Project Report
Report details
Produced on: 10/24/2022
Project details
Project name: NMBC - AHU-VRV
Client Name:
Customer reference:
Quotation reference:
The output of the VRV Xpress software is based on Daikin-genuine capacity tables that relate to the Japanese Industry
Standard. The VRV Xpress software provides a selection of outdoor and indoor units with optimal efficiency to fit cooling and
heating load requirements.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 1
Material list
Model Quantity Description
RXQ12ARYFK 2 RXQ-ARYFK (High Ambient VRV X)
RXYTQ8UYF 6 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ16UYF 13 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ10UYF 5 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ12UYF 12 RXYTQ-UYF (VRV IV High Ambient)
RXYTQ14UYF 1 RXYTQ-UYF (VRV IV High Ambient)
EKEXV200 1 Expansion valve kit for air handling
applications
EKEXV250 3 Expansion valve kit for air handling
applications
EKEXV400 19 Expansion valve kit for air handling
applications
EKEXV500 7 Expansion valve kit for air handling
applications
KHRQ22M75T 11 Refnet branch piping kit
BHFQ22P1007 8 Outdoor unit multi connection piping kit for 2
modules
BHFQ22P1517 6 Outdoor unit multi connection piping kit for 3
modules
BRC1H52W 14 Remote controller (white)
EKEQFCBA 5 Control X/Y/W
EKEQMCBA 25 Control Z
KRP4A51 14 Wiring adapter for electrical appendices
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 2
Indoor unit details
Table of abbreviations
Abbreviation Description
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Max SC Available sensible cooling capacity
PIC Power input in cooling mode @ 50Hz
Tmp H Indoor temperature in heating
Rq HC Required heating capacity
Max HC Available heating capacity
PIH Power input in heating mode @ 50Hz
Sound Sound pressure level low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
MOP Maximum Overcurrent Protection
WxHxD WidthxHeightxDepth
Weight Weight of the device
Min coil Minimum coil volume
Max coil Maximum coil volume
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 3
14 01 00 500L1 M AHU01 - RXYTQ42UYF = RXYTQ16UYF + RXYTQ16UYF + RXYTQ10UYF
°C kW kW kW m³ m³
14 01 00 EKEXV500 n/a n/a 63.0 0.01320 0.01650
500L1 M
AHU01 box 1
14 01 00 EKEXV500 n/a n/a 63.0 0.01320 0.01650
500L1 M
AHU01 box 2
n/a
Remarks
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 4
Name FCU Cooling
Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
28.6
°C kW kW kW m³ m³
14 G 00 EKEXV250 n/a n/a 31.5 0.00661 0.00825
G00P4 M
CAHU01 box
1
n/a
Remarks
°C kW kW kW m³ m³
14 G 00 EKEXV250 n/a n/a 31.5 0.00661 0.00825
G00P4 M
CAHU02 box
1
n/a
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 5
Name Room Sound PS MCA MOP WxHxD Weight
dBA A inch kg
14 G 00 G00P4 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
M CAHU02
box 1
Remarks
°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU01 box 1
n/a
Remarks
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 6
Name FCU Cooling
Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
AHU04 box
1
15 03 00 EKEXV400 n/a 44.4 47.4 n/a 6.0 n/a
300M1 M
AHU04 box
2
88.8
°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU04 box 1
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU04 box 2
n/a
Remarks
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 7
Name FCU Heating
Tmp H Rq HC Max HC PIH Min coil Max coil
°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU07 box 1
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU07 box 2
n/a
Remarks
°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU05 box 1
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 8
Name FCU Heating
Tmp H Rq HC Max HC PIH Min coil Max coil
°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU05 box 2
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU05 box 3
n/a
Remarks
°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU08 box 1
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 9
Name FCU Heating
Tmp H Rq HC Max HC PIH Min coil Max coil
°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU08 box 2
