Professional Documents
Culture Documents
Amendment No: 14
As the information contained in this publication is subject to change from time to time, Endeavour
Energy gives no warranty that the information is correct or complete or is a definitive statement of
procedures. Endeavour Energy reserves the right to vary the content of this publication as and
when required. You should make independent inquiries to satisfy yourself as to correctness and
currency of the content. Endeavour Energy expressly disclaims all and any liability to any persons
whatsoever in respect of anything done or not done by any such person in reliance, whether in
whole or in part, on this document.
CONTENTS
1.0 PURPOSE............................................................................................................................ 4
2.0 SCOPE ................................................................................................................................ 4
3.0 REFERENCES ..................................................................................................................... 4
4.0 DEFINITIONS AND ABBREVIATIONS ................................................................................ 5
5.0 ACTIONS ............................................................................................................................. 8
5.1 Duty of care.................................................................................................................... 8
5.2 Safety standards............................................................................................................ 9
5.3 Standards ....................................................................................................................... 9
5.4 Deviations from an instruction ..................................................................................... 9
5.5 Maintenance minimum criteria overview ..................................................................... 9
5.5.1 General...................................................................................................................... 9
5.5.2 Environmental............................................................................................................ 9
5.5.3 Insulation coordination ............................................................................................... 9
5.5.4 Spares ..................................................................................................................... 10
5.5.5 Interchangeable components ................................................................................... 10
5.5.6 Quality of materials and workmanship ..................................................................... 10
5.5.7 Maintenance data entry and asset structures ........................................................... 10
5.5.8 Data validation update ............................................................................................. 10
5.6 Routine maintenance .................................................................................................. 10
5.6.1 General.................................................................................................................... 10
5.6.2 Inspections .............................................................................................................. 10
5.6.3 Maintenance work.................................................................................................... 11
5.6.4 Condition monitoring ................................................................................................ 11
5.6.5 Diagnostic testing using infra-red thermometry ........................................................ 11
5.7 Materials used in maintenance ................................................................................... 11
5.7.1 General.................................................................................................................... 11
5.7.2 Insulation oil and oil handling equipment ................................................................. 11
1.0 PURPOSE
To define the broad maintenance requirements for all equipment relating to transmission and zone
substations.
2.0 SCOPE
This instruction is to be read in conjunction with all relevant transmission and zone substation
Mains Maintenance Instructions and Substation Maintenance Instructions.
It covers routine, condition based, and fault and emergency maintenance for all transmission and
zone substation equipment, including substations, switching stations and field reclosers.
This and any referenced instructions are designed to cover all the general requirements that need
to be satisfied when maintaining transmission and zone substation assets.
The Regional Transmission Managers are responsible for preparing detailed workplace
instructions for the maintenance of transmission and zone substation equipment based on this
instruction. Workplace instructions shall be coordinated between all regions so that each type of
asset will be maintained in the same manner.
3.0 REFERENCES
Internal
Company Policy 4.0 - Environment
Company Policy 9.2.5 - Network Asset Design
Company Policy 9.9.1 - Network Asset Maintenance
Company Procedure GPE 0069 - Polychlorinated Biphenyl (PCB) Management
Company Procedure GSU 0006 - Disposal of Surplus Goods and Equipment
Company Procedure GSY 0067 – Personal Protective Equipment
Company Procedure GSY 1065 - Asbestos Management
Company Form FSY 0118 - Worksite Coordination/ Hazard and Risk Assessment
Environmental Management Standards
Equipment Technical Specification ETS0029 – Regenerated Mineral Insulating Oil
Protection Maintenance Instruction PMI 4120 – Maintenance of protection
Substation Maintenance Instruction SMI101 - Minimum requirements for maintenance of
distribution substation equipment
Substation Maintenance Instruction SMI 102 – Substation batteries
Substation Maintenance Instruction SMI 103 – Testing of in-service insulation oil
Substation Maintenance Instruction SMI 104 – Major substation earthing system test
Substation Maintenance Instruction SMI 106 – Zone and transmission substation
accommodation
Substation Maintenance Instruction SMI 108 – Miscellaneous substation equipment
Substation Maintenance Instruction SMI 109 – SCADA equipment
Substation Maintenance Instruction SMI 110 – Voltage regulating equipment
Substation Maintenance Instruction SMI 115 – Oil separators and bunds
Substation Maintenance Instruction SMI 117 – Essential spares
Substation Maintenance Instruction SMI 119 – Transmission and zone substation data entry,
asset structure and nameplate details
Substation Maintenance Instruction SMI 124 - Maintenance data entry and defect
prioritisation
Substation Maintenance Instruction SMI 150 – Isolating transformers
Substation Maintenance Instruction SMI 151 – On load tap changers and tap changer motor
boxes
External
ENA National Electricity Network Safety Code (Doc 01-2008)
Electricity Supply Act 1995 (as amended)
Work Health and Safety Act 2011(NSW)
AS 1767:1999 - Insulating liquids
AS 1851:2005 - Maintenance of fire protection systems and equipment
AS 1852 - International electrotechnical vocabulary
AS 2067 - Substations and high voltage installations exceeding 1 kV a.c.
