You are on page 1of 104

VRV Selection

Project Report

Report details
Produced on: 10/24/2022

Application version: 2022.10.19.3

Project details
Project name: NMBC - AHU-VRV

Solution name: AS-R05

Client Name:

Customer reference:

Quotation reference:

Project number: 1007883/1285578

The output of the VRV Xpress software is based on Daikin-genuine capacity tables that relate to the Japanese Industry
Standard. The VRV Xpress software provides a selection of outdoor and indoor units with optimal efficiency to fit cooling and
heating load requirements.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 1
Material list
Model Quantity Description
RXQ12ARYFK 2 RXQ-ARYFK (High Ambient VRV X)
RXYTQ8UYF 6 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ16UYF 13 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ10UYF 5 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ12UYF 12 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ14UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV200 1 Expansion valve kit for air handling
applications
EKEXV250 3 Expansion valve kit for air handling
applications
EKEXV400 19 Expansion valve kit for air handling
applications
EKEXV500 7 Expansion valve kit for air handling
applications
KHRQ22M75T 11 Refnet branch piping kit
BHFQ22P1007 8 Outdoor unit multi connection piping kit for 2
modules
BHFQ22P1517 6 Outdoor unit multi connection piping kit for 3
modules
BRC1H52W 14 Remote controller (white)
EKEQFCBA 5 Control X/Y/W
EKEQMCBA 25 Control Z
KRP4A51 14 Wiring adapter for electrical appendices

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 2
Indoor unit details
Table of abbreviations

Abbreviation Description
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Max SC Available sensible cooling capacity
PIC Power input in cooling mode @ 50Hz
Tmp H Indoor temperature in heating
Rq HC Required heating capacity
Max HC Available heating capacity
PIH Power input in heating mode @ 50Hz
Sound Sound pressure level low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
MOP Maximum Overcurrent Protection
WxHxD WidthxHeightxDepth
Weight Weight of the device
Min coil Minimum coil volume
Max coil Maximum coil volume

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 3
14 01 00 500L1 M AHU01 - RXYTQ42UYF = RXYTQ16UYF + RXYTQ16UYF + RXYTQ10UYF

Capacity data at conditions and connection ratio (95) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
14 01 00 EKEXV500 n/a 56.6 59.0 n/a 6.0 n/a
500L1 M
AHU01 box
1
14 01 00 EKEXV500 n/a 56.6 59.0 n/a 6.0 n/a
500L1 M
AHU01 box
2
113.1

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
14 01 00 EKEXV500 n/a n/a 63.0 0.01320 0.01650
500L1 M
AHU01 box 1
14 01 00 EKEXV500 n/a n/a 63.0 0.01320 0.01650
500L1 M
AHU01 box 2
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
14 01 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
500L1 M
AHU01 box 1
14 01 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
500L1 M
AHU01 box 2

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

14 G 00 G00P4 M CAHU01-Right - RXQ12ARYFK

Capacity data at conditions and connection ratio (83) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
14 G 00 EKEXV250 n/a 28.6 29.5 n/a 6.0 n/a
G00P4 M
CAHU01 box
1

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 4
Name FCU Cooling
Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
28.6

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
14 G 00 EKEXV250 n/a n/a 31.5 0.00661 0.00825
G00P4 M
CAHU01 box
1
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
14 G 00 G00P4 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
M CAHU01
box 1

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

14 G 00 G00P4 M CAHU02-Left - RXQ12ARYFK

Capacity data at conditions and connection ratio (83) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
14 G 00 EKEXV250 n/a 28.6 29.5 n/a 6.0 n/a
G00P4 M
CAHU02 box
1
28.6

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
14 G 00 EKEXV250 n/a n/a 31.5 0.00661 0.00825
G00P4 M
CAHU02 box
1
n/a

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 5
Name Room Sound PS MCA MOP WxHxD Weight
dBA A inch kg
14 G 00 G00P4 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
M CAHU02
box 1

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M1 M AHU01 - RXYTQ16UYF

Capacity data at conditions and connection ratio (100) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV400 n/a 36.0 47.4 n/a 6.0 n/a
300M1 M
AHU01 box
1
36.0

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU01 box 1
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU01 box 1

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M1 M AHU04 - RXYTQ32UYF = RXYTQ16UYF + RXYTQ16UYF

Capacity data at conditions and connection ratio (100) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV400 n/a 44.4 47.4 n/a 6.0 n/a
300M1 M

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 6
Name FCU Cooling
Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
AHU04 box
1
15 03 00 EKEXV400 n/a 44.4 47.4 n/a 6.0 n/a
300M1 M
AHU04 box
2
88.8

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU04 box 1
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU04 box 2
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU04 box 1
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU04 box 2

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M1 M AHU07 - RXYTQ32UYF = RXYTQ16UYF + RXYTQ16UYF

Capacity data at conditions and connection ratio (100) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV400 n/a 44.4 47.4 n/a 6.0 n/a
300M1 M
AHU07 box
1
15 03 00 EKEXV400 n/a 44.4 47.4 n/a 6.0 n/a
300M1 M
AHU07 box
2
88.8

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 7
Name FCU Heating
Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU07 box 1
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU07 box 2
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU07 box 1
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU07 box 2

