ﺣﺴﺎﺑﺎت اﻟﺘﻜﻴﻴﻒ
DESCRIPTION 1. pages
PAC -01 08 - 23
-Air System Output Data
-Air System Input Data
-Space Description
PAC -02 24 - 39
-Air System Output Data
-Air System Input Data
-Space Description
FCU-01 40 – 46
-Air System Output Data
-Air System Input Data
-Space Description 3.
FCU -02 47 – 53
-Air System Output Data
-Air System Input Data
-Space Description 3.
FCU -03 54 - 60
-Air System Output Data
-Air System Input Data
-Space Description
FCU -04 61 - 67
-Air System Output Data
-Air System Input Data
-Space Description
FCU -05 68 - 74
-Air System Output Data
-Air System Input Data
-Space Description
FCU -06 75 - 83
-Air System Output Data
-Air System Input Data
-Space Description
FCU -07 84 - 90
-Air System Output Data
-Air System Input Data
-Space Description
FCU -08 91 - 97
-Air System Output Data
-Air System Input Data
-Space Description
FCU -09 98 - 104
-Air System Output Data
-Air System Input Data
-Space Description
1 of 207
Design Weather Parameters & MSHGs
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:46PM
Design Parameters:
2 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Schedule Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:47PM
EQUPMENT (Fractional)
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4
LIGHT (Fractional)
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4
3 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
Schedule Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:47PM
PEOPLE (Fractional)
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4
Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O
2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O
3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O
4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O
O = Occupied; U = Unoccupied
Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4
4 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Wall Constructions
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:47PM
EXTERNAL WALL
Wall Details
Outside Surface Color Dark
Absorptivity 0.900
Overall U-Value 0.473 W/(m²-°K)
Partition
Wall Details
Outside Surface Color Dark
Absorptivity 0.900
Overall U-Value 1.829 W/(m²-°K)
5 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Roof Constructions
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:47PM
ROOF
Roof Details
Outside Surface Color Dark
Absorptivity 0.900
Overall U-Value 0.510 W/(m²-°K)
6 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Window Constructions
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:47PM
CW
Window Details:
Detailed Input No
Height 1.00 m
Width 1.00 m
Overall U-Value 2.500 W/(m²-°K)
Overall Shade Coefficient 0.400
SKYLIGHT
Window Details:
Detailed Input No
Height 0.90 m
Width 0.90 m
Overall U-Value 0.910 W/(m²-°K)
Overall Shade Coefficient 0.320
WIND (1)
Window Details:
Detailed Input No
Height 2.50 m
Width 0.50 m
Overall U-Value 2.500 W/(m²-°K)
Overall Shade Coefficient 0.400
WIND (2)
Window Details:
Detailed Input No
Height 2.00 m
Width 0.50 m
Overall U-Value 2.500 W/(m²-°K)
Overall Shade Coefficient 0.400
WIND (3)
Window Details:
Detailed Input No
Height 0.50 m
Width 0.50 m
Overall U-Value 6.000 W/(m²-°K)
Overall Shade Coefficient 0.400
WIND (4)
Window Details:
Detailed Input No
Height 1.70 m
Width 0.50 m
Overall U-Value 6.000 W/(m²-°K)
Overall Shade Coefficient 0.400
WIND (5)
Window Details:
Detailed Input No
Height 2.00 m
Width 0.50 m
Overall U-Value 6.000 W/(m²-°K)
Overall Shade Coefficient 0.400
7 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
PAC-01
-Air System Output Data
-Air System Input Data
-Space Description
8 of 207
Air System Sizing Summary for PAC-01
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:50PM
9 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for PAC-01
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:50PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
10 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for PAC-01
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:50PM
11 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
PAC-01 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:48PM
1. General Details:
Air System Name PAC-01
Equipment Type Packaged Rooftop Units
Air System Type Single Zone CAV
Number of zones 1
2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
00- (G-03) MALE REVIEW H x1
00- (G-05) MONEY CHANGER x1
00- (G-06) COM.MONEY CHA x1
00- (G-07) OFFICE x1
00- (G-08) OFFICE x1
00- (G-10) OFFICE x1
00- (G-11) OFFICE x1
00-(G-02)1/2 INFORMATION x1
00- (G-9,12) SOCIAL RESE x1
00- (G-13) OFFICE x1
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load 53.5 kW
Design OAT 35.0 °C
Equipment Sizing Auto-Sized
Capacity Oversizing Factor 0.0 %
ARI Performance Rating 2.96 EER
Conventional Cutoff OAT 12.8 °C
Low Temperature Operation Not used
13 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 153.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 105.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 10.0 0 0 0
W 67.0 23 0 0
NW 20.0 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 34.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
14 of 207
Hourly Analysis Program v.4.4 Page 1 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 7.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 15.0 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
15 of 207
Hourly Analysis Program v.4.4 Page 2 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 6.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
16 of 207
Hourly Analysis Program v.4.4 Page 3 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 21.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 25.0 3 0 0
S 21.0 3 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
17 of 207
Hourly Analysis Program v.4.4 Page 4 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 8.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 3 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
18 of 207
Hourly Analysis Program v.4.4 Page 5 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 12.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 2 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
19 of 207
Hourly Analysis Program v.4.4 Page 6 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 12.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 2 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
20 of 207
Hourly Analysis Program v.4.4 Page 7 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 13.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 2 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 20.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
21 of 207
Hourly Analysis Program v.4.4 Page 8 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 37.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 30.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
22 of 207
Hourly Analysis Program v.4.4 Page 9 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
00-(G-02)1/2 INFORMATION
1. General Details:
Floor Area 50.5 m²
Avg. Ceiling Height 4.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 13.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 16.0 16 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
23 of 207
Hourly Analysis Program v.4.4 Page 10 of 10
PAC-02
-Air System Output Data
-Air System Input Data
-Space Description
24 of 207
Air System Sizing Summary for PAC-02
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:50PM
25 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for PAC-02
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:50PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
26 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for PAC-02
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:50PM
27 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
PAC-02 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:48PM
1. General Details:
Air System Name PAC-02
