the current of the opposite end is converted by the setting.
[87L.K_Cr_CT]. If the CT ratio on both ends are same, this setting should be set as "1" on both
ends, and its recommended value is 1.
IM1n and IM2n are primary rated current and secondary rated current of terminal M respectively
3
IN1n and IN2n are primary rated current and secondary rated current of terminal N respectively
The secondary rated current is considered internally, so only primary rated current should be
calculated.
Suppose CT ratio is as below, and then, IM1n is not less than IN1n
Terminal M Terminal N
𝐼𝑀1𝑛 𝐼𝑁1𝑛
𝐾M = 𝐾𝑁 =
𝐼𝑀2𝑛 𝐼𝑁2𝑛
𝐼𝑁1𝑛
[87L.K_Cr_CT]=1.00 [87𝐿. 𝐾_𝐶𝑟_𝐶𝑇] =
𝐼𝑀1𝑛
For example:
Terminal M Terminal N
KM = 2500: 1 𝐾𝑁 = 1250: 5
[87L.K_Cr_CT]=1.00 [87L.K_Cr_CT]=0.50
5. 87L.I_Knee1
It is used to set current setting of knee point 1 for steady-state current differential element.
It should be greater than the restrained current corresponding to point A as shown in figure below.
The sensitivity and reliability should be considered, and the undesired operation for external fault
with CT saturation should be avoided.
IDiffΦ
k=1
k2
k1
IH
IBiasΦ
A Knee1 Knee2
3 Where:
Knee1 and Knee2 are the restraint current setting [87L.I_Knee1] and [87L.I_Knee2] respectively.
6. 87L.I_Knee2
It is used to set current setting of knee point 2 for steady-state current differential element.
It should be greater than the setting [87L.I_Knee1]. It is indicated in the figure as above. The
sensitivity and reliability should be considered, and the undesired operation for external fault with
CT saturation should be prevented.
If more reliability is required, the setting could be decreased, for example, 1A. If more sensitivity is
required, the setting could be increased, for example, 3A. Because the DPFC differential element
can meet the sensitivity requirement, it is not recommended to increase the setting due to
sensitivity requirement.
7. 87L.Slope1
It is used to set the slope 1 of steady-state current differential element. It is indicated in the figure
as above.
The sensitivity and reliability should be considered, and the unwanted operation for external fault
with CT saturation should be prevented.
If more reliability is required, the setting could be increased, for example, 0.6. Normally it should
be less than the setting [87L.Slope2]. Because the DPFC differential element can meet the
sensitivity requirement, it can not be less than 0.5.
8. 87L.Slope2
It is used to set the slope 2 of steady-state current differential element. It is indicated in the figure
as above.
The sensitivity and reliability should be considered, and the unwanted operation for external fault
If more reliability is required, the setting could be increased, for example, 0.8. If more sensitivity is
required, the setting could be increased, for example, 0.6. Normally, it should be greater than the
setting [87L.Slope1].
9. 87L.t_Op_Neutral
It is used to set the time delay for neutral current differential element.
10. 87L.XC1L
3
It is used to set positive-sequence capacitive impedance of the transmission line.
The setting principle is same with the [87L.XC0L] which is shown as bellow.
11. 87L.XC0L
If the setting [87L.En_CapCurrComp] is set as "Enabled", they should be set based on actual
parameters of the whole line (secondary value). If actual parameters are not available, the
following data can be used as a reference. The capacitive impedance and capacitive current of
overhead line per 100km based on different voltage class:
If the setting [87L.En_CapCurrComp] is set as "Disabled", the setting will not be used in
caculation. They can be set as any value within their setting range.
Its recommended value is 10000Ω. Normally, zero-sequence capacitive impedance must be equal
to or greater than positive-sequence capacitive impedance.
12. 87L.Z_LocReac
If shunt reactor is equipped with the local substation, it shall be set as the secondary value of
shunt reactor of local substation, otherwise, it can be set as "60000Ω". When the logic setting
[87L.En_CapCurrComp] is set as "Disabled", this setting will not be used in the calculation and
can be set as any value within its setting range.
13. 87L.Z_LocGndReac
It is used to set the impedance setting of ground reactor of the local end.
If ground reactor is equipped with the local substation, it shall be set as the secondary value of
ground reactor of local substation, otherwise, it can be set as "60000Ω". When the logic setting
[87L.En_CapCurrComp] is set as "Disabled", this setting will not be used in the calculation and
can be set as any value within its setting range.
14. 87L.Z_RmtReac
If shunt reactor is equipped with the remote substation, it shall be set as the secondary value of
shunt reactor of remote substation, otherwise, it can be set as "60000Ω". When the logic setting
[87L.En_CapCurrComp] is set as "Disabled", this setting will not be used in the calculation and
can be set as any value within its setting range.
15. 87L.Z_RmtGndReac
If ground reactor is equipped with the remote substation, it shall be set as the secondary value of
ground reactor of remote substation, otherwise, it can be set as "60000Ω". When the logic setting
[87L.En_CapCurrComp] is set as "Disabled", this setting will not be used in the calculation and
can be set as any value within its setting range.
16. 87L.En
17. 87L.En_DPFC1
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
18. 87L.En_DPFC2
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
19. 87L.En_Biased1
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
20. 87L.En_Biased2
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
21. 87L.En_Neutral
3
It is used to enable/disable neutral current differential element.
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
22. 87L.En_InterTrp
The precondition is that the setting [87L.En] is set as "Enabled". Its recommended value is
"Enabled".
When a fault associated with high resistance occurs in the outlet of long transmission line, the
device of local end, which is near the fault, can pick up immediately, but, considering the influence
of a considerable power source, the device of the remote end, which is far from the fault, cannot
pick up due to inapparent fault component. In order to avoid this case, any protection (such as
distance protection, overcurrent protection and etc.) of local end operates, inter-trip signal of
corresponding phase will be sent to the remote end. After receiving the inter-trip signal, the device
of the remote end can pick up, if corresponding basic differential condition is met and the setting
[87L.En_InterTrp] is set as "Enabled", the faulty phase will be inter-tripped. This setting is
generally set as "Enabled".
23. 87L.En_LocDiff
If the setting [87L.En_LocDiff] is set as "Enabled", then independent current differential protection
is enabled which means local current differential protection can operate without permissive signal
from remote end.
When CT circuit failure occurs at one end, FD and current differential protection on the end may
operate. However, FD on the other end will not operate and not send any permissive signal of
current differential protection. Therefore, the current differential protection will not maloperate.
If the operation is not allowed for differential protection during CT circuit failure under normal
condition, then [87L.En_LocDiff] should be set as "Disabled".
24. 87L.En_CapCurrComp
If the capacitive current should be compensated to increase the sensitivity, it should be set as
"Enabled".
25. 87L.En_CTS_Blk
If CT circuit failure associated with internal fault or pickup due to system disturbance is detected,
the device will show two kinds of behavior.
3 If logic setting [87L.En_CTS_Blk] (differential protection being blocked during CT circuit failure) is
set as "Enabled", the current differential protection will be blocked.
If logic setting [87L.En_CTS_Blk] is set as "Disabled" and the current differential current of the
faulty phase is more than the differential current setting [87L.I_Pkp_CTS] during CT circuit failure,
the current differential protection will operate.
⚫ LCD
⚫ PCS-Studio
POTT
85.Opt_Mode PUTT
Blocking
Disabled
85.En_Ch_PhSeg
Enabled
Disabled
85.En_WI
Enabled
Disabled
85.En_WI_Pkp
Enabled
Disabled
85.En_Trp_Send
Enabled
Disabled
85.En_PilotTrp_Send
Enabled
Disabled
3
85.En_52b_Send
Enabled
Disabled
85.En_52b_Echo
Enabled
Disabled
85.Z.En
Enabled
Disabled
85.En_Unblocking1
Enabled
Phase-to-phase
85.Opt_Ch1
Phase-to-ground
Disabled
85.ZX.En
Enabled
1. 85.Opt_Mode
2. 85.En_Ch_PhSeg
Generally, for parallel lines or multi-circuits, this setting is recommended to be set as "Enabled".
The permissive scheme can use PLC channel or optic fiber channel as communication channel.
These signals, which are used to initiate sending permissive signal, can use phase-segregated
signal scheme or common signal scheme. For pilot protection adopting common signal scheme,
the signal "85-x.Recv1" is used. For pilot protection adopting phase-segregated signal scheme,
3 three signals are used, they are "85-x.Recv1" for phase A, "85-x.RecvB" for phase B and
"85-x.RecvC" for phase C.
3. 85.En_WI
If the device locates on weak end, it should be enabled. Otherwise, it should be disabled.
4. 85.U_UV_WI
This setting is set to be lower than the minimum voltage value under normal operation condition.
Usually, it is recommeded be set as 60% rated phase voltage.
In case of an internal fault on the line, the fault current supplied to the fault point from the weak
power source is very small or even nil, both forward and reverse element do not operate. Thus, the
pilot distance protection could not operate at both ends of the line. The weak infeed logic is used
for this condition.
When the weak infeed logic is enabled ([85.En_WI] is set as "Enabled"), ,if the voltage is lower
than the setting [85.U_UV_WI] after the device picks up, upon receiving the signal from the remote
end, the weak infeed end will echo the signal back for 200ms. In this way, the pilot distance
protection on the other end can operate.
5. 85.En_WI_Pkp
This setting is recommended to be set as "Enabled" for the weak infeed end when the device can
not pick up for internal faults in some extreme situations.
6. 85.En_Trp_Send
It is used to enable/disable sending permissive signals by any tripping. If only the pilot protection
(pilot distance protection and pilot directional earth-fault protection) is required to trigger sending
permissive signal, this setting can be set as "Disabled".
7. 85.En_PilotTrp_Send
It is used to enable/disable sending permissive signals when the pilot protection (pilot distance
This logic is a supplement for the pilot protection. When the pilot protection operates, the
permissive signal will be extended to make sure the device on the other end can reliably receive
the permissive signal and operate.
8. 85.En_52b_Send
It is used to enable/disable sending permissive signals by the circuit breaker open position when
the device picks up.
9. 85.En_52b_Echo 3
It is used to enable/disable echo permissive signals by the circuit breaker open position when the
device does not pick up.
10. 85.Z.En
11. 85.En_Unblocking1
This setting is recommended to be set as "Enabled" when unblocking scheme is required due to
pilot channel failure.
When pilot channel fails, the device may not receive signal from the remote end. For this case,
pilot distance protection can adopt unblocking scheme. While pilot channel is blocked, the
signaling equipment will provide a contact to the device as unblocking signal. When the device
receives unblocking signal from the signaling equipment, it will recognize channel failure, and
unblocking signal will be taken as permissive signal temporarily.
12. 85.Opt_Ch1
It is recommended that the blocking logic adopts phase-to-ground channel, and the permissive
logic adopts phase-to-phase channel.
13. 85.t_Unblocking1
It is used to set the releasing time of unblocking scheme for pilot channel 1 when the setting
[85.En_Unblocking1] is set as "Enabled".
14. 85.t_DPU_Blocking1
It is used to set time delay for blocking scheme of pilot distance protection operation.
If the setting [85.Opt_PilotMode] is set as "Blocking", blocking scheme will operate with a time
delay [85.t_DPU_Blocking1] if both forward element operates and blocking signal is not received.
This time delay should be longer than the summation of the propagation time delay of pilot
3 channel and pickup time of fault detector element. In addition, the time dalay should prevent from
maloperation under current reversal condtion. The recommended setting principle is as follows.
[85.t_DPU_Blocking1]=t1+t2+Δt
Where:
Δt is the margin time, in order to prevent pilot distance protection from undesired operating under
current reversal condtion, it normally should be more than 50ms
15. 85.t_DPU_CR1
[85.t_DPU_CR1]=T1-T2-T3
Where:
T1 indicates that the transfer time during which the direction judgement of the device that is near
the fault in local line changes from reverse direction to forward direction when a fault happens to
the adjacent line. It is necessary to consider the operating time of the device that is near the fault
in the adjacent line, the operating time of the contact, the operating time of the circuit breaker and
the operating time of the forward direction element.
T2 indicates the channel delay, which shall be set according to the actual channel delay.
T3 indicates the time during which the remote device sends the signal, which shall be set
according to the actual sending time of the remote device.
Based on the above setting principles, if the fastest operating time of the device in the adjacent
line is calculated as 10ms, the fastest operating time of the contact is calculated as 5ms, the
fastest operating time of the circuit breaker is calculated as 25ms, and the fastest operating time of
the forward direction element is calculated as 15ms, then:
T1=10ms+5ms+25ms+15ms=55ms
[85.t_DPU_CR1]=55ms-15ms-20ms=20ms
The setting should be not less than 10ms, which ensure that the current reversal logic does not
incorrectly detect for internal fault.
16. 85.t_DDO_CR1
[85.t_DDO_CR1]=T1+T2
Where:
T1 indicates the transfer time difference between local device whose direction judgement changes
from reverse direction to forward direction and remote device whose direction judgement changes
from forward direction to reverse direction, and a certain time margin shall be considered.
T2 indicates the dropoff time of the channel delay, which shall be set according to the actual
situation of the channel.
Based on the above setting principles, if the transfer time difference between local device and
remote device is calculated as 10ms, the dropoff time of the channel delay is calculated as 15ms,
then:
[85.t_DDO_CR1]=10ms+15ms=25ms
If the dropoff of the forward direction element of the remote device is slow, T2 needs to increase
the margin appropriately according to the actual situation.
17. 85.ZX.En
Zone extension is usually used in combination with automatic reclosure. It can be activated
internally by pilot protection, the integrated automatic reclosure or externally by a binary input.
When pilot protection is out of service due to pilot channel failure or no pilot protection is provided,
as a supplement of pilot protection, zone extension can clear the fault within the whole line
instantaneously. Different from pilot distance protection, zone extension can also operate for
external close up fault in parallel line, but power supply can be restored by AR. So zone extension
should be blocked when AR is out of service and is not ready.
18. 85.t_DPU_ZX
It is used to set pickup time delay for zone extension of pilot distance protection
The delay time is set in accordance with the application type, usually to zero or a very small delay.
⚫ PCS-Studio
3 Project NodeDevice NodeSettingGroup*Protection SettingsPilot Scheme Settings
Disabled
85.DEF.En
Enabled
Disabled
85.DEF.En_BlkAR
Enabled
Disabled
85.DEF.En_IndepCh
Enabled
Disabled
85.En_Unblocking2
Enabled
1. 85.DEF.En
2. 85.DEF.En_BlkAR
3. 85.DEF.En_IndepCh
Disabled: pilot directional earth-fault protection sharing same channel with pilot distance protection
Pilot directional earth-fault protection can share the channel with pilot distance protection or use
independent channel to initiate sending signal.
3
When the setting [85.DEF.En_IndepCh] is set as "Disabled", pilot directional earth-fault protection
which comprises permissive scheme and blocking scheme can share pilot channel 1 with pilot
distance protection.
When the setting [85.DEF.En_IndepCh] is set as "Enabled", pilot directional earth-fault protection
which comprises permissive scheme and blocking scheme uses independent pilot channel 2.
For underreach mode (PUTT), pilot directional earth-fault should adopt independent pilot channel
2 and work as overreach mode. That means [85.DEF.En_IndepCh] should set as "Enabled".
4. 85.En_Unblocking2
It is used to enable/disable unblocking scheme for pilot DEF via pilot channel 2. This setting is
recommended to be set as "Enabled" when unblocking scheme is required due to pilot channel
failure.
If pilot directional earth-fault protection uses independent channel 2 to initiate sending and
receiving signal, the signal will not be received from remote end when pilot channel fails. For this
case, pilot protection can adopt unblocking scheme. While pilot channel is blocked, the signaling
equipment will provide a contact to the device as unblocking signal. When the device receives
unblocking signal from the signaling equipment, it will recognize channel failure, and unblocking
signal will be taken as permissive signal temporarily.
5. 85.t_Unblocking2
It is used to set pickup releasing time delay of unblocking scheme for pilot channel 2.
It is used to set the releasing time of unblocking scheme for pilot channel 2 when the setting
[85.En_Unblocking2] is set as "Enabled".
6. 85.DEF.3I0_Set
It should ensure that pilot directional earth-fault protection is sensitive enough when an earth fault
happens in the remote end of the line.
7. 85.DEF.t_DPU
8. 85.t_DPU_CR2
It is used to set time delay pickup for current reversal logic when pilot directional earth-fault
protection adopts independent pilot channel 2.
Generally, there is a time delay in pilot directional earth-fault protection. Hence, the setting can be
decreased appropriately if the time delay can meet the requirement of corret operation during
current reversal. Otherwise, the setting shall be set refer to the setting [85.t_DPU_CR1].
3 9. 85.t_DDO_CR2
It is used to set time delay dropoff for current reversal logic when pilot directional earth-fault
protection adopts independent pilot channel 2.
Generally, there is a time delay in pilot directional earth-fault protection. Hence, the setting can be
decreased appropriately if the time delay can meet the requirement of corret operation during
current reversal. Otherwise, the setting shall be set refer to the setting [85.t_DDO_CR1].
In the case of parallel lines, pilot distance protection shall have the
capability to protect the whole line when an earth fault happens.
⚫ PCS-Studio
Disabled
21D.En
Enabled
It is an additional function of distance zone1 protection to accelerate its operation for the close-up
fault. It is set according to underreaching scheme, usually take 60%~70% of the line impedance,
and as for double-circuit lines, 50% of the line impedance is recommended.
2. 21D.En
It is a logic setting, which is used to enable or disable DPFC distance protection. If the line length
is too short (for example, less than 10km) or the SIR (Source Impedance Ratio) is too large
(SIR>30).