n/a
Remarks
°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU09 box 1
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M1 M
AHU09 box 2
n/a
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 10
Name Room Sound PS MCA MOP WxHxD Weight
dBA A inch kg
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU09 box 1
15 03 00 - 230V 1ph 8.5 x 15.8 x 3.1 2.9
300M1 M
AHU09 box 2
Remarks
°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M2 M
AHU02 box 1
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M2 M
AHU02 box 2
n/a
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 11
Remarks
°C kW kW kW m³ m³
15 03 00 EKEXV500 n/a n/a 63.0 0.01320 0.01650
300M2 M
AHU03 box 1
n/a
Remarks
°C kW kW kW m³ m³
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M2 M
AHU05 box 1
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M2 M
AHU05 box 2
15 03 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
300M2 M
AHU05 box 3
n/a
Remarks
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 13
Name FCU Heating
Tmp H Rq HC Max HC PIH Min coil Max coil
°C kW kW kW m³ m³
15 03 00 EKEXV200 n/a n/a 27.7 0.00463 0.00660
300M1 M
FAHU01 box
1
n/a
Remarks
°C kW kW kW m³ m³
15 03 00 EKEXV500 n/a n/a 69.3 0.01320 0.01650
300M1 M
FAHU02 box
1
n/a
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 14
Remarks
°C kW kW kW m³ m³
15 03 00 EKEXV500 n/a n/a 69.3 0.01320 0.01650
300M1 M
FAHU02 box
2
n/a
Remarks
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 15
Name FCU Heating
Tmp H Rq HC Max HC PIH Min coil Max coil
°C kW kW kW m³ m³
15 03 00 EKEXV500 n/a n/a 69.3 0.01320 0.01650
300M1 M
FAHU02 box
3
n/a
Remarks
°C kW kW kW m³ m³
15 03 00 EKEXV250 n/a n/a 34.7 0.00661 0.00825
300M2 M
FAHU01 box
1
n/a
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 16
Remarks
°C kW kW kW m³ m³
17 1 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
100M1 M
AHU01 box 1
17 1 00 EKEXV400 n/a n/a 50.0 0.00926 0.01320
100M1 M
AHU01 box 2
n/a
Remarks
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 17
Name FCU Cooling
Tmp C Rq TC Max TC Rq SC Tevap Max SC PIC
°C kW kW kW °C kW kW
(DBT/WBT)
15 03 00 EKEXV500 n/a 36.6 37.8 n/a 6.0 n/a
300M2 M
FAHU01 box
1
36.6
°C kW kW kW m³ m³
15 03 00 EKEXV500 n/a n/a 63.0 0.01320 0.01650
300M2 M
FAHU01 box
1
n/a
Remarks
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 18
Outdoor unit details
Table of abbreviations
Abbreviation Description
Name Logical name of the device
Model Device model name
CR Connection ratio
Tmp C Outdoor conditions in cooling
WFR per module Water flow per outdoor unit module
CC Available cooling capacity
Rq CC Required cooling capacity
PIC Power input in cooling mode
InC Water inlet temperature in cooling mode
OutC Water outlet temperature in cooling mode
Tmp H Outdoor conditions in heating (dry bulb temp. / RH)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
PIH Power input in heating mode
InH Water inlet temperature in heating mode
OutH Water outlet temperature in heating mode
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (16.4ft actual piping length) excluding extra
refrigerant charge. For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
MOP Maximum Overcurrent Protection
FLA Fan Motor Input
RLA Nominal Running Amps
WxHxD WidthxHeightxDepth
Weight Weight of the device
EER EER value at nominal condition
IEER IEER value at nominal condition
COP47 COP value at nominal condition and at ambient temperature of 8°C
COP17 COP value at nominal condition and at ambient temperature of -8°C
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 19
Outdoor details
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 21
Name Model PS MCA MOP RLA FLA WxHxD Weight
A A A A inch kg
C - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
15 03 00 RXYTQ32UYF 400V 3Nph
300M1 M
AHU08
A - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
B - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
15 03 00 RXYTQ34UYF 400V 3Nph
300M1 M
AHU09
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
C - RXYTQ10UYF 22.0 25.0 9.3 48.8 x 66.3 x 234.0
30.1
15 03 00 RXYTQ34UYF 400V 3Nph
