Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.
1. Material List
Model Type Model Name Qty Description
Outdoor unit RXQ12TAYM 2 Cooling only VRV IV(TAYM)
RXQ16TAYM 1 Cooling only VRV IV(TAYM)
RXQ18TAYM 4 Cooling only VRV IV(TAYM)
Indoor unit FXMQ100PAVE 8 VRV M-PA - Unidad de conducto montada en el techo
FXMQ125PAVE 4 VRV M-PA - Unidad de conducto montada en el techo
FXMQ20PAVE 1 VRV M-PA - Unidad de conducto montada en el techo
FXMQ25PAVE 4 VRV M-PA - Unidad de conducto montada en el techo
FXMQ32PAVE 1 VRV M-PA - Unidad de conducto montada en el techo
FXMQ50PAVE 2 VRV M-PA - Unidad de conducto montada en el techo
FXMQ63PAVE 1 VRV M-PA - Unidad de conducto montada en el techo
FXMQ80PAVE 18 VRV M-PA - Unidad de conducto montada en el techo
Branch unit BHFP22P100 2 Outdoor unit multi connection piping kit
BHFP22P151 1 Outdoor unit multi connection piping kit
KHRP26A22T 14 Refnet branch piping kit
KHRP26A33T 6 Refnet branch piping kit
KHRP26A72T 11 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 5 Refnet branch piping kit
Option or add-on BRC1E63 39 Wired Remote Controller (Navigation Remote Controller)
Refrigerant R410A 56.3kg Extra refrigerant charge
Copper pipe Piping ¼" 37.6m Copper pipe
Piping ⅜" 224.1m Copper pipe
Piping ½" 71.3m Copper pipe
Piping ⅝" 236.1m Copper pipe
Piping ¾" 44.4m Copper pipe
Piping ⅞" 74.4m Copper pipe
Piping 1" 5.3m Copper pipe
Piping 1⅛" 52.1m Copper pipe
Piping 1¼" 16.7m Copper pipe
Piping 1⅜" 24.0m Copper pipe
Piping 1½" 9.0m Copper pipe
Piping 1⅝" 41.0m Copper pipe
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 1
2. Indoor Unit Details
2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / wet bulb temp.)
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tdis C Indoor unit discharge air temperature in cooling
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 2
2.2. VRV - 1 - RXQ52TAYM
Capacity data at conditions and connection ratio (104%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C cfm
FC-1-19 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-20 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-21 FXMQ100PAVE 24.0 / 17.0 n/a 36681 n/a 29477 Auto 10.8 1130
FC-1-22 FXMQ100PAVE 24.0 / 17.0 n/a 36681 n/a 29477 Auto 10.8 1130
FC-1-36 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-37 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-38 FXMQ125PAVE 24.0 / 17.0 n/a 46064 n/a 36571 Auto 10.6 1377
FC-1-39 FXMQ63PAVE 24.0 / 17.0 n/a 23373 n/a 18603 Auto 10.4 689
FC-1-15 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-16 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-17 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-18 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-33 FXMQ125PAVE 24.0 / 17.0 n/a 46064 n/a 36571 Auto 10.6 1377
FC-1-34 FXMQ100PAVE 24.0 / 17.0 n/a 36681 n/a 29477 Auto 10.8 1130
FC-1-35 FXMQ100PAVE 24.0 / 17.0 n/a 36681 n/a 29477 Auto 10.8 1130
The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.