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M1 M AHU05 - RXYTQ44UYF = RXYTQ16UYF + RXYTQ16UYF + RXYTQ12UYF

Capacity data at conditions and connection ratio (109) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV400 n/a 38.9 47.4 n/a 6.0 n/a
300M1 M
AHU05 box
1
15 03 00 EKEXV400 n/a 38.9 47.4 n/a 6.0 n/a
300M1 M
AHU05 box
2
15 03 00 EKEXV400 n/a 38.9 47.4 n/a 6.0 n/a
300M1 M
AHU05 box
3
116.6

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU05 box 1

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 8
Name FCU Heating
Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU05 box 2
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU05 box 3
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU05 box 1
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU05 box 2
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU05 box 3

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M1 M AHU08 - RXYTQ32UYF = RXYTQ16UYF + RXYTQ16UYF

Capacity data at conditions and connection ratio (100) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV400 n/a 44.0 47.4 n/a 6.0 n/a
300M1 M
AHU08 box
1
15 03 00 EKEXV400 n/a 44.0 47.4 n/a 6.0 n/a
300M1 M
AHU08 box
2
88.0

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU08 box 1

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 9
Name FCU Heating
Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU08 box 2
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU08 box 1
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU08 box 2

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M1 M AHU09 - RXYTQ34UYF = RXYTQ12UYF + RXYTQ12UYF + RXYTQ10UYF

Capacity data at conditions and connection ratio (94) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV400 n/a 46.8 47.4 n/a 6.0 n/a
300M1 M
AHU09 box
1
15 03 00 EKEXV400 n/a 46.8 47.4 n/a 6.0 n/a
300M1 M
AHU09 box
2
93.6

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU09 box 1
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU09 box 2
n/a

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 10
Name Room Sound PS MCA MOP WxHxD Weight
dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU09 box 1
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU09 box 2

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M2 M AHU02 - RXYTQ34UYF = RXYTQ12UYF + RXYTQ12UYF + RXYTQ10UYF

Capacity data at conditions and connection ratio (94) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV400 n/a 46.0 47.4 n/a 6.0 n/a
300M2 M
AHU02 box
1
15 03 00 EKEXV400 n/a 46.0 47.4 n/a 6.0 n/a
300M2 M
AHU02 box
2
92.0

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M2 M
AHU02 box 1
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M2 M
AHU02 box 2
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M2 M
AHU02 box 1
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M2 M
AHU02 box 2

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 11
Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M2 M AHU03 - RXYTQ20UYF = RXYTQ12UYF + RXYTQ8UYF

Capacity data at conditions and connection ratio (100) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV500 n/a 51.3 59.0 n/a 6.0 n/a
300M2 M
AHU03 box
1
51.3

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV500 n/a n/a 63.0 0.01320 0.01650
300M2 M
AHU03 box 1
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M2 M
AHU03 box 1

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M2 M AHU05 - RXYTQ46UYF = RXYTQ16UYF + RXYTQ16UYF + RXYTQ14UYF

Capacity data at conditions and connection ratio (104) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV400 n/a 43.2 47.4 n/a 6.0 n/a
300M2 M
AHU05 box
1
15 03 00 EKEXV400 n/a 43.2 47.4 n/a 6.0 n/a
300M2 M
AHU05 box
2
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 12
Name FCU Cooling
Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV400 n/a 43.2 47.4 n/a 6.0 n/a
300M2 M
AHU05 box
3
129.6

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M2 M
AHU05 box 1
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M2 M
AHU05 box 2
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M2 M
AHU05 box 3
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M2 M
AHU05 box 1
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M2 M
AHU05 box 2
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M2 M
AHU05 box 3

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M1 M FAHU01 - RXYTQ8UYF

Capacity data at conditions and connection ratio (100) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV200 n/a 20.0 24.6 n/a 6.0 n/a
300M1 M
FAHU01 box
1
20.0

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 13
Name FCU Heating
Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV200 n/a n/a 27.7 0.00463 0.00660
300M1 M
FAHU01 box
1
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
FAHU01 box 1

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M1 M FAHU02-A - RXYTQ20UYF = RXYTQ12UYF + RXYTQ8UYF

Capacity data at conditions and connection ratio (100) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV500 n/a 51.1 61.6 n/a 6.0 n/a
300M1 M
FAHU02 box
1
51.1

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV500 n/a n/a 69.3 0.01320 0.01650
300M1 M
FAHU02 box
1
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
FAHU02 box 1

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 14
Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M1 M FAHU02-B - RXYTQ20UYF = RXYTQ12UYF + RXYTQ8UYF

Capacity data at conditions and connection ratio (100) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV500 n/a 51.1 61.6 n/a 6.0 n/a
300M1 M
FAHU02 box
2
51.1

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV500 n/a n/a 69.3 0.01320 0.01650
300M1 M
FAHU02 box
2
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
FAHU02 box 2

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M1 M FAHU02-C - RXYTQ20UYF = RXYTQ12UYF + RXYTQ8UYF

Capacity data at conditions and connection ratio (100) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV500 n/a 51.1 61.6 n/a 6.0 n/a
300M1 M
FAHU02 box
3
51.1

