Produced on 12/01/2015 with Xpress Selection V7.0.1 - database DIL 11.1.

Project name LATIHAN 1


Project address Jakarta
Reference Modul
Client name Dani DL
Client address Jakarta
Revision Dian

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Qty Description
RXMQ8AY1 1 Cooling only VRV IV S+RA
RXQ8TY1 1 Cooling only VRV IV STANDARD
FXAQ32PVE 1 VRV AP - Wall Mounted(Flat Panel)
FXAQ40PVE 1 VRV AP - Wall Mounted(Flat Panel)
FXFQ100LUV1 2 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXFQ25LUV1 1 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXMQ20PVE 1 VRV M - Ceiling Mounted Duct
FXMQ40PVE 2 VRV M - Ceiling Mounted Duct
KHRP26A22T 4 Refnet branch piping kit
KHRP26A33T 2 Refnet branch piping kit
DCM601A51 1 intelligent Touch Manager
BRC1E62 8 Wired Remote Controller (Navigation Remote Controller)
BYCP125K-W1 3 Decoration panel
DCM601A52 1 iTM Plus Adaptor
R410A 3,0kg Extra refrigerant charge
Piping 6,4 21,8m
Piping 9,5 43,4m
Piping 12,7 21,8m
Piping 15,9 39,4m
Piping 19,1 4,0m

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 1
2. Indoor Unit Details 2.1.
Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / RH)
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tmp H Indoor temperature in heating
Rq HC Required heating capacity
Max HC Available heating capacity
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
Fuses Fuses
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 2
2.2. Outdoor 1 - RXQ8TY1
Capacity data at conditions and connection ratio (98%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflow
°C kW kW kW kW °C °C kW kW l/s
r. keluarga dan dapur FXFQ100LUV1 22,0 / 55% 6,7 9,1 5,6 7,1 6,0 n/a n/a n/a 533
r. tidur tamu FXAQ32PVE 22,0 / 55% 2,5 2,9 1,7 2,1 6,0 n/a n/a n/a 142
r. prakterk FXAQ40PVE 22,0 / 55% 2,9 3,6 2,2 2,8 6,0 n/a n/a n/a 200
r. tamu FXFQ25LUV1 22,0 / 55% 2,3 2,3 1,8 2,1 6,0 n/a n/a n/a 217
Σ 14,4 n/a

Name Sound PS MCA Fuses WxHxD Wght


dBA A mm kg
r. keluarga dan dapur 32-43 230V 1ph 1,3 Factory Std 840x288x840 25
r. tidur tamu 31-38 220V 1ph 0,4 Factory Std 795x290x238 11
r. prakterk 34-39 220V 1ph 0,4 Factory Std 1050x290x238 14
r. tamu 27-30 230V 1ph 0,3 Factory Std 840x246x840 20

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 3
2.3.Outdoor 2 - RXMQ8AY1
Capacity data at conditions and connection ratio (100%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflow
°C kW kW kW kW °C °C kW kW l/s
r. keluarga FXFQ100LUV1 22,0 / 55% 6,1 9,1 5,0 7,1 6,0 n/a n/a n/a 533
r. pembantu FXMQ20PVE 22,0 / 55% 1,3 1,8 1,1 1,6 6,0 n/a n/a n/a 150
r. tidur anak FXMQ40PVE 22,0 / 55% 3,0 3,6 2,6 3,1 6,0 n/a n/a n/a 267
r. tidur utama FXMQ40PVE 22,0 / 55% 3,1 3,6 2,6 3,1 6,0 n/a n/a n/a 267
Σ 13,5 n/a

All outdoor and indoor unit capacity values are for a VRV system operating with an evaporating temperature
of 6,0°C.

Name Sound PS MCA Fuses WxHxD Wght


dBA A mm kg
r. keluarga 32-43 230V 1ph 1,3 Factory Std 840x288x840 25
r. pembantu 29-33 220V 1ph 0,6 Factory Std 550x300x700 25
r. tidur anak 35-39 220V 1ph 1,4 Factory Std 700x300x700 28
r. tidur utama 35-39 220V 1ph 1,4 Factory Std 700x300x700 28

Outdoor unit placed 3,0m below the indoor units.


The minimum connection ratio for this height difference is 50%.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 4
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / RH)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Run Amps Running Amps
St Curr Starting current
Fuses Fuses
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 5
3.2.Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC Piping
% °C kW kW °C kW kW m
Outdoor 1 RXQ8TY1 98 35,0 17,5 14,4 22,1
Outdoor 2 RXMQ8AY1 100 35,0 17,4 13,5 23,0

Name Model Refrigerant


Type Bse Refr Ex Refr
kg kg
Outdoor 1 RXQ8TY1 R410A 5,9 1,7
Outdoor 2 RXMQ8AY1 R410A 5,8 1,3

Name Model PS MCA MFA Run Amps St Curr Fuses WxHxD Wght
A A A A mm kg
Outdoor 1 RXQ8TY1 400V 3ph 16,1 20 Factory Std 930x1657x765 185
Outdoor 2 RXMQ8AY1 400V 3ph 18,5 25 Factory Std 940x1430x320 138

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 6
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

4.1. Piping Outdoor 1

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 7
4.2.Piping Outdoor 2

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 8
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

5.1. Wiring Outdoor 1


to centralized controller
P1,P2
Outdoor 1 r. tidur tamu BRC1E62
RXQ8TY1 FXAQ32PVE
OUT F1,F2 IN F1,F2 F1,F2 L,N 0,4A 1p h
L1,L2,L3,N 16 A 3ph
P1,P2
r. prakterk BRC1E62
FXAQ40PVE
F1,F2 L,N 0,4A 1p h

P1,P2
r. tamu BRC1E62
FXFQ25LUV1
F1,F2 L,N 0,3A 1p h

P1,P2
r. keluarga dan dapur BRC1E62
FXFQ100LUV1
F1,F2 L,N 1,3A 1p h

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 9
5.2.Wiring Outdoor 2
to centralized controller
P1,P2
Outdoor 2 r. tidur anak BRC1E62
RXMQ8AY1 FXMQ40PVE
OUT F1,F2 IN F1,F2 F1,F2 L,N 1,4A 1p h
L1,L2,L3,N 19 A 3ph
P1,P2
r. tidur utama BRC1E62
FXMQ40PVE
F1,F2 L,N 1,4A 1p h

P1,P2
r. pembantu BRC1E62
FXMQ20PVE
F1,F2 L,N 0,6A 1p h

P1,P2
r. keluarga BRC1E62
FXFQ100LUV1
F1,F2 L,N 1,3A 1p h

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 10
6. Device Options
6.1. Indoor Unit Options
Model Description Used by

BYCP125K-W1 Decoration panel r. keluarga dan dapur [FXFQ100LUV1] r. tamu [FXFQ25LUV1] r. keluarga [FXFQ100LUV1]

6.2. Centralized Controller Options


Model Description Used by
DCM601A52 iTM Plus Adaptor DCM601A51

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 11
7. Centralized Controllers
7.1. Concept
Global Controller Models Control Groups

iTouchManager Control group 1


# controllers 1 Outdoor 1 (4) # outdoors 1
# indoors 4

Control group 2
Outdoor 2 (4) # outdoors 1
# indoors 4

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 12
7.2.Control group 1
Outdoor 1 (4)
RXQ8TY1 OUT F1,F2

iTouchManager
DCM601A51

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 13
7.3.Control group 2
Outdoor 2 (4)
RXMQ8AY1 OUT F1,F2

iTM Plus Adaptor


DCM601A52

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 14
7.4.Dimensional Drawings

iTouchManager DCM601A51

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 15