SPEC IN
GCM
Page 3
The minimum connection ratio for this height difference is 50%.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 4
2.3. VRV - 2 - RXQ24TAYM
Capacity data at conditions and connection ratio (108%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C cfm
FC-1-01 FXMQ125PAVE 24.0 / 17.0 n/a 46064 n/a 36571 Auto 10.6 1377
FC-1-02 FXMQ125PAVE 24.0 / 17.0 n/a 46064 n/a 36571 Auto 10.6 1377
FC-1-03 FXMQ25PAVE 24.0 / 17.0 n/a 9213 n/a 7879 Auto 11.5 318
FC-1-04 FXMQ50PAVE 24.0 / 17.0 n/a 18426 n/a 15914 Auto 11.4 636
FC-1-23 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-24 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-25 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-26 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 5
2.4. VRV - 3 - RXQ36TAYM
Capacity data at conditions and connection ratio (117%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tdis C Airflow
°C BTU/h BTU/h BTU/h BTU/h °C °C cfm
FC-1-05 FXMQ20PAVE 24.0 / 17.0 n/a 7336 n/a 6739 Auto 13.3 318
FC-1-06 FXMQ32PAVE 24.0 / 17.0 n/a 11772 n/a 9213 Auto 10.1 335
FC-1-07 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-08 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-27 FXMQ100PAVE 24.0 / 17.0 n/a 36681 n/a 29477 Auto 10.8 1130
FC-1-28 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-29 FXMQ100PAVE 24.0 / 17.0 n/a 36681 n/a 29477 Auto 10.8 1130
FC-1-30 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-09 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-10 FXMQ80PAVE 24.0 / 17.0 n/a 29515 n/a 23691 Auto 10.5 883
FC-1-11 FXMQ25PAVE 24.0 / 17.0 n/a 9213 n/a 7879 Auto 11.5 318
FC-1-12 FXMQ25PAVE 24.0 / 17.0 n/a 9213 n/a 7879 Auto 11.5 318
FC-1-14 FXMQ50PAVE 24.0 / 17.0 n/a 18426 n/a 15914 Auto 11.4 636
FC-1-13 FXMQ25PAVE 24.0 / 17.0 n/a 9213 n/a 7879 Auto 11.5 318
FC-1-31 FXMQ100PAVE 24.0 / 17.0 n/a 36681 n/a 29477 Auto 10.8 1130
FC-1-32 FXMQ100PAVE 24.0 / 17.0 n/a 36681 n/a 29477 Auto 10.8 1130
The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.
SPEC IN
GCM
Page 6
The minimum connection ratio for this height difference is 50%.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 7
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
▼ Optimized selection: Smaller outdoor model selected than standard proposed model
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
EER EER at nominal conditions for standard efficiency series (nominal temperatures, 100% connection ratio and
without considering pipe length corrections)
Tmp H Outdoor conditions in heating (dry bulb temp. / wet bulb temp.)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
COP COP at nominal conditions for standard efficiency series (nominal temperatures, 100% connection ratio and
without considering pipe length corrections)
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 8
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC EER (*) Tmp H HC Rq HC COP (*)
% °C BTU/h BTU/h BTU/h/W °C BTU/h BTU/h W/W
VRV - 1 RXQ52TAYM 104 29.0 428466 498344 11.3
VRV - 2 RXQ24TAYM ▼ 108 29.0 229046 (-3.7%) 237827 13
VRV - 3 RXQ36TAYM ▼ 117 29.0 340598 (-12.4%) 388985 11.1
(*) The EER and COP values are calculated at nominal conditions: nominal temperatures, 100% connection ratio
and without considering pipe length corrections.
Sufficient distance should be respected between the modules according to the service & operation space rules as
mentioned in the databook.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 9
3.2.1. VRV - 1 - RXQ52TAYM
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 10
3.2.2. VRV - 2 - RXQ24TAYM
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 11
3.2.3. VRV - 3 - RXQ36TAYM
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 12
4. Piping Diagrams
Pipes marked with a short red stripe in the diagrams must be connected to the device with a reducing joint.
