Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.
1. Material List
Model Qty Description
RHXYQ22AYL 1 Heat pump VRV IV 380V(YL)LA
FXAQ20PVE 2 VRV AP - De Pared (Panel Plano)
FXFQ125AVE 1 VRV FA - Unidad de casete montada en el techo (Flujo circular)
FXFQ32AVE 1 VRV FA - Unidad de casete montada en el techo (Flujo circular)
FXFQ63AVE 8 VRV FA - Unidad de casete montada en el techo (Flujo circular)
KHRP26A22T 5 Refnet branch piping kit
KHRP26A33T 1 Refnet branch piping kit
KHRP26A72T 5 Refnet branch piping kit
BRC1E62 12 Wired Remote Controller (Navigation Remote Controller)
BYCP125K-W1 10 Decoration panel
R410A 16.4kg Extra refrigerant charge
Piping ¼" 4.5m
Piping ⅜" 48.4m
Piping ½" 13.5m
Piping ⅝" 75.2m
Piping ¾" 9.6m
Piping ⅞" 4.5m
Piping 1⅛" 49.9m
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 1
2. Indoor Unit Details
2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / wet bulb temp.)
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tdis C Indoor unit discharge air temperature in cooling
Tdis H Indoor unit discharge air temperature in heating
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 2
2.2. VRV - 1 - RHXYQ22AYL
Capacity data at conditions and connection ratio (127%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Tdis H Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C °C cfm
UE - 1 FXFQ32AVE 27.0 / 19.0 n/a 12284 n/a 9895 6.0 15.7 35.6 441
UE - 2 FXAQ20PVE 27.0 / 19.0 n/a 7507 n/a 6483 6.0 14.6 36.3 265
UE - 3 FXAQ20PVE 27.0 / 19.0 n/a 7507 n/a 6483 6.0 14.6 36.3 265
UE - 4 FXFQ125AVE 27.0 / 19.0 n/a 47770 n/a 32415 6.0 11.6 46.0 1059
UE - 5 FXFQ63AVE 27.0 / 19.0 n/a 24226 n/a 16378 6.0 12.5 44.2 569
UE - 6 FXFQ63AVE 27.0 / 19.0 n/a 24226 n/a 16378 6.0 12.5 44.2 569
UE - 7 FXFQ63AVE 27.0 / 19.0 n/a 24226 n/a 16378 6.0 12.5 44.2 569
UE - 8 FXFQ63AVE 27.0 / 19.0 n/a 24226 n/a 16378 6.0 12.5 44.2 569
UE - 9 FXFQ63AVE 27.0 / 19.0 n/a 24226 n/a 16378 6.0 12.5 44.2 569
UE - 10 FXFQ63AVE 27.0 / 19.0 n/a 24226 n/a 16378 6.0 12.5 44.2 569
UE - 11 FXFQ63AVE 27.0 / 19.0 n/a 24226 n/a 16378 6.0 12.5 44.2 569
UE - 12 FXFQ63AVE 27.0 / 19.0 n/a 24226 n/a 16378 6.0 12.5 44.2 569
The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 3
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
▼ Optimized selection: Smaller outdoor model selected than standard proposed model
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / wet bulb temp.)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 4
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC
% °C BTU/h BTU/h °C BTU/h BTU/h
VRV - 1 RHXYQ22AYL ▼ 127 29.8 197822 (-26.4%) 268877 13.9 / 8.8 262777 (-13.5%) 303681
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 5
3.2.1. VRV - 1 - RHXYQ22AYL
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 6
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.
UE - 10
FXFQ63AVE
4.0m 2.2m
⅜"×⅝" ⅜"×⅝"
KHRP26A22T
UE - 11
FXFQ63AVE
6.0m
⅜"×⅝"
UE - 12
FXFQ63AVE
1.7m 2.0m
⅝"×1⅛" ⅜"×⅝"
KHRP26A72T
UE - 9
FXFQ63AVE
4.2m 2.0m
⅝"×1⅛" ⅜"×⅝"
KHRP26A72T
UE - 8
FXFQ63AVE
4.5m 2.0m
½"×1⅛" ⅜"×⅝"
KHRP26A72T
UE - 7
FXFQ63AVE
4.5m 2.0m
½"×1⅛" ⅜"×⅝"
KHRP26A72T
UE - 6
FXFQ63AVE
4.5m 2.0m
⅜"×⅞" ⅜"×⅝"
KHRP26A33T
UE - 5
FXFQ63AVE
6.6m 2.0m
⅜"×¾" ⅜"×⅝"
KHRP26A22T
UE - 4
FXFQ125AVE
5.3m 1.6m
⅜"×⅝" ¼"×½"
KHRP26A22T
UE - 1
FXFQ32AVE
2.6m 0.6m
⅜"×⅝" ¼"×½"
KHRP26A22T
UE - 3
FXAQ20PVE
2.3m
¼"×½"
UE - 2
FXAQ20PVE
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 7
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 8
6. Device Options
6.1. Indoor Unit Options
Model Description Used by
BYCP125K-W1 Decoration panel UE - 1 [FXFQ32AVE] UE - 4 [FXFQ125AVE] UE - 5 [FXFQ63AVE]
UE - 6 [FXFQ63AVE] UE - 7 [FXFQ63AVE] UE - 8 [FXFQ63AVE]
UE - 9 [FXFQ63AVE] UE - 10 [FXFQ63AVE] UE - 11 [FXFQ63AVE]
UE - 12 [FXFQ63AVE]
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 9