⚫ LCD
⚫ PCS-Studio
21L.Ang_Alpha 5~30 1 °
21L.Ang_Beta 5~30 1 °
21L.LoadEnch.phi 5~50 1 °
Mho
21L.ZG.Opt_Characteristic
Quad
Mho
3 21L.ZP.Opt_Characteristic
Quad
21L1.phi1_Reach 30~89 1 °
21L1.ZG.RCA 0~45 1 °
21L1.ZG.phi_Shift 0~30 1 °
Disabled
21L1.ZG.En
Enabled
Disabled
21L1.ZG.En_BlkAR
Enabled
Disabled
21L1.ZG.En_3I0
Enabled
Disabled
21L1.ZG.En_NeuDir_Blk
Enabled
Disabled
21L1.ZG.En_NegDir_Blk
Enabled
21L1.ZP.RCA 0~45 1 °
21L1.ZP.phi_Shift 0~30 1 °
Disabled
21L1.ZP.En
Enabled
Disabled
3
21L1.ZP.En_BlkAR
Enabled
Disabled
21L1.ZP.En_NegDir_Blk
Enabled
Disabled
21L1.LoadEnch.En
Enabled
Disabled
21L1.En_PSBR
Enabled
Disabled
21L1.En_ReacLine
Enabled
Forward
21L2.DirMode Reverse
Non_Directional
21L2.phi1_Reach 30~89 1 °
21L2.ZG.RCA 0~45 1 °
21L2.ZG.phi_Shift 0~30 1 °
Disabled
21L2.ZG.En
Enabled
Disabled
21L2.ZG.En_BlkAR
Enabled
3 Disabled
21L2.ZG.En_3I0
Enabled
Disabled
21L2.ZG.En_NeuDir_Blk
Enabled
Disabled
21L2.ZG.En_NegDir_Blk
Enabled
21L2.ZP.RCA 0~45 1 °
21L2.ZP.phi_Shift 0~30 1 °
Disabled
21L2.ZP.En
Enabled
Disabled
21L2.ZP.En_BlkAR
Enabled
Disabled
21L2.ZP.En_NegDir_Blk
Enabled
Disabled
21L2.En_ShortDly
Enabled
Disabled
21L2.LoadEnch.En
Enabled
Disabled
21L2.En_PSBR
Enabled
Disabled
21L2.En_ReacLine
Enabled
Forward
3
21L3.DirMode Reverse
Non_Directional
21L3.phi1_Reach 30~89 1 °
21L3.ZG.RCA 0~45 1 °
21L3.ZG.phi_Shift 0~30 1 °
Disabled
21L3.ZG.En
Enabled
Disabled
21L3.ZG.En_BlkAR
Enabled
Disabled
21L3.ZG.En_3I0
Enabled
Disabled
21L3.ZG.En_NeuDir_Blk
Enabled
Disabled
21L3.ZG.En_NegDir_Blk
Enabled
21L3.ZP.RCA 0~45 1 °
21L3.ZP.phi_Shift 0~30 1 °
Disabled
21L3.ZP.En
Enabled
Disabled
21L3.ZP.En_BlkAR
Enabled
Disabled
21L3.ZP.En_NegDir_Blk
Enabled
Disabled
21L3.En_ShortDly
Enabled
Disabled
21L3.LoadEnch.En
Enabled
Disabled
21L3.En_PSBR
Enabled
Disabled
21L3.En_ReacLine
Enabled
Forward
21L4.DirMode Reverse
Non_Directional
21L4.phi1_Reach 30~89 1 °
21L4.ZG.RCA 0~45 1 °
Disabled
21L4.ZG.En
Enabled
Disabled
21L4.ZG.En_BlkAR
Enabled
Disabled
21L4.ZG.En_3I0
Enabled
Disabled
21L4.ZG.En_NeuDir_Blk
Enabled
Disabled
21L4.ZG.En_NegDir_Blk
Enabled
21L4.ZP.RCA 0~45 1 °
21L4.ZP.phi_Shift 0~30 1 °
Disabled
21L4.ZP.En
Enabled
Disabled
21L4.ZP.En_BlkAR
Enabled
Disabled
21L4.ZP.En_NegDir_Blk
Enabled
3 Disabled
21L4.En_ShortDly
Enabled
Disabled
21L4.LoadEnch.En
Enabled
Disabled
21L4.En_PSBR
Enabled
Disabled
21L4.En_ReacLine
Enabled
Forward
21L5.DirMode Reverse
Non_Directional
21L5.phi1_Reach 30~89 1 °
21L5.ZG.RCA 0~45 1 °
21L5.ZG.phi_Shift 0~30 1 °
Disabled
21L5.ZG.En
Enabled
Disabled
21L5.ZG.En_BlkAR
Enabled
Disabled
21L5.ZG.En_3I0
Enabled
Disabled
3
21L5.ZG.En_NeuDir_Blk
Enabled
Disabled
21L5.ZG.En_NegDir_Blk
Enabled
21L5.ZP.RCA 0~45 1 °
21L5.ZP.phi_Shift 0~30 1 °
Disabled
21L5.ZP.En
Enabled
Disabled
21L5.ZP.En_BlkAR
Enabled
Disabled
21L5.ZP.En_NegDir_Blk
Enabled
Disabled
21L5.En_ShortDly
Enabled
Disabled
21L5.LoadEnch.En
Enabled
Disabled
21L5.En_PSBR
Enabled
Disabled
21L5.En_ReacLine
Enabled
Forward
21L6.DirMode Reverse
3 Non_Directional
21L6.phi1_Reach 30~89 1 °
21L6.ZG.RCA 0~45 1 °
21L6.ZG.phi_Shift 0~30 1 °
Disabled
21L6.ZG.En
Enabled
Disabled
21L6.ZG.En_BlkAR
Enabled
Disabled
21L6.ZG.En_3I0
Enabled
Disabled
21L6.ZG.En_NeuDir_Blk
Enabled
Disabled
21L6.ZG.En_NegDir_Blk
Enabled
21L6.ZP.RCA 0~45 1 °
21L6.ZP.phi_Shift 0~30 1 °
Disabled
21L6.ZP.En
Enabled
Disabled
21L6.ZP.En_BlkAR
Enabled
Disabled
21L6.ZP.En_NegDir_Blk
Enabled
Disabled
21L6.En_ShortDly
Enabled
Disabled
21L6.LoadEnch.En
Enabled
Disabled
21L6.En_PSBR
Enabled
Disabled
21L6.En_ReacLine
Enabled
21L.PilotFwd.phi1_Reach 30~89 1 °
21L.PilotFwd.ZG.RCA 0~45 1 °
Disabled
21L.PilotFwd.ZG.En_3I0
Enabled
Disabled
21L.PilotFwd.ZG.En_NeuDir_Blk
Enabled
Disabled
3 21L.PilotFwd.ZG.En_NegDir_Blk
Enabled
21L.PilotFwd.ZP.RCA 0~45 1 °
Disabled
21L.PilotFwd.ZP.En_NegDir_Blk
Enabled
Disabled
21L.PilotFwd.LoadEnch.En
Enabled
Disabled
21L.PilotFwd.En_PSBR
Enabled
Disabled
21L.PilotFwd.En_ReacLine
Enabled
21L.PilotRev.phi1_Reach 30~89 1 °
21L.PilotRev.ZG.RCA 0~45 1 °
Disabled
21L.PilotRev.ZG.En_3I0
Enabled
21L.PilotRev.ZP.RCA 0~45 1 °
Disabled
21L.PilotRev.LoadEnch.En
Enabled
Disabled
3
21L.PilotRev.En_PSBR
Enabled
Disabled
21L.PilotRev.En_ReacLine
Enabled
1. 21L.Ang_Alpha
It is used to set the angle of directional line in the second quadrant (when the setting
[21Lx.DirMode] is set as "Forward") or fourth quadrant (when the setting [21Lx.DirMode] is set as
"Reverse") for quadrilateral phase-to-ground distance element.
If the line positive-sequence angle is large, for example, more than 80 degree, or the system
behind the device is weak power source, this setting should be increaseded appropriately,
considering the error of line paramter and measured impedance.
2. 21L.Ang_Beta
It is used to set the angle of directional line in the fourth quadrant (when the setting [21Lx.DirMode]
is set as "Forward") or second quadrant (when the setting [21Lx.DirMode] is set as "Reverse") for
quadrilateral distance element.
3. 21L.LoadEnch.phi
[21L.LoadEnch.phi]>φLoad_Max+φθ
4. 21L.LoadEnch.R_Set
It should be less than the minimum impedance measured during heavy load conditions.
Assume that the maximum permissive load is Smax (MVA), and corresponding minimum voltage is
Umin (kV) and then under this operation condition, the recommended setting principle is as below:
2
𝑈𝑚𝑖𝑛
[21𝐿. 𝐿𝑜𝑎𝑑𝐸𝑛𝑐ℎ. 𝑅_𝑆𝑒𝑡] < 𝐾𝑟𝑒𝑙 × 𝑅𝑚𝑖𝑛 = 𝐾𝑟𝑒𝑙 ×
𝑆𝑚𝑎𝑥
6. 21L.ZG.Opt_Characteristic
7. 21L.ZP.Opt_Characteristic
8. 21L*.DirMode
9. 21L*.Real_K0
It is used to set real component of zero-sequence compensation coefficient for zone * of distance
protection (*=1~6)
𝑍̇0𝐿 − 𝑍̇1𝐿
[21𝐿 ∗. 𝑅𝑒𝑎𝑙_𝐾0] = 𝑅𝑒𝑎𝑙 { }
3𝑍̇1𝐿
Z0L and Z1L are zero and positive sequence impedance of the line respectively.
10. 21L*.Imag_K0
𝑍̇0𝐿 − 𝑍̇1𝐿
[21𝐿 ∗. 𝐼𝑚𝑎𝑔_𝐾0] = 𝐼𝑚𝑎𝑔 {
3𝑍̇1𝐿
} 3
Z0L and Z1L are zero and positive sequence impedance of the line respectively.
11. 21L*.phi1_Reach
It is used to set phase angle of positive-sequence impedance for zone i of distance protection.
(*=1~6)
𝑋1
[21𝐿𝑖. 𝑝ℎ𝑖1_𝑅𝑒𝑎𝑐ℎ] = 𝑡𝑎𝑛−1 ( )
𝑅1
12. 21L*.ZG.RCA
It is used to set downward offset angle of the reactance line for zone * of quadrilateral
phase-to-ground distance element. (*=1~6)
The setting is used to prevent phase-to-ground distance element from overreaching during the
fault with resistance. The setting is associated with the setting [21L*.En_ReacLine]. And its value
is valid when the setting [21L*.En_ReacLine] is set as "Enabled".
The setting is recommended to be set according to the maximum fault resistance considered for
phase-to-ground fault.
13. 21L*.ZG.Z_Set
➢ For Zone 1
Zone1 is expected to protect the most part of the line. The recommended setting principle is:
Where overhead lines are connected in parallel or operate in close proximity for the whole or part
of their length, mutual coupling exists between the two circuits. For the case where one circuit of a
parallel line is out of service and earthed at both ends, an earth fault on the remote busbar may
result in maloperation of phase-to-ground zone 1.
In this case, it is recommended to reduce the setting. Krel is recommended to be set as 0.7 or
less. It should prevent maloperation when a fault occurs on the remote busbar of line.
3 ➢ For Zone 2
The setting should be sensitive enough to the earth fault on the remote end of the protected line,
and coordinates with the setting of zone 1 of the adjacent line. For more complex power system,
for instance, If there is a transformer or there are many adjacent lines connected to the remote bus,
the coordination should be changed accordingly.
To coordinate with zone 1 of the adjacent line, the recommended setting principle is:
[21L2.ZG.Z_Set]=K1×(ZL+KZmin×Zdz1)
KZmin is the minimum value between positive-sequence infeed coefficient and zero-sequence
infeed coefficient under all the operation conditions.
KZ=Iadj/Iloc
Iadj is positive-sequence current on the adjacent line when a fault happens to the adjacent line.
Iloc is positive-sequence current on the protected line when a fault happens to the adjacent line.
It should be noted that the setting should be greater than 1.2×ZL to make sure adequate sensitivity
is acheived. If it is not satisfied based on above setting rule, then zone2 of the protected line
should coordinate with zone2 of the adjacent line, in both impedance setting and time delay
setting.
For parallel circuit, the setting tends to underreach due to mutual coupling. Therefore, it is
recommended to increase the setting.
➢ For Zone 3
Zone3 is both the backup for the protected line and the remote back for the adjacent line. Thus, it
should coordinate with the setting of zone 2 of the adjacent line. For more complex power system,
for instance, if there is a transformer or there are many adjacent lines connected to the remote end
of the adjacent line, the coordination should be changed accordingly.
To coordinate with zone 2 of the adjacent line, the recommended setting principle is:
[21L3.ZG.Z_Set]=K1×(ZL+KZmin×Zdz2)
It should be noted that, if ZL2 is the line impedance of the adjacent line, then the setting should be
greater than 1.2×(ZL+ KZmax×ZL2) to make sure adequate sensitivity is acheived. If it is not satisfied
based on above setting rule, then zone3 of the protected line should coordinate with zone3 of the
adjacent line, in both impedance setting and time delay setting.
It is used to set shift impedance setting of zone * of phase-to-ground distance element (*=2~6)
It is common offset impedance setting of phase-to-ground distance element (Mho and Quad
characteristics)
It is associated with the setting [21L*.DirMode]. It is valid when the direction setting [21L*.DirMode]
is set as "Non-directional". Because Zone1 is internally fixed in forward direction, this setting is
avalaible for Zone2~Zone6.
15. 21L*.ZG.R_Set
If this setting is too large compared with [21L*.ZG.Z_Set], then overreach is likely to happen. Thus,
the recommended setting principle is:
[21L*.ZG.R_Set]≤4×[21L*.ZG.Z_Set]
16. 21L*.ZG.R_Offset
It is used to set shift resistance setting of zone * of phase-to-ground distance element. (Quad
characteristics, *=1~6)
⚫ For the Quad characteristic distance protection with direction, it is used to cut off the
unwanted area in second quadrant.
⚫ For the Quad characteristic distance protection without direction, it is used for the offset
boundary of the operation area.
17. 21L*.ZG.phi_Shift
It is used to set phase shift of zone * of phase-to-ground distance element. (Mho characteristics,
*=1~6)
In order to improve the performance against high resistance fault, phase shift is applied to
polarized voltage in phase-to-ground distance element and phase-to-phase distance element.
⚫ Line length is not smaller than 10km and smaller than 40km: 0°~15°
3 ⚫ Line length is not smaller than 40km: 0°
18. 21L*.ZG.t_Op
It is common time delay setting of phase-to-ground distance protection. (Mho and Quad
characteristics)
➢ For Zone 1
➢ For Zone 2
[21L2.ZG.t_Op]=Δt
Otherwise, this setting shall coordinate with the time delay of phase-to-ground distance element of
zone 2 in the adjacent line, and the recommended setting principle is:
[21L2.ZG.t_Op]=t2+Δt
Where:
➢ For Zone 3
[21L3.ZG.t_Op]=t2+Δt
Otherwise, this setting shall coordinate with the time delay of phase-to-ground distance element of
zone 3 in the adjacent line, and the recommended setting principle is:
[21L3.ZG.t_Op]=t3+Δt
Where:
3
Time delay of zone 3 of phase-to-ground distance element usually take
3s~3.5s, and the requirement of time-delay operation must be confirmed by
the user.
19. 21L*.ZG.t_ShortDly
It is used to set short time delay of zone * of phase-to-ground distance element (*=2~6)
It is common short time delay of phase-to-ground distance element. (Mho and Quad
characteristics)
Under some situation, distance protection with normal time delay should operate with a shorter
time delay. For example, main protection is lost on the downstream line and distance protection on
local line should be accelerated to operate.
20. 21L*.ZG.En
21. 21L*.ZG.En_BlkAR
AR will be blocked when phase-to-ground distance element operates if the setting is set as
"Enabled".
22. 21L*.ZG.En_3I0
Phase-to-ground distance element will be controlled by the signal "FD.ROC_Pkp" if the setting is
set as "Enabled".
23. 21L*ZG.En_NeuDir_Blk
24. 21L*.ZG.En_NegDir_Blk
25. 21L*.ZP.RCA
It is used to set downward offset angle of the reactance line for zone * of quadrilateral
phase-to-phase distance element. (*=1~6).
The setting is used to prevent phase-to-phase distance element from overreaching during the fault
with resistance. The setting is associated with the setting [21L*.En_ReacLine]. And its value is
valid when the setting [21L*.En_ReacLine] is set as "Enabled".
The setting is recommended to be set according to the maximum fault resistance considered for
phase-to-phase fault.
26. 21L*.ZP.Z_Set
➢ For Zone 1
Zone1 is expected to protect the most part of the line. The recommended setting principle is:
Where overhead lines are connected in parallel or run in close proximity for the whole or part of
their length, mutual coupling exists between the two circuits. For the case where one circuit of a
parallel line is out of service and earthed at both ends, an earth fault on the remote busbar may
result in mal-operation of zone 1 phase-to-phase element. In this case, it is recommended to
reduce the setting. Krel is recommended to be set as 0.7 or less. It should avoid mal-operation
when a fault occurs on the remote busbar of line.
➢ For Zone 2
3
The setting should be sensitive enough to the earth fault on the remote end of the protected line,
and coordinates with the setting of zone 1 of the adjacent line. For more complex power system,
for instance, If there is a transformer or there are many adjacent lines connected to the remote bus,
the coordination should be changed accordingly.
To coordinate with zone 1 of the adjacent line, the recommended setting principle is:
[21L2.ZP.Z_Set]=K1×(ZL +KZ×Zdz1)
KZ = Iadj/Iloc
Iadj is positive-sequence current on the adjacent line when a fault happens on the adjacent line.
Iloc is positive-sequence current on the protected line when a fault happens on the adjacent line.
It should be noted that, the setting should be greater than 1.2×ZL to make sure adequate
sensitivity is acheived. If it is not satisfied based on above setting rule, then zone2 of the protected
line should coordinate with zone2 of the adjacent line, in both impedance setting and time delay
setting.
For parallel circuit, the setting tends to underreach due to mutual coupling. Therefore, it is
recommended to increase the setting.
➢ For Zone 3
Zone3 is both the backup for the protected line and the remote back for the adjacent line. Thus, it
should coordinate with the setting of zone 2 of the adjacent line. For more complex power system,
for instance, If there is a transformer or there are many adjacent lines connected to the remote end
of the adjacent line, the coordination should be changed accordingly.
To coordinate with zone 2 of the adjacent line, the recommended setting principle is:
[21L3.ZP.Z_Set]=K1×(ZL +KZmin×Zdz2)
It should be noted that, if ZL2 is the line impedance of the adjacent line, then the setting should be
greater than 1.2×(ZL+ KZmax×ZL2) to make sure adequate sensitivity is acheived. If it is not satisfied
based on above setting rule, then zone3 of the protected line should coordinate with zone3 of the
adjacent line, in both impedance setting and time delay setting.
27. 21L*.ZP.Z_Offset
It is used to set shift impedance setting of zone * of phase-to-phase distance element. (Mho or
Quad characteristics, *=2~6)
It is associated with the setting [21L*.DirMode]. It is valid when the direction setting [21L*.DirMode]
is set as "Non-directional". Because Zone1 is internally fixed in forward direction, this setting is
avalaible for Zone2~Zone6.
28. 21L*.ZP.R_Set
If this setting is too large compared with [21L*.ZP.Z_Set], then overreach is likely to happen. Thus,
the recommended setting principle is:
[21L*.ZP.R_Set]≤4×[21L*.ZP.Z_Set]
29. 21L*.ZP.R_Offset
It is used to set shift resistance setting of zone * of quadrilateral phase-to-phase distance element.
( *=1~6)
⚫ For the Quad characteristic distance protection with direction, it is used to cut off the
unwanted area in second quadrant.
⚫ For the Quad characteristic distance protection without direction, it is used for the offset
boundary of the operation area.
30. 21L*.ZP.phi_Shift
It is used to set phase shift of zone * of Mho phase-to-phase distance element. (*=1~6)
In order to improve the performance against high resistance fault, phase shift is applied to
polarized voltage in phase-to-phase distance element and phase-to-phase distance element.
⚫ Line length is not smaller than 10km and smaller than 40km: 0°~15°
31. 21L*.ZP.t_Op
➢ For Zone 1
➢ For Zone 2
[21L2.ZG.t_Op]=Δt
Otherwise, this setting shall coordinate with the time delay of phase-to- phase distance element of
zone 2 in the adjacent line, and the setting rule is as follows:
[21L2.ZG.t_Op] = t2+Δt
Where:
t2 is the time delay of phase-to- phase distance element of zone 2 in adjacent line.
➢ For Zone 3
[21L3.ZG.t_Op]=t2+Δt
Otherwise, this setting shall coordinate with the time delay of phase-to-phase distance element of
zone 3 in the adjacent line, and the setting rule is as follows:
[21L3.ZG.t_Op]=t3+Δt
Where:
32. 21L*.ZP.t_ShortDly
It is used to set short time delay of zone * of phase-to-phase distance element (Mho or Quad
characteristics,*=2~6)
Under some situation, distance protection with normal time delay should operate with a shorter
time delay. For example, main protection is lost on the downstream line and distance protection on
local line should be accelerated to operate.
