Produced on 10/12/2020 with Xpress Selection V8.9.1 - database DIL 15.2.

Project name LPMP PROJECT


Project address --
Indonesia
Reference --
Client name --
Client address --
Revision --

Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Qty Description
RXQ34AMY14 1 Cooling only VRV A(18,20HP multi module)ID
RXQ42AMY14 1 Cooling only VRV A(18,20HP multi module)ID
FXAQ63AVM4 2 VRV A(AVM4) - Wall Mounted
FXFQ125AV4 11 VRV F(AV4) - Ceiling Mounted Cassette(Round Flow)
FXFQ140AV4 4 VRV F(AV4) - Ceiling Mounted Cassette(Round Flow)
FXFQ80AV4 1 VRV F(AV4) - Ceiling Mounted Cassette(Round Flow)
KHRP26A22T 2 Refnet branch piping kit
KHRP26A33T 5 Refnet branch piping kit
KHRP26A72T 6 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 3 Refnet branch piping kit
DCM601A51 1 intelligent Touch Manager
BRC1E63 18 Wired Remote Controller (Navigation Remote Controller)
BYCQ125EAF 16 Standard panel(Fresh white)
BHFP22P100 1 Outdoor unit multi connection piping kit
BHFP22P151 1 Outdoor unit multi connection piping kit
R410A 49.9kg Extra refrigerant charge
Piping ⅜" 222.0m
Piping ½" 30.0m
Piping ⅝" 171.0m
Piping ¾" 105.0m
Piping ⅞" 53.0m
Piping 1⅛" 35.0m
Piping 1⅜" 53.0m
Piping 1⅝" 49.0m

2. Outdoor Unit Details


2.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 1
Tmp H Outdoor conditions in heating (dry bulb temp. / wet bulb temp.)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 2
2.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC
% °C BTU/h BTU/h °C BTU/h BTU/h
OU:LT.2 RXQ34AMY14 105 35.0 266932 263350
OU:LT.3 RXQ42AMY14 119 35.0 342539 231557

Name Model Piping Refrigerant


m Type Bse Refr Ex Refr
kg kg
OU:LT.2 RXQ34AMY14 86.5 R410A 16.6 22.0
OU:LT.3 RXQ42AMY14 85.0 R410A 22.0 27.9

Name Model PS MCA WxHxD Wght


A mm kg
OU:LT.2 RXQ34AMY14 400V 3ph
× RXQ18AY14 30.2 1240×1657×765 260
× RXQ16AY14 30.2 1240×1657×765 260
OU:LT.3 RXQ42AMY14 400V 3ph
× RXQ18AY14 30.2 1240×1657×765 260
× RXQ12AY14 22.5 930×1657×765 185
× RXQ12AY14 22.5 930×1657×765 185

Sufficient distance should be respected between the modules according to the service & operation space rules as
mentioned in the databook.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 3
2.2.1. OU:LT.2 - RXQ34AMY14
Model Qty Description
RXQ34AMY14 1 Cooling only VRV A(18,20HP multi module)ID
FXAQ63AVM4 1 VRV A(AVM4) - Wall Mounted
FXFQ125AV4 6 VRV F(AV4) - Ceiling Mounted Cassette(Round Flow)
FXFQ80AV4 1 VRV F(AV4) - Ceiling Mounted Cassette(Round Flow)
KHRP26A22T 1 Refnet branch piping kit
KHRP26A33T 2 Refnet branch piping kit
KHRP26A72T 3 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 1 Refnet branch piping kit
BRC1E63 8 Wired Remote Controller (Navigation Remote Controller)
BYCQ125EAF 7 Standard panel(Fresh white)
BHFP22P100 1 Outdoor unit multi connection piping kit
R410A 22.0kg Extra refrigerant charge
Piping ⅜" 79.0m
Piping ½" 16.0m
Piping ⅝" 53.0m
Piping ¾" 53.0m
Piping ⅞" 26.0m
Piping 1⅛" 17.0m
Piping 1⅜" 52.0m