AS 2467 - Maintenance of electrical switchgear
AS/NZS 3947 - Low voltage switchgear and controlgear
AS 60265.2:2005 - High-voltage switches - High-voltage switches for rated voltages of 52kV
and above
Definitions - general
For the purpose of this SMI, referenced SMIs and any associated project, the following general
definitions shall apply:
AIS air insulated switchgear
drawings Drawings and detailed drawings shall mean all drawings
indicated by a drawing number and any drawings referenced to
by that drawing or any drawing referenced to by a referenced
drawing
Ellipse Endeavour Energy asset database
EMS Environmental Management Standard
exercise Trip and close the circuit breaker electrically
GIS Gas Insulated Switchgear
HAZMAT Hazardous material
MSDS Material Safety Data Sheets
A disconnector is capable of opening and closing a circuit when negligible current is broken or
made. Negligible current implies currents up to 0.5A, such as the capacitance currents of
bushings, busbars, connections, very short lengths of cables, and currents of voltage transformers
or dividers.
A disconnector is capable of opening and closing a circuit when no significant change occurs in the
voltage across the terminals of each of the poles of the isolator. No significant change of voltage
refers to such applications as the bypassing of circuit breakers.
A disconnector is capable of carrying currents under normal circuit conditions and carrying, for a
specified time, currents under abnormal conditions, such as those of short-circuit.
Fuse (refer AS 1852 [441] - 1985)
A switching device that, by the fusion of one or more of its specially designed and proportioned
components, opens the circuit in which it is inserted and breaks the current when it exceeds a
given value for a sufficient time.
Note: The fuse comprises all the parts that form the complete switching device.
A fuse element is that part of a fuse designed to melt when the fuse operates.
A fuse-link is that part of a fuse, including the fuse element(s), which requires replacement by a
new fuse-link after the fuse has operated and before the fuse is put back into service.
A current-limiting fuse is a fuse that, during and by its operation at its rated breaking capacity, limits
the current to a value substantially lower than the peak value of the prospective current.
An expulsion fuse is a fuse in which the arc is extinguished by expulsion of gases produced by the
arc (an expulsion fuse does not exhibit significant current limiting features).
Fuse switch (refer AS 1852 [441] - 1985)
A switch in which a fuse link, or fuse carrier with fuse link, forms the moving contact.
Switch fuse combination (refer AS 1852 [441] - 1985)
A combination of a three-pole switch with three (3) fuses provided with strikers, the operation of
any striker causing all three (3) poles of the switch to open automatically.
Note: Also known as a fuse-switch combination.
Switch-fuse (refer AS 1852 [441] - 1985)
A switch in which one or more poles have a fuse in series in a composite unit.
Definitions - maintenance of electrical switchgear
Maintenance (refer AS 2467)
Routine maintenance is organised and carried out in accordance with a predetermined policy or
plan to prevent breakdown or reduce the likelihood of an item failing to meet an acceptable
condition.
Non-routine maintenance is unplanned maintenance that is not the result of a breakdown.
Inspection (refer AS 2467)
Maintenance action comprising a careful scrutiny of an item, carried out without dismantling and
using all the senses as required, to detect anything that causes the item to fail to meet an
acceptable condition.
Note: An inspection may be followed by an operational check.
Overhaul (refer AS 2467)
Maintenance of an item, including examination and replacement or rebuilding as required.
Overhaul can be further categorised as follows:
5.0 ACTIONS
containing asbestos. In transformers, gaskets may be made out of asbestos material, while arcing
chutes in circuit breakers may also contain asbestos.
If any equipment is suspected of containing asbestos, Endeavour Energy's procedure GSY 1065
must be followed to manage the associated risks.
5.2 Safety standards
All employees shall abide by Endeavour Energy’s Safety Rules and the ENA National Electricity
Network Safety Code (Doc 01-2008) throughout the duration of the work to be carried out as a
result of this instruction.
5.3 Standards
All maintenance, design, construction, testing and commissioning shall be carried out in
accordance with Endeavour Energy’s substation instructions, protection instructions, mains
instructions, Environmental Management Standards, ESAA industry guidelines, manufacturers’
and suppliers’ literature and recommendations, and the Australian Standards, as appropriate.