FC-1-20
FXMQ80PAVE
2.2m 2.2m
¾"×1¼" ⅜"×⅝"
KHRP26A72T
FC-1-21
FXMQ100PAVE
5.5m 1.5m
¾"×1¼" ⅜"×⅝"
KHRP26A72T
FC-1-22
FXMQ100PAVE
9.0m 4.5m
⅝"×1¼" ⅜"×⅝"
KHRP26A72T
FC-1-36
FXMQ80PAVE
5.3m 4.5m
½"×1" ⅜"×⅝"
KHRP26A33T
FC-1-37
FXMQ80PAVE
8.2m 1.5m
½"×⅞" ⅜"×⅝"
KHRP26A22T
FC-1-38
FXMQ125PAVE
8.8m
⅜"×⅝"
FC-1-39
FXMQ63PAVE
17.0m 2.2m 4.5m
¾"×1⅜" ½"×1⅛" ⅜"×⅝"
KHRP26A73T + KHRP26A72T
KHRP26M73TP
FC-1-18
FXMQ80PAVE
2.0m 4.0m
⅜"×⅞" ⅜"×⅝"
KHRP26A33T
FC-1-17
FXMQ80PAVE
1.7m 1.7m
⅜"×¾" ⅜"×⅝"
KHRP26A22T
FC-1-16
FXMQ80PAVE
10.5m
⅜"×⅝"
FC-1-15
FXMQ80PAVE
3.5m 8.0m
½"×1⅛" ⅜"×⅝"
KHRP26A72T
FC-1-35
FXMQ100PAVE
1.6m 6.5m
⅜"×⅞" ⅜"×⅝"
KHRP26A33T
FC-1-34
FXMQ100PAVE
7.8m
⅜"×⅝"
FC-1-33
FXMQ125PAVE
The actual length (40.7m) from the first branch to FC-1-38 exceeds 40.0m. The intermediate pipes are sized up
The actual length (48.0m) from the first branch to FC-1-39 exceeds 40.0m. The intermediate pipes are sized up
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 13
4.2. Piping VRV - 2
VRV - 2
RXQ24TAYM
RXQ12TAYM RXQ12TAYM
½"×1⅛" ½"×1⅛"
BHFP22P100
FC-1-02
FXMQ125PAVE
2.3m 4.7m
⅜"×⅝" ¼"×½"
KHRP26A22T
FC-1-03
FXMQ25PAVE
5.3m
¼"×½"
FC-1-04
FXMQ50PAVE
5.0m 1.7m 4.3m
½"×1⅛" ⅜"×¾" ⅜"×⅝"
KHRP26A72T KHRP26A22T
FC-1-24
FXMQ80PAVE
6.3m
⅜"×⅝"
FC-1-23
FXMQ80PAVE
2.6m 2.2m
⅜"×¾" ⅜"×⅝"
KHRP26A22T
FC-1-25
FXMQ80PAVE
9.2m
⅜"×⅝"
FC-1-26
FXMQ80PAVE
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 14
4.3. Piping VRV - 3
VRV - 3
RXQ36TAYM
RXQ18TAYM RXQ18TAYM
⅝"×1⅛" ⅝"×1⅛"
BHFP22P100
FC-1-27
FXMQ100PAVE
9.3m
⅜"×⅝"
FC-1-28
FXMQ80PAVE
2.8m 1.5m
⅜"×¾" ⅜"×⅝"
KHRP26A22T
FC-1-30
FXMQ80PAVE
12.5m
⅜"×⅝"
FC-1-29
FXMQ100PAVE
1.0m 3.0m
⅜"×⅝" ⅜"×⅝"
KHRP26A22T
FC-1-07
FXMQ80PAVE
0.7m 2.8m
⅜"×⅝" ¼"×½"
KHRP26A22T
FC-1-06
FXMQ32PAVE
2.5m
¼"×½"
FC-1-05
FXMQ20PAVE
19.5m 8.0m 1.6m 3.8m
⅝"×1⅛" ⅜"×⅞" ⅜"×¾" ⅜"×⅝"
KHRP26A72T KHRP26A33T KHRP26A22T
FC-1-10
FXMQ80PAVE
5.5m
⅜"×⅝"
FC-1-09
FXMQ80PAVE
0.6m 7.0m
⅜"×⅝" ¼"×½"
KHRP26A22T
FC-1-14
FXMQ50PAVE
1.8m 8.3m
⅜"×⅝" ¼"×½"
KHRP26A22T
FC-1-13
FXMQ25PAVE
1.2m 4.5m
⅜"×⅝" ¼"×½"
KHRP26A22T
FC-1-12
FXMQ25PAVE
2.5m
¼"×½"
FC-1-11
FXMQ25PAVE
8.0m 8.5m
⅜"×⅞" ⅜"×⅝"
KHRP26A33T
FC-1-31
FXMQ100PAVE
5.1m
⅜"×⅝"
FC-1-32
FXMQ100PAVE