No setting rule is recommended for this setting. Please set this setting according to the application
condition.
33. 21L*.ZP.En
34. 21L*.ZP.En_BlkAR
AR will be blocked when phase-to-phase distance element operates if the setting is set as
"Enabled".
35. 21L*.ZP.En_NegDir_Blk
36. 21L*.En_ShortDly
Normally, Zone 1 is used as instant distance protection, so this setting is only used for Zone
2~Zone 6.
37. 21L*.LoadEnch.En
It is used to enable/disable load trapezoid characteristics for zone * of distance protection. (Mho or
Quad characteristics, *=1~6) 3
38. 21L*.En_PSBR
When the setting is set as "Enabled", the power swing blocking for distance protction will be
released if corresponding conditions are satisfied.
39. 21L*.En_ReacLine
It is used to enable/disable zone * of distance protection controlled by the reactance line. (Mho or
Quad characteristics, *=1~6)
40. 21L.PilotFwd.Real_K0
It is used to set real component of zero-sequence compensation coefficient for forward pilot
distance zone.
𝑍̇0𝐿 − 𝑍̇1𝐿
[21𝐿. 𝑃𝑖𝑙𝑜𝑡𝐹𝑤𝑑. 𝑅𝑒𝑎𝑙_𝐾0] = 𝑅𝑒𝑎𝑙 { }
3𝑍̇1𝐿
Z0L and Z1L are zero and positive sequence impedance of the line respectively.
41. 21L.PilotFwd.Imag_K0
It is used to set imaginary component of zero-sequence compensation coefficient for forward pilot
distance zone.
𝑍̇0𝐿 − 𝑍̇1𝐿
[21𝐿. 𝑃𝑖𝑙𝑜𝑡𝐹𝑤𝑑. 𝐼𝑚𝑎𝑔_𝐾0] = 𝑅𝑒𝑎𝑙 { }
3𝑍̇1𝐿
Z0L and Z1L are zero and positive sequence impedance of the line respectively.
42. 21L.PilotFwd.phi1_Reach
It is used to set phase angle of positive-sequence impedance for forward pilot distance zone.
𝑋1
[21𝐿. 𝑃𝑖𝑙𝑜𝑡𝐹𝑤𝑑. 𝑝ℎ𝑖1_𝑅𝑒𝑎𝑐ℎ] = 𝑡𝑎𝑛−1 ( )
𝑅1
X1 and R1 are positive sequence reactance and resistance of the line respectively
3 43. 21L.PilotFwd.ZG.RCA
It is used to set downward offset angle of the reactance line for quadrilateral forward
phase-to-ground pilot distance element.
The setting is used to prevent phase-to-ground distance element from overreaching during the
fault with resistance. The setting is associated with the setting [21L.PilotFwd.En_ReacLine]. And
its value is valid when the setting [21L.PilotFwd.En_ReacLine] is set as "Enabled".
The setting is recommended to be set according to the maximum fault resistance considered for
phase-to-ground fault.
44. 21L.PilotFwd.ZG.Z_Set
It is used to set impedance setting of forward pilot distance zone. (Mho or Quad characteristics,
phase-to-ground)
This setting shall be sensitive enough to the fault in the remote end of the protected line. For lines
longer than 60km, it is usually set 1.3~1.5 times the impedance of whole line, for shorter lines,
1.5~2.0 times the impedance of whole line is recommended.
For parallel lines, phase-to-ground zone element of pilot distance protection will tend to
underreach due to mutual coupling. Therefore, it is recommended to increase the setting.
45. 21L.PilotFwd.ZG.R_Set
It is used to set resistance setting of quadrilateral forward phase-to-ground pilot distance element.
If this setting is too large compared with [21L.PilotFwd.ZG.Z_Set], then overreach is likely to
happen. Thus, the recommended setting principle is:
[21L.PilotFwd.ZG.R_Set]≤4×[21L.PilotFwd.ZG.Z_Set]
46. 21L.PilotFwd.ZG.R_Offset
It is used to set shift resistance setting of quadrilateral forward phase-to-ground pilot distance
element.
47. 21L.PilotFwd.ZG.En_3I0
It is used to enable/disable forward pilot distance zone controlled by residual current fault detector
element. (Mho or Quad characteristics, phase-to-ground)
Forward pilot distance zone (phase-to-ground) will be controlled by the signal "FD.ROC_Pkp" if
the setting is set as "Enabled".
48. 21L.PilotFwd.ZG.En_NeuDir_Blk
49. 21L.PilotFwd.ZG.En_NegDir_Blk
50. 21L.PilotFwd.ZP.RCA
It is used to set downward offset angle of the reactance line for quadrilateral forward
phase-to-phase pilot distance element.
The setting is used to prevent phase-to-phase distance element from overreaching during the fault
with resistance. The setting is associated with the setting [21L.PilotFwd.En_ReacLine]. And its
value is valid when the setting [21L.PilotFwd.En_ReacLine] is set as "Enabled".
The setting is recommended to be set according to the maximum fault resistance considered for
phase-to-phase fault.
51. 21L.PilotFwd.ZP.Z_Set
It is used to set impedance setting of forward phase-to-phase pilot distance element. (Mho or
Quad characteristics)
This setting shall be sensitive enough to the fault in the remote end of the protected line. For lines
longer than 60km, it is usually set 1.3~1.5 times the impedance of whole line, for shorter lines,
For parallel lines, phase-to-phase zone element of pilot distance protection will tend to underreach
due to mutual coupling. Therefore, it is recommended to increase the setting.
52. 21L.PilotFwd.ZP.R_Set
It is used to set resistance setting of quadrilateral forward phase-to-phase pilot distance element.
If this setting is too large compared with [21L.PilotFwd.ZP.Z_Set], then overreach is likely to
happen. Thus, the recommended setting principle is:
[21L.PilotFwd.ZP.R_Set]≤4×[21L.PilotFwd.ZP.Z_Set]
3 53. 21L.PilotFwd.ZP.R_Offset
It is used to set shift resistance setting of quadrilateral forward phase-to-phase pilot distance
element.
54. 21L.PilotFwd.ZP.En_NegDir_Blk
55. 21L.PilotFwd.LoadEnch.En
It is used to enable/disable load trapezoid characteristics for forward pilot distance zone. (Mho or
Quad characteristics)
56. 21L.PilotFwd.En_PSBR
It is used to enable/disable forward pilot distance zone controlled by PSBR. (Mho or Quad
characteristics)
When the setting is set as "Enabled", the power swing blocking for forward pilot distance zone will
be released if corresponding conditions are satisfied.
57. 21L.PilotFwd.En_ReacLine
It is used to enable/disable forward pilot distance zone controlled by the reactance line. (Mho or
Quad characteristics)
58. 21L.PilotRev.Real_K0
It is used to set real component of zero-sequence compensation coefficient for reverse pilot
distance zone.
𝑍̇0𝐿 − 𝑍̇1𝐿
[21𝐿. 𝑃𝑖𝑙𝑜𝑡𝑅𝑒𝑣. 𝑅𝑒𝑎𝑙_𝐾0] = 𝑅𝑒𝑎𝑙 { }
3𝑍̇1𝐿
Where:
Z0L and Z1L are zero and positive sequence impedance of the line respectively.
59. 21L.PilotRev.Imag_K0
It is used to set imaginary component of zero-sequence compensation coefficient for reverse pilot
distance zone.
Where:
Z0L and Z1L are zero and positive sequence impedance of the line respectively.
60. 21L.PilotRev.phi1_Reach
It is used to set phase angle of positive-sequence impedance for reverse pilot distance zone.
𝑋1
[21𝐿. 𝑃𝑖𝑙𝑜𝑡𝑅𝑒𝑣. 𝑝ℎ𝑖1_𝑅𝑒𝑎𝑐ℎ] = 𝑡𝑎𝑛−1 ( )
𝑅1
Where:
X1 and R1 are positive sequence reactance and resistance of the line respectively
61. 21L.PilotRev.ZG.RCA
It is used to set downward offset angle of the reactance line for reverse pilot distance zone.
(phase-to-ground)
It is used to prevent reverse pilot distance zone (phase-to-ground) from overreaching during the
fault with resistance. The setting is associated with the setting [21L.PilotRev.En_ReacLine]. And it
is valid only if the setting [21L.PilotRev.En_ReacLine] is set as "Enabled".
The setting is recommended to be set according to the maximum fault resistance considered for
phase-to-ground fault.
62. 21L.PilotRev.ZG.Z_Set
It is used to set impedance setting of reverse pilot distance zone. (Mho or Quad characteristics,
phase-to-ground)
Under weak power source condition, when an internal fault occurs, the device at weak power
source end could not detect the fault, then pilot distance protection could not operate for internal
fault. The problem is eliminated by the weak infeed logic based on the impedance setting of pilot
distance protection in reverse direction. Shown as following figure, if permissive signal from
remote side is received by weak infeed end, while the pilot reverse zone doesn’t start, then it is
confirmed as internal fault.
21L.PilotFwd.ZG.Z_Set
ZL
21L.PilotRev.ZG.Z_Rev
3 EM M A Fault B N EN
21L.PilotRev.ZG.Z_Rev
21L.PilotFwd.ZG.Z_Set
The protection area of reverse pilot distance element should overlap the protection area of the
fowward pilot distance element in reverse direction. Thus, the recommended setting principle is:
Where:
63. 21L.PilotRev.ZG.R_Set
It is used to set resistance setting of quadrilateral reverse phase-to-phase pilot distance element.
If this setting is too large compared with [21L.PilotRev.ZG.Z_Set], then overreach is likely to
happen. Thus, the recommended setting principle is:
[21L.PilotRev.ZG.R_Set]≤4×[21L.PilotRev.ZP.G_Set]
64. 21L.PilotRev.ZG.R_Offset
It is used to set shift resistance setting of quadrilateral reverse phase-to-ground pilot distance
zone.
65. 21L.PilotRev.ZG.En_3I0
It is used to enable/disable reverse pilot distance zone controlled by residual current fault detector
element. (phase-to-ground)
Reverse pilot distance zone (phase-to-ground) will be controlled by the signal "FD.ROC_Pkp" if
the setting is set as "Enabled".
66. 21L.PilotRev.ZP.RCA
It is used to set downward offset angle of the reactance line for reverse phase-to-phase pilot
distance element.
It is used to prevent reverse phase-to-ground pilot distance element from overreaching during the
fault with resistance. The setting is associated with the setting [21L.PilotRev.En_ReacLine]. And it
is valid only if the setting [21L.PilotRev.En_ReacLine] is set as "Enabled".
The setting is recommended to be set according to the maximum fault resistance considered for
phase-to-ground fault.
Under weak power source condition, when an internal fault occurs, the device at weak power
source end could not detect the fault, then pilot distance protection could not operate for internal
fault. The problem is eliminated by the weak infeed logic based on the impedance setting of pilot
distance protection in reverse direction. Shown as following figure, if permissive signal from
remote side is received by weak infeed end, while the pilot reverse zone doesn′t start, then it is
confirmed as internal fault.
21L.PilotFwd.ZP.Z_Set
ZL
21L.PilotRev.ZP.Z_Rev
EM M A Fault B N EN
21L.PilotRev.ZP.Z_Rev
21L.PilotFwd.ZP.Z_Set
The protection area of reverse pilot distance element should overlap the protection area of the
fowward pilot distance element in reverse direction. Thus, the recommended setting principle is:
Where:
68. 21L.PilotRev.ZP.R_Set
It is used to set resistance setting of quadrilateral reverse phase-to-phase pilot distance element.
If this setting is too large compared with [21L.PilotRev.ZP.Z_Set], then overreach is likely to
happen. Thus, the recommended setting principle is:
[21L.PilotRev.ZP.R_Set]≤4×[21L.PilotRev.ZP.Z_Set]
69. 21L.PilotRev.ZP.R_Offset
It is used to set shift resistance setting of quadrilateral reverse phase-to-phase pilot distance zone.
70. 21L.PilotRev.LoadEnch.En
It is used to enable/disable load trapezoid characteristics for reverse pilot distance zone.
71. 21L.PilotRev.En_PSBR
When the setting is set as "Enabled", the power swing blocking for reverse pilot distance zone will
be released if corresponding conditions are satisfied.
72. 21L.PilotRev.En_ReacLine
It is used to enable/disable reverse pilot distance zone controlled by the reactance line.
⚫ LCD
⚫ PCS-Studio
Disabled
78.En
Enabled
Disabled
78.En_Trp
Enabled
78.phi1_Reach 30~89 1 °
78.phi_Start 0~180 1 °
78.phi_Trp 0~180 1 °
78.N_Limit 1~20 1
1. 78.En
3
It is used to enable/disable out-of-step protection.
2. 78.En_Trp
3. 78.Z_Fwd
4. 78.Z_Rev
In order to locate the distance between the oscillation center and where the device is equipped,
setting impedance measurement element is used to confirm the operation range of separation
device, the operation characteristic of zone relay is based on impedance discrimination.
Out-of-step protection will operate when both zone relay and out-of-step relay operate.
ZM ZLine ZN
EM 52 52 EN
I U
IED
ZRev ZFwd
Where:
ZFwd is the impedance from zone relay location to side-N system, i.e., [78.Z_Fwd]
ZRev is the impedance from zone relay location to side-M system, i.e., [78.Z_Rev]
5. 78.phi1_Reach
It is used to set the system impedance angle for the zone detector.
The impedance angle is calculated based on the line parameters. The equation is as bellow.
𝑋1
[78. 𝑝ℎ𝑖1_𝑅𝑒𝑎𝑐ℎ] = 𝑡𝑎𝑛−1 ( )
𝑅1
Where:
X1 and R1 are positive sequence reactance and resistance of the line respectively.
3 6. 78.phi_Start
7. 78.phi_Trp
It is used to set the maximum tripping angle after out-of-step protection operating, which is used to
prevent the circuit breaker from incorrect operation due to too large current during tripping.
8. 78.N_Limit
If the device detects the out-of-step condition and issues tripping command after the time delay
(i.e., the setting [78.N_Limit]), performing separation. The setting depends on the coordination of
the out of step relays.
⚫ LCD
⚫ PCS-Studio
Disabled
3
21SOTF.En
Enabled
Disabled
21SOTF.Z2.En_ManCls
Enabled
Disabled
21SOTF.Z3.En_ManCls
Enabled
Disabled
21SOTF.Z4.En_ManCls
Enabled
Disabled
21SOTF.Z2.En_3PAR
Enabled
Disabled
21SOTF.Z3.En_3PAR
Enabled
Disabled
21SOTF.Z4.En_3PAR
Enabled
Disabled
21SOTF.Z2.En_PSBR
Enabled
Disabled
21SOTF.Z3.En_PSBR
Enabled
Disabled
21SOTF.Z4.En_PSBR
Enabled
Disabled
21SOTF.Z2.En_1PAR
Enabled
Disabled
21SOTF.En_PDF
Enabled
ManClsBI
3 CBPos
SOTF.Opt_Mode_ManCls ManClsBI/CBPos
AutoInit
All
1. SOTF.t_En
It should be more than the fixed time of closing the circuit breaker, but should not be too long. Its
recommended value is 3s.
The setting is shared by distance SOTF protection, phase current SOTF protection and residual
current SOTF protection.
2. 21SOTF.t_ManCls
It is used to set time delay of distance protection accelerating to trip when manual closing.
3. 21SOTF.t_3PAR
It is used to set time delay of distance protection accelerating to trip when 3-pole reclosing.
4. 21SOTF.t_1PAR
It is used to set time delay of distance protection accelerating to trip when 1-pole reclosing.
5. 21SOTF.En
6. 21SOTF.Z2.En_ManCls
7. 21SOTF.Z3.En_ManCls
8. 21SOTF.Z4.En_ManCls
9. 21SOTF.Z2.En_3PAR
10. 21SOTF.Z3.En_3PAR
11. 21SOTF.Z4.En_3PAR
It is used to enable/disable zone 2 controlled by PSB of distance SOTF protection for 3-pole
reclosing.
13. 21SOTF.Z3.En_PSBR
It is used to enable/disable zone 3 controlled by PSB of distance SOTF protection for 3-pole
reclosing.
14. 21SOTF.Z4.En_PSBR
It is used to enable/disable zone 4 controlled by PSB of distance SOTF protection for 3-pole
reclosing.
15. 21SOTF.Z2.En_1PAR
16. 21SOTF.t_PDF
It is used to set time delay of distance protection operating under pole discrepancy conditions.
This setting is the time delay for distance SOTF protection for another fault on the healthy phase
during pole discrepancy condition. The setting is recommended to set as 150ms.
17. 21SOTF.En_PDF
Under pole discrepancy condition after single-phase tripping, distance SOTF protection for pole
discrepancy will operate with the time delay [21SOTF.t_PDF] if another fault happens to the
healthy phase. This function is provided based on the high possibility that the late fault might be at
the same point with the previous fault, which could reduce the fault clearing time.
Distance SOTF protection for pole discrepancy will operate for external
fault on healthy phase during pole discrepancy condition after a time delay
of 150ms, however the fault will be cleared in 150ms, so the possibility of
maloperation for external fault is very low. But users should evaluate
carefully.
18. SOTF.U_Ddl
When manual SOTF mode is set as "AutoInit", i.e., initiated by no voltage detection, distance
SOTF protection will be initiated by dead line check. When three phases currents are all smaller
than 0.04In and no fault detector element operates, SOTF logic will be enabled with the time delay
[SOTF.t_Ddl] if three phase voltages are all smaller than the setting [SOTF.U_Ddl].
19. SOTF.t_Ddl
20. SOTF.Opt_Mode_ManCls
The setting provides the selection for accelerated tripping mode, which can be from circuit breaker
position, external binary signal of manual closing or dead line check, the options are shown as
follows.