Equipment Type Packaged Rooftop Units
Air System Type Single Zone CAV
Number of zones 1
2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
00-(G-02)1/2 INFORMATION x1
00- (G-22) OFFICE x1
00- (G-32) FEM. REVIEW H x1
00- (G-24) OFFICE x1
00- (G-23,26) SOCIAL RES x1
00- (G-27) OFFICE x1
00- (G-29) COM.MONEY CHA x1
00- (G-28) OFFICE x1
00- (G-30) MONEY CHANGER x1
00- (G-25) OFFICE x1
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load 53.2 kW
Design OAT 35.0 °C
Equipment Sizing Auto-Sized
Capacity Oversizing Factor 0.0 %
ARI Performance Rating 2.96 EER
Conventional Cutoff OAT 12.8 °C
Low Temperature Operation Not used
29 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 13.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 2 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 20.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
30 of 207
Hourly Analysis Program v.4.4 Page 1 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 37.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 30.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
31 of 207
Hourly Analysis Program v.4.4 Page 2 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 13.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 2 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
32 of 207
Hourly Analysis Program v.4.4 Page 3 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 13.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 2 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
33 of 207
Hourly Analysis Program v.4.4 Page 4 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 8.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 3 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
34 of 207
Hourly Analysis Program v.4.4 Page 5 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 21.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 25.0 3 0 0
N 21.0 3 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
35 of 207
Hourly Analysis Program v.4.4 Page 6 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 6.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
36 of 207
Hourly Analysis Program v.4.4 Page 7 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 7.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 15.0 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
37 of 207
Hourly Analysis Program v.4.4 Page 8 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
1. General Details:
Floor Area 153.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 105.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 10.0 0 0 0
W 67.0 23 0 0
SW 20.0 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 34.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
38 of 207
Hourly Analysis Program v.4.4 Page 9 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM
00-(G-02)1/2 INFORMATION
1. General Details:
Floor Area 50.5 m²
Avg. Ceiling Height 4.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 13.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 16.0 16 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
39 of 207
Hourly Analysis Program v.4.4 Page 10 of 10
FCU-01
-Air System Output Data
-Air System Input Data
-Space Description
40 of 207
Air System Sizing Summary for FCU-01
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:03PM
41 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-01
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:03PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
42 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-01
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:03PM
43 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-01 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:02PM
1. General Details:
Air System Name FCU-01
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
01- (F-01) DEP. HEAD x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
44 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-01 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:02PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
45 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:03PM
1. General Details:
Floor Area 29.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 12.0 0 0 0
NW 15.0 2 2 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
46 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-02
-Air System Output Data
-Air System Input Data
-Space Description
47 of 207
Air System Sizing Summary for FCU-02
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:05PM
48 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-02
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:05PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
49 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-02
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:05PM
50 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-02 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:05PM
1. General Details:
Air System Name FCU-02
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
01- (F-02) OFFICE x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
51 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-02 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:05PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
52 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:04PM
1. General Details:
Floor Area 83.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 59.0 7 0 0
S 10.0 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 31.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
53 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-03
-Air System Output Data
-Air System Input Data
-Space Description
54 of 207
Air System Sizing Summary for FCU-03
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:06PM
55 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-03
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:06PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
56 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-03
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:06PM
57 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-03 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:06PM
1. General Details:
Air System Name FCU-03
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
01- (F-04) OFFICE x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
58 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-03 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:06PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
59 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:06PM
1. General Details:
Floor Area 52.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 35.0 5 0 0
S 35.0 3 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 23.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
60 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-04
-Air System Output Data
-Air System Input Data
-Space Description
61 of 207
Air System Sizing Summary for FCU-04
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM
62 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-04
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
63 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-04
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM
64 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-04 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM
1. General Details:
Air System Name FCU-04
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
01- (F-05) OFFICE x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
65 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-04 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
66 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:06PM
1. General Details:
Floor Area 54.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 35.0 5 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
67 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-05
-Air System Output Data