Australian Standards are to be adopted in general. British, IEC or other international standards
may be used if such standards are no less exacting than the corresponding Australian Standard. If
other standards are to be used, a copy of the relevant standard shall be forwarded to the Manager
Asset Standards & Design and written approval given before it may be used.
All employees shall have the appropriate workplace instructions and contingency plans in place to
cover related safety, environmental and operational issues as outlined in Endeavour Energy’s
Company Procedures (Safety - Electrical) and Company Procedures (Safety - General), and in
accordance with the relevant Environmental Management Standards.
5.4 Deviations from an instruction
In general, the maintenance work scope must be according to the manufacturer’s instructions,
while the maintenance frequencies must be according to this maintenance instruction. Written
approval must be obtained from the Manager Asset Standards & Design to deviate from these
requirements. Any request for deviations must be fully documented and contain substantiating
proof of performance to the recommended Australian Standard or other standard, as nominated in
the instruction.
5.5 Maintenance minimum criteria overview
Each item of equipment shall be specified, chosen, designed, installed, tested, maintained and
commissioned to meet the following minimum requirements.
5.5.1 General
For general requirements, such as electrical, mechanical and technological; the contractor shall be
fully responsible to check that all items of plant and equipment are supplied to be compatible with
each other and the installation is complete in all respects, including finishing, painting, labeling and
the like.
5.5.2 Environmental
All equipment shall be suitable for the environment in which it will need to operate. Kiosks,
cubicles and similar enclosures shall be adequately ventilated to restrict condensation and, where
necessary, anti-condensation heaters shall be fitted with thermostatic control. Contactors, relays,
steelwork, equipment and the like, shall be protected against corrosion by, for example, suitable
galvanising, plating, or painting.
5.5.3 Insulation coordination
Plant and equipment shall be designed and installed so that insulation coordination is provided
between different items of plant, such as transformers, surge arresters, circuit breakers and
transmission lines, and also between different components of items within a particular item of
equipment.
5.5.4 Spares
Spare parts used in equipment must be from the original equipment manufacturer or under their
license, as locally fabricated parts may de-rate the switchgear with respect to fault current
withstand capability, lightning impulse withstand voltages, and current ratings. Accordingly, locally
fabricated spares may not be used unless they have been type-tested or otherwise proven to be fit
for purpose, and their use approved by the Manager Asset Standards & Design.
5.5.5 Interchangeable components
Components of similar types of switchgear shall be interchangeable as far as possible, without the
need to modify designs and settings.
5.5.6 Quality of materials and workmanship
All materials used shall be new and of a quality and class most suitable for working under the
conditions specified without distortion, deterioration or setting up undue stresses on other
equipment.
All work shall be neat and carried out to trade standards and in a professional manner.
5.5.7 Maintenance data entry and asset structures
All details for maintenance activities, defects, prioritisation and the like, shall be entered into Ellipse
within one week of the work being completed. This data is to be entered at the lowest possible
level of asset (refer to SMI 119 and SMI 124 for maintenance data entry requirements.
Results of the review of hazardous materials shall be provided to the Asset Owner (Transmission
Manager) within one week of the work being completed. The Transmission Manager shall arrange
the update of HAZMAT Register.
5.5.8 Data validation update
The work activity is to include the entering of any general data that has not been included in
Ellipse, for the particular item on which the work is being performed. If other data not listed in the
instructions is considered necessary, the Manager Asset Standards & Design should be informed
and the data collected. The parent/child hierarchy is shown in the SMI schedules to allow the
correct input of data (refer to SMI 119 - Transmission and zone substation data entry, asset
structure and details, for details of the Ellipse hierarchy).
Care is to be taken to check that equipment used for oil handling is clean and not infected with
PCB. Reference shall be made to Endeavour Energy’s PCB Management Plan and Company
Procedure GPE 0069 - Polychlorinated Biphenyl (PCB) Management.