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 15
Name FCU Heating
Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV500 n/a n/a 69.3 0.01320 0.01650
300M1 M
FAHU02 box
3
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
FAHU02 box 3

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

15 03 00 300M2 M FAHU01 - RXYTQ10UYF

Capacity data at conditions and connection ratio (100) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV250 n/a 26.7 30.8 n/a 6.0 n/a
300M2 M
FAHU01 box
1
26.7

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV250 n/a n/a 34.7 0.00661 0.00825
300M2 M
FAHU01 box
1
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M2 M
FAHU01 box 1

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 16
Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

17 1 00 100M1 M AHU01 - RXYTQ34UYF = RXYTQ12UYF + RXYTQ12UYF + RXYTQ10UYF

Capacity data at conditions and connection ratio (94) as entered

Name FCU Cooling


Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
17 1 00 EKEXV400 n/a 46.3 47.4 n/a 6.0 n/a
100M1 M
AHU01 box
1
17 1 00 EKEXV400 n/a 46.3 47.4 n/a 6.0 n/a
100M1 M
AHU01 box
2
92.5

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
17 1 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
100M1 M
AHU01 box 1
17 1 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
100M1 M
AHU01 box 2
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
17 1 00 100M1 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
M AHU01 box
1
17 1 00 100M1 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
M AHU01 box
2

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

100 00 01 29M 1M AHU01 - RXYTQ20UYF = RXYTQ12UYF + RXYTQ8UYF

Capacity data at conditions and connection ratio (100) as entered

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 17
Name FCU Cooling
Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV500 n/a 36.6 37.8 n/a 6.0 n/a
300M2 M
FAHU01 box
1
36.6

Name FCU Heating


Tmp H Rq HC Max HC PIH Min coil Max coil

°C kW kW kW m³ m³
15 03 00 EKEXV500 n/a n/a 63.0 0.01320 0.01650
300M2 M
FAHU01 box
1
n/a

Name Room Sound PS MCA MOP WxHxD Weight


dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M2 M
FAHU01 box 1

Remarks

Outdoor vs. indoor position

Outdoor unit placed at the same level as the indoor units.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 18
Outdoor unit details
Table of abbreviations

Abbreviation Description
Name Logical name of the device
Model Device model name
CR Connection ratio
Tmp C Outdoor conditions in cooling
WFR per module Water flow per outdoor unit module
CC Available cooling capacity
Rq CC Required cooling capacity
PIC Power input in cooling mode
InC Water inlet temperature in cooling mode
OutC Water outlet temperature in cooling mode
Tmp H Outdoor conditions in heating (dry bulb temp. / RH)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
PIH Power input in heating mode
InH Water inlet temperature in heating mode
OutH Water outlet temperature in heating mode
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (16.4ft actual piping length) excluding extra
refrigerant charge. For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
MOP Maximum Overcurrent Protection
FLA Fan Motor Input
RLA Nominal Running Amps
WxHxD WidthxHeightxDepth
Weight Weight of the device
EER EER value at nominal condition
IEER IEER value at nominal condition
COP47 COP value at nominal condition and at ambient temperature of 8°C
COP17 COP value at nominal condition and at ambient temperature of -8°C

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 19
Outdoor details

Name Model CR Cooling Heating Piping


Tmp C CC Rq CC Tmp H HC Rq HC
% °C kW kW °C kW kW m
(DBT/WBT)
14 01 00 RXYTQ42UYF 95.2 37.9 116.9 113.1 0.0/-0.7 96.0 0.0 7.5
500L1 M
AHU01
14 G 00 RXQ12ARYFK 83.3 37.9 33.2 28.6 / 0.0 0.0 7.5
G00P4 M
CAHU01-
Right
14 G 00 RXQ12ARYFK 83.3 37.9 33.2 28.6 / 0.0 0.0 7.5
G00P4 M
CAHU02-
Left
15 03 00 RXYTQ16UYF 100.0 37.9 44.6 36.0 0.0/-0.7 32.1 0.0 7.5
300M1 M
AHU01
15 03 00 RXYTQ32UYF 100.0 37.9 89.2 88.8 0.0/-0.7 72.3 0.0 7.5
300M1 M
AHU04
15 03 00 RXYTQ32UYF 100.0 37.9 89.2 88.8 0.0/-0.7 72.3 0.0 7.5
300M1 M
AHU07
15 03 00 RXYTQ44UYF 109.1 37.9 124.6 116.6 0.0/-0.7 99.0 0.0 7.5
300M1 M
AHU05
15 03 00 RXYTQ32UYF 100.0 37.9 89.2 88.0 0.0/-0.7 72.3 0.0 7.5
300M1 M
AHU08
15 03 00 RXYTQ34UYF 94.1 37.9 94.1 93.6 0.0/-0.7 76.7 0.0 7.5
300M1 M
AHU09
15 03 00 RXYTQ34UYF 94.1 37.9 94.1 92.0 0.0/-0.7 76.7 0.0 7.5
300M2 M
AHU02
15 03 00 RXYTQ20UYF 100.0 37.9 55.4 51.3 0.0/-0.7 40.5 0.0 7.5
300M2 M
AHU03
15 03 00 RXYTQ46UYF 104.3 37.9 129.9 129.6 0.0/-0.7 104.8 0.0 7.5
300M2 M
AHU05
15 03 00 RXYTQ8UYF 100.0 37.9 22.0 20.0 0.0/-0.7 19.7 0.0 7.5
300M1 M
FAHU01
15 03 00 RXYTQ20UYF 100.0 37.9 55.0 51.1 0.0/-0.7 40.5 0.0 7.5
300M1 M
FAHU02-A
15 03 00 RXYTQ20UYF 100.0 37.9 55.0 51.1 0.0/-0.7 40.5 0.0 7.5
300M1 M
FAHU02-B
15 03 00 RXYTQ20UYF 100.0 37.9 55.0 51.1 0.0/-0.7 40.5 0.0 7.5
300M1 M
FAHU02-C
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 20
Name Model CR Cooling Heating Piping
Tmp C CC Rq CC Tmp H HC Rq HC
% °C kW kW °C kW kW m
(DBT/WBT)
15 03 00 RXYTQ10UYF 100.0 37.9 27.5 26.7 0.0/-0.7 23.1 0.0 7.5
300M2 M
FAHU01
17 1 00 RXYTQ34UYF 94.1 37.9 94.1 92.5 0.0/-0.7 76.7 0.0 7.5
100M1 M
AHU01
100 00 01 RXYTQ20UYF 100.0 37.9 37.7 36.6 0.0/-0.7 40.5 0.0 7.5
29M 1M
AHU01