-Air System Input Data
-Space Description
68 of 207
Air System Sizing Summary for FCU-05
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM
69 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-05
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
70 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-05
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:08PM
71 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-05 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM
1. General Details:
Air System Name FCU-05
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
01- (F-07) DEP. HEAD x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
72 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-05 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
73 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:08PM
1. General Details:
Floor Area 32.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 13.0 1 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 19.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
74 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-06
-Air System Output Data
-Air System Input Data
-Space Description
75 of 207
Air System Sizing Summary for FCU-06
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM
76 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-06
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
77 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-06
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM
78 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-06 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM
1. General Details:
Air System Name FCU-06
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
01- (F-06) CORR x1
01- (F-08) MAIN LOBBY x1
01- (F-14) CORR x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
79 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-06 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
80 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:09PM
1. General Details:
Floor Area 30.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
81 of 207
Hourly Analysis Program v.4.4 Page 1 of 3
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:09PM
1. General Details:
Floor Area 155.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 50.0 38 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 73.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
82 of 207
Hourly Analysis Program v.4.4 Page 2 of 3
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:09PM
1. General Details:
Floor Area 30.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
83 of 207
Hourly Analysis Program v.4.4 Page 3 of 3
FCU-07
-Air System Output Data
-Air System Input Data
-Space Description
84 of 207
Air System Sizing Summary for FCU-07
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM
85 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-07
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
86 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-07
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM
87 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-07 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM
1. General Details:
Air System Name FCU-07
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
01- (F-19) DEP. HEAD x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
88 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-07 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
89 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:14PM
1. General Details:
Floor Area 29.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 12.0 0 0 0
SW 15.0 2 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
90 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-08
-Air System Output Data
-Air System Input Data
-Space Description
91 of 207
Air System Sizing Summary for FCU-08
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:14PM
92 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-08
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:14PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
93 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-08
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:14PM
94 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-08 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:14PM
1. General Details:
Air System Name FCU-08
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
01- (F-18) OFFICE x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
95 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-08 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:14PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
96 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:14PM
1. General Details:
Floor Area 83.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 59.0 7 0 0
N 10.0 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 23.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
97 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-09
-Air System Output Data
-Air System Input Data
-Space Description
98 of 207
Air System Sizing Summary for FCU-09
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:15PM
99 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-09
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:15PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
100 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-09
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:15PM
101 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-09 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:15PM
1. General Details:
Air System Name FCU-09
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
01- (F-13) DEP. HEAD x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
102 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-09 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:15PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
103 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:16PM
1. General Details:
Floor Area 32.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 12.0 1 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 19.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
104 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-10
-Air System Output Data
-Air System Input Data
-Space Description
105 of 207
Air System Sizing Summary for FCU-10
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM
106 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-10
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
107 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-10
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM
108 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-10 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:18PM
1. General Details:
Air System Name FCU-10
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
01- (F-15) OFFICE x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
109 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-10 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:18PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
110 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:16PM
1. General Details:
Floor Area 57.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 37.0 6 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 33.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
111 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-11
-Air System Output Data
-Air System Input Data
-Space Description
112 of 207
Air System Sizing Summary for FCU-11
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM
113 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-11
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
114 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-11
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM
115 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-11 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM
1. General Details:
Air System Name FCU-11
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
01- (F-16) OFFICE x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
116 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-11 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
117 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:17PM
1. General Details:
Floor Area 52.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 37.0 6 0 0
N 35.0 3 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 33.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
118 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-12
-Air System Output Data
-Air System Input Data
-Space Description
119 of 207
Air System Sizing Summary for FCU-12
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:19PM
120 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-12
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:19PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
121 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-12
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:19PM
122 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-12 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:19PM
1. General Details:
Air System Name FCU-12
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
02- (S-02) SECRETARY x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
123 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-12 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:19PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
124 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:19PM
1. General Details:
Floor Area 29.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 15.0 2 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
125 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-13
-Air System Output Data
-Air System Input Data
-Space Description
126 of 207
Air System Sizing Summary for FCU-13
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:20PM
127 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-13
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:20PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
128 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-13
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:20PM
129 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-13 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:20PM
1. General Details:
Air System Name FCU-13
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
01- (F-02) OFFICE x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
130 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-13 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:20PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
131 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:20PM
1. General Details:
Floor Area 71.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 15.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 46.0 7 0 0
S 10.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 71.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 22.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
132 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-14
-Air System Output Data
-Air System Input Data
-Space Description
133 of 207
Air System Sizing Summary for FCU-14
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:23PM
134 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-14
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:23PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
135 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-14
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:23PM
136 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-14 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:21PM
1. General Details:
Air System Name FCU-14
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
02- (S-08) OFFICE x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
137 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-14 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:21PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
138 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:22PM
1. General Details:
Floor Area 51.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 35.0 5 5 0
S 35.0 3 3 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 51.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 23.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
139 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-15
-Air System Output Data
-Air System Input Data
-Space Description
140 of 207
Air System Sizing Summary for FCU-15
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM
141 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-15
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
142 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-15
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM
143 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-15 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM
1. General Details:
Air System Name FCU-15
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
02- (S-09) CONTROL ROOM x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
144 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-15 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
145 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:22PM
1. General Details:
Floor Area 28.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 28.0 5 5 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 28.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
146 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-16
-Air System Output Data
-Air System Input Data
-Space Description
147 of 207
Air System Sizing Summary for FCU-16
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:25PM
148 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-16
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:25PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
149 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-16
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:25PM
150 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-16 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM
1. General Details:
Air System Name FCU-16
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
02- (S-12) ARCHIVE x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
151 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-16 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
152 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:26PM
1. General Details:
Floor Area 51.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 20.0 3 3 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 51.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
153 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-17
-Air System Output Data
-Air System Input Data
-Space Description
154 of 207
Air System Sizing Summary for FCU-17
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:26PM
155 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-17
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:26PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
156 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-17
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:26PM
157 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-17 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:26PM
1. General Details:
Air System Name FCU-17
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
02- (S-20) CORR x1
02- (S-11,10) WAT.&CORR x1
02- (S-15) MAIN LOBB x1
02- (S-15) MULTI PURPOSE x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
158 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-17 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:26PM
1 2307.4 - - 178.1
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