Maint. interval
Cap. Switch
Fault cycles
Op. cycles
Reference
Latitude
(years)
cycles
Routine
Item Brand Type
maintenance
Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
B18
Westinghouse Minor o/haul 5.5^ 0.5 - - -
Major o/haul
11 1 - 5 -
Major o/haul 11 1 - 7 -
Inspection 0.5 - - - -
Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
South Wales
D series
Electric
Minor o/haul 5.5^ 0.5 - - -
Major o/haul 11 1 - 6 -
Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
Hawker
All Thermovision # 1 - - - -
Siddeley
Minor o/haul 5.5^ 0.5 - - -
Major o/haul 11 1 - 4 -
Inspection 0.5 - - - -
Maint. interval
Cap. Switch
Fault cycles
Op. cycles
Reference
Latitude
(years)
cycles
Routine
Item Brand Type
maintenance
Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
SMI 200
6 0.5 - - -
maintenance
Major
12 0.5 500 6 300
maintenance
Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
36kV Minor
AEI LGIC44 6 0.5 - - -
maintenance
Bulk oil Major
12 0.5 500 6 -
maintenance
Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
Reyrolle L800
Major
9 0.5 500 6 -
maintenance
Inspection 0.5 - - - -
All other Exercise ** 1 - - - -
SMI 200
brands and --- Minor o/haul 4.5 - - - -
types
Major o/haul 9 - 500 6 300
Inspection 0.5 - - - -
EIB All types Minor o/haul 4.5 - - - -
12/24kV Major o/haul 9 - - 4 -
Inspection 0.5 - - - -
Min. oil All other
brands and --- Minor o/haul 4.5 - - - -
types Major o/haul 9 - - 7 -
Inspection 0.5 0.5 - - -
Exercise ** 1 0.25 - - -
Magrini
MG (indoor) Minor
Galileo 6 0.5 - - -
maintenance
Major
12 0.5 500 7 -
maintenance
Inspection 0.5 0.5 - - -
Exercise ** 1 0.25 - - -
SMI 200
36kV
Magrini Minor
MGE (outdoor) 6 0.5 - - -
Galileo maintenance
Min. oil
Major
12 0.5 500 7 -
maintenance
Inspection 0.5 - - - -
Maint. interval
Cap. Switch
Fault cycles
Op. cycles
Reference
Latitude
(years)
cycles
Routine
Item Brand Type
maintenance
Inspection 0.5 - - - -
SMI 200
72.5kV
Sprecher & Exercise ** 1 0.25 - - -
HPF
Min. oil Schuh Minor o/haul 6 - - - -
Major o/haul 12 - 500 7 300
Inspection 0.5 - - - -
All other Exercise ** 1 - - - -
brands and ---
types Minor o/haul 4.5 - - - -
Major o/haul 9 - 500 7 300
Inspection 0.5 0.5 - - -
Exercise ** 1 0.25 - - -
HLR Minor
6 0.5 - - -
maintenance
Major
ASEA 12 0.5 500 7 -
maintenance
SMI 200
Inspection 0.5 - - - -
HLD145/1200A Exercise ** 1 - - - -
HPL13L6352B
145kV &C Minor o/haul 4.5 - - - -
Major o/haul 9 - 500 7 300
Min. oil Inspection 0.5 - - - -
All other Exercise ** 1 - - - -
brands and ---
types Minor o/haul 4.5 - - - -
Major o/haul 9 - 800 7 -
^Outdoor bulk oil circuit breaker maintenance cycle can be changed to 4.5 years to align with bay maintenance outages.
* Westinghouse oil circuit breakers:
a) Breakers that perform capacitor-switching operations are to be maintained six monthly or at 300 capacitor switching
operations, whichever occurs first.
b) The dielectric dissipation factor of circuit breaker bushings to be tested as set out in Annexure 2 in SMI 200.
** Exercise only to be carried out if the circuit breaker has not been operated within the last year.
Referen
interval
cycles *
(years)
(years)
switch
cycles
Maint.
Cap.
Fault
Routine
ce
@
maintenance
Inspection 0.5 - - - -
Minor o/haul 12 0.5 - - - SMI
ABB HB
200
12/24kV Major o/haul - - - * -
SF6 Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
ABB GK1M
Minor o/haul 12 0.5 - - -
Major o/haul - - - * -
Op.cycle
Latitude
Referen
interval
cycles *
(years)
(years)
switch
cycles
Maint.
Cap.