All: initiated by both binary input of manual closing, CB position, or initated by no voltage detection
⚫ PCS-Studio
50/51P.DIR.RCA -180~179 1 °
3
50/51P.DIR.RCA_NegOC -180~179 1 °
50/51P.DIR.phi_Min_Fwd 10~90 1 °
50/51P.DIR.phi_Max_Fwd 10~90 1 °
50/51P.DIR.phi_Min_Rev 10~90 1 °
50/51P.DIR.phi_Max_Rev 10~90 1 °
Upp
50/51P.DIR.Opt_PolarizedVolt Up
U1
Disabled
50/51P.En_VTS_Blk
Enabled
PhaseBlk
50/51P.HMB.Opt_Blk CrossBlk
MaxPhaseBlk
50/51P1.En_Volt_Blk Disabled
Enabled
Non_Directional
50/51P1.Opt_Dir Forward
Reverse
Disabled
50/51P1.En_Hm_Blk
Enabled
3 Disabled
50/51P1.En
Enabled
Trp
50/51P1.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
50/51P1.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51P1.Opt_Curve_DropOut
DefTime
IDMT
Disabled
50/51P2.En_Volt_Blk
Enabled
Non_Directional
50/51P2.Opt_Dir Forward
Reverse
Disabled
50/51P2.En_Hm_Blk
Enabled
Disabled
50/51P2.En
Enabled
Trp
50/51P2.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
50/51P2.Opt_Curve
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
IECN
IECV
IECI
IECE
IECST
IECLT
3 IECDefTime
UserDefine
Inst
50/51P2.Opt_Curve_DropOut DefTime
IDMT
Disabled
50/51P3.En_Volt_Blk
Enabled
Non_Directional
50/51P3.Opt_Dir Forward
Reverse
Disabled
50/51P3.En_Hm_Blk
Enabled
Disabled
50/51P3.En
Enabled
Trp
50/51P3.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
3
ANSILTE
ANSILTV
ANSILT
50/51P3.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51P3.Opt_Curve_DropOut DefTime
IDMT
Disabled
50/51P4.En_Volt_Blk
Enabled
Non_Directional
50/51P4.Opt_Dir Forward
Reverse
3 Disabled
50/51P4.En_Hm_Blk
Enabled
Disabled
50/51P4.En
Enabled
Trp
50/51P4.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
50/51P4.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51P4.Opt_Curve_DropOut DefTime
IDMT
Disabled
50/51P5.En_Volt_Blk
Enabled
Non_Directional
50/51P5.Opt_Dir Forward
Reverse
Disabled
50/51P5.En_Hm_Blk
Enabled
Disabled
50/51P5.En
Enabled
Trp
50/51P5.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
50/51P5.Opt_Curve
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
IECN
IECV
IECI
IECE
3 IECST
IECLT
IECDefTime
UserDefine
Inst
50/51P5.Opt_Curve_DropOut DefTime
IDMT
Disabled
50/51P6.En_Volt_Blk
Enabled
Non_Directional
50/51P6.Opt_Dir Forward
Reverse
Disabled
50/51P6.En_Hm_Blk
Enabled
Disabled
50/51P6.En
Enabled
Trp
50/51P6.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
3
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
50/51P6.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51P6.Opt_Curve_DropOut DefTime
IDMT
Phase overcurrent protection is provided with six stages, each stage has independent current
setting, time delay and control logic. Generally, stage 1 of phase overcurrent protection requires
instantaneously operating, and the protected range shall not be less than 20% of the total line.
Stage 2 of phase overcurrent protection shall protect the whole line. Stage 3 and stage 4 of phase
overcurrent protection can be backup protection for the line, and also can be remote backup
protection for the adjacent line.
1. 50/51P.VCE.Upp
𝑈𝑚𝑖𝑛
[50/51𝑃. 𝑉𝐶𝐸. 𝑈𝑝𝑝] =
𝐾𝑟𝑒𝑙
Where:
Umin is the possible minimum phase-to-phase voltage during normal operation, which can be
normally taken as 0.9Un. (Un is secondary value of the rated phase-to-phase voltage)
2. 50/51P.VCE.U2
The setting should be greater than the imbalanced voltage during normal operation, the
imbalanced voltage value can be determined through actual measurement.
3. 50/51P.VCE.3U0
The setting should be larger than the maximum residual voltage during normal operation.
4. 50/51P.DIR.RCA
Ua
[50/51P.DIR.phi_Min_Fwd]
Non-operating Ia
area
[50/51P.DIR.RCA]
Operating area in
reverse direction
3
[50/51P.DIR.phi_Max_Fwd]
[50/51P.DIR.phi_Min_Rev] Non-operating
area
By setting the characteristic angle to determine the most sensitive forward angle of phase current,
using phase current with phase polarized voltage to determine the direction of phase current in
forward direction or reverse direction. The setting defines the system impedance angle of
positive-sequence circuit.
5. 50/51P.DIR.RCA_NegOC
By setting the characteristic angle to determine the most sensitive forward angle of
negative-sequence current, using negative-sequence current with negative-sequence voltage to
determine the direction of negative-sequence current in forward direction or reverse direction.
6. 50/51P.DIR.phi_Min_Fwd
It is used to set the minimum boundary in forward direction of phase overcurrent protection.
7. 50/51P.DIR.phi_Max_Fwd
It is used to set the maximum boundary in forward direction of phase overcurrent protection.
8. 50/51P.DIR.phi_Min_Rev
It is used to set the minimum boundary in reverse direction of phase overcurrent protection.
9. 50/51P.DIR.phi_Max_Rev
It is used to set the maximum boundary in reverse direction of phase overcurrent protection.
10. 50/51P.DIR.Opt_PolarizedVolt
It is used to select the voltage polarization mode of direction control element for phase overcurrent
protection.
11. 50/51P.DIR.I_Min
It is used to set the minimum operating current setting of direction control element.
12. 50/51P.DIR.U_Min
It is used to set the minimum operating voltage setting of direction control element.
13. 50/51P.En_VTS_Blk
When VT circuit fails, phase overcurrent protection will be blocked if the setting is set as
"Enabled". Phase overcurrent protection is not controlled by direction control element and voltage
control element if the setting is set as "Disabled".
14. 50/51P.HMB.K_Hm2
In order to prevent phase overcurrent protection from maloperation during the transformer
energized for transformer-in-line applicaiton, harmonic control element can be used to block phase
overcurrent protection. When the percentage of second harmonic component to fundamental
component in phase current is larger than the setting [50/51P.HMB.K_Hm2], harmonic control
element operates to block phase overcurrent protection if the setting [50/51Pi.En_Hm_Blk] is set
as "Enabled".
If second harmonic component of phase current is lower than 0.04In, then harmonic calculation is
not carried out and harmonic control element does not operate.
15. 50/51P.HMB.I_Rls
16. 50/51P.HMB.Opt_Blk
17. 50/51P*.I_Set
It is used to set the current setting for stage * of phase overcurrent protection. (*=1~6)
Where:
Imax is the maximum three-phase short-circuit current measured at the location where the device is
installed in case of short circuit at the end of the protected line.
Krel is reliable coefficient, considering relay setting value error, short-circuit current calculation error,
as well as influence of non-periodic component on protection in short-circuit current, taking
1.2~1.3 or above.
⚫ Phase overcurrent protection with definite time delay requires protecting the whole line and
cooperating with phase overcurrent protection of adjacent line. According to the specific
condition of adjacent line protection, the setting calculation principle is as follows:
Where:
Kb.max is branch coefficient of current, which is equal to the ratio of the current passing through the
device to the current passing through the faulty line during an earth fault at the end of protected
range of the coordinated stage of overcurrent protection of the line.
⚫ Phase overcurrent protection with definite time delay requires being used as backup
protection of the transformer equipped with transformer current differential protection, the
setting shall be set and calculated according to the following equation.
Where:
Imax is the maximum three-phase short-circuit current of the local line when a fault happens to the
other sides of the transformer for phase overcurrent protection which is permitted to cover the
transformer.
⚫ Due to the time dely of phase overcurrent protection with definite-time characteristics is longer
if the fault is closer to the power source, phase overcurrent protection with inverse-time
characteristics is used to shorten the operation time, the setting calculation principle is as
follows:
𝐾𝑟𝑒𝑙 × 𝐾𝑠𝑠
[50/51𝑃 ∗. 𝐼_𝑆𝑒𝑡] = × 𝐼𝐿.𝑚𝑎𝑥
𝐾𝑟𝑒
Where:
Kss is self-starting coefficient, determined by specific connection and load property via network.
18. 50/51P*.t_Op
It is used to set the operating time delay for stage * of phase overcurrent protection. (*=1~6)
⚫ When the operating current is in coordination with instantaneous overcurrent protection of the
adjacent line, the operating time of definite-time phase overcurrent protection is:
[50/51P*.t_Op]=t1+Δt
Where:
t1 is the fixed operating time of instantaneous overcurrent protection of the adjacent line, about
0.06~0.1s, or neglected sometimes
⚫ When the operating current is in coordination with definite-time stage of phase overcurrent
protection of adjacent line, the operating time of definite-time phase overcurrent protection is:
[50/51P*.t_Op]=t2+Δt
Where:
t2 is the fixed operating time of the coordinated stage of phase overcurrent protection of adjacent
line.
19. 50/51P*.t_DropOut
It is used to set the dropout time delay for stage * of phase overcurrent protection. (*=1~6)
20. 50/51P*.En_Volt_Blk
21. 50/51P*.Opt_Dir
It is used to select the direction characteristic for stage * of phase overcurrent protection. (*=1~6)
Non_Directional: no direction
22. 50/51P*.En_Hm_Blk
23. 50/51P*.En
24. 50/51P*.Opt_Trp/Alm
25. 50/51P*.Opt_Curve
It is used to select the operating characteristics curve for stage * of phase overcurrent protection.
(*=1~6)
UserDefine: Programmable
When the setting is set as "UserDefine", the user can customize the inverse-time curve
characteristic by setting constants K, α and C.
26. 50/51P*.Opt_Curve_DropOut
It is used to select the dropout characteristics curve for stage * of phase overcurrent protection.
(*=1~6)
When the operating characteristics curve is selected as ANSI inverse-time characteristic, the
dropout characteristic curve can be selected as instantaneous dropout characteristics,
definite-time dropout characteristics and ANSI inverse-time dropout characteristics.
27. 50/51P*.TMS
It is used to set time multiplier setting for stage * of inverse-time phase overcurrent protection.
(*=1~6)
This setting can be deduced according to the operating time required by inverse-time phase
overcurrent protection.
28. 50/51P*.tmin
It is used to set the minimum operating time for stage * of inverse-time phase overcurrent
protection. (*=1~6)
When inverse-time characteristic is selected, if calculated operating time is less than the setting 3
[50/51P*.tmin], then the operating time changes to the value of the setting [50/51P*.tmin]
automatically.
Where:
29. 50/51P*.K
It is used to set the constant "K" for stage * of customized inverse-time phase overcurrent
protection. (*=1~6)
The setting shall be set according to the expected inverse-time characteristics of phase
overcurrent protection. It is valid only if the setting [50/51P*.Opt_Curve] is set as "UserDefine".
30. 50/51P*.Alpha
It is used to set the constant "α" for stage * of customized inverse-time phase overcurrent
protection. (*=1~6)
The setting shall be set according to the expected inverse-time characteristics of phase
overcurrent protection. It is valid only if the setting [50/51P*.Opt_Curve] is set as "UserDefine".
31. 50/51P*.C
It is used to set the constant "C" for stage * of customized inverse-time phase overcurrent
protection. (*=1~6)'
The setting shall be set according to the expected inverse-time characteristics of phase
overcurrent protection. It is valid only if the setting [50/51P*.Opt_Curve] is set as "UserDefine".
⚫ PCS-Studio
1. 50PSOTF.I_Set
2. 50PSOTF.t_Op
3. 50PSOTF.Up_Set
In order to improve the reliability, phase current SOTF protection can select phase voltage element
as auxiliary criterion.
4. 50PSOTF.Upp_Set
In order to improve the reliability, phase current SOTF protection can select phase-phase voltage
element as auxiliary criterion.
5. 50PSOTF.U2_Set
3
It is used to set Voltage setting for negative-sequence overvoltage supervision logic.
In order to improve the reliability, phase current SOTF protection can select negative-sequence
voltage element as auxiliary criterion.
6. 50PSOTF.3U0_Set
In order to improve the reliability, phase current SOTF protection can select zero-sequence
voltage element as auxiliary criterion.
7. 50PSOTF.En_Up_UV
It is used to enable/disable phase undervoltage supervision logic for phase current SOTF
protection.
If the setting is set as "Disabled", the phase undervoltage criterion will not take effect.
8. 50PSOTF.En_Upp_UV
It is used to enable/disable phase-phase undervoltage supervision logic for phase current SOTF
protection.
If the setting is set as "Disabled", the phase-phase undervoltage criterion will not take effect.
9. 50PSOTF.En_U2_OV
If the setting is set as "Disabled", the negative-sequence overvoltage criterion will not take effect.
10. 50PSOTF.En_3U0_OV
It is used to enable/disable zero-sequence overvoltage supervision logic for phase current SOTF
protection.
If the setting is set as "Disabled", the zero-sequence ovevoltage criterion will not take effect.
11. 50PSOTF.En
It is used to enable/disable second harmonic blocking for phase overcurrent SOTF protection.
For in-line transformer application, large inrush current generated during manual closing and
3 auto-reclosing will lead to an undesired operation of phase current SOTF protection. Second
harmonic blocking can be selected by the setting [50PSOTF.En_Hm2_Blk] to prevent
maloperation due to inrush current.
⚫ PCS-Studio
50/51G.DIR.RCA -180~179 1 °
50/51G.DIR.phi_Min_Fwd 10~90 1 °
50/51G.DIR.phi_Max_Fwd 10~90 1 °
50/51G.DIR.phi_Min_Rev 10~90 1 °
50/51G.DIR.phi_Max_Rev 10~90 1 °
Disabled
50/51G.En_VTS_Blk
Enabled
Non_Directional
50/51G1.Opt_Dir Forward
Reverse
3
Disabled
50/51G1.En_Hm_Blk
Enabled
Disabled
50/51G1.En
Enabled
Trp
50/51G1.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
50/51G1.Opt_Curve ANSILT
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51G1.Opt_Curve_DropOut DefTime
IDMT
Non_Directional
50/51G2.Opt_Dir Forward
Reverse
Disabled
50/51G2.En_Hm_Blk
Enabled
Disabled
50/51G2.En
Enabled
Trp
50/51G2.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
50/51G2.Opt_Curve ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
IECN
IECV
IECI
IECE
IECST
IECLT
3
IECDefTime
UserDefine
Inst
50/51G2.Opt_Curve_DropOut DefTime
IDMT
Non_Directional
50/51G3.Opt_Dir Forward
Reverse
Disabled
50/51G3.En_Hm_Blk
Enabled
Disabled
50/51G3.En
Enabled
50/51G3.Opt_Trp/Alm Trp
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
3 ANSILTE
ANSILTV
ANSILT
50/51G3.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51G3.Opt_Curve_DropOut DefTime
IDMT
Non_Directional
50/51G4.Opt_Dir Forward
Reverse
Disabled
50/51G4.En_Hm_Blk
Enabled
Disabled
50/51G4.En
Enabled
3
Trp
50/51G4.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
50/51G4.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51G4.Opt_Curve_DropOut DefTime
IDMT
Non_Directional
50/51G5.Opt_Dir Forward
Reverse
Disabled
50/51G5.En_Hm_Blk
Enabled
Disabled
50/51G5.En
Enabled
Trp
50/51G5.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
50/51G5.Opt_Curve ANSILTE
ANSILTV
ANSILT
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51G5.Opt_Curve_DropOut DefTime
3
IDMT
Non_Directional
50/51G6.Opt_Dir Forward
Reverse
Disabled
50/51G6.En_Hm_Blk
Enabled
Disabled
50/51G6.En
Enabled
Trp
50/51G6.Opt_Trp/Alm
Alm
ANSIE
50/51G6.Opt_Curve ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
IECN
3 IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51G6.Opt_Curve_DropOut DefTime
IDMT
1. 50/51G.DIR.RCA
-U0
[50/51G.DIR.phi_Min_Fwd]
Non-operating I0
area
Operating area in
[50/51G.DIR.phi_Max_Rev] forward direction
[50/51G.DIR.RCA]
Operating area in
reverse direction
3
[50/51G.DIR.phi_Max_Fwd]
Non-operating
area
[50/51G.DIR.phi_Min_Rev]
By setting the characteristic angle to determine the most sensitive forward angle of zero-sequence
current, using zero-sequence current with zero-sequence voltage to determine the direction of
zero-sequence current in forward direction or reverse direction.
For line protection, when the CT polarity is on the busbar side, its recommended value is 45°.
2. 50/51G.DIR.phi_Min_Fwd
It is used to set the minimum boundary in forward direction of earth fault protection.
3. 50/51G.DIR.phi_Max_Fwd
It is used to set the maximum boundary in forward direction of earth fault protection.
4. 50/51G.DIR.phi_Min_Rev
It is used to set the minimum boundary in reverse direction of earth fault protection.
5. 50/51G.DIR.phi_Max_Rev
It is used to set the maximum boundary in reverse direction of earth fault protection.
6. 50/51G.DIR.I_Min
It is used to set the minimum operating current setting of direction control element.
7. 50/51G.DIR.U_Min
It is used to set the minimum operating voltage setting of direction control element.
Its recommended value is 4V. Considering the sensitivity of earth fault with high resistance, the
recommended value is 0.5~2V. When it cooperates with other protection with direction control
element, it is recommended to add 0.5~1V on the basis of the similar setting of other protection.
8. 50/51G.En_VTS_Blk
It is used to enable/disable earth fault protection is blocked by VT circuit failure when VT circuit
supervision is enabled and VT circuit fails.
3 When VT circuit fails, earth fault protection will be blocked if the setting is set as "Enabled". Earth
fault protection is not controlled by direction control element if the setting is set as "Disabled".
9. 50/51G.HMB.K_Hm2
In order to prevent earth fault protection from maloperation during the transformer energized for
transformer-in-line applicaiton, harmonic control element can be used to block earth fault
protection. When the percentage of second harmonic component to fundamental component in
phase current is larger than the setting [50/51G.HMB.K_Hm2], harmonic control element operates
to block phase overcurrent protection if the setting [50/51Gi.En_Hm_Blk] is set as "Enabled".
If second harmonic component of residual current is lower than 0.04In, then harmonic calculation
is not carried out and harmonic control element does not operate.
10. 50/51G.HMB.I_Rls
It shall be greater than possible maximum inrush current of the transformer. It is recommended to
set as 20In.
11. 50/51G*.3I0_Set
It is used set the zero-sequence current setting for stage * of earth fault protection. (*=1~6)
1) When stage * of earth fault protection is used as fast protection, the following conditions
should be considered.
⚫ It shall be greater than the maximum residual current under pole disagreement condition.
⚫ It shall be greater than the maximum residual current when internal fault happens to the end
of the line.
Where:
2) When stage * of earth fault protection is used as definite-time protection, it should coordinate
with the protection of other adjacent line.
⚫ It shall be greater than the maximum residual current under pole disagreement condition.
⚫ It shall coordinate with the measurement element in the adjacent line and ensure sensitive
enough for the fault happening to the end of the line.
3
[50/51𝐺 ∗ .3𝐼0_𝑆𝑒𝑡] = 𝐾𝑟𝑒𝑙 × 𝐾𝑏𝑟 × 𝐼0.𝐴𝑑𝑗
Where:
Kbr is the branching coefficient of residual current, which is equal to ratio of residual current
passing through the device to passing through the faulty line during an earth fault at the end of
protected section of coordinated stage of earth fault protection of the line. Maximum value among
various operation conditions can be taken
3) When earth fault protection is used as backup protection for ground fault of this line through
resistor and ground fault of adjacent elements, and its primary current value should not be
more than 300A. Under the condition of avoidance from the maximum unbalance current of
three-phase short circuit at other sides of the transformer at the end of this line, it is necessary
to meet the requirement that the fault at the end of the adjacent lines has sufficient sensitivity;
it is necessary to check the coordination condition with the definite-time earth fault protection
of the adjacent line, and the operating time is set according to the coordination relation.
Where:
Kst is same type coefficient, taken as 0.5 when the transformer is of the same type.
4) When earth fault protection is used as inverse-time protecton, the calculation principle is
Where:
12. 50/51G*.t_Op
It is used to set the operating time delay for stage * of earth fault protection. (*=1~6)
⚫ When earth fault protection as definite-time protection coordinates with adjacent line, this
setting should be set according to coordinate with time delay of earth fault protection of the
subordinate line.
3 Its calculation principle is:
Where:
⚫ If it is used independently, it should be greater than maximum operation time of system pole
discrepancy.