Name Model PS MCA MOP RLA FLA WxHxD Weight


A A A A inch kg
14 01 00 RXYTQ42UYF 400V 3Nph
500L1 M
AHU01
A - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
B - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
C - RXYTQ10UYF 22.0 25.0 9.3 48.8 x 66.3 x 234.0
30.1
14 G 00 RXQ12ARYFK 400V 3Nph 26.9 48.8 x 65.2 x 220.0
G00P4 M 30.1
CAHU01-
Right
14 G 00 RXQ12ARYFK 400V 3Nph 26.9 48.8 x 65.2 x 220.0
G00P4 M 30.1
CAHU02-Left
15 03 00 RXYTQ16UYF 400V 3Nph 31.0 40.0 19.3 48.8 x 66.3 x 283.0
300M1 M 30.1
AHU01
15 03 00 RXYTQ32UYF 400V 3Nph
300M1 M
AHU04
A - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
B - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
15 03 00 RXYTQ32UYF 400V 3Nph
300M1 M
AHU07
A - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
B - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
15 03 00 RXYTQ44UYF 400V 3Nph
300M1 M
AHU05
A - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
B - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 21
Name Model PS MCA MOP RLA FLA WxHxD Weight
A A A A inch kg
C - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
15 03 00 RXYTQ32UYF 400V 3Nph
300M1 M
AHU08
A - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
B - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
15 03 00 RXYTQ34UYF 400V 3Nph
300M1 M
AHU09
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
C - RXYTQ10UYF 22.0 25.0 9.3 48.8 x 66.3 x 234.0
30.1
15 03 00 RXYTQ34UYF 400V 3Nph
300M2 M
AHU02
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
C - RXYTQ10UYF 22.0 25.0 9.3 48.8 x 66.3 x 234.0
30.1
15 03 00 RXYTQ20UYF 400V 3Nph
300M2 M
AHU03
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ8UYF 16.1 20.0 8.0 36.6 x 66.3 x 198.0
30.1
15 03 00 RXYTQ46UYF 400V 3Nph
300M2 M
AHU05
A - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
B - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
C - RXYTQ14UYF 27.0 32.0 15.8 48.8 x 66.3 x 283.0
30.1
15 03 00 RXYTQ8UYF 400V 3Nph 16.1 20.0 8.0 36.6 x 66.3 x 198.0
300M1 M 30.1
FAHU01
15 03 00 RXYTQ20UYF 400V 3Nph
300M1 M
FAHU02-A
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ8UYF 16.1 20.0 8.0 36.6 x 66.3 x 198.0
30.1

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 22
Name Model PS MCA MOP RLA FLA WxHxD Weight
A A A A inch kg
15 03 00 RXYTQ20UYF 400V 3Nph
300M1 M
FAHU02-B
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ8UYF 16.1 20.0 8.0 36.6 x 66.3 x 198.0
30.1
15 03 00 RXYTQ20UYF 400V 3Nph
300M1 M
FAHU02-C
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ8UYF 16.1 20.0 8.0 36.6 x 66.3 x 198.0
30.1
15 03 00 RXYTQ10UYF 400V 3Nph 22.0 25.0 9.3 48.8 x 66.3 x 234.0
300M2 M 30.1
FAHU01
17 1 00 RXYTQ34UYF 400V 3Nph
100M1 M
AHU01
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
C - RXYTQ10UYF 22.0 25.0 9.3 48.8 x 66.3 x 234.0
30.1
100 00 01 RXYTQ20UYF 400V 3Nph
29M 1M
AHU01
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ8UYF 16.1 20.0 8.0 36.6 x 66.3 x 198.0
30.1