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 15
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 16
5.2. Wiring VRV - 2
P1,P2
VRV - 2
FC-1-01 BRC1E63
RXQ24TAYM
FXMQ125PAVE
IN F1,F2 F1,F2
RXQ12TAYM L, N 3.4A 1ph
Q1,Q2 L1,L2,L3,N P1,P2
24A 3ph FC-1-02 BRC1E63
FXMQ125PAVE
RXQ12TAYM F1,F2
Q1,Q2 L1,L2,L3,N L, N 3.4A 1ph
24A 3ph P1,P2
FC-1-03 BRC1E63
FXMQ25PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
FC-1-04 BRC1E63
FXMQ50PAVE
F1,F2
L, N 1.6A 1ph
P1,P2
FC-1-24 BRC1E63
FXMQ80PAVE
F1,F2
L, N 2.3A 1ph
P1,P2
FC-1-23 BRC1E63
FXMQ80PAVE
F1,F2
L, N 2.3A 1ph
P1,P2
FC-1-25 BRC1E63
FXMQ80PAVE
F1,F2
L, N 2.3A 1ph
P1,P2
FC-1-26 BRC1E63
FXMQ80PAVE
F1,F2
L, N 2.3A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 17
5.3. Wiring VRV - 3
P1,P2
VRV - 3
FC-1-08 BRC1E63
RXQ36TAYM
FXMQ80PAVE
IN F1,F2 F1,F2
RXQ18TAYM L, N 2.3A 1ph
Q1,Q2 L1,L2,L3,N P1,P2
31A 3ph FC-1-27 BRC1E63
FXMQ100PAVE
RXQ18TAYM F1,F2
Q1,Q2 L1,L2,L3,N L, N 2.9A 1ph
31A 3ph P1,P2
FC-1-28 BRC1E63
FXMQ80PAVE
F1,F2
L, N 2.3A 1ph
P1,P2
FC-1-30 BRC1E63
FXMQ80PAVE
F1,F2
L, N 2.3A 1ph
P1,P2
FC-1-29 BRC1E63
FXMQ100PAVE
F1,F2
L, N 2.9A 1ph
P1,P2
FC-1-07 BRC1E63
FXMQ80PAVE
F1,F2
L, N 2.3A 1ph
P1,P2
FC-1-06 BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
FC-1-05 BRC1E63
FXMQ20PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
FC-1-10 BRC1E63
FXMQ80PAVE
F1,F2
L, N 2.3A 1ph
P1,P2
FC-1-09 BRC1E63
FXMQ80PAVE
F1,F2
L, N 2.3A 1ph
P1,P2
FC-1-14 BRC1E63
FXMQ50PAVE
F1,F2
L, N 1.6A 1ph
P1,P2
FC-1-13 BRC1E63
FXMQ25PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
FC-1-12 BRC1E63
FXMQ25PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
FC-1-11 BRC1E63
FXMQ25PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
FC-1-31 BRC1E63
FXMQ100PAVE
F1,F2
L, N 2.9A 1ph
P1,P2
FC-1-32 BRC1E63
FXMQ100PAVE
F1,F2
L, N 2.9A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 18
6. Device Options
6.1. Outdoor Unit Options
Model Description Used by
BHFP22P100 Outdoor unit multi connection piping kit VRV - 3 [RXQ36TAYM] VRV - 2 [RXQ24TAYM]
BHFP22P151 Outdoor unit multi connection piping kit VRV - 1 [RXQ52TAYM]
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
SPEC IN
GCM
Page 19