Fault
Routine
ce
@
Item Brand Type
s
maintenance
Inspection 0.5 - - - -
Schneider/
SM6 Minor o/haul 12 0.5 - - -
Merlin Gerin
Major o/haul - - - * -
Inspection 0.5 - - - -
Yorkshire YSF6 Minor o/haul 12 0.5 - - -
Major o/haul - - - * -
Inspection 0.5 - - - -
All other
brand and Minor o/haul 12 0.5 - - -
types Major o/haul - - - * -
Inspection 0.5 - - - -
Magrini Exercise ** 1 0.25 - - -
Galileo/ 36GI-E25
Merlin Gerin Minor o/haul 12 0.5 - - -
Major o/haul - - 2000 * 2500
Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
EDF Minor o/haul 12 0.5 - - -
2000/
36kV Major o/haul - - 10,000 * 4000
ABB SMI
^ 200
SF6 Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
PASS M00
Minor o/haul 12 0.5 - - -
Major o/haul - - 3,000 * -
Inspection 0.5 - - -
All other Exercise ** 1 - - -
brands and ---
types Minor o/haul 4.5 - - -
Major o/haul 9 5000 100 2500
Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
EDF Minor o/haul 12 0.5 - - -
2000/
Major o/haul - - 10,000 * 4000
ABB ^
Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
PASS M00
72.5kV Minor o/haul 12 0.5 - - - SMI
Major o/haul - - 3,000 * - 200
SF6
Inspection 0.5 - - - -
Areva / Exercise ** 1 0.25 - - -
DT1
Alsthom Minor o/haul 12 0.5 - - -
Major o/haul - - 2000 *
Inspection 0.5 - - - -
GEC / Exercise ** 1 0.25 - - -
Sprecher & HGF
Schuh Minor o/haul 12 0.5 - - -
Major o/haul - - 2500 *
Op.cycle
Latitude
Referen
interval
cycles *
(years)
(years)
switch
cycles
Maint.
Cap.
Fault
Routine
ce
@
Item Brand Type
s
maintenance
Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
Siemens 3AP1DT
Minor o/haul 12 0.5 - - -
Major o/haul - - 6000 *
Inspection 0.5 - - -
All other Exercise ** 1 - - -
brands and ---
types Minor o/haul 4.5 - - -
Major o/haul 9 5000 100 2500
HPL145/2501 Inspection 0.5 - - -
HPL72.5- Exercise ** 1 - - -
170/25A1
ELF-1AR Minor o/haul 4.5 - - -
ASEA/Brown HPLBL61002A Major o/haul 9 5000 100 2500
Boveri Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
PASS M00
Minor o/haul 12 0.5 - - -
Major o/haul - - 3,000 * -
Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
Areva DT1
Minor o/haul 12 0.5 - - -
Major o/haul - - 2000 * 2500
Inspection 0.5 - - - -
145kV GEC / Exercise ** 1 0.25 - - -
Sprecher & HGF SMI
Schuh Minor o/haul 12 0.5 - - - 200
SF6
Major o/haul - - 2500 *
Inspection 0.5 - - - -
3AP1DT/ Exercise ** 1 - - - -
Siemens
3AP1FG Minor o/haul 12 0.5 - - -
Major o/haul - - 6000 * -
Inspection 0.5 - - - -
Hyosung HCSP-144B Exercise ** 1 - - - -
Minor o/haul 12 0.5 - - -
Major o/haul - - 2000 * -
Inspection 0.5 - - -
All other Exercise ** 1 - - -
brands and ---
types Minor o/haul 4.5 - - -
Major o/haul 9 2500 25 -
** Exercise only to be carried out if the circuit breaker has not been operated within the last year.
cycles *
Op.cycl
interval
(years)
(years)
switch
cycles
Maint.
Fault
Cap.
Routine
es
@
Inspection 0.5 - - - -
12/24kV ABB /Calor Exercise ** 1 0.25 - - - SMI
VD4
Vacuum Emag Minor o/haul 12 0.5 - - - 200
Major o/haul - - - * -
Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
GEC SBV
Minor o/haul 12 0.5 - - -
Major o/haul - 0.5 - * -
Inspection 0.5 - - - -
Reyrolle LMVP Minor o/haul 12 0.5 - - -
Major o/haul - - - * -
Inspection 0.5 - - - -
Major o/haul - - - * -
Inspection 0.5 - - - -
PD(TEV) test 1 0.25 - - -
Siemens 3AF
Minor o/haul 12 0.5 - - - SMI
Major o/haul - - - * - 200
Inspection 0.5 - - - -
Siemens 3AH Minor o/haul 12 0.5 - - -
Major o/haul - - - * -
Inspection 0.5 - - - -
Tamco VW2 Minor o/haul 12 0.5 - - -
Major o/haul - - - * -
Inspection 0.5 - - - -
All other
brand and Minor o/haul 12 0.5 - - -
types
Major o/haul - - - * -
Inspection 0.5 - - - -
Alstom / Exercise ** 1 0.25 - - -
OX36
Areva / GEC Minor o/haul 12 0.5 1,000 100 -
#
Major o/haul - - 5,000 - -
Inspection 0.5 - - - -
Hawker Exercise ** 1 0.25 - - -
Horizon
Siddeley Minor o/haul 12 0.5 - - -
Major o/haul - - 10,000 * 2500
36kV SMI
Inspection 0.5 - - - - 200
Vacuum
Exercise ** 1 - - - -
Sumitomo /
NVBOA Minor o/haul 12 0.5 - - -
Meidensha
Major o/haul - - 10,000 * -
Inspection 0.5 - - - -
Exercise ** 1 0.25 - - -
Minor o/haul 12 0.5 - - -
Schneider VOX
10,000
Major o/haul - - - -
#
Note: SF6 and vacuum circuit breakers that perform capacitor switching operations are to have operational checks, as
defined in SMI 200, performed 12 monthly.