300M2 M
AHU02
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
C - RXYTQ10UYF 22.0 25.0 9.3 48.8 x 66.3 x 234.0
30.1
15 03 00 RXYTQ20UYF 400V 3Nph
300M2 M
AHU03
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ8UYF 16.1 20.0 8.0 36.6 x 66.3 x 198.0
30.1
15 03 00 RXYTQ46UYF 400V 3Nph
300M2 M
AHU05
A - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
B - RXYTQ16UYF 31.0 40.0 19.3 48.8 x 66.3 x 283.0
30.1
C - RXYTQ14UYF 27.0 32.0 15.8 48.8 x 66.3 x 283.0
30.1
15 03 00 RXYTQ8UYF 400V 3Nph 16.1 20.0 8.0 36.6 x 66.3 x 198.0
300M1 M 30.1
FAHU01
15 03 00 RXYTQ20UYF 400V 3Nph
300M1 M
FAHU02-A
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ8UYF 16.1 20.0 8.0 36.6 x 66.3 x 198.0
30.1
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 22
Name Model PS MCA MOP RLA FLA WxHxD Weight
A A A A inch kg
15 03 00 RXYTQ20UYF 400V 3Nph
300M1 M
FAHU02-B
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ8UYF 16.1 20.0 8.0 36.6 x 66.3 x 198.0
30.1
15 03 00 RXYTQ20UYF 400V 3Nph
300M1 M
FAHU02-C
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ8UYF 16.1 20.0 8.0 36.6 x 66.3 x 198.0
30.1
15 03 00 RXYTQ10UYF 400V 3Nph 22.0 25.0 9.3 48.8 x 66.3 x 234.0
300M2 M 30.1
FAHU01
17 1 00 RXYTQ34UYF 400V 3Nph
100M1 M
AHU01
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
C - RXYTQ10UYF 22.0 25.0 9.3 48.8 x 66.3 x 234.0
30.1
100 00 01 RXYTQ20UYF 400V 3Nph
29M 1M
AHU01
A - RXYTQ12UYF 24.0 32.0 12.7 48.8 x 66.3 x 234.0
30.1
B - RXYTQ8UYF 16.1 20.0 8.0 36.6 x 66.3 x 198.0
30.1
Sound Data
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 23
Name Model Sound Power Sound Pressure
Seasonal Efficiency
% %
14 01 00 500L1 RXYTQ42UYF - - - - 5.62
M AHU01
14 G 00 G00P4 RXQ12ARYFK - - - - 5.51
M CAHU01-Right
14 G 00 G00P4 RXQ12ARYFK - - - - 5.51
M CAHU02-Left
15 03 00 300M1 RXYTQ16UYF - - - - 5.36
M AHU01
15 03 00 300M1 RXYTQ32UYF - - - - 5.36
M AHU04
15 03 00 300M1 RXYTQ32UYF - - - - 5.36
M AHU07
15 03 00 300M1 RXYTQ44UYF - - - - 5.64
M AHU05
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 24
Name Model ηs,h heating ηs,c cooling SCOP SEER CSPF
% %
15 03 00 300M1 RXYTQ32UYF - - - - 5.36
M AHU08
15 03 00 300M1 RXYTQ34UYF - - - - 5.76
M AHU09
15 03 00 300M2 RXYTQ34UYF - - - - 5.76
M AHU02
15 03 00 300M2 RXYTQ20UYF - - - - 5.97
M AHU03
15 03 00 300M2 RXYTQ46UYF - - - - 5.46
M AHU05
15 03 00 300M1 RXYTQ8UYF - - - - 5.81
M FAHU01
15 03 00 300M1 RXYTQ20UYF - - - - 5.97
M FAHU02-A
15 03 00 300M1 RXYTQ20UYF - - - - 5.97
M FAHU02-B
15 03 00 300M1 RXYTQ20UYF - - - - 5.97
M FAHU02-C
15 03 00 300M2 RXYTQ10UYF - - - - 6.13
M FAHU01
17 1 00 100M1 RXYTQ34UYF - - - - 5.76
M AHU01
100 00 01 29M RXYTQ20UYF - - - - 5.97
1M AHU01
Refrigerant information
Name Model Refrigerant type GWP Base charge Extra charge TCO2
kg kg equivalent
14 01 00 500L1 RXYTQ42UYF R410A 2087.5 33.90 unknown 70.8
M AHU01
14 G 00 G00P4 RXQ12ARYFK R410A 2087.5 9.30 unknown 19.4
M CAHU01-
Right
14 G 00 G00P4 RXQ12ARYFK R410A 2087.5 9.30 unknown 19.4
M CAHU02-
Left
15 03 00 RXYTQ16UYF R410A 2087.5 11.80 unknown 24.6
300M1 M
AHU01
15 03 00 RXYTQ32UYF R410A 2087.5 23.60 unknown 49.3
300M1 M
AHU04
15 03 00 RXYTQ32UYF R410A 2087.5 23.60 unknown 49.3
300M1 M
AHU07
15 03 00 RXYTQ44UYF R410A 2087.5 34.00 unknown 71
300M1 M
AHU05
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 25
15 03 00 RXYTQ32UYF R410A 2087.5 23.60 unknown 49.3
300M1 M
AHU08
15 03 00 RXYTQ34UYF R410A 2087.5 31.10 unknown 64.9
300M1 M
AHU09
15 03 00 RXYTQ34UYF R410A 2087.5 31.10 unknown 64.9
300M2 M
AHU02
15 03 00 RXYTQ20UYF R410A 2087.5 17.10 unknown 35.7
300M2 M
AHU03
15 03 00 RXYTQ46UYF R410A 2087.5 35.30 unknown 73.7
300M2 M
AHU05
15 03 00 RXYTQ8UYF R410A 2087.5 6.70 unknown 14
300M1 M
FAHU01
15 03 00 RXYTQ20UYF R410A 2087.5 17.10 unknown 35.7
300M1 M
FAHU02-A
15 03 00 RXYTQ20UYF R410A 2087.5 17.10 unknown 35.7
300M1 M
FAHU02-B
15 03 00 RXYTQ20UYF R410A 2087.5 17.10 unknown 35.7
300M1 M
FAHU02-C
15 03 00 RXYTQ10UYF R410A 2087.5 10.30 unknown 21.5
300M2 M
FAHU01
17 1 00 100M1 RXYTQ34UYF R410A 2087.5 31.10 unknown 64.9
M AHU01
100 00 01 29M RXYTQ20UYF R410A 2087.5 17.10 unknown 35.7