13. 50/51G*.t_DropOut
It is used to set the dropout time delay for stage * of earth fault protection. (*=1~6)
14. 50/51G*.Opt_Dir
It is used to select the direction characteristic for stage * of earth fault protection. (*=1~6)
Non_Directional: no direction
15. 50/51G*.En_Hm_Blk
It is used to enable/disable stage * of earth fault protection controlled by harmonic control element.
(*=1~6)
16. 50/51G*.En
17. 50/51G*.Opt_Trp/Alm
It is used to enable/disable stage * of earth fault protection operate to trip or alarm. (*=1~6)
18. 50/51G*.Opt_Curve
It is used to select the operating characteristics curve for stage * of earth fault protection. (*=1~6)
UserDefine: Programmable
When the setting is set as "UserDefine", the user can customize the inverse-time curve
characteristic by setting constants K, α and C.
19. 50/51G*.Opt_Curve_DropOut
It is used to select the dropout characteristics curve for stage * of earth fault protection. (*=1~6)
When the operating characteristics curve is selected as ANSI inverse-time characteristic, the
dropout characteristic curve can be selected as instantaneous dropout characteristics,
definite-time dropout characteristics and ANSI inverse-time dropout characteristics.
20. 50/51G*.TMS
It is used to set time multiplier setting for stage * of inverse-time earth fault protection. (*=1~6)
This setting can be deduced according to the operating time required by inverse-time earth fault
protection.
21. 50/51G*.tmin
3 It is used to set the minimum operating time for stage * of inverse-time earth fault protection.
(*=1~6)
When inverse-time characteristic is selected, if calculated operating time is less than the setting
[50/51G*.tmin], then the operating time changes to the value of the setting [50/51G*.tmin]
automatically.
Where:
22. 50/51G*.K
It is used to set the constant “K” for stage * of customized inverse-time earth fault protection.
(*=1~6)
The setting shall be set according to the expected inverse-time characteristics of earth fault
protection. It is valid only if the setting [50/51G*.Opt_Curve] is set as "UserDefine".
23. 50/51G*.Alpha
It is used to set the constant “α” for stage * of customized inverse-time earth fault protection.
(*=1~6)
The setting shall be set according to the expected inverse-time characteristics of earth fault
protection. It is valid only if the setting [50/51G*.Opt_Curve] is set as "UserDefine".
24. 50/51G*.C
It is used to set the constant “C” for stage * of customized inverse-time earth fault protection.
(*=1~6)
The setting shall be set according to the expected inverse-time characteristics of earth fault
protection. It is valid only if the setting [50/51G*.Opt_Curve] is set as "UserDefine".
⚫ PCS-Studio
Disabled
50GSOTF.En
Enabled
Disabled
50GSOTF.En_Hm2_Blk
Enabled
1. 50GSOTF.3I0_Set
The setting should ensure sufficient sensitivity to ground fault with high impedance at the end of
the line.
2. 50GSOTF.t_Op_1P
It is used to set time delay for residual current SOTF protection when 1 pole closed.
3. 50GSOTF.t_Op_3P
It is used to set time delay for residual current SOTF protection when 3 pole closed.
4. 50GSOTF.En
5. 50GSOTF.En_Hm2_Blk
For in-line transformer application, large inrush current generated during manual closing and
auto-reclosing will lead to an undesired operation of residual current SOTF protection. Second
harmonic blocking can be selected by the setting [50GSOTF.En_Hm2_Blk] to prevent
maloperation due to inrush current.
3
3.15 Negative-sequence Overcurrent Protection (50/51Q)
⚫ PCS-Studio
50/51Q.DIR.RCA -180~179 1 °
50/51Q.DIR.phi_Min_Fwd 10~90 1 °
50/51Q.DIR.phi_Max_Fwd 10~90 1 °
50/51Q.DIR.phi_Min_Rev 10~90 1 °
50/51Q.DIR.phi_Max_Rev 10~90 1 °
Disabled
50/51Q.En_VTS_Blk
Enabled
Non_Directional
50/51Q1.Opt_Dir Forward
Reverse
Disabled
50/51Q1.En
Enabled
Trp
50/51Q1.Opt_Trp/Alm
Alm
3
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
ANSILT
50/51Q1.Opt_Curve
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51Q1.Opt_Curve_DropOut DefTime
IDMT
50/51Q2.Opt_Dir Forward
Reverse
Disabled
50/51Q2.En
Enabled
Trp
50/51Q2.Opt_Trp/Alm
Alm
ANSIE
ANSIV
ANSIN
ANSIM
ANSIDefTime
ANSILTE
ANSILTV
50/51Q2.Opt_Curve ANSILT
IECN
IECV
IECI
IECE
IECST
IECLT
IECDefTime
UserDefine
Inst
50/51Q2.Opt_Curve_DropOut DefTime
IDMT
1. 50/51Q.DIR.RCA
-U2
[50/51Q.DIR.phi_Min_Fwd]
Non-operating I2
area
[50/51Q.DIR.phi_Max_Rev]
Operating area in
forward direction
[50/51Q.DIR.RCA]
Operating area in
reverse direction
[50/51Q.DIR.phi_Max_Fwd]
Non-operating
area
[50/51Q.DIR.phi_Min_Rev]
By setting the characteristic angle to determine the most sensitive forward angle of
negative-sequence current, using negative-sequence current with negative-sequence voltage to
determine the direction of negative-sequence current in forward direction or reverse direction.
2. 50/51Q.DIR.phi_Min_Fwd
protection.
3. 50/51Q.DIR.phi_Max_Fwd
4. 50/51Q.DIR.phi_Min_Rev
5. 50/51Q.DIR.phi_Max_Rev
6. 50/51Q.DIR.I_Min
It is use to set the minimum operating current setting of direction control element.
7. 50/51Q.DIR.U_Min
It is use to set the minimum operating voltage setting of direction control element.
8. 50/51Q.En_VTS_Blk
When VT circuit fails, negative-sequence overcurrent protection will be blocked if the setting is set
as "Enabled". Negative-sequence overcurrent protection is not controlled by direction control
element if the setting is set as "Disabled".
9. 50/51Q*.I2_Set
1
𝐼2.2𝑃 = 𝐼
2 3𝑃
Where:
For line protection, only when the pickup current of negative-sequence overcurrent element is
equal to 0.5 times the pickup setting of phase overcurrent element fixedly, the relative sensitivity
coefficient of two-phase short circuit is equal to 1. During setting calculation, the coordination of
sensitivity can be carried out only according to the three-phase short circuit and the overcurrent
protection with adjacent lines.
The setting of negative-sequence overcurrent protection can be referred to the setting of phase
overcurrent protection.
3
[50/51𝑄 ∗. 𝐼2_𝑆𝑒𝑡] = 𝐾𝑛 × 𝐼𝐿.𝑚𝑎𝑥
Where:
10. 50/51Q*.t_Op
It is used to set the operating time delay for stage * of negative-sequence overcurrent protection.
(*=1 or 2)
It should be set being identical with the time delay of phase overcurrent protection. Because the
fault happens in the same point, the protection with higher sensitivity between phase overcurrent
protection and negative-sequence overcurrent protection will operate in priority.
11. 50/51Q*.t_DropOut
It is used to set the dropout time delay for stage * of negative-sequence overcurrent protection.
(*=1 or 2)
12. 50/51Q*.Opt_Dir
Non_Directional: no direction
13. 50/51Q*.En
14. 50/51Q*.Opt_Trp/Alm
15. 50/51Q*.Opt_Curve
It is used to select the operating characteristics curve for stage * of negative-sequence overcurrent
protection. (*=1 or 2)
3 ANSIE: ANSI Extremely Inverse
UserDefine: Programmable
When the setting is set as "UserDefine", the user can customize the inverse-time curve
characteristic by setting constants K, α and C.
16. 50/51Q*.Opt_Curve_DropOut
It is used to select the dropout characteristics curve for stage * of negative-sequence overcurrent
protection. (*=1 or 2)
When the operating characteristics curve is selected as ANSI inverse-time characteristic, the
dropout characteristic curve can be selected as instantaneous dropout characteristics,
definite-time dropout characteristics and ANSI inverse-time dropout characteristics.
17. 50/51Q*.TMS 3
It is used to set time multiplier setting for stage * of inverse-time negative-sequence overcurrent
protection. (*=1 or 2)
The setting can be deduced according to the operating time required by inverse-time
negative-sequence overcurrent protection.
18. 50/51Q*.tmin
It is used to set the minimum operating time for stage * of inverse-time negative-sequence
overcurrent protection. (*=1 or 2)
When inverse-time characteristic is selected, if calculated operating time is less than the setting
[50/51Q*.tmin], then the operating time changes to the value of the setting [50/51Q*.tmin]
automatically.
19. 50/51Q*.K
It is used to set the constant "K" for stage * of customized inverse-time negative-sequence
overcurrent protection (*=1 or 2)
20. 50/51Q*.Alpha
It is used to set the constant "α" for stage * of customized inverse-time negative-sequence
overcurrent protection. (*=1 or 2)
21. 50/51Q*.C
It is used to set the constant "C" for stage * of customized inverse-time negative-sequence
overcurrent protection. (*=1 or 2)
Up
59P1.Opt_Up/Upp
Upp
3P
59P1.Opt_1P/3P
1P
Disabled
59P1.En
Enabled
Trp
59P1.Opt_Trp/Alm
Alm
ANSIDefTime
IECDefTime
59P1.Opt_Curve
UserDefine
InvTime_U
59P1.Opt_Curve_DropOut Inst
DefTime
Up
3
59P2.Opt_Up/Upp
Upp
3P
59P2.Opt_1P/3P
1P
Disabled
59P2.En
Enabled
Trp
59P2.Opt_Trp/Alm
Alm
ANSIDefTime
IECDefTime
59P2.Opt_Curve
UserDefine
InvTime_U
Inst
59P2.Opt_Curve_DropOut
DefTime
1. 59P*.Opt_Up/Upp
It is used to select the calculation voltage used by stage * of phase overvoltage protection. (*=1 or
2)
2. 59P*.Opt_1P/3P
It is used to select the voltage criterion used by stage * of phase overvoltage protection. (*=1 or 2)
3P: 3-out-of-3 mode, i.e., phase overvoltage protection detects three-phase voltages or three
phase-to-phase voltages.
1P: 1-out-of-3 mode, i.e., phase overvoltage protection detects any phase voltage or
phase-to-phase voltage.
3. 59P*.U_Set
It is used to set the voltage setting for stage * of phase overvoltage protection. (*=1 or 2)
The setting should be set according to the actual isolation requirements of the system equipment.
and the setting [59P*.Opt_Up/Upp].
If the setting [59P*.Opt_Up/Upp] is set as "Upp", then phase-to-phase voltage will be used for
calculation, [59P*.U_Set] should be set as phase-to-phase voltage.
If the setting [59P*.Opt_Up/Upp] is set as "Up", then phase voltage will be used for calculation,
[59P*.U_Set] should be set as phase voltage.
Application example:
If the operating criterion adopts phase-to-phase voltage, Un=110V, 1.3 times Un is assigned for
overvoltage protection. The setting will be given as below:
[59P*.Opt_Up/Upp]=Upp
[59P*.U_Set]=143V
If the operating criterion adopts phase-to-ground voltage, Un=63.5V, 1.3 times Un is assigned for
[59P*.Opt_Up/Upp]=Up
[59P*.U_Set]=82.55V
Where:
4. 59P*.K_DropOut
It is used to set the dropout coefficient for stage * of phase overvoltage protection. (*=1 or 2)
5. 59P*.t_Op
It is used to set the operating time delay for stage * of phase overvoltage protection. (*=1 or 2)
It shall be set according to the withstanding voltage ability of protected equipment, and its
recommended value is 0.3s~1s.
6. 59P*.t_DropOut
It is used to set the dropout time delay for stage * of phase overvoltage protection. (*=1 or 2)
The setting is valid when definite-time dropout characteristics is selected, and its recommended
value is 0.
7. 59Pi.En
8. 59P*.Opt_Trp/Alm
It is used to enable/disable stage * of phase overvoltage protection operate to trip or alarm (*=1 or
2)
9. 59P*.Opt_Curve
It is used to select the operating characteristics curve for stage * of phase overvoltage protection.
(*=1 or 2)
UserDefine: Programmable
When the setting is set as "UserDefine", the user can customize the inverse-time curve
characteristic by setting constants K, α and C.
10. 59P*.Opt_Curve_DropOut
3 It is used to set the dropout characteristics curve for stage * of phase overvoltage protection (*=1
or 2)
11. 59P*.TMS
It is used to set time multiplier setting for stage * of inverse-time phase overvoltage protection. (*=1
or 2)
The setting can be deduced according to the operating time required by inverse-time phase
overvoltage protection.
12. 59P*.tmin
It is used to set the minimum operating time for stage * of inverse-time phase overvoltage
protection. (*=1 or 2)
When inverse-time characteristics is selected, if calculated operating time is less than the setting
[59P*.tmin], then the operating time changes to the setting [59P*.tmin] automatically. Its
recommended value is 0.02s.
13. 59P*.K
It is used to set the constant “K” for stage * of customized inverse-time phase overvoltage
protection. (*=1 or 2)
The setting shall be set according to the expected inverse-time characteristics of pahse
overvoltage protection. It is valid only if the setting [59P*.Opt_Curve] is set as "UserDefine".
14. 59Pi.Alpha
It is used to set the constant “C” for stage * of customized inverse-time phase overvoltage
protection. (*=1 or 2)
The setting shall be set according to the expected inverse-time characteristics of pahse
overvoltage protection. It is valid only if the setting [59P*.Opt_Curve] is set as "UserDefine".
15. 59Px.C
It is used to set the constant “α” for stage i of customized inverse-time phase overvoltage
protection. (i=1 or 2)
The setting shall be set according to the expected inverse-time characteristics of pahse
overvoltage protection. It is valid only if the setting [59P*.Opt_Curve] is set as "UserDefine".
⚫ PCS-Studio
Disabled
59G1.En
Enabled
Trp
59G1.Opt_Trp/Alm
Alm
Disabled
59G2.En
Enabled
59G2.Opt_Trp/Alm Trp
Alm
1. 59G*.3U0_Set
It is used to set the voltage setting for stage * of residual overvoltage protection. (*=1 or 2)
It shall be greater than maximum unbalanced residual voltage under normal conditions.
0.5 × 𝑈2𝑛
[59𝐺 ∗ .3𝑈0_𝑆𝑒𝑡] =
1.732
2 × 𝑈2𝑛
[59𝐺 ∗ .3𝑈0_𝑆𝑒𝑡] =
1.732
1.2 × 𝑈2𝑛
[59𝐺 ∗ .3𝑈0_𝑆𝑒𝑡] =
1.732
2. 59G*.K_DropOut
It is used to set the dropout coefficient for stage * of residual overvoltage protection. (*=1 or 2)
3. 59G*.t_Op
It is used to set the operating time delay for stage * of residual overvoltage protection. (*=1 or 2)
It shall be set to keep residual overvotlage protection away from the influence of transient
characteristics and its recommended value is 0.3s~0.5s.
4. 59G*.t_DropOut
It is used to set the dropout time delay for stage * of residual overvoltage protection. (*=1 or 2)
5. 59G*.En
6. 59G*.Opt_Trp/Alm
It is used to enable/disable stage * of residual overvoltage protection operate to trip or alarm. (*=1
or 2)
⚫ LCD
⚫ PCS-Studio
Disabled
59Q1.En
Enabled
Trp
59Q1.Opt_Trp/Alm
Alm
Disabled
59Q2.En
Enabled
Trp
59Q2.Opt_Trp/Alm
Alm
1. 59Q*.U2_Set
3
It is used to set the voltage setting for stage * of negative-sequence overvoltage protection. (i=1 or
2)
The setting should be set according to negative-sequence voltage. The calculation principle is as
below.
𝐾𝑟𝑒𝑙 × 𝑈2𝑛
[59𝑄 ∗. 𝑈2_𝑆𝑒𝑡] =
1.732
Where:
Krel needs to be set according to the specific application. If the negative-sequence overvoltage
protection is used to release the relevant current protection when detecting the reverse phase
sequence connection or the asymmetric fault, the setting can be not very sensitive, and Krel is
recommended to be set as 0.1.
If the negative-sequence overvoltage protection is used to detect the unbalance of the rotating
motor and prevent the motor from overheating and burning out, Krel is recommended to be set as
0.03.
Application example:
0.1 × 100
[59𝑄 ∗. 𝑈2𝑆𝑒𝑡 ] = = 5.78𝑉
1.732
In addition, the setting should be more thant the maximum unbalance negative-sequence voltage
during normal operation.
2. 59Q*.K_DropOut
It is used to set the dropout coefficient for stage * of negative-sequence overvoltage protection.
(*=1 or 2)
The setting can be appropriately reduced to prevent frequent jitter if the negative-sequence
3. 59Q*.t_Op
It is used to set the operating time delay for stage * of negative-sequence overvoltage protection.
(*=1 or 2)
The time delay can be appropriately reduced if the operating threshold of negative-sequence
voltage is large, for example, 1s.
If the negative-sequence voltage setting is small, it is recommended to set this setting as a larger
value, for example, 5s. 3
4. 59Q*.t_DropOut
It is used to set the dropout time delay for stage * of negative-sequence overvoltage protection.
(*=1 or 2)
5. 59Q*.En
6. 59Q*.Opt_Trp/Alm
⚫ LCD
⚫ PCS-Studio
Up
27P1.Opt_Up/Upp
Upp
3P
27P1.Opt_1P/3P
1P
3 None
Curr
27P1.Opt_LogicMode CBPos
CurrOrCBPos
CurrAndCBPos
Disabled
27P1.En_VTS_Blk
Enabled
Disabled
27P1.En
Enabled
Trp
27P1.Opt_Trp/Alm
Alm
ANSIDefTime
IECDefTime
27P1.Opt_Curve
UserDefine
InvTime_U
Inst
27P1.Opt_Curve_DropOut
DefTime
Up
27P2.Opt_Up/Upp
Upp
3P
3
27P2.Opt_1P/3P
1P
None
Curr
27P2.Opt_LogicMode CBPos
CurrOrCBPos
CurrAndCBPos
Disabled
27P2.En_VTS_Blk
Enabled
Disabled
27P2.En
Enabled
Trp
27P2.Opt_Trp/Alm
Alm
ANSIDefTime
IECDefTime
27P2.Opt_Curve
UserDefine
InvTime_U
27P2.Opt_Curve_DropOut Inst
DefTime
1. 27P*.Opt_Up/Upp
It is used to select the calculation voltage used by stage * of phase undervoltage protection. (*=1
or 2)
2. 27P*.Opt_1P/3P
It is used to select the voltage criterion used by stage * of phase undervoltage protection. (*=1 or
2)
3P: 3-out-of-3 mode, i.e., phase undervoltage protection detects three-phase voltages or three
phase-to-phase voltages.
1P: 1-out-of-3 mode, i.e., phase undervoltage protection detects any phase voltage or
phase-to-phase voltage.
3. 27P*.Opt_LogicMode
The option of auxiliary criterion mode for stage * of phase undervoltage protection (*=1 or 2)
None: no check
When the load current is relatively fixed and is larger than 0.04In, the current criterion is
recommended, such as the capacitor and reactor load. Otherwise, the breaker position criterion is
recommended.