# Major overhaul to be carried out either after specified ops cycle or when contact wear indicator shows primary contact
wear.
^ 2000 for capacitor banks without inrush reactor, 4000 for capacitor banks with inrush reactor.
* Refer to Annexure 1 for details on the fault cycles of these circuit breakers.
@ Op cycle is the number of CB operations at load current.
** Exercise only to be carried out if the circuit breaker has not been operated within the last year.
5.8.2 HV switchgear
Table 4: HV Switchgear
Maintenance Latitude
Voltage Routine
Item Brand Type interval (years) Ref.
kV maintenance
(years)
Inspection 0.5 -
12 Holec MD4 PD(TEV) test and SMI
Indoor 1 0.25
Switch and switch thermovision 212
fuse units epoxy Major overhaul 6 0.5
encapsulated Inspection 0.5 -
SMI
12 ABB RGB 12 Indoor PD(TEV) test 1 0.25
212
Major overhaul 6 0.5
Inspection 0.5 -
SMI
12 Holec SVS Indoor PD(TEV) test 1 0.25
212
Switch and switch Major overhaul 6 0.5
fuse combination Inspection 0.5 -
sheet steel SMI
12 ABB Safelink Indoor PD(TEV) test 1 0.25
enclosed 212
Major overhaul 12 1
Inspection 0.5 -
Merlin Gerin SMI
12/24 Indoor PD(TEV) test 1 0.25
SM6 212
Major overhaul 12 1
Areva/ Inspection 0.5 -
SMI
12 Schneider Indoor PD(TEV) test 1 0.25
212
Fluokit M24 Major overhaul 12 1
Other Inspection 0.5 -
(SF6 or PD(TEV) test 1 0.25 SMI
12/24 Indoor
vacuum 212
Major overhaul 12 1
interruption)
Inspection 0.5 -
Switch and switch
Indoor/ PD(TEV) test and SMI
fuse combinations 12 --- 1 0.25
outdoor thermovision 212
oil
Major overhaul 6 0.5
Inspection 0.5 -
Fault throwers 145 --- Outdoor Minor 4.5 - *
Major overhaul 9 -
Indoor/ Inspection 0.5 - SMI
Links 12 to 36 ---
outdoor Major overhaul 9 - 204
Indoor/ Inspection 0.5 - SMI
Air break switches 12 to 145 ---
outdoor Major overhaul 9 - 204
Indoor/ Inspection 0.5 - SMI
Isolators # 12 to 145 ---
outdoor Major overhaul 12^ 0.5 204
Inspection 0.5 -
12/24 --- Indoor *
Major overhaul 9 0.5
Inspection 0.5 -
Switch earthing # 36 to 145 --- Indoor
Major overhaul 12^ 0.5 SMI
Inspection 0.5 - 204
12 to 145 --- Outdoor
Major overhaul 12^ 0.5
*Maintenance references same as similar switchgear
^Recommended period for major overhaul, however the period can be reduced or extended as required to coincide with
work on other equipment.
# Excludes isolators and earthing switches associated with 36-145kV air and gas insulated switchgear. Maintenance
requirements for equipment associated with 36-145 kV air and gas insulated switchboards can be found in 5.8.3 and
5.8.4. Isolators and earthing switches within 12/24kV capacitor banks (indoor and enclosed) shall be maintained with the
capacitor bank maintenance (refer to 5.8.8 and Substation Maintenance SMI 209 - Capacitors).
Table 5: Switchboards
Fault cycle
Reference
Op.cycles
Latitude
interval
(years)
(years)
Maint.