Sound Data

Name Model Sound Power Sound Pressure

Cooling Heating Cooling Heating


dBA dBA dBA dBA
14 01 00 500L1 RXYTQ42UYF 89 - 68 -
M AHU01
14 G 00 G00P4 RXQ12ARYFK - - 59 -
M CAHU01-Right
14 G 00 G00P4 RXQ12ARYFK - - 59 -
M CAHU02-Left

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 23
Name Model Sound Power Sound Pressure

Cooling Heating Cooling Heating


dBA dBA dBA dBA
15 03 00 300M1 RXYTQ16UYF 86 - 64 -
M AHU01
15 03 00 300M1 RXYTQ32UYF 89 - 67 -
M AHU04
15 03 00 300M1 RXYTQ32UYF 89 - 67 -
M AHU07
15 03 00 300M1 RXYTQ44UYF 90 - 68 -
M AHU05
15 03 00 300M1 RXYTQ32UYF 89 - 67 -
M AHU08
15 03 00 300M1 RXYTQ34UYF 87 - 66 -
M AHU09
15 03 00 300M2 RXYTQ34UYF 87 - 66 -
M AHU02
15 03 00 300M2 RXYTQ20UYF 83 - 63 -
M AHU03
15 03 00 300M2 RXYTQ46UYF 90 - 68 -
M AHU05
15 03 00 300M1 RXYTQ8UYF 78 - 57 -
M FAHU01
15 03 00 300M1 RXYTQ20UYF 83 - 63 -
M FAHU02-A
15 03 00 300M1 RXYTQ20UYF 83 - 63 -
M FAHU02-B
15 03 00 300M1 RXYTQ20UYF 83 - 63 -
M FAHU02-C
15 03 00 300M2 RXYTQ10UYF 79 - 59 -
M FAHU01
17 1 00 100M1 RXYTQ34UYF 87 - 66 -
M AHU01
100 00 01 29M RXYTQ20UYF 83 - 63 -
1M AHU01

Seasonal Efficiency

Name Model ηs,h heating ηs,c cooling SCOP SEER CSPF

% %
14 01 00 500L1 RXYTQ42UYF - - - - 5.62
M AHU01
14 G 00 G00P4 RXQ12ARYFK - - - - 5.51
M CAHU01-Right
14 G 00 G00P4 RXQ12ARYFK - - - - 5.51
M CAHU02-Left
15 03 00 300M1 RXYTQ16UYF - - - - 5.36
M AHU01
15 03 00 300M1 RXYTQ32UYF - - - - 5.36
M AHU04
15 03 00 300M1 RXYTQ32UYF - - - - 5.36
M AHU07
15 03 00 300M1 RXYTQ44UYF - - - - 5.64
M AHU05
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 24
Name Model ηs,h heating ηs,c cooling SCOP SEER CSPF

% %
15 03 00 300M1 RXYTQ32UYF - - - - 5.36
M AHU08
15 03 00 300M1 RXYTQ34UYF - - - - 5.76
M AHU09
15 03 00 300M2 RXYTQ34UYF - - - - 5.76
M AHU02
15 03 00 300M2 RXYTQ20UYF - - - - 5.97
M AHU03
15 03 00 300M2 RXYTQ46UYF - - - - 5.46
M AHU05
15 03 00 300M1 RXYTQ8UYF - - - - 5.81
M FAHU01
15 03 00 300M1 RXYTQ20UYF - - - - 5.97
M FAHU02-A
15 03 00 300M1 RXYTQ20UYF - - - - 5.97
M FAHU02-B
15 03 00 300M1 RXYTQ20UYF - - - - 5.97
M FAHU02-C
15 03 00 300M2 RXYTQ10UYF - - - - 6.13
M FAHU01
17 1 00 100M1 RXYTQ34UYF - - - - 5.76
M AHU01
100 00 01 29M RXYTQ20UYF - - - - 5.97
1M AHU01

For more information go to: https://energylabel.daikin.eu/.

Refrigerant information

Name Model Refrigerant type GWP Base charge Extra charge TCO2
kg kg equivalent
14 01 00 500L1 RXYTQ42UYF R410A 2087.5 33.90 unknown 70.8
M AHU01
14 G 00 G00P4 RXQ12ARYFK R410A 2087.5 9.30 unknown 19.4
M CAHU01-
Right
14 G 00 G00P4 RXQ12ARYFK R410A 2087.5 9.30 unknown 19.4
M CAHU02-
Left
15 03 00 RXYTQ16UYF R410A 2087.5 11.80 unknown 24.6
300M1 M
AHU01
15 03 00 RXYTQ32UYF R410A 2087.5 23.60 unknown 49.3
300M1 M
AHU04
15 03 00 RXYTQ32UYF R410A 2087.5 23.60 unknown 49.3
300M1 M
AHU07
15 03 00 RXYTQ44UYF R410A 2087.5 34.00 unknown 71
300M1 M
AHU05