When the breaker position can be acquired, and the load current is also larger than 0.04In,
When the circuit breaker of the incoming line has been tripped and the busbar loses voltage,
phase undervoltage protection is still desired to operate at this time, so the breaker position
criterion needs to be selected.
4. 27P*.U_Set
It is used to set the voltage setting for stage * of phase undervoltage protection. (*=1 or 2)
The setting should be set according to the actual stability level of power system, but it should
ensure sensitive enough to the fault at the end of the line and not be greater than the minimum
operation voltage under normal conditions.
3
The setting should also be set according to the setting [27P*.Opt_Up/Upp].
If the setting [27P*.Opt_Up/Upp] is set as "Upp", then phase-to-phase voltage will be used for
calculation, [27P*.U_Set] should be set as phase-to-phase voltage.
If the setting [27Pi.Opt_Up/Upp] is set as "Up", then phase voltage will be used for calculation,
[27P*.U_Set] should be set as phase voltage.
Application example:
If the operating criterion adopts phase-to-phase voltage, Un=110V, 0.7 times Un is assigned for
undervoltage protection. The setting will be given as below:
[27P*.Opt_Up/Upp]=Upp
[27P*.U_Set]=77V
If the operating criterion adopts phase-to-ground voltage, Un=63.5V, 0.7 times Un is assigned for
undervoltage protection. The setting will be given as below:
[27P*.Opt_Up/Upp]=Up
[27P*.U_Set]=44.45V
5. 27P*.K_DropOut
It is used to set the dropout coefficient for stage * of phase undervoltage protection. (*=1 or 2)
6. 27P*.t_Op
It is used to set the operating time delay for stage * of phase undervoltage protection. (*=1 or 2)
7. 27P*.t_DropOut
It is used to set the dropout time delay for stage * of phase undervoltage protection. (*=1 or 2)
This setting is valid when definite-time drop-out characteristic is selected, and its recommended
value is 0.
8. 27P*.En_VTS_Blk
When the setting [27P*.En_VTS_Blk] is set as "Enabled", phase undervoltage protection will be
blocked if VT circuit fails.
9. 27P*.En
10. 27P*.Opt_Trp/Alm
3 It is used to enable/disable stage * of phase undervoltage protection operate to trip or alarm. (*=1
or 2)
11. 27P*.Opt_Curve
It is used to select the operating characteristics curve for stage * of phase undervoltage protection.
(*=1 or 2)
UserDefine: Programmable
When the setting is set as "UserDefine", the user can customize the inverse-time curve
characteristic by setting constants K, α and C.
12. 27P*.Opt_Curve_DropOut
It is used to select the dropout characteristics curve for stage * of phase undervoltage protection.
(*=1 or 2)
13. 27P*.TMS
It is used to set time multiplier setting for stage * of inverse-time phase undervoltage protection.
(*=1 or 2)
The setting can be deduced according to the operating time required by inverse-time phase
undervoltage protection.
14. 27P*.tmin
It is used to set the minimum operating time for stage * of inverse-time phase undervoltage
protection. (*=1 or 2)
When inverse-time characteristics is selected, if calculated operating time is less than the setting
[27P*.tmin], then the operating time changes to the setting [27P*.tmin] automatically. Its
recommended value is 0.03s.
15. 27P*.K
It is used to set the constant “K” for stage * of customized inverse-time phase undervoltage
protection. (*=1 or 2)
3
The setting shall be set according to the expected inverse-time characteristics of pahse
undervoltage protection. It is valid only if the setting [27P*.Opt_Curve] is set as "UserDefine".
16. 27P*.Alpha
It is used to set the constant “α” for stage * of customized inverse-time phase undervoltage
protection. (*=1 or 2)
The setting shall be set according to the expected inverse-time characteristics of pahse
undervoltage protection. It is valid only if the setting [27P*.Opt_Curve] is set as "UserDefine".
17. 27P*.C
It is used to set the constant “C” for stage * of customized inverse-time phase undervoltage
protection. (*=1 or 2)
The setting shall be set according to the expected inverse-time characteristics of pahse
undervoltage protection. It is valid only if the setting [27P*.Opt_Curve] is set as "UserDefine".
⚫ LCD
⚫ PCS-Studio
Disabled
81O1.En
Enabled
Disabled
81O3.En
Enabled
Disabled
81O4.En
Enabled
1. 81.Upp_Blk
It is used to set the phase-to-phase voltage setting used to block frequency protection (including
overfrequency protection, underfrequency protection and frequency rate-of-change protection).
When any phase-to-phase voltage is smaller than the setting [81.Upp_Blk], the frequency
protection will be blocked. It is a general setting and shared by overfrequency protection,
underfrequency protection and frequency rate-of-change protection.
The setting should be set according to the phase-to-phase voltage. Its recommended value is
0.7Unn (Unn is rated phase-to-phase voltage).
2. 81O*.f_Set
It is used to set the frequency setting for stage * of overfrequency protection. (*=1~4)
All stages can be set based on the same graduation. After rejecting some power supplies and
each stage operating, the system frequency should be restored near rated frequency. Because
compound mode of generators (hydroelectric, thermal power, nuclear power with different capacity
and proportion, different adaptability to abnormal frequency), system structure and operation
mode are different in different power system, they should be set according to system frequency
and stability control strategy.
3. 81O*.t_Op
It is used to set the time delay for stage * of overfrequency protection. (*=1~4)
4. 81O*.En
⚫ LCD
⚫ PCS-Studio
Disabled
81U1.En
Enabled
Disabled
81U2.En
Enabled
Disabled
81U3.En
Enabled
Disabled
81U4.En
Enabled
3
3.21.3 Calculation Principle
1. 81.Upp_Blk
2. 81U*.f_Set
It is used to set the frequency setting for stage * of underfrequency protection. (*=1~6)
All stages can adopt cascade connection, and small graduation can be set among them, for
example, taking 0.2Hz. Selecting one special stage, it can avoid system frequency always keeping
in a certain frequency. When some loads are shed after other stages of underfrequency protection
operate to shed major loads and make system frequency restore to normal value.
3. 81U*.t_Op
It is used to set the time delay for stage * of underfrequency protection. (*=1~6)
4. 81U*.En
⚫ LCD
⚫ PCS-Studio
Disabled
3
81R1.En
Enabled
Disabled
81R2.En
Enabled
Disabled
81R3.En
Enabled
Disabled
81R4.En
Enabled
1. 81.Upp_Blk
2. 81R*.df/dt_Set
It is used to set the frequency rate-of-change setting for stage * of frequency rate-of-change
protection. (*=1~6)
If the system frequency quickly decreases due to large active power shortage after the system
fault, it is required to remove the overload line as soon as possible, to avoid frequency collapse,
and its recommended value is -0.8~-2Hz/s.
If the system frequency quickly increases due to surplus system power (more than 20%), the
generator rejection should be executed, to avoid the frequency increasing, and its recommended
value is 0.8~2Hz/s.
3. 81R*.t_Op
3 It is used to set the time delay for stage * of frequency rate-of-change protection. (*=1~6)
4. 81R*.f_Pkp
It is used to set the pickup frequency setting for stage * of frequency rate-of-change protection.
(*=1~6)
5. 81R*.En
⚫ PCS-Studio
Disabled
32R1.En
Enabled
Trp
32R1.Opt_Trp/Alm
Alm
Disabled
32R2.En
Enabled
Trp
32R2.Opt_Trp/Alm
Alm
1. 32R*.U1_VCE
It is used to set the positive-sequence voltage setting which is used to block stage * of reverse
power protection. (*=1or 2)
2. 32R*.I1_CCE
It is used to set the positive-sequence current setting which is used to block stage * of reverse
power protection. (*=1or 2)
3. 32R*.U2_VCE
It is used to set the negative-sequence voltage setting which is used to block stage * of reverse
power protection. (*=1or 2)
4. 32R*.P_Set
It is used to set the power setting for stage * of reverse power protection. (*=1or 2)
Generally, it should be set according to the minimum measurable power under reverse power
conditions.
5. 32R*.t_Op
3 The operating time delay for stage * of reverse power protection (*=1or 2)
6. 32R*.En
7. 32R*.Opt_Trp/Alm
It is used to enable/disable stage * of reverse power protection operate to trip or alarm. (*=1 or 2)
⚫ LCD
⚫ PCS-Studio
1P
37.Opt_1P/3P
3P
None
Curr
37.Opt_LogicMode CBPos
CurrOrCBPos
CurrAndCBPos
Disabled
37.En
Enabled
Trp
3
37.Opt_Trp/Alm
Alm
1. 37.I_Set
The setting should ensure that undercurrent protection can reliably operate after the bus
connected with the capacitor loses the voltage, and undercurrent protection can reliably drop off
after the bus voltage returns to normal
2. 37.t_Op
It should coordinate with the operating time of backup protection of outgoing line at local end.
[37. 𝑡_𝑂𝑝] = 𝑡 ′ + ∆𝑡
Where:
𝑡 ′ is the operating time of backup protection which undercurrent protection need to coordinate
with.
3. 37.Opt_1P/3P
If the setting is set as "1P", undercurrent protection will discriminate any phase current with the
current criterion. If the setting is set as "3P", undercurrent protection will discriminate three-phases
currents with the current criterion.
4. 37.Opt_LogicMode
None: no check
When the load current is relatively constant and is larger than 0.04In, the setting is recommende to
set as "Curr", such as the capacitor and reactor load. Otherwise, it is recommended to set as
"CBPos".
When the CB position can be acquired, and the load current is also larger than 0.04In, the setting
is recommende to set as "CurrAndCBPos".
When the circuit breaker of incoming line has been tripped and the busbar loses voltage,
undercurrent protection is still desired to operate at this time, the setting is recommended to set as
"CBPos".
If the CB position cannot be acquired, the setting is recommended to set as "None". However, the
other method should be adopted to ensure that undercurrent protection will not always operate
before the equipment is put into operation because the circuit breaker is not closed and there is no
current at this time, and undercurrent protection can reliably drop off after the abnormal condition
disappears.
5. 37.En
6. 37.Opt_Trp/Alm
⚫ PCS-Studio
Disabled
CBx.50BF.En
Enabled
Disabled
CBx.50BF.En_ReTrp
Enabled
Disabled
CBx.50BF.En_t1
Enabled
Disabled
CBx.50BF.En_t2
Enabled
Disabled
CBx.50BF.En_3I0_1P
Enabled
Disabled
CBx.50BF.En_Ip
Enabled
CBx.50BF.En_3I0_3P Disabled
Enabled
Disabled
CBx.50BF.En_I2_3P
Enabled
Disabled
CBx.50BF.En_CB_Ctrl
Enabled
Disabled
3 CBx.50BF.En_Alm_Init
Enabled
1. CBx.50BF.I_Set
It is used to set the phase current setting of detecting breaker failure protection.
The measured phase current is used to detect the circuit breaker failure. The setting should can
detect the fault with small fault current. It could be chosen in accordance with the most sensitive
protection function that initiate the breaker failure protection.
2. CBx.50BF.3I0_Set
It is used to set the zero-sequence current setting of detecting breaker failure protection.
In the grouded systems via high impedance, the residual current is normally much smaller than the
short-circuit currents for the single-phase earth fault. In order to reliably detect the circuit breaker
failure under the single-phase earth fault, it is necessary to add the zero-sequence current
detection by the setting [CBx.50BF.En_3I0_1P] (set as "Enabled"). At this time, the phase current
setting [CBx.50BF.I_Set] could be set more sensitive.
Taking into account that the faulty current is too small for generator or transformer fault, the
sensitivity of phase current element may not meet the requirements, zero-sequence current
criterion and negative-sequence current criterion are provided in addition to the phase overcurrent
element for breaker failure protection initiated by input signal [CBx.50BF.ExTrp3P] from external
tripping. They can be enabled or disabled by the settings [CBx.50BF.En_3I0_3P] and
[CBx.50BF.En_I2_3P] respectively.
The setting [CBx.50BF.3I0_Set] shall be greater than maximum zero-sequence unbalance current
(3I0) under normal operation condition.
3. CBx.50BF.I2_Set
It is used to set the negative-sequence current setting of detecting breaker failure protection.
4. CBx.50BF.t_ReTrp
The setting defines the time delay of re-tripping for breaker failure protection, generally set as
5ms~50ms.
5. CBx.50BF.t1_Op
It is used to set the time delay for the first stage of breaker failure protection.
Breaker failure protection will send three-phase tripping command to trip local circuit breaker when
the time delay of [CBx.50BF.t1_Op] is expired. The setting [CBx.50BF.t1_Op] is set as short as
3
possible on the premise that the selectivity of breaker failure protection is warrantable.
[CBx.50BF.t1_Op]=t0+tB+Δt
Where:
tB is the drop off time of the operation element, generally taken as 0.02~0.04s.
Normally, it is used to trip local circuit breaker again before the second stage of breaker failure
protection operating in case that the local circuit breaker could open to prevent to trip the adjacent
circuit breakers.
6. CBx.50BF.t2_Op
It is used to set the time delay for the second stage of breaker failure protection.
Breaker failure protection will send three-phase tripping command to trip adjacent circuit breakers
when the time delay of [CBx.50BF.t2_Op] is expired. The setting [CBx.50BF.t2_Op] is set as short
as possible on the premise that the selectivity of breaker failure protection is warrantable and
undesired operation must be avoided. Besides, the setting should be greater than the setting
[CBx.50BF.t1_Op] with safety margin.
[CBx.50BF.t2_Op]=t0+tB+Δt
Where:
tB is the drop off time of the operation element, generally taken as 0.02~0.04s.
7. CBx.50BF.En
8. CBx.50BF.En_ReTrp
When the setting is set as "Enabled", the instantaneous re-tripping function is in service.
After receiving tripping signal from the device and the corresponding current criterion or CB
position criterion is met, then the re-trip command will be issued to trip local circuit breaker.
9. CBx.50BF.En_t1
10. CBx.50BF.En_t2
11. CBx.50BF.En_3I0_1P
12. CBx.50BF.En_Ip
It is used to enable/disable phase overcurrent criterion of breaker failure protection via external
three-phases initiating signal "CBx.50BF.ExTrp3P".
When the seting is set as "Enabled", the phase current criterion via external three-phases
initiating signal "CBx.50BF.ExTrp3P" is valid.
13. CBx.50BF.En_3I0_3P
14. CBx.50BF.En_I2_3P
15. CBx.50BF.En_CB_Ctrl
It is used to enable/disable breaker failure protection be initiated by CB open position via external
three-phases initiating signal "CBx.50BF.ExTrp3P".
For some special protection (for example, mechanical protection or voltage protection), the fault
current maybe is too small to meet the current criterion when they operate. In order to make
breaker failure protection can also operate under the above situation, CB open position is used
instead of the current criterion. The precondition is that binary input signal [CBx.50BF.ExTrp_WOI]
should be assigned by external trip signal.
3
16. CBx.50BF.En_Alm_Init
It is used to enable/disable the supervision of binary input initiating signal of breaker failure
protection. If the setting is set as "Enabled", and the initiating status of the binary input signal
maintains more than 10s, then the binary input initiating signal will be considered as invalid and an
alarm "CBx.50BF.Alm_Int" will be issued. If it is set as "Disabled", then the binary input signal will
not be supervised.
⚫ LCD
⚫ PCS-Studio
Disabled
87STB.En
Enabled
Disabled
87STB.En_Diff_Alm
Enabled
Disabled
87STB.En_CTS_Blk
Enabled
3
3.26.3 Calculation Principle
1. 87STB.I_Pkp
It shall be greater than the maximal unbalance current under normal rated load, i.e.,
[87STB.I_Pkp]=KRel×(Ker+Δm)×In
Where:
Ker is the ratio errors of CT (k=0.03X2 for class 10P, k=0.01X2 for clase 5P and TP).
Δm is the error caused by the difference between CT ratios at two sides, and 0.05 is
recommended.
This setting should ensure sensitive enough for internal fault with the minimum operation mode
and the sensitivity coefficient is not smaller than 1.5.
Generally, the fault current for stub zone fault is high, the recommended setting value is not less
than 0.5In.
2. 87STB.I_Alm
The setting is used to detect the abnormal current condition, such as CT circuit fail, it should be
greater than the maximal unbalance current under normal load operation condition.
3. 87STB.Slope
The setting is the slope of current differential protection operate-restrain characteristic. This setting
should be given according to the system condition and its application.
4. 87STB.t_Op
Generally, this setting is set as zero. In special cases, it can be set with additional time delay, for
example for reverse interlocking.
5. 87STB.En
6. 87STB.En_Alm
If the alarm signal of differential current abnormality [87STB.Alm_Diff] is issued, stub differential
protection will be blocked if [87STB.En_CTS_Blk] is set as "Enabled"
⚫ LCD
⚫ PCS-Studio
Disabled
CBx.50DZ.En
Enabled
Disabled
CBx.50DZ.En_Alm_Init
Enabled
2. CBx.50DZ.t_Op
4. CBx.50DZ.En_Alm_Init
It is used to enable/disable abnormality check of initiating signal for dead zone protection.
⚫ PCS-Studio
Disabled
46BC.En
Enabled
Trp
46BC.Opt_Trp/Alm
Alm
2. 46BC.I2/I1_Set
The network of single-phase broken condition is similar to that of two-phases earthing fault, 3
positive-sequence, negative-sequence and zero-sequence network is connected in parallel,
I2/I1=Z0/(Z0+Z2), generally, zero-sequence impedance is larger than positive-sequence
impedance, i.e., I2/I1>0.5. The network of two-phases broken condition is similar to that of
single-phase earthing fault, positive-sequence, negative-sequence and zero-sequence network is
connected in series, so I2/I1=1. Hence, broken conductor protection based on the ratio of
negative-sequence current to positive-sequence current can detect the broken-conductor fault.
3. 46BC.t_Op
4. 46BC.En
5. 46BC.Opt_Trp/Alm
⚫ PCS-Studio
Disabled
3 CBx.62PD.En
Enabled
Disabled
CBx.62PD.En_3I0/I2_Ctrl
Enabled
Disabled
CBx.62PD.En_Init_Alm
Enabled
1. CBx.62PD.3I0_Set
In order to improve the reliability of pole discrepancy protection, zero-sequence current element
can be selected as auxiliary criterion.
2. CBx.62PD.I2_Set
3. CBx.62PD.t_Op
4. CBx.62PD.En
5. CBx.62PD.En_3I0/I2_Ctrl
It is used to enable/disable residual current criterion and negative-sequence current criterion for
If the setting is set as "Enabled" pole discrepancy protection can operate only when the
zero-sequence current element or negative-sequence current element meet the criterion.
6. CBx.62PD.En_Alm_Init
It is used to enable/disable abnormality check of initiating signal for pole discrepancy protection.
⚫ PCS-Studio
Disabled
TT.En
Enabled
Disabled
TT.En_FD_Ctrl
Enabled
Disabled
TT.En_BlkAR
Enabled
Disabled
TT.En_CB_Ctrl
Enabled
1. TT.t_Op
2. TT.En
3. TT.En_FD_Ctrl
If the setting is set as "Enabled", transfer trip can operate only when the device picks up.
4. TT.En_BlkAR
3 5. TT.En_CB_Ctrl
If the setting is set as "Enabled", transfer trip can operate only when the circuit breaker of any
phase is in closed position.