Routine
Voltage Brand Item
maintenance
Inspection 0.5 - - -
Overall SMI
Merlin Installation Clean and
1 0.25 - - 210
36kV Gerin vacuum
and
FG4/F400 Minor o/haul 12 0.5 - -
Circuit breaker manual
Major o/haul - - 10,000 *
Overall
Inspection 0.5 - - -
Installation
Exercise ** 1 0.25 - -
WSA SMI
Alstom / Minor o/haul 12 0.5 10,000 -
36kV 210
Areva WS Circuit breaker
Major o/haul - - - * and
manual
Disconnector / Minor o/haul - - 1000 -
earth switch Major o/haul - - 2,000 -
Overall
Inspection 0.5 - - -
Installation
Exercise ** 1 0.25 - - SMI
Minor o/haul 12 0.5 2,000 - 210
GV30 and
TAMCO wipe
manual
36kV Circuit breaker gap
GV3 Major o/haul - 10,000 *
reduces
to 1mm
Minor o/haul 12 0.5 - - SMI
Disconnector / 210
earth switch Major o/haul - - 2,000 - and
manual
Overall
Inspection 0.5 - - -
Installation
Exercise ** 1 0.25 - - SMI
ABB Circuit breaker Minor o/haul 12 0.5 - - 210
72.5kV
ELG/ENK and
Major o/haul - - 1,500 * manual
Disconnecting Minor o/haul 12 - - -
switch Major o/haul - - 2,500 -
*Refer to Annexure 1 for details on the fault cycles of these circuit breakers.
** Exercise only to be carried out if the circuit breaker has not been operated within the last year.
Reference
Op.cycles
Latitude
interval
(years)
(years)
Maint.
cycles
Fault
Routine
Brand Item
maintenance
*Refer to Annexure 1 – Fault cycles for vacuum/SF6 CBs for details on the fault cycles of these circuit breakers.
5.8.5 Transformers
Table 7: Transformers
*The last oil test during warranty period shall be carried out six (6) months before warranty expiry.
# Excludes voltage transformers associated with 36-145kV indoor air and gas insulated switchgear. Maintenance
requirements (if any) for these voltage transformers are included separately in the specific switchgear maintenance
schedules (refer to 5.8.3 and 5.8.4).
^Recommended period for major overhaul, however the period can be reduced or extended as required to coincide with
work on other equipment.
@ Padmount auxiliary transformers are only to be inspected and do not require a major overhaul.
Latitude
Voltage Routine Maintenance Operation
Item Type (years) Ref.
kV maintenance interval (years) cycles
Inspection 0.5 - -
Major overhaul 7 1 25000
B, BC Replace energy
---
and C accumulator spring (in
- - 50000
conjunction with major
overhaul)
BC and #
--- Oil drainage 1 - -
C
Reinhausen Inspection 0.5 - -
D ---
Major overhaul 7 1 50000
Inspection 0.5 - -
F ---
Major overhaul 7 1 35000
Inspection 0.5 - -
M ---
Major overhaul 7 1 80000
Inspection 0.5 - -
V ---
Major overhaul 7 1 70000
Inspection 0.5 - -
ACEC - ---
Major overhaul 7 - 20000
Associated Inspection 0.5 - - SMI
Tap 151
All ---
Changers Major overhaul 7 1 60000 *
Ltd
Inspection 0.5 - -
Ferranti - ---
Major overhaul 7 1 20000
English Inspection 0.5 - -
- ---
Electric Major overhaul 7 1 30000
Inspection 0.5 - -
UCG
Major overhaul 7 1 100,000
Inspection 0.5 - -
ABB UCL
Major overhaul 7 1 100,000
Inspection 0.5 - -
UZF
Major overhaul 7 1 100,000
F317 Inspection 0.5 - -
Fuller and ---
F315 Major overhaul 7 1 50,000
All other Inspection 0.5 - -
brands and - ---
types Major overhaul 7 1 60000 *
* Number of operations can be extended or reduced to coincide with manufacturer’s recommendations for a specific
type.
# Drain the oil in the tap changer until no carbon contaminated oil emerges. Do not drain all the oil in the tap changer, as
it will cause the damage of the tap changer.
monthly
monthly
Monthly
Three-
Yearly
yearly
Five -
Item
Six-
Pump sets (electric motor driven)
Fire detection
AS 1851
Fire alarm monitoring systems
Table 1.11(A)
Gaseous fire extinguishing systems
Fire blankets
Passive fire and smoke systems (fire doors and fire stopping)
Maintenance
Voltage Routine
Item Location interval Ref.