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 25
15 03 00 RXYTQ32UYF R410A 2087.5 23.60 unknown 49.3
300M1 M
AHU08
15 03 00 RXYTQ34UYF R410A 2087.5 31.10 unknown 64.9
300M1 M
AHU09
15 03 00 RXYTQ34UYF R410A 2087.5 31.10 unknown 64.9
300M2 M
AHU02
15 03 00 RXYTQ20UYF R410A 2087.5 17.10 unknown 35.7
300M2 M
AHU03
15 03 00 RXYTQ46UYF R410A 2087.5 35.30 unknown 73.7
300M2 M
AHU05
15 03 00 RXYTQ8UYF R410A 2087.5 6.70 unknown 14
300M1 M
FAHU01
15 03 00 RXYTQ20UYF R410A 2087.5 17.10 unknown 35.7
300M1 M
FAHU02-A
15 03 00 RXYTQ20UYF R410A 2087.5 17.10 unknown 35.7
300M1 M
FAHU02-B
15 03 00 RXYTQ20UYF R410A 2087.5 17.10 unknown 35.7
300M1 M
FAHU02-C
15 03 00 RXYTQ10UYF R410A 2087.5 10.30 unknown 21.5
300M2 M
FAHU01
17 1 00 100M1 RXYTQ34UYF R410A 2087.5 31.10 unknown 64.9
M AHU01
100 00 01 29M RXYTQ20UYF R410A 2087.5 17.10 unknown 35.7
1M AHU01
The system(s) contain fluorinated greenhouse gases.

When extra refrigerant charge requirements are not calculated, TCO2 equivalent is calculated only considering the base
refrigerant charge. Depending on the field pipe length extra refrigerant needs to be added which will increase the TCO2
equivalent.

14 01 00 500L1 M AHU01 - RXYTQ42UYF = RXYTQ16UYF + RXYTQ16UYF + RXYTQ10UYF

Model Quantity Description


RXYTQ16UYF 2 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ10UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV500 2 Expansion valve kit for air handling applications
KHRQ22M75T 1 Refnet branch piping kit
BHFQ22P1517 1 Outdoor unit multi connection piping kit for 3 modules
BRC1H52W 1 Remote controller (white)
EKEQMCBA 2 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 26
Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 33.90 unknown 70.8

The system(s) contain fluorinated greenhouse gases.

Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 22.2mmx41.3mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 27
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 41.3mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

14 G 00 G00P4 M CAHU01-Right - RXQ12ARYFK

Model Quantity Description


RXQ12ARYFK 1 RXQ-ARYFK (High Ambient VRV X)
EKEXV250 1 Expansion valve kit for air handling applications
BRC1H52W 1 Remote controller (white)
EKEQMCBA 1 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 9.30 unknown 19.4

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 28
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 15.9mmx28.6mm

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 29
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 100.0%
Refrigerant pipe diameters 15.9mm (liquid) x 28.6mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

14 G 00 G00P4 M CAHU02-Left - RXQ12ARYFK

Model Quantity Description


RXQ12ARYFK 1 RXQ-ARYFK (High Ambient VRV X)
EKEXV250 1 Expansion valve kit for air handling applications
BRC1H52W 1 Remote controller (white)
EKEQMCBA 1 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 9.30 unknown 19.4

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 30
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 15.9mmx28.6mm

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 31
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 100.0%
Refrigerant pipe diameters 15.9mm (liquid) x 28.6mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M1 M AHU01 - RXYTQ16UYF

Model Quantity Description


RXYTQ16UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV400 1 Expansion valve kit for air handling applications
BRC1H52W 1 Remote controller (white)
EKEQMCBA 1 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 11.80 unknown 24.6

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 32
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 15.9mmx31.8mm

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 33
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 15.9mm (liquid) x 31.8mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M1 M AHU04 - RXYTQ32UYF = RXYTQ16UYF + RXYTQ16UYF

Model Quantity Description


RXYTQ16UYF 2 RXYTQ-UYF (VRV IV High Ambient)
EKEXV400 2 Expansion valve kit for air handling applications
KHRQ22M75T 1 Refnet branch piping kit
BHFQ22P1007 1 Outdoor unit multi connection piping kit for 2 modules
BRC1H52W 1 Remote controller (white)
EKEQMCBA 2 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 23.60 unknown 49.3

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 34
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 22.2mmx38.1mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 35
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 38.1mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M1 M AHU07 - RXYTQ32UYF = RXYTQ16UYF + RXYTQ16UYF

Model Quantity Description


RXYTQ16UYF 2 RXYTQ-UYF (VRV IV High Ambient)
EKEXV400 2 Expansion valve kit for air handling applications
KHRQ22M75T 1 Refnet branch piping kit
BHFQ22P1007 1 Outdoor unit multi connection piping kit for 2 modules
BRC1H52W 1 Remote controller (white)
EKEQMCBA 2 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 23.60 unknown 49.3

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 36
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 22.2mmx38.1mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 37
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 38.1mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M1 M AHU05 - RXYTQ44UYF = RXYTQ16UYF + RXYTQ16UYF + RXYTQ12UYF

Model Quantity Description


RXYTQ16UYF 2 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ12UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV400 3 Expansion valve kit for air handling applications
KHRQ22M75T 2 Refnet branch piping kit
BHFQ22P1517 1 Outdoor unit multi connection piping kit for 3 modules
BRC1H52W 1 Remote controller (white)
EKEQMCBA 3 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 34.00 unknown 71