⚫ LCD
⚫ PCS-Studio
Disabled
En_MPF_Blk_AR
Enabled
Disabled
En_3PF_Blk_AR
Enabled
Disabled
Line.En_PhSFail
Enabled
Line.En_PhSF_Blk_AR Disabled
Enabled
Disabled
CBx.En_Trp3P
Enabled
1. En_MPF_Blk_AR
3
It is used to enable/disable auto-reclosing blocked when multi-phase fault happens.
2. En_3PF_Blk_AR
3. Line.t_PhSFail
It is used to set the time delay of confirming faulty phase selection failure.
4. Line.En_PhSFail
5. Line.En_PhSF_Blk_AR
6. t_Dwell_Trp
The tripping contact shall drop off when the faulty current disappears or the protection element
drops off. It ensures that the tripping pulse will be kept as same as the setting [t_Dwell_Trp] at
least after the tripping signal is issued.
7. CBx.En_Trp3P
It is used to enable/disable three-phase tripping mode of circuit breaker No.x for any fault
conditions.
⚫ LCD
⚫ PCS-Studio
CBx.79.Num 1~4 1
Disabled
CBx.79.En_AddDly
Enabled
1. CBx.79.Opt_RSYN_ValidMode
It is used to select the control source of synchronism check mode for AR.
Synchronism check mode can be selected by external signal via binary inputs or internal logic
settings. If the setting [CBx.79.Opt_RSYN_ValidMode] set as "Setting", synchronism check mode
is determined by the internal logic settings. If the settings [CBx.79.Opt_RSYN_ValidMode] set as
"Config", AR mode is determined by the input signals
CBx.79.Sel_SynChk
CBx.79.Sel_SynDd_RefDd
CBx.79.Sel_SynLv_RefDd
CBx.79.Sel_SynDd_RefLv
CBx.79.Sel_NoChk
If the settings [CBx.79.Opt_RSYN_ValidMode] set as "Config", and there is on binary input was
energized, then the synchronism check mode for AR is abnormal and the alarm signal will be
issued.
CBx.79.En_SynChk
CBx.79.En_SynDd_RefDd
CBx.79.En_SynLv_RefDd
CBx.79.En_SynDd_RefLv
3 CBx.79.En_NoChk
If the settings [CBx.79.Opt_RSYN_ValidMode] set as "Setting", and all corresponding settings are
set as "Disabled", then the synchronism check mode for AR is abnormal and the alarm signal will
be issued.
2. CBx.79.En_SynChk
3. CBx.79.En_SynDd_RefDd
It is used to enable/disable dead synchronization voltage and dead reference voltage check for
AR.
4. CBx.79.En_SynLv_RefDd.
It is used to enable/disable live synchronization voltage and dead reference voltage check for AR.
5. CBx.79.En_SynDd_RefLv
It is used to enable/disable dead synchronization voltage and live reference voltage check for AR.
6. CBx.79.En_NoChk
7. CBx.79.Num
The AR function could be set as one-shot or multi-shot. Through the setting [CBx.79.N_Rcls], the
maximum number of reclosing attempts can be set up to 4 times. Generally, only one-shot AR is
selected.
The table below shows the number of reclose attempts with respect to the settings and AR modes.
The setting should be set according to system stability requirement, meanwhile, arc-extinguishing
of instantaneous fault and insulation recovery ability should also be considered. Generally, this
setting is greater than 0.5s, 1.0s is recommended.
9. CBx.79.t_Dd_3PS1
10. CBx.79.t_Dd_3PS2
11. CBx.79.t_Dd_3PS3
12. CBx.79.t_Dd_3PS4
13. CBx.79.t_CBClsd
It is used to set the waiting time needed by the circuit-breaker to obtain the AR ready state after
the circuit breaker is closed.
It is the minimum time delay for circuit breaker in closed position before AR gets ready. The
duration of the circuit breaker in closed position before fault occurrence is not less than the setting
[CBx.79.t_CBClsd] for a successful reclosing.
14. CBx.79.t_CBReady
3 It is used to set time delay to wait for CB healthy, and begin to timing when the input signal
[CBx.79.CB_Healthy] is de-energized and if it is not energized within this time delay, AR will be
blocked.
The input signal [CBx.79.CB_Healthy] must be energized before auto-reclosure gets ready.
Because most circuit breakers can finish one complete process: open-closed-open, it is necessary
that circuit breaker has enough energy before reclosing. When the dead time delay of AR is
exhausted, if the input signal [CBx.79.CB_Healthy] is still not energized within time delay
[CBx.79.t_CBReady], AR will be blocked. If this function is not required, the input signal
[CBx.79.CB_Healthy] can be not to configure, and its logical state will be thought as "1" by default.
15. CBx.79.t_Wait_Chk
The setting is the maximum allowable time used for synchronism check. It is valid only if the
synchronism check mode is selected. If the synchronism check condition is not met after the delay
time elapsed, the synchronism check failed and the auto-reclosing will be blocked.
16. CBx.79.t_Reclaim
The reset time of circuit breaker after auto-reclosing operation. With the assignment of the close
command, the automatic reclosing function goes into the reclaim time state. During this time, it is
decided if the current reclosing cycle was successful or not.
⚫ If during the reclaim time no further tripping occurs, the currently running automatic reclosing
cycle was successful.
⚫ If during the reclaim time another tripping occurred, the currently running automatic reclosing
cycle was not successful. If other automatic reclosing cycles are permitted, one of these
cycles will be used to continue the process. In contrast, if the currently executed cycle was the
last permissible cycle, the automatic reclosing process will end and be reported as
unsuccessful.
17. CBx.79.t_DDO_Blk
It is used to set dropout time delay of blocking AR, when blocking signal for AR disappears, AR
blocking condition drops out after this time delay.
AR will be blocked immediately once the blocking condition of AR appears, and the blocking
condition of AR will drop off with a time delay [CBx.79.t_DDO_BlkAR] after blocking signal
disappears.
18. CBx.79.t_AddDly
19. CBx.79.t_WaitMaster
It is used to set maximum wait time for reclosing permissive signal from master AR.
The setting defines the maximum wait time for reclosing permissive signal from master AR. To
prevent further impacts by slave AR reclosing, the output signal "CBx.79.WaitToSlave" of master
AR is usually configured to the signal "CBx.79.WaitMaster" of slave AR. Slave AR is permissible to
reclosing only if master AR is reclosed successfully.
This setting should cooperate with the setting [CBx.79.Opt_Priority]. It is invalid if the setting
[CBx.79.Opt_Priority] is set as "None".
20. CBx.79.t_SecFault
It is used to set the time delay of discriminating another fault in the AR inprogress period. The
timer starts count after 1-pole AR initiated, if another fault happens during this time delay, 3-pole
AR will be initiated. If another fault happens after that time, It will be recognized as the second fault
and AR will be blocked if the setting [CBx.79.En_PDF_Blk] is set as "Enabled".
21. CBx.79.t_PersistTrp
When there is a fault on an overhead line, the concerned circuit breakers will be tripped normally.
After fault is cleared, the tripping command will drop off immediately. In case the circuit breaker is
in failure, etc., and the tripping signal of the circuit breaker maintains and exceeds the time delay
[CBx.79.t_PersistTrp], AR will be blocked. This setting should be longer than the longest tripping
time of circuit breaker plus safety margin.
22. CBx.79.t_Fail
It is used to set the time delay waiting for CB close position to conform reclosing successful.
3 The setting is the time delay from reclosing command sent to unsuccessful reclosing, which shall
be greater than the reclosing operation time of circuit breaker. This time will be valid if the setting
[CBx.79.En_FailCheck] is set as "Enabled".
⚫ If during the time CB is closed, the currently running automatic reclosing cycle was
successful.
⚫ If during the time CB remains open, the currently running automatic reclosing cycle was not
successful, the automatic reclosing process will end and be reported as fail.
If the reclosing is considered as unsuccessful, the device will issue a signal (CBx.79.Fail_Rcls) to
indicate that the reclosing is unsuccessful. AR will not enter into the ready state unless the circuit
breaker position drops off , and can only begin to enter into the ready state again after the circuit
breaker is closed.
23. CBx.79.t_PW
The setting shall be set according to actual requirements, if no tripping latch circuit, then the value
should be greater than the reclosing time of circuit breaker.
For the circuit breaker without anti-pump interlock, the setting [CBx.79.En_CutPulse] is available
to control the reclosing pulse. When this function is enabled, if the device operates to trip during
reclosing, the reclosing pulse will drop off immediately, so as to prevent multi-shot reclosing onto
fault.
24. CBx.79.En_AddDly
25. CBx.79.En_FailCheck
26. CBx.79.En_PDF_Blk
It is used to enable/disable auto-reclosing blocked when a fault occurs under pole discrepancy
condition.
27. CBx.79.En_CutPulse
For the circuit breaker without anti-pump interlock, a setting [CBx.79.En_CutPulse] is available to
control the reclosing pulse. When this function is enabled, if the device operates to trip during
3
reclosing, the reclosing pulse will drop off immediately, so as to prevent multi-shot reclosing onto
fault.
28. CBx.79.En
29. CBx.79.Opt_Enable
Setting: only the setting, which means AR function is controlled only by setting [CBx.79.En].
Setting&Config: the setting and configuration signal, which means AR function is controlled not
only by setting [CBx.79.En], but also by external binary input which could be configured by
PCS-Studio.
30. CBx.79.En_CBInit
This setting is available for selection if AR is initiated by CB status. Under normal conditions, when
AR is ready to reclosing, AR will be initiated if circuit breaker is open and corresponding phase
current is nil. AR initiated by CB status can be divided into initiating 1-pole AR and 3-pole AR. For
more details, please refer to "PCS-931S Technical Manual".
31. CBx.79.Opt_Priority
The output signal "CBx.79.WaitToSlave" of master AR will be usually configured to the input signal
3 "CBx.79.WaitMaster" of slave AR. Slave AR is permissible to reclosing only if master AR is
reclosed successfully.
32. CBx.79.Opt_ValidMode
AR mode can be selected by external signal via binary input signals or internal logic settings. If the
setting [CBx.79.Opt_ValidMode] set as "Setting", AR mode is determined by the settings. If the
settings [CBx.79.Opt_ValidMode] set as "Config", AR mode is determined by the binary input
signals.
CBx.79.Sel_1PAR
CBx.79.Sel_3PAR
CBx.79.Sel_1P/3PAR
CBx.79.En_1PAR
CBx.79.En_3PAR
CBx.79.En_1P/3PAR
33. CBx.79.En_1P
34. CBx.79.En_3P
35. CBx.79.En_1P/3P
⚫ LCD 3
MainMenuSettingsProtection SettingsLine Settings
⚫ PCS-Studio
1. X1L
It is used for calculation of fault location, and it should be set the same as actual value.
2. R1L
It is used for calculation of fault location, and it should be set the same as actual value.
3. X0L
It is used for calculation of fault location, and it should be set the same as actual value.
4. R0L
It is used for calculation of fault location, and it should be set the same as actual value.
5. X0M
It is used for calculation of fault location, and it should be set the same as actual value.
6. R0M
3 It is used to set zero-sequence mutual resistance of the whole line. (secondary value)
It is used for calculation of fault location, and it should be set the same as actual value.
When an earth fault occurred on a line of parallel lines arrangement, for cases where precise fault
location is required for long lines with high mutual coupling, mutual compensation is then required
to improve the distance measurement. The residual current from the parallel line should be added
to the device, and the settings of mutual zero-sequence reactance, mutual zero-sequence
resistance should be set as the practical value. If the residual current from the parallel line isn’t
injected to the device, then the settings of mutual zero-sequence reactance, mutual
zero-sequence resistance should be set as 0.
7. LineLength
It is used for calculation of fault location, and it should be set the same as actual value.
4 Control Settings
Table of Contents
List of Tables
⚫ PCS-Studio
Setting
CBx.25.Opt_ValidMode
Config
Disabled
CBx.25.En_SynChk
Enabled
Disabled
CBx.25.En_DdChk
Enabled
Ua
Ub
Uc
CBx.25.Opt_U_SynChk
Uab
Ubc
Uca
SynDdRefDd
SynLvRefDd
SynDdRefLv
CBx.25.Opt_Mode_DdChk RefDd
SynDd
4 SynLvRefDd/SynDdRefLv
AnySideDd
CBx.25.t_Reset 0~60 1 s
CBx.25.t_Close_CB 0~2000 1 ms
Disabled
CBx.25.En_f_Diff_Chk
Enabled
Disabled
CBx.25.En_df/dt_Chk
Enabled
1. CBx.25.Opt_ValidMode
Setting: the mode of synchronism check is determined by the settings [CBx.25.En_SynChk] and
[CBx.25.En_DdChk];
Config: the mode of synchronism check is determined by the input signals "in_syn_chk" and
"in_vol_chk" via PCS-Studio configuration tool.
2. CBx.25.En_SynChk
3. CBx.25.En_DdChk
4. CBx.25.U_UV
It should be set according to the pecentage of secondary rated phase voltage (Un) or secondary
rated phase-to-phase votlage (Unn) based on the value of the setting [CBx.25.Opt_U_SynChk].
When the voltage at reference side or synchronous side is less than the setting, the synchro-check
will be blocked. 4
Its recommended value is 80.00%Un.
5. CBx.25.U_OV
It should be set according to the pecentage of secondary rated phase voltage (Un) or secondary
rated phase-to-phase votlage (Unn) based on the value of the setting [CBx.25.Opt_U_SynChk].
When the voltage at reference side or synchronous side is more than the setting, the
synchro-check will be blocked.
6. CBx.25.f_UF
When the system frequency is less than the setting, the synchro-check will be blocked.
7. CBx.25.f_OF
When the system frequency is more than the setting, the synchro-check will be blocked.
8. CBx.25.Opt_U_SynChk
The setting is valid only when the synchronization side or the reference side voltage is
4 three-phase. Please set it according to the actual synchronization voltage.
9. CBx.25.U_Diff_Set
10. CBx.25.f_Diff_Set
11. CBx.25.df/dt_Set
It is used to set the threshold of rate-of-change of frequency difference for synchronism check.
12. CBx.25.phi_Diff_Set
13. CBx.25.phi_Comp
14. CBx.25.Opt_Mode_DdChk
15. CBx.25.U_DdChk
16. CBx.25.U_LvChk
The window starts from the receiving moment of synchronous closing command and ends when
all synchronous closing criteria are met or timeout. The timeout causes the synchronism check
failure.
18. CBx.25.t_Close_CB
It is used to set circuit breaker closing time. It is the time from receiving closing command pulse till
the CB is completely closed. Please set it according to the mechanism operating time of the circuit
breaker.
19. 25.En_f_Diff_Chk
20. 25.En_df/dt_Chk
⚫ PCS-Studio
NoVoltSel
DblBusOneCB
CBx.VoltSel.Opt_CBConfig
3/2BusCB
3/2TieCB
It is used to select the circuit breaker No.x arrangement for voltage selection.
3/2BusCB: bus side circuit breaker for one and a half breakers
3/2TieCB: line side circuit breaker for one and a half breakers
Please set it according to the actual the circuit breaker arrangement, and it should be set as
"NoVoltSel" if no voltage selection is adopted and the voltage selection logic is disabled.
⚫ LCD
⚫ PCS-Studio
CB**.DPS.t_DPU 0~60000 1 ms
Disabled
CB**.DPS.En_Alm
Enabled
CB**.DPS.t_Alm 0~60000 1 ms
DS**.DPS.t_DPU 0~60000 1 ms
Disabled
DS**.DPS.En_Alm
Enabled
4
DS**.DPS.t_Alm 0~60000 1 ms
2. CB**.DPS.t_DPU
It is used to set the DPU (delay pick up) time of DPS (double point status), i.e. debounce time. (for
circuit breaker No.**)
The setting value should be greater than the CB operating time to avoid the intermediate state in
the process of CB opening or closing.
3. CB**.DPS.En_Alm
4. CB**.DPS.t_Alm
It is used to set time delay of DPS alarm. (for circuit breaker No.**)
5. DS**.DPS.t_DPU
It is used to set the DPU (delay pick up) time of DPS, i.e. debounce time. (for circuit breaker No.**)
The setting value should be greater than the DS operating time to avoid the intermediate state in
the process of DS opening or closing.
6. DS**.DPS.En_Alm
7. DS**.DPS.t_Alm
It is used to set time delay of DPS alarm. (for circuit breaker No.**)
⚫ LCD
⚫ PCS-Studio
CB**.t_PW_Opn 0~60000 1 ms
CB**.t_PW_Cls 0~60000 1 ms
DS**.t_PW_Opn 0~60000 1 ms
DS**.t_PW_Cls 0~60000 1 ms
DirCtrl**.t_PW_Opn 0~60000 1 ms
DirCtrl**.t_PW_Cls 0~60000 1 ms
1. CB**.t_PW_Opn
It is used to set pulse width (PW), i.e. holding time, for opening output of circuit breaker No.**.
The setting value should be long enough to start the relay in the CB opening circuit.
2. CB**.t_PW_Cls
It is used to set pulse width (PW), i.e. holding time, for closing output of circuit breaker No.**.
The setting value should be long enough to start the relay in the CB closing circuit.
3. DS**.t_PW_Opn
It is used to set pulse width (PW), i.e. holding time, for opening output of disconnector switch
No.**.
The setting value should be long enough to start the relay in the DS opening circuit.
4. DS**.t_PW_Cls
It is used to set pulse width (PW), i.e. holding time, for closing output of disconnector switch No.**.
The setting value should be long enough to start the relay in the DS closing circuit.
5. DirCtrl**.t_PW_Opn
It is used to set pulse width (PW), i.e. holding time, for opening output of direct control object No.**.
The setting value should be long enough to start the relay in the direct control opening circuit.
4
Its recommended value is 500ms.
6. DirCtrl**.t_PW_Cls
It is used to set pulse width (PW), i.e. holding time, for closing output of direct control object No.**.
The setting value should be long enough to start the relay in the direct control closing circuit.
⚫ LCD
⚫ PCS-Studio
Disabled
CB**.En_CILO_Opn
Enabled
Disabled
CB**.En_CILO_Cls
Enabled
Disabled
DS**.En_CILO_Opn
Enabled
Disabled
DS**.En_CILO_Cls
Enabled
Disabled
DirCtrl**.En_CILO_Opn
Enabled
Disabled
DirCtrl**.En_CILO_Cls
Enabled
1. CB**.En_CILO_Opn
It is used to enable/disable open output of circuit breaker No.** controlled by the interlocking logic.
2. CB**.En_CILO_Cls
4 It is used to enable/disable closing output of circuit breaker No.** controlled by the interlocking
logic.
3. DS**.En_CILO_Opn
It is used to enable/disable open output of disconnector switch No.** controlled by the interlocking
logic.
4. DS**.En_CILO_Cls
5. DirCtrl**.En_CILO_Opn
It is used to enable/disable open output of direct control object No.** controlled by the interlocking
logic.
6. DirCtrl**.En_CILO_Cls
It is used to enable/disable closing output of direct control object No.** controlled by the
interlocking logic.
5 Measurement Settings
Table of Contents
List of Tables
5
Table 5.1-1 Function settings (single circuit breaker) ............................................................. 5-1
5.1 Function
⚫ LCD
⚫ PCS-Studio
Disabled
Prot.En_Alm_ROV
Enabled
Disabled
Prot.En_Alm_ROC
Enabled
Disabled
Prot.En_Alm_ROV
Enabled
Disabled
Prot.En_Alm_UV
Enabled
Disabled
Prot.En_Alm_ROC
Enabled
Disabled
5 Prot.CB1.En_Alm_ROC
Enabled
Disabled
Prot.CB2.En_Alm_ROC
Enabled
Ia-Ib-Ic
Prot.Opt_CT_Measmt
Ia-Ic
Ia-Ib-Ic
Prot.CB1.Opt_CT_Measmt
Ia-Ic
Ia-Ib-Ic
Prot.CB2.Opt_CT_Measmt
Ia-Ic
1. Prot.En_Alm_ROV
2. Prot.3U0_Alm_ROV
It is used to set the threshold of residual overvoltage supervision, which is indicated by the
percentage of the rated value.