159 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:26PM
1. General Details:
Floor Area 37.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 37.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
160 of 207
Hourly Analysis Program v.4.4 Page 1 of 4
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:26PM
1. General Details:
Floor Area 217.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 65.0 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 30.0 °C
Ambient at Space Max Temp. 39.8 °C
Unconditioned Space Min Temp. 15.0 °C
Ambient at Space Min Temp. 7.1 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 73.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
161 of 207
Hourly Analysis Program v.4.4 Page 2 of 4
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:26PM
1. General Details:
Floor Area 118.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 82.0 53 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 118.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 30.0 °C
Ambient at Space Max Temp. 39.8 °C
Unconditioned Space Min Temp. 15.0 °C
Ambient at Space Min Temp. 7.1 °C
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 73.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
162 of 207
Hourly Analysis Program v.4.4 Page 3 of 4
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:26PM
1. General Details:
Floor Area 30.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 30.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
163 of 207
Hourly Analysis Program v.4.4 Page 4 of 4
FCU-18
-Air System Output Data
-Air System Input Data
-Space Description
164 of 207
Air System Sizing Summary for FCU-18
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:32PM
165 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-18
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:32PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
166 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-18
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:32PM
167 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-18 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:32PM
1. General Details:
Air System Name FCU-18
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
02- (S-24) DEP. HEAD x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
168 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-18 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:32PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
169 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:28PM
1. General Details:
Floor Area 29.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 12.0 2 2 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 29.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
170 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-19
-Air System Output Data
-Air System Input Data
-Space Description
171 of 207
Air System Sizing Summary for FCU-19
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM
172 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-19
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
173 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-19
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM
174 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-19 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM
1. General Details:
Air System Name FCU-19
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
02- (S-23) OFFICE x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
175 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-19 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
176 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:28PM
1. General Details:
Floor Area 84.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 59.0 7 7 0
N 10.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 84.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
177 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-20
-Air System Output Data
-Air System Input Data
-Space Description
178 of 207
Air System Sizing Summary for FCU-20
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM
179 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-20
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
180 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-20
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM
181 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-20 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM
1. General Details:
Air System Name FCU-20
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
02- (S-18) DEP. HEAD x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
182 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-20 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
183 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:28PM
1. General Details:
Floor Area 24.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 12.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 24.0 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 15.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
184 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-21
-Air System Output Data
-Air System Input Data
-Space Description
185 of 207
Air System Sizing Summary for FCU-21
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:30PM
186 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-21
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:30PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
187 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-21
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:30PM
188 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-21 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:30PM
1. General Details:
Air System Name FCU-21
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
02- (S-19) OFFICE x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
189 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-21 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:30PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
190 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:28PM
1. General Details:
Floor Area 57.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 37.0 6 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 33.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
191 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-22
-Air System Output Data
-Air System Input Data
-Space Description
192 of 207
Air System Sizing Summary for FCU-22
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:29PM
193 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-22
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:29PM
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated
194 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-22
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:29PM
195 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-22 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:29PM
1. General Details:
Air System Name FCU-22
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
02- (S-21) OFFICE x1
Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
196 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-22 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:29PM
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
197 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:28PM
1. General Details:
Floor Area 52.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 37.0 6 0 0
N 35.0 3 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 33.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C
198 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Ventilation Calculations
199 of 207
Zuhair Fayez Partnership
Made by :ASIS Date 20/08/2011 Project Ministry Of Social Affairs
Bldg. J10-13503
Checked by : SMM Date 20/08/2011 Contract : Sheet No. 1 of 2
Revised by : SMM Date : Section : HVAC Calc. No.