Standard factory refrigerant charge (5m actual piping length) = 16.6kg


Extra refrigerant charge = 79.0m(ø⅜") × 0.057 + 52.0m(ø¾") × 0.26 + 1.0m(ø⅝") × 0.17 + 16.0m(ø½") × 0.11 + A +
B = 22.0kg
A [ CR 105%, actual length 85.0m ] = 2.0kg
B [ 34HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 4
2.2.2. OU:LT.3 - RXQ42AMY14
Model Qty Description
RXQ42AMY14 1 Cooling only VRV A(18,20HP multi module)ID
FXAQ63AVM4 1 VRV A(AVM4) - Wall Mounted
FXFQ125AV4 5 VRV F(AV4) - Ceiling Mounted Cassette(Round Flow)
FXFQ140AV4 4 VRV F(AV4) - Ceiling Mounted Cassette(Round Flow)
KHRP26A22T 1 Refnet branch piping kit
KHRP26A33T 3 Refnet branch piping kit
KHRP26A72T 3 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 2 Refnet branch piping kit
BRC1E63 10 Wired Remote Controller (Navigation Remote Controller)
BYCQ125EAF 9 Standard panel(Fresh white)
BHFP22P151 1 Outdoor unit multi connection piping kit
R410A 27.9kg Extra refrigerant charge
Piping ⅜" 143.0m
Piping ½" 14.0m
Piping ⅝" 118.0m
Piping ¾" 52.0m
Piping ⅞" 27.0m
Piping 1⅛" 18.0m
Piping 1⅜" 1.0m
Piping 1⅝" 49.0m

Standard factory refrigerant charge (5m actual piping length) = 22.0kg


Extra refrigerant charge = 143.0m(ø⅜") × 0.057 + 50.0m(ø¾") × 0.26 + 4.0m(ø⅝") × 0.17 + 14.0m(ø½") × 0.11 + A
+ B = 27.9kg
A [ CR 119%, actual length 83.0m ] = 4.5kg
B [ 42HP ] = 0.0kg

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 5
3. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

3.1. Piping OU:LT.2


OU:LT.2
RXQ34AMY14
RXQ18AY14 RXQ16AY14

⅝"×1⅛" ½"×1⅛"

BHFP22P100

#1.1 52.0m #1.7 1.0m #1.11 15.0m #1.13 1.0m


¾"×1⅜" ⅝"×1⅛" ½"×1⅛" ⅜"×¾"
KHRP26A73T + KHRP26A72T KHRP26A72T KHRP26A22T
KHRP26M73TP

#1.12 3.0m #1.14 2.0m #1.15 2.0m


⅜"×⅝" ⅜"×⅝" ⅜"×⅝"
RUANG LT2.8 RUANG LT2.8 RUANG LT2.7
#1.8 18.0m FXFQ125AV4 FXFQ125AV4 FXAQ63AVM4
⅜"×⅞"
KHRP26A33T

#1.9 7.0m #1.10 14.0m


⅜"×⅝" ⅜"×⅝"
RUANG LT2.6 RUANG LT2.6
#1.2 1.0m #1.4 8.0m FXFQ125AV4 FXFQ125AV4
½"×1⅛" ⅜"×⅞"
KHRP26A72T KHRP26A33T

#1.3 12.0m #1.5 5.0m #1.6 7.0m


⅜"×⅝" ⅜"×⅝" ⅜"×⅝"
RUANG LT2.5 RUANG LT2.4 RUANG LT2.3
FXFQ125AV4 FXFQ125AV4 FXFQ80AV4

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 6
3.2. Piping OU:LT.3
OU:LT.3
RXQ42AMY14
RXQ18AY14 RXQ12AY14 RXQ12AY14

⅝"×1⅛" ½"×1⅛" ½"×1⅛"


⅝"×1⅜"
BHFP22P151

#2.1 49.0m #2.11 1.0m #2.17 18.0m


¾"×1⅝" ⅝"×1⅛" ⅜"×⅞"
KHRP26A73T + KHRP26A72T KHRP26A33T
KHRP26M73TP

#2.18 6.0m #2.19 14.0m


⅜"×⅝" ⅜"×⅝"
RUANG LT3.6 RUANG LT3.6
#2.12 14.0m #2.14 2.0m FXFQ125AV4 FXFQ125AV4
½"×1⅛" ⅜"×¾"
KHRP26A72T KHRP26A22T

#2.13 4.0m #2.15 10.0m #2.16 17.0m


⅜"×⅝" ⅜"×⅝" ⅜"×⅝"
RUANG LT3.8 RUANG LT3.8 RUANG LT3.7
#2.2 1.0m #2.6 3.0m FXFQ125AV4#2.8 5.0m FXFQ125AV4 FXAQ63AVM4
¾"×1⅜" ⅝"×1⅛" ⅜"×⅞"
KHRP26A73T + KHRP26A72T KHRP26A33T
KHRP26M73TP