4. Prot.U_Alm_UV
It is used to set the threshold of phase undervoltage supervision, which is indicated by the
percentage of the rated value.
5. Prot.ZeroDrift_U
It is used to set the threshold to limit the zero-drift influence of the protection voltage due to the
temperature or other environmental factors. The measured value less than this setting will be
regarded as a zero drift and ignored.
6. Prot.En_Alm_ROC
7. Prot.CB1.En_Alm_ROC
It is used to enable/disable residual overcurrent supervision of circuit breaker No.1. (double CBs
application)
8. Prot.CB2.En_Alm_ROC
It is used to enable/disable residual overcurrent supervision of circuit breaker No.2. (double CBs
application)
9. Prot.3I0_Alm_ROC
It is used to set the threshold of residual overcurrent supervision, which is indicated by the
percentage of the rated value. (single CB application)
10. Prot.CB1.3I0_Alm_ROC
It is used to set the threshold of residual overcurrent supervision for circuit breaker No.1, which is
indicated by the percentage of the rated value. (double CBs application)
11. Prot.CB2.3I0_Alm_ROC
It is used to set the threshold of residual overcurrent supervision for circuit breaker No.2, which is
indicated by the percentage of the rated value. (double CBs application)
12. Prot.Opt_CT_Measmt
5 It is used to select CT wiring mode which used by current measurement. (single CB application)
13. Prot.CB1.Opt_CT_Measmt
It is used to select CT wiring mode for circuit breaker No.1 which used by current measurement.
(double CBs application)
14. Prot.CB2.Opt_CT_Measmt
It is used to select CT wiring mode for circuit breaker No.2 which used by current measurement.
(double CBs application)
15. Prot.ZeroDrift_I
It is used to set the threshold to limit the zero-drift influence of the current due to the temperature
or other environmental factors. A measured value less than this setting will be regarded as a zero
16. Prot.CB1.ZeroDrift_I
It is used to set the threshold to limit the zero-drift influence of the current due to the temperature
or other environmental factors. A measured value less than this setting will be regarded as a zero
drift and ignored. (double CBs application)
17. Prot.CB2.ZeroDrift_I
It is used to set the threshold to limit the zero-drift influence of the current due to the temperature
or other environmental factors. A measured value less than this setting will be regarded as a zero
drift and ignored. (double CBs application)
18. Prot.ZeroDrift_PQ
It is used to set the threshold to limit the zero-drift influence of the power due to the temperature or
other environmental factors. A measured value less than this setting will be regarded as a zero
5
drift and ignored. (single CB application)
19. Prot.CB1.ZeroDrift_PQ
It is used to set the threshold to limit the zero-drift influence of the power due to the temperature or
other environmental factors. A measured value less than this setting will be regarded as a zero
drift and ignored. (double CBs application)
20. Prot.CB2.ZeroDrift_PQ
It is used to set the threshold to limit the zero-drift influence of the power due to the temperature or
other environmental factors. A measured value less than this setting will be regarded as a zero
drift and ignored. (double CBs application)
21. 3I0Adj.ZeroDrift_I
It is used to set the threshold to limit the zero-drift influence of the residual current from parallel line
due to the temperature or other environmental factors. A measured value less than this setting will
be regarded as a zero drift and ignored.
22. UB1.USyn.ZeroDrift_U
It is used to set the threshold to limit the zero-drift influence of the synchronism voltage (UB1) due
to the temperature or other environmental factors. A measured value less than this setting will be
regarded as a zero drift and ignored.
23. UL2.USyn.ZeroDrift_U
It is used to set the threshold to limit the zero-drift influence of the synchronism voltage (UL2) due
to the temperature or other environmental factors. A measured value less than this setting will be
regarded as a zero drift and ignored.
24. UB2.USyn.ZeroDrift_U
It is used to set the threshold to limit the zero-drift influence of the synchronism voltage (UB2) due
to the temperature or other environmental factors. A measured value less than this setting will be
regarded as a zero drift and ignored.
⚫ LCD
⚫ PCS-Studio
MMTR.I2n 1~5 1 A
1. MMTR.U2n
2. MMTR.I2n
Table of Contents
List of Tables
⚫ LCD
⚫ PCS-Studio
Disabled
En_PMU
Enabled
P_Class
Opt_Class_PMU
M_Class
N_Chgd_CFG 0~65535 1
Port_TCP 0~65535 1
Port_UDP 1024~65535 1
1. En_PMU
2. Opt_Class_PMU
This algorithm adopts a short time window, so its response speed is fast. It is suitable for fast
protection and control applications, but the ability of suppressing the out-of-band signals is poor.
This algorithm adopts a long time window, so its accuracy is high for measuring steady and
dynamic signal, and can suppress the out-of-brand signals. However, its response speed is slower
than that when adopting P_Class.
3. DataRate
It is used to set data transmission rate of PMU reporting synchrophasor data to the parent IEDs
(such as, PDC or PMU master station).
The rate is generally equal to or less than the rated frequency of power system.
For the 50Hz system, the selectable rates are 100, 50, 25, 10 frames per second.
For the 60Hz system, the selectable rates are 120, 60, 30, 20, 15, 12, 10 frames per second.
4. Substation_PMU
5. N_Chgd_CFG
It is used to indicate the version of CFG of PMU, and inform the client when the CFG-1 has
6 changed.
The starting value of the setting is 0, and it should increase by 1 every time CFG-1 is adjusted. For
example, changing the branch name or rating will cause the change of CFG-1, so the setting
should be modified.
6. Port_TCP
It is used to set TCP port for PMU based on IEEE C37.118 standard.
There are three kinds of communication modes available for PMU, TCP, UDP and TCP-UDP mode.
When adopting the TCP or TCP-UDP mode, the TCP port will be used. The port values of all TCP
clients should be consistent with the setting value.
The default port of TCP is 4712, and it is invalid when the setting [PDC**.Opt_Protocol] is set as
"UDP")
7. Port_UDP
It is used to set UDP port for PMU based on IEEE C37.118 standard.
There are three kinds of communication modes available for PMU, TCP, UDP and TCP-UDP mode.
When adopting the UDP or TCP-UDP mode, the UDP port will be used. The port values of all UDP
receivers should be consistent with the setting value.
The default port of TCP is 4713, and it is invalid when the setting [PDC**.Opt_Protocol] is set as
"TCP")
⚫ LCD
⚫ PCS-Studio
PDC**.IP_TCP 0.0.0.0~255.255.255.255
PDC**.IP_UDP_Dest 0.0.0.0~255.255.255.255 6
PDC**.IP_MulticastSrc 0.0.0.0~255.255.255.255
None
TCP
PDC**.Opt_Protocol
UDP
TCP-UDP
Unicast
PDC**.Opt_UDP Broadcast
Multicast
PDC**.IDCODE 1~65534
PDC**.IDCODE 1~65534
It is used to set the name of PDC (Phasor Data Concentrators) connecting with PMU.
2. PDC**.IP_TCP
It is used to set destination IP address of connected PDC** using TCP communication protocol.
This setting is valid when the setting [PDC**.Opt_Protocol] is set as "TCP" or "TCP-UDP". The
communication of PMU is based on whitelisting, only when the IP address of the TCP client has
been set in the PMU, the client has the right to communicate with PMU using TCP communication
protocol.
If the PDC does not exist or the TCP or TCP-UDP mode is not adopted, the IP address can be set
as "0.0.0.0".
3. PDC**.IP_UDP_Dest
It is used to set destination IP address of connected PDC** using UDP communication protocol.
This setting is valid when the setting [PDC**.Opt_Protocol] is set as "UDP" or "TCP-UDP". The
6 PMU transmits the UDP message to this address. It may be unicast address, broadcast address
or multicast address. It is noted that the IP address should match with the setting
[PDC**.Opt_UDP].
4. PDC**.IP_MulticastSrc
It is used to set the multicast source IP address of PDC** using UDP communication protocol, it is
consistent with some network interface IP address of the device. This network interface uses this
IP address to transmit UDP message to multicast group. Since the IP addresss of the muticast
group and any network interface of the device have the different network segments, this setting
essentially informs the PMU which network interface to send UDP multicast message.
The setting is valid when the setting [PDC**.Opt_Protocol] is set as "UDP" or "TCP-UDP", and the
setting [PDC**.Opt_UDP] is set as "Multicast".
It should be set as IP address of the Ethernet port which is chosen to tranmitting UDP multicast
message.
5. PDC**.Opt_Protocol
TCP: in TCP communication mode, configuration frames (CFG-1/2), command frames (CMD), and
DATA frames (DATA) defined in the IEEE C37.118 standard are transmitted via TCP connections.
When using TCP mode, the settings [Port_TCP] and [PDC**.IP_TCP] need to be set.
UDP: in UDP communication mode, configuration frames (CFG-1/2), command frames (CMD),
and DATA frames (DATA) defined in the IEEE C37.118 standard are transmitted via UDP
messages.
It shall be consistent with the communication protocol of the PDC at the opposite end. Its
recommended value is "TCP".
6. PDC**.Opt_UDP
The setting is valid when the setting [PDC**.Opt_Protocol] is set as "UDP" or "TCP-UDP". For the
communication between the PMU and the third-party PDCs, the setting is recommended to be set
as "Multicast".
7. PDC**.IDCODE
6
It is used to set ID code of the PDC**.
The setting can identify each PDC for the protocol. Please set the setting according to the site
IDCODE planning, and it should be consistent with the IDCODE of the PDC at the opposite end.
⚫ LCD
⚫ PCS-Studio
None
Bay
xx.Opt_UnitType 1
Bus(U_3P)
Bus(U_1P)
U1
Ua
xx.Opt_U_MeasFreq 1
Ub
Uc
Disabled
xx.En_TrigDFR
Enabled
This setting together with the [Name_**] (in submenu "PMU Label Settings") form a complete
measurement name, and the total length is no more than 16 characters.
The name of PMU bay is generally composed of station code and bay name, with a total length of
no more than 12 characters, and it is recommended to set the name according to 12 characters.
2. xx.U1n
3. xx.I1n
4. xx.Opt_UnitType
Bus(U_1P): measuring single-phase voltage, the current and power quantities are not measured
and displayed. Besides, zero-sequence and negative-sequence voltage are not calculated, their
values are fixed as "0".
When the setting is set as "Bus(U_1P)", it is recommended to use the phase-A voltage.
5. xx.Opt_U_MeasFreq
Its recommended value is "U1", because the frequency measurement function will not be affected
in case of single-phase or two-phase VT failure.
6. xx.En_TrigDFR
It is used to enable/disable trigger disturbance fault recording function in case any following over
limit situation
If the setting is set as "Enabled", the triggering flag will be mapped in "STAT" field of PMU data
frame with a time delay of four power-frequency cycles when the triggering condition is satisfied.
For an independent PMU device, the recording will be performed in the above-mentioned case,
but for the device integrating with the PMU function, the above-mentioned case will not affect the
recording function, the device starts the recording function according to its own criterion.
7. xx.Up_UpLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
8. xx.U1_UpLmt
9. xx.U2_UpLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
10. xx.U0_UpLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
11. xx.Up_LowLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
12. xx.U1_LowLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
13. xx.Ip_UpLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
14. xx.I1_UpLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
16. xx.I0_UpLmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
17. xx.f_Diff_Lmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
18. xx.df/dt_Lmt
For some special AC bay, such as the load with frequent fluctuation, the threshold value can be
increased appropriately.
⚫ LCD
⚫ PCS-Studio
Disabled
Link_BI_TrigDFR
Enabled
Disabled
BI_**.En_TrigDFR
Enabled
1. Name_BI_**
The setting generally composed of station name and binary input name. Its total length should not
exceed 16 characters.
2. Link_BI_TrigDFR
It is used to enable/disable disturbance fault recording function in case status changing of any
binary signal for PMU.
If the setting is set as "Enabled", the status of the binary input is changed and its corresponding
setting [BI_**.En_TrigDFR] is set as "Enabled", the triggering flag will be mapped in "STAT" field of
PMU data frame. For an independent PMU device, the recording will be performed in the
above-mentioned case, but for the device integrating with the PMU function, the above-mentioned
case will not affect the recording function, the device starts the recording function according to its
own criterion.
3. BI_**.En_TrigDFR
It is used to enable/disable disturbance fault recording function in case status changing of the
binary signal BI_** for PMU.
If the setting is set as "Enabled", the status of the binary input is changed and its corresponding
setting [BI_**.En_TrigDFR] is set as "Enabled", the triggering flag will be mapped in "STAT" field of
PMU data frame. For an independent PMU device, the recording will be performed in the
above-mentioned case, but for the device integrating with the PMU function, the above-mentioned
case will not affect the recording function, the device starts the recording function according to its
own criterion.
⚫ PCS-Studio
1. Name_Amp_Ua
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
2. Name_Amp_Ub
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
3. Name_Amp_Uc
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
4. Name_Amp_U0
It is recommended to adopt the form "-" + "the type of the measurement quantity".
5. Name_Amp_U1
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
6. Name_Amp_U2
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
7. Name_Amp_Ia
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
8. Name_Amp_Ib
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
9. Name_Amp_Ic
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
6 Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
10. Name_Amp_I0
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
11. Name_Amp_I1
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
12. Name_Amp_I2
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
13. Name_Ang_Ua
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
14. Name_Ang_Ub
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
6
Please set the setting according to the actual measured quantity.
15. Name_Ang_Uc
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
16. Name_Ang_U0
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
17. Name_Ang_U1
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
18. Name_Ang_U2
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
19. Name_Ang_Ia
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
6 It is recommended to adopt the form "-" + "the type of the measurement quantity".
20. Name_Ang_Ib
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
21. Name_Ang_Ic
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
22. Name_Ang_I0
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
23. Name_Ang_I1
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
24. Name_Ang_I2
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
6
Please set the setting according to the actual measured quantity.
25. Name_f
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
26. Name_df/dt
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
27. Name_P
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
28. Name_Q
The setting will affect the name of the corresponding measurement quantity in the submenu "PMU
Bay Settings".
It is recommended to adopt the form "-" + "the type of the measurement quantity".
Table of Contents
List of Tables
⚫ LCD
MainMenuSettingsTWFL Settings
⚫ PCS-Studio
TWFL.t_Diff_InterSubst_Set 0~20 1 ms
xx.TWFL.Rmt.Substation
1. TWFL.t_Diff_InterSubst_Set
It is used to set the time deviation setting between local substation and remote substation.
It can simply monitor the deviation of clock synchronization between the devices on both sides. 7
When the deviation exceeds the setting, the travelling-wave fault location (TWFL) will be blocked.
When the optical-fiber channel is normal and the IRIG-B signal is connected to the devices on both
sides, the setting should be 2ms larger than the quantity "TWFL.t_Diff_InterSubst" which can be
checked in the path MainMenuStatusTWFL StatusTWFL ClockSyn Status.
2. TWFL.t_Diff_InterSubst_Set
Please set the setting according to the actual substation name in the remote end.
3. xx.TWFL.Velocity_Set
It recommends measuring the actual TW velocity when commissioning the device. With the circuit
breakers open at both sides, close the local circuit breaker to energize the line. Check the local
TW recording, find the first moment (t1) when the current obviously changes, and find the second
L
moment (t2) when the current obviously changes near the time t1 + 2 ×
C
Where:
C is the estimated TW velocity, 294m/us for the overhead line, 150m/us for the cable
𝐿
[𝑥𝑥. 𝑇𝑊𝐹𝐿. 𝑉𝑒𝑙𝑜𝑐𝑖𝑡𝑦_𝑆𝑒𝑡] = 2 ×
𝑡2 − 𝑡1
8 Supervision Settings
Table of Contents
List of Tables
⚫ LCD
⚫ PCS-Studio
1. VTS.En
2. VTS.Opt_VT
It is used to select voltage source for protection calculation, busbar VT or line VT.
Bus: busbar VT 8
Bay: bay VT
3. VTS.t_DPU
4. VTS.t_DDO
5. VTS.U1_Set
6. VTS.3U0_Set
7. VTS.U2_Set
⚫ PCS-Studio
Disabled
CBx.CTS.En
Enabled
1. CBx.CTS.3I0_Set
It should be greater than the maximum unbalanced current and less than load current, at the same
time, it should be sensitive enough.
2. CBx.CTS.3U0_Set
It should be greater than the maximum unbalanced voltage, and it should be sensitive enough.
3. CBx.CTS.t_DPU
4. CBx.CTS.t_DDO
5. CBx.CTS.En
9 Logic Links
Table of Contents
List of Tables
⚫ PCS-Studio
Disabled
Link_01
Enabled
Disabled
Link_02
Enabled
Disabled
Link_03
Enabled
Disabled
Link_04
Enabled
Disabled
Link_05
Enabled
Disabled
Link_06
Enabled
Disabled
Link_07
Enabled
9
Disabled
Link_08
Enabled
1. Link_xx
These function link settings can be used for logic programming via PCS-Studio configuration tool
to convenient to enable or disable the function element, please refer to "Function Link in
Application Manual"
This logic link setting can also be configured by remote control command from local SCADA
system, master station in control center, etc.
⚫ LCD
⚫ PCS-Studio
Disabled
**.GLink_Send
Enabled
1. Bxx.Name_**_GCommLink.GLink_Send
** can be defined by editing the "English Description" in the "Basic Information" page. Now
corresponding ** in the above table will change simultaneously. Please refer to "Logic Symbols in
Application Manual".
This link setting can also be configured by remote control command from local SCADA system,
9 master station in control center, etc.
If this logic link setting is configured as "Disabled", all the sent GOOSE data will be cleared to 0.
⚫ PCS-Studio
Disabled
GLink_RecvSim
Enabled
Disabled
Bxx.Name_**_GCommLink.GLink_Recv
Enabled
1. GLink_RecvSim 9
It is used to enable/disable the allowance to accept simulated GOOSE messages.
This logic link setting can also be configured by remote control command from local SCADA
system, master station in control center, etc.
2. Bxx.Name_**_GCommLink.GLink_Recv
This link setting can also be configured by remote control command from local SCADA system,
master station in control center, etc.
If this logic link setting is configured as "Disabled", the alarm signals "GAlm_ADisc",
"GAlm_BDisc", "GAlm_Maint_Unmatched" of this GOOSE communication link will NOT be
processed and issued.
⚫ LCD
⚫ PCS-Studio
Disabled
SVLink_RecvSim
Enabled
Disabled
Bxx.Name_**_SVCommLink.SVLink_Recv
Enabled
This logic link setting can also be configured by remote control command from local SCADA
system, master station in control center, etc.
2. Bxx.Name_**_SVCommLink.SVLink_Recv
This link setting can also be configured by remote control command from local SCADA system,
master station in control center, etc.
If this logic link setting is configured as "Disabled", the alarm signals "SVAlm_ADisc",
"SVAlm_BDisc", "SVAlm_Maint_Unmatched" of this SV communication link will NOT be
processed and issued.