kV maintenance
(years)
Inspection 0.5
Bushings/wall bushing 12 to 145 Indoor/outdoor
Minor overhaul 5*
Inspection 0.5
Insulators 12 to 145 Indoor/outdoor
Minor overhaul 5*
Inspection 0.5
Surge arrestors 12 to 145 Indoor/outdoor Minor overhaul ^
Replace 30
Cable boxes 12 to 145 Indoor/outdoor Inspection 0.5
Inspection 0.5 SMI
108
Control panels - Indoor/outdoor Minor overhaul 5
Diagnostic test 1
Inspection 0.5
Busbars/conductors/connections 12 to 145 Indoor/outdoor
Diagnostic test 1
Panel lamps - Indoor/outdoor Inspection 0.5
Inspection 0.5
Lightning masts - Outdoor
Minor overhaul 5
Voltage chart recorder - label units out of
- - Inspection 0.5
service and remove fuses
ABB ABBACUS Minor overhaul 1
11kV capacitors Major overhaul 9*
AmpControl Minor overhaul 1 SMI
Capacitors 12 to 145
11kV capacitors Major overhaul 9* 209
Other Inspections 0.5
capacitors Major overhaul 9*
SMI
Auxiliary board - - Inspection 0.5
250
Inspection 0.5 SMI
Compressor - -
Minor overhaul 9* 200
SMI
RCD Testing #
108
* Recommended period for minor/major overhaul, however period can be extended as required to coincide with work on
other equipment.
^ Maintenance shall align with major equipment in the bay and shall only be carried out if extended isolation for surge
arrestor maintenance does not result in extended outage of network.
# Testing of RCDs shall be carried out in accordance with the table below:
Table 11: RCD Testing
* Where V/R is incorporated in the SCADA software, the minor overhaul is to be done as part of the SCADA routine
maintenance.
Maintenance interval
Item Routine maintenance Ref.
(years)
Inspection 0.5
Earth grid SMI
Test 12
104
Inspection 0.5
Portable earthing equipment
Test 3
Inspection 0.5 SMI
Indoor CB earthing trucks
Test and maintain 3 200
Note: The following is only applicable to batteries in zone and transmission substations. Refer to SMI101 for
maintenance requirements for batteries associated with distribution assets.
Maint.
Item Routine maintenance interval Ref.
(years)
5.8.13 Accommodation
Table 16: Accommodation
Maintenance interval
Item Season Routine maintenance Ref.
(years)
- Inspection 0.5
Building/yard
- Minor overhaul 1
October to March Minor overhaul 2 weeks
Lawns and gardens
April to September Minor overhaul 4 weeks
Grass mowing - Minor overhaul Keep height to 100mm
Back flow prevention - Inspection 0.5
device - Minor Overhaul 1
Roof access system - Inspection 1 SMI
Spill kit - Inspection 0.5 106
Lighting tower winding
- Minor Overhaul 1
mechanism
Building Interior
- Minor Overhaul 12 weeks*
Hygiene
Gross pollutant traps / - Inspection 1
stormwater drains / on-
- Minor overhaul As required
site detention systems
Maintenance interval
Item Season Routine maintenance Ref.
(years)
- Inspection 0.5
In-ground oil/water
separator - Minor overhaul 1
- Major overhaul 3 SMI
- Inspection 0.5 115
Coalescing plate As required or maximum of
- Minor overhaul
oil/water separator six (6) month interval
- Major overhaul 1
* Interior cleaning may be performed at 8 weeks for more frequently visited sites as required
5.8.14 Reclosers
Table 17: Reclosers
General Manager Asset Management has the authority and responsibility for approving this
instruction.
Manager Asset Standards & Design has the authority and responsibility for making
recommendations to the General Manager Asset Management in respect to this instruction.
Network Maintenance Manager has the authority and responsibility for keeping the content of this
instruction up to date.
Network Substations Manager has the authority and responsibility for interpreting test results in
conjunction with the Network Maintenance Manager.
The Regional Transmission Managers have the authority and responsibility for:
confirming that Endeavour Energy employees or contractors performing the work have
appropriate qualifications;
meeting the requirements of this instruction;
working in accordance with local and statutory requirements;
maintaining a high level of public safety;
confirming that employees are conversant with, and work in accordance with, the Electrical
Safety Rules; and
analysing test results to identify potential problems and take appropriate action.
The fault cycle is dependent on individual characteristics of the circuit breaker type and the fault current that is
interrupted. The fault cycle for each of these circuit breakers has been (conservatively) determined by using the
maximum fault level at the substation where the type of circuit breaker is located. The table below provides the formula
that can be used to calculate the fault cycle for each of these circuit breaker types.
Note: The fault cycle for a circuit breaker may be reviewed if the fault level for a substation significantly changes (for
example, due to changes in network configuration). The Network Maintenance Manager may be consulted to obtain the
fault cycle for new circuit breakers installed.
The fault cycle assigned to an after-fault maintenance MST shall be rounded to values as shown in the table below. This
is to provide easier interpretation when running reports.
As detailed in SMI 200, when the number of fault operations for (any pole/phase of) a circuit breaker has been reached,
certain checks must be made prior to carrying out major maintenance. These checks (which may include reviewing the
validity of recorded faults and taking dynamic resistance measurements) are necessary to determine if the circuit breaker
actually requires major intrusive maintenance.