#2.7 9.0m #2.9 7.0m #2.10 14.0m


⅜"×⅝" ⅜"×⅝" ⅜"×⅝"
RUANG LT3.4 RUANG LT3.4 RUANG LT3.4
#2.3 4.0m FXFQ140AV4 FXFQ140AV4 FXFQ140AV4
⅜"×⅞"
KHRP26A33T

#2.4 13.0m #2.5 20.0m


⅜"×⅝" ⅜"×⅝"
RUANG LT3.5 RUANG LT3.10
FXFQ125AV4 FXFQ140AV4

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 7
4. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

4.1. Wiring OU:LT.2


to centralized controller
P1,P2
OU:LT.2 BRC1E63
RUANG LT2.5
RXQ34AMY14
FXFQ125AV4
OUT F1,F2 IN F1,F2 F1,F2
RXQ18AY14 L,N 1.6A 1ph
Q1,Q2 L1,L2,L3,N P1,P2
30.2A 3ph RUANG LT2.4 BRC1E63
FXFQ125AV4
RXQ16AY14 F1,F2
Q1,Q2 L1,L2,L3,N L,N 1.6A 1ph
30.2A 3ph P1,P2
RUANG LT2.3 BRC1E63
FXFQ80AV4
F1,F2
L,N 1A 1ph
P1,P2
RUANG LT2.6 BRC1E63
FXFQ125AV4
F1,F2
L,N 1.6A 1ph
P1,P2
RUANG LT2.6 BRC1E63
FXFQ125AV4
F1,F2
L,N 1.6A 1ph
P1,P2
RUANG LT2.8 BRC1E63
FXFQ125AV4
F1,F2
L,N 1.6A 1ph
P1,P2
RUANG LT2.8 BRC1E63
FXFQ125AV4
F1,F2
L,N 1.6A 1ph
P1,P2
RUANG LT2.7 BRC1E63
FXAQ63AVM4
F1,F2
L,N 0.7A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 8
4.2. Wiring OU:LT.3
to centralized controller
P1,P2
OU:LT.3 BRC1E63
RUANG LT3.5
RXQ42AMY14
FXFQ125AV4
OUT F1,F2 IN F1,F2 F1,F2
RXQ18AY14 L,N 1.6A 1ph
Q1,Q2 L1,L2,L3,N P1,P2
30.2A 3ph RUANG LT3.10 BRC1E63
FXFQ140AV4
RXQ12AY14 F1,F2
Q1,Q2 L1,L2,L3,N L,N 1.8A 1ph
22.5A 3ph P1,P2
RUANG LT3.4 BRC1E63
RXQ12AY14 FXFQ140AV4
Q1,Q2 L1,L2,L3,N F1,F2
22.5A 3ph L,N 1.8A 1ph
P1,P2
RUANG LT3.4 BRC1E63
FXFQ140AV4
F1,F2
L,N 1.8A 1ph
P1,P2
RUANG LT3.4 BRC1E63
FXFQ140AV4
F1,F2
L,N 1.8A 1ph
P1,P2
RUANG LT3.8 BRC1E63
FXFQ125AV4
F1,F2
L,N 1.6A 1ph
P1,P2
RUANG LT3.8 BRC1E63
FXFQ125AV4
F1,F2
L,N 1.6A 1ph
P1,P2
RUANG LT3.7 BRC1E63
FXAQ63AVM4
F1,F2
L,N 0.7A 1ph
P1,P2
RUANG LT3.6 BRC1E63
FXFQ125AV4
F1,F2
L,N 1.6A 1ph
P1,P2
RUANG LT3.6 BRC1E63
FXFQ125AV4
F1,F2
L,N 1.6A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 9