Checked by HAHA Date : Job No. J10-13503 File
Subject : VENTILATION VOLUME FLOW RATE CALCULATIONS
Room Dimensions Fan Selection Data
Space Name & No. Length Width Height Volume No. of Air Air flow rate
m m m m3 change/Hour LPS
200 of 207
Zuhair Fayez Partnership
Made by :ASIS Date 20/08/2011 Project Ministry Of Social Affairs
Bldg. J10-13503
Checked by : SMM Date 20/08/2011 Contract : Sheet No. 2 of 2
Revised by : SMM Date : Section : HVAC Calc. No.
Checked by HAHA Date : Job No. J10-13503 File
Subject : VENTILATION VOLUME FLOW RATE CALCULATIONS
Room Dimensions Fan Selection Data
Space Name & No. Length Width Height Volume No. of Air Air flow rate
m m m m3 change/Hour LPS
ELEC (B5-02)
ELEC. (B5 02) 4 00
4.00 3 00
3.00 3 25
3.25 39 0
39.0 6 65
65
EF-B5-03 SAY 65 LPS
201 of 207
External Static Pressure
Calculations
202 of 207
Zuhair Fayez Partnership
Made by :ASIS Date : 21.08.11 Project Ministry Of Social Affairs
Bldg. 503
Checked by : SMM Date : 21.08.11 Contract : Sheet No. 1 of 2
Revised by : SMM Date : Section : HVAC Calc. No.
Checked by : Date : Job No. J10-13503 File
Subject : EXTERNAL STATIC LOSSES SUMMARY
Total external static losses = Total supply duct losses + Total return duct losses
Total external static losses = 375.9 Pa
Adding 10% factor of safety = 37.59 Pa
Total external static losses = 413.49 Pa
Say 415 Pa
203 of 207
Zuhair Fayez Partnership
Made by :ASIS Date : 21.08.11 Project Ministry Of Social Affairs
Bldg. 503
Checked by : SMM Date : 21.08.11 Contract : Sheet No. 1 of 2
Revised by : SMM Date : Section : HVAC Calc. No.
Checked by : Date : Job No. J10-13503 File
Subject : EXTERNAL STATIC LOSSES SUMMARY
Total external static losses = Total supply duct losses + Total return duct losses
Total external static losses = 375.9 Pa
Adding 10% factor of safety = 37.59 Pa
Total external static losses = 413.49 Pa
Say 415 Pa
204 of 207
Air Balance
205 of 207
Zuhair Fayez Partnership
Made by :ASIS Date : 21.08.11 Project Ministry Of Social Affairs
Bldg. 503
Checked by : SMM Date : 21.08.11 Contract : Sheet No. 1 of 2
Revised by : SMM Date : Section : HVAC Calc. No.
Checked by : Date : Job No. J10-13503 File
Subject : Zone [Load/M3 , Air Balance & No. of Air Change/Hr.]
INPUT DATA :
ZONE NO. : 01
ZONE HEIGHT= 3 M
ZONE EXHAUST AIR FLOW RATE = 310 LPS EF-01 = 310 LPS(part)
OUTPUT DATA :
206 of 207
Zuhair Fayez Partnership
Made by :ASIS Date : 21.08.11 Project Ministry Of Social Affairs
Bldg. 503
Checked by : SMM Date : 21.08.11 Contract : Sheet No. 1 of 2
Revised by : SMM Date : Section : HVAC Calc. No.
Checked by : Date : Job No. J10-13503 File
Subject : Zone [Load/M3 , Air Balance & No. of Air Change/Hr.]
INPUT DATA :
ZONE NO. : 02
ZONE HEIGHT= 3 M
ZONE EXHAUST AIR FLOW RATE = 310 LPS EF-02 = 310 LPS(part)
OUTPUT DATA :
207 of 207