1M AHU01
The system(s) contain fluorinated greenhouse gases.
When extra refrigerant charge requirements are not calculated, TCO2 equivalent is calculated only considering the base
refrigerant charge. Depending on the field pipe length extra refrigerant needs to be added which will increase the TCO2
equivalent.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 26
Refrigerant information
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 27
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 41.3mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 28
Pipe capacities
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 29
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 100.0%
Refrigerant pipe diameters 15.9mm (liquid) x 28.6mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 30
Pipe capacities
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 31
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 100.0%
Refrigerant pipe diameters 15.9mm (liquid) x 28.6mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 32
Pipe capacities
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 33
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 15.9mm (liquid) x 31.8mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 34
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 35
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 38.1mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 36
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 37
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 38.1mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 38
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 39
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 41.3mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 40
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 41
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 38.1mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 42
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 43
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 38.1mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 44
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 45
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 38.1mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 46
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 47
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 19.1mm (liquid) x 31.8mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 48
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 49
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 41.3mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
Pipe capacities
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 51
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 12.7mm (liquid) x 22.2mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 52
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 53
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 19.1mm (liquid) x 31.8mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 54
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 55
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 19.1mm (liquid) x 31.8mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 56
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 57
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 19.1mm (liquid) x 31.8mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
Pipe capacities
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 59
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 12.7mm (liquid) x 25.4mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 60
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 61
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 22.2mm (liquid) x 38.1mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
Refrigerant information
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 62
Pipe capacities
Remarks
Sufficient distance should be respected between the modules according to the service & operation space rules as mentioned
in the databook.