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 38
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 22.2mmx41.3mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 39
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 41.3mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M1 M AHU08 - RXYTQ32UYF = RXYTQ16UYF + RXYTQ16UYF

Model Quantity Description


RXYTQ16UYF 2 RXYTQ-UYF (VRV IV High Ambient)
EKEXV400 2 Expansion valve kit for air handling applications
KHRQ22M75T 1 Refnet branch piping kit
BHFQ22P1007 1 Outdoor unit multi connection piping kit for 2 modules
BRC1H52W 1 Remote controller (white)
EKEQMCBA 2 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 23.60 unknown 49.3

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 40
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 22.2mmx38.1mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 41
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 38.1mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M1 M AHU09 - RXYTQ34UYF = RXYTQ12UYF + RXYTQ12UYF + RXYTQ10UYF

Model Quantity Description


RXYTQ12UYF 2 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ10UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV400 2 Expansion valve kit for air handling applications
KHRQ22M75T 1 Refnet branch piping kit
BHFQ22P1517 1 Outdoor unit multi connection piping kit for 3 modules
BRC1H52W 1 Remote controller (white)
EKEQMCBA 2 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 31.10 unknown 64.9

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 42
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 22.2mmx38.1mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 43
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 38.1mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M2 M AHU02 - RXYTQ34UYF = RXYTQ12UYF + RXYTQ12UYF + RXYTQ10UYF

Model Quantity Description


RXYTQ12UYF 2 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ10UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV400 2 Expansion valve kit for air handling applications
KHRQ22M75T 1 Refnet branch piping kit
BHFQ22P1517 1 Outdoor unit multi connection piping kit for 3 modules
BRC1H52W 1 Remote controller (white)
EKEQMCBA 2 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 31.10 unknown 64.9

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 44
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 22.2mmx38.1mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 45
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 38.1mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M2 M AHU03 - RXYTQ20UYF = RXYTQ12UYF + RXYTQ8UYF

Model Quantity Description


RXYTQ12UYF 1 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ8UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV500 1 Expansion valve kit for air handling applications
BHFQ22P1007 1 Outdoor unit multi connection piping kit for 2 modules
BRC1H52W 1 Remote controller (white)
EKEQMCBA 1 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 17.10 unknown 35.7

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 46
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 19.1mmx31.8mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 47
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 19.1mm (liquid) x 31.8mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M2 M AHU05 - RXYTQ46UYF = RXYTQ16UYF + RXYTQ16UYF + RXYTQ14UYF

Model Quantity Description


RXYTQ16UYF 2 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ14UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV400 3 Expansion valve kit for air handling applications
KHRQ22M75T 2 Refnet branch piping kit
BHFQ22P1517 1 Outdoor unit multi connection piping kit for 3 modules
BRC1H52W 1 Remote controller (white)
EKEQMCBA 3 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 35.30 unknown 73.7

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 48
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 22.2mmx41.3mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 49
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 41.3mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M1 M FAHU01 - RXYTQ8UYF

Model Quantity Description


RXYTQ8UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV200 1 Expansion valve kit for air handling applications
EKEQFCBA 1 Control X/Y/W

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 6.70 unknown 14

The system(s) contain fluorinated greenhouse gases.

Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 50
Maximum Connection Index Diameters
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 12.7mmx22.2mm

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 51
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 12.7mm (liquid) x 22.2mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M1 M FAHU02-A - RXYTQ20UYF = RXYTQ12UYF + RXYTQ8UYF

Model Quantity Description


RXYTQ12UYF 1 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ8UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV500 1 Expansion valve kit for air handling applications
BHFQ22P1007 1 Outdoor unit multi connection piping kit for 2 modules
EKEQFCBA 1 Control X/Y/W

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 17.10 unknown 35.7

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 52
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 19.1mmx31.8mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 53
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 19.1mm (liquid) x 31.8mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M1 M FAHU02-B - RXYTQ20UYF = RXYTQ12UYF + RXYTQ8UYF

Model Quantity Description


RXYTQ12UYF 1 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ8UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV500 1 Expansion valve kit for air handling applications
BHFQ22P1007 1 Outdoor unit multi connection piping kit for 2 modules
EKEQFCBA 1 Control X/Y/W

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 17.10 unknown 35.7

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 54
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 19.1mmx31.8mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 55
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 19.1mm (liquid) x 31.8mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M1 M FAHU02-C - RXYTQ20UYF = RXYTQ12UYF + RXYTQ8UYF

Model Quantity Description


RXYTQ12UYF 1 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ8UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV500 1 Expansion valve kit for air handling applications
BHFQ22P1007 1 Outdoor unit multi connection piping kit for 2 modules
EKEQFCBA 1 Control X/Y/W

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 17.10 unknown 35.7

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 56
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 19.1mmx31.8mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 57
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 19.1mm (liquid) x 31.8mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

15 03 00 300M2 M FAHU01 - RXYTQ10UYF

Model Quantity Description


RXYTQ10UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV250 1 Expansion valve kit for air handling applications
EKEQFCBA 1 Control X/Y/W

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 10.30 unknown 21.5

The system(s) contain fluorinated greenhouse gases.

Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 58
Maximum Connection Index Diameters
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 12.7mmx25.4mm

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 59
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 12.7mm (liquid) x 25.4mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

17 1 00 100M1 M AHU01 - RXYTQ34UYF = RXYTQ12UYF + RXYTQ12UYF + RXYTQ10UYF

Model Quantity Description


RXYTQ12UYF 2 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ10UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV400 2 Expansion valve kit for air handling applications
KHRQ22M75T 1 Refnet branch piping kit
BHFQ22P1517 1 Outdoor unit multi connection piping kit for 3 modules
BRC1H52W 1 Remote controller (white)
EKEQMCBA 2 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 31.10 unknown 64.9

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 60
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 22.2mmx38.1mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 61
Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 38.1mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

100 00 01 29M 1M AHU01 - RXYTQ20UYF = RXYTQ12UYF + RXYTQ8UYF

Model Quantity Description


RXYTQ12UYF 1 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ8UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV500 1 Expansion valve kit for air handling applications
BHFQ22P1007 1 Outdoor unit multi connection piping kit for 2 modules
BRC1H52W 1 Remote controller (white)
EKEQMCBA 1 Control Z
KRP4A51 1 Wiring adapter for electrical appendices

Refrigerant information

Refrigerant type GWP Base charge Extra charge TCO2 equivalent


kg kg
R410A 2087.5 17.10 unknown 35.7

The system(s) contain fluorinated greenhouse gases.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 62
Pipe capacities

Maximum Connection Index Diameters


149.9 9.5mmx15.9mm
199.9 9.5mmx19.1mm
289.9 9.5mmx22.2mm
419.9 12.7mmx28.6mm
639.9 15.9mmx28.6mm
919.9 19.1mmx34.9mm
> 919.9 19.1mmx41.3mm
Main pipe size up 19.1mmx31.8mm

Remarks

Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.

Piping limitations

Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 19.1mm (liquid) x 31.8mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 63
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 64
Piping diagrams
Piping 14 01 00 500L1 M AHU01

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 65
Piping 14 G 00 G00P4 M CAHU01-Right

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 66
Piping 14 G 00 G00P4 M CAHU02-Left

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 67
Piping 15 03 00 300M1 M AHU01

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 68
Piping 15 03 00 300M1 M AHU04

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 69
Piping 15 03 00 300M1 M AHU07

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 70
Piping 15 03 00 300M1 M AHU05

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 71
Piping 15 03 00 300M1 M AHU08

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 72
Piping 15 03 00 300M1 M AHU09

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 73
Piping 15 03 00 300M2 M AHU02

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 74
Piping 15 03 00 300M2 M AHU03

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 75
Piping 15 03 00 300M2 M AHU05

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 76
Piping 15 03 00 300M1 M FAHU01

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 77
Piping 15 03 00 300M1 M FAHU02-A

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 78
Piping 15 03 00 300M1 M FAHU02-B

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 79
Piping 15 03 00 300M1 M FAHU02-C

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 80
Piping 15 03 00 300M2 M FAHU01

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 81
Piping 17 1 00 100M1 M AHU01

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 82
Piping 100 00 01 29M 1M AHU01

Piping

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 83
Wiring diagrams
Wiring 14 01 00 500L1 M AHU01

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 84
Wiring 14 G 00 G00P4 M CAHU01-Right

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 85
Wiring 14 G 00 G00P4 M CAHU02-Left

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 86
Wiring 15 03 00 300M1 M AHU01

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 87
Wiring 15 03 00 300M1 M AHU04

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 88
Wiring 15 03 00 300M1 M AHU07

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 89
Wiring 15 03 00 300M1 M AHU05

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 90
Wiring 15 03 00 300M1 M AHU08

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 91
Wiring 15 03 00 300M1 M AHU09

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 92
Wiring 15 03 00 300M2 M AHU02

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 93
Wiring 15 03 00 300M2 M AHU03

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 94
Wiring 15 03 00 300M2 M AHU05

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 95
Wiring 15 03 00 300M1 M FAHU01

Remarks

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 96
Wiring 15 03 00 300M1 M FAHU02-A

Remarks

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 97
Wiring 15 03 00 300M1 M FAHU02-B

Remarks

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 98
Wiring 15 03 00 300M1 M FAHU02-C

Remarks

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 99
Wiring 15 03 00 300M2 M FAHU01

Remarks

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 100
Wiring 17 1 00 100M1 M AHU01

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 101
Wiring 100 00 01 29M 1M AHU01

Remarks

P1P2 = AWG 18-2 is required - however always refer to local code for further information.

F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).

Note: The shield should only be earthed at outdoor unit side, not at the indoor units!

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 102
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 103
Best Practices
Residual Current Circuit Breaker

For better protection of installations against the risk of fire, power supply of indoor and outdoor units must be protected with
a Residual Current Circuit Breaker. For protection against fire, we recommend a sensitivity of 300mA. The selected RCCB
should be of the type B, suitable for inverter devices and indicated by the symbols here below. Further electrical characteristics
of the RCCB must be selected in accordance with local regulation.

For a complete list of all required safety precautions, warnings and attention points, please consult the “general safety
precautions manual” delivered with the unit.

The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 104