Piping limitations
Description Value
Maximum total length 10,000.0m
Maximum longest actual length 50.0m
Maximum longest equivalent length 55.0m
Maximum main pipe length (size up of main pipe required if longer) -
Maximum length first branch to indoor unit(size up of intermediate pipes required if longer) 40.0m
Maximum length first branch to indoor unit 40.0m
Maximum length of indoor units to nearest branch 40.0m
Maximum length difference between longest and shortest distance to indoor units 40.0m
Maximum height difference, outdoor unit below indoor units 40.0m
Minimum connection ratio, outdoor unit below indoor units -
Maximum height difference, outdoor unit above indoor units 40.0m
Minimum connection ratio, outdoor unit above indoor units -
Maximum height difference in technical cooling, outdoor unit below indoor units 40.0m
Maximum height difference in technical cooling, outdoor unit above indoor units 40.0m
Maximum height difference between indoor units 15.0m
Connection ratio range 75.0% - 110.0%
Refrigerant pipe diameters 19.1mm (liquid) x 31.8mm
(gas)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET (size up of intermediate -
pipes required if longer)
Maximum equivalent length from BP unit or VRV indoor to VRV REFNET 40.0m
Maximum actual length between CM and HM -
Maximum height difference between CM and HM -
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 63
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 64
Piping diagrams
Piping 14 01 00 500L1 M AHU01
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 65
Piping 14 G 00 G00P4 M CAHU01-Right
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 66
Piping 14 G 00 G00P4 M CAHU02-Left
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 67
Piping 15 03 00 300M1 M AHU01
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 68
Piping 15 03 00 300M1 M AHU04
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 69
Piping 15 03 00 300M1 M AHU07
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 70
Piping 15 03 00 300M1 M AHU05
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 71
Piping 15 03 00 300M1 M AHU08
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 72
Piping 15 03 00 300M1 M AHU09
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 73
Piping 15 03 00 300M2 M AHU02
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 74
Piping 15 03 00 300M2 M AHU03
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 75
Piping 15 03 00 300M2 M AHU05
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 76
Piping 15 03 00 300M1 M FAHU01
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 77
Piping 15 03 00 300M1 M FAHU02-A
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 78
Piping 15 03 00 300M1 M FAHU02-B
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 79
Piping 15 03 00 300M1 M FAHU02-C
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 80
Piping 15 03 00 300M2 M FAHU01
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 81
Piping 17 1 00 100M1 M AHU01
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 82
Piping 100 00 01 29M 1M AHU01
Piping
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter
might be required.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 83
Wiring diagrams
Wiring 14 01 00 500L1 M AHU01
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 84
Wiring 14 G 00 G00P4 M CAHU01-Right
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 85
Wiring 14 G 00 G00P4 M CAHU02-Left
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 86
Wiring 15 03 00 300M1 M AHU01
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 87
Wiring 15 03 00 300M1 M AHU04
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 88
Wiring 15 03 00 300M1 M AHU07
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 89
Wiring 15 03 00 300M1 M AHU05
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 90
Wiring 15 03 00 300M1 M AHU08
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 91
Wiring 15 03 00 300M1 M AHU09
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 92
Wiring 15 03 00 300M2 M AHU02
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 93
Wiring 15 03 00 300M2 M AHU03
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 94
Wiring 15 03 00 300M2 M AHU05
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 95
Wiring 15 03 00 300M1 M FAHU01
Remarks
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 96
Wiring 15 03 00 300M1 M FAHU02-A
Remarks
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 97
Wiring 15 03 00 300M1 M FAHU02-B
Remarks
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 98
Wiring 15 03 00 300M1 M FAHU02-C
Remarks
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 99
Wiring 15 03 00 300M2 M FAHU01
Remarks
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 100
Wiring 17 1 00 100M1 M AHU01
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 101
Wiring 100 00 01 29M 1M AHU01
Remarks
P1P2 = AWG 18-2 is required - however always refer to local code for further information.
F1F2 IN/OUT transmission wiring, use 2-core wires of 0,75 to 1,25 mm² size cables, without shield (but shielded cable can be
used if local regulation prescribes it).
Note: The shield should only be earthed at outdoor unit side, not at the indoor units!
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 102
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 103
Best Practices
Residual Current Circuit Breaker
For better protection of installations against the risk of fire, power supply of indoor and outdoor units must be protected with
a Residual Current Circuit Breaker. For protection against fire, we recommend a sensitivity of 300mA. The selected RCCB
should be of the type B, suitable for inverter devices and indicated by the symbols here below. Further electrical characteristics
of the RCCB must be selected in accordance with local regulation.
For a complete list of all required safety precautions, warnings and attention points, please consult the “general safety
precautions manual” delivered with the unit.
The VRV Selection application is property of Daikin Europe N.V. Daikin Europe N.V. cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Selection application. 104