TABLE OF CONTENT

DESCRIPTION 1. pages

General Data 01- 07


a. Design Weather Parameters.
b. Schedules Data.
c. Wall Construction.
d. Roof Construction.
e. Window Constructions.

PAC -01 08 - 23
-Air System Output Data
-Air System Input Data
-Space Description

PAC -02 24 - 39
-Air System Output Data
-Air System Input Data
-Space Description

FCU-01 40 – 46
-Air System Output Data
-Air System Input Data
-Space Description 3.

FCU -02 47 – 53
-Air System Output Data
-Air System Input Data
-Space Description 3.
FCU -03 54 - 60
-Air System Output Data
-Air System Input Data
-Space Description

FCU -04 61 - 67
-Air System Output Data
-Air System Input Data
-Space Description

FCU -05 68 - 74
-Air System Output Data
-Air System Input Data
-Space Description

FCU -06 75 - 83
-Air System Output Data
-Air System Input Data
-Space Description

FCU -07 84 - 90
-Air System Output Data
-Air System Input Data
-Space Description

FCU -08 91 - 97
-Air System Output Data
-Air System Input Data
-Space Description
FCU -09 98 - 104
-Air System Output Data
-Air System Input Data
-Space Description

FCU -10 105 - 111


-Air System Output Data
-Air System Input Data
-Space Description

FCU -11 112- 118


-Air System Output Data
-Air System Input Data
-Space Description

FCU -12 119 - 125


-Air System Output Data
-Air System Input Data
-Space Description

FCU -13 126 - 132


-Air System Output Data
-Air System Input Data
-Space Description

FCU -14 133 - 139


-Air System Output Data
-Air System Input Data
-Space Description
FCU -15 140 - 146
-Air System Output Data
-Air System Input Data
-Space Description

FCU -16 147 - 153


-Air System Output Data
-Air System Input Data
-Space Description

FCU -17 154- 163


-Air System Output Data
-Air System Input Data
-Space Description

FCU -18 164 - 170


-Air System Output Data
-Air System Input Data
-Space Description

FCU -19 171- 177


-Air System Output Data
-Air System Input Data
-Space Description

FCU -20 178 - 184


-Air System Output Data
-Air System Input Data
-Space Description
FCU -21 185 - 191
-Air System Output Data
-Air System Input Data
-Space Description

FCU -22 192 - 198


-Air System Output Data
-Air System Input Data
-Space Description

Ventilation Calculations 199 - 201

Static pressure 202 - 204

Air balance 205 - 207


1-General Data
a. Design Weather Parameters.
b. Schedules Data.
c. Wall Construction Type
d. Roof Construction Type.
e. Window Constructions Type.

1 of 207
Design Weather Parameters & MSHGs
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:46PM

Design Parameters:

City Name NAGRAN


Location Saudi Arabia
Latitude 17.6 Deg.
Longitude 44.4 Deg.
Elevation 1212.0 m
Summer Design Dry-Bulb 39.8 °C
Summer Coincident Wet-Bulb 21.3 °C
Summer Daily Range 12.6 °K
Winter Design Dry-Bulb 7.1 °C
Winter Design Wet-Bulb 0.3 °C
Atmospheric Clearness Number 1.00
Average Ground Reflectance 0.20
Soil Conductivity 1.385 W/(m-°K)
Local Time Zone (GMT +/- N hours) -3.0 hours
Consider Daylight Savings Time No
Simulation Weather Data noneN/A
Current Data is User Modified
Design Cooling Months January to December

Design Day Maximum Solar Heat Gains

(The MSHG values are expressed in W/m² )

Month N NNE NE ENE E ESE SE SSE S


January 92.6 92.6 169.3 442.1 661.8 776.4 787.1 711.8 645.6
February 101.2 101.2 296.0 547.1 724.1 789.2 731.8 612.5 510.9
March 109.5 167.2 433.7 621.3 740.6 746.9 639.0 456.0 319.6
April 121.6 312.7 534.6 668.3 699.4 643.4 491.4 260.8 154.6
May 158.7 408.2 588.4 679.7 667.9 560.8 373.7 153.6 129.7
June 200.6 437.6 597.9 669.2 641.3 526.3 324.7 131.6 129.7
July 165.6 402.7 570.7 659.8 654.2 553.0 364.0 150.9 132.3
August 127.6 311.3 515.1 638.2 680.9 622.9 471.8 252.0 154.1
September 113.2 157.7 418.4 602.6 694.3 709.0 617.0 443.1 317.6
October 103.7 103.7 296.4 535.3 682.5 754.6 719.9 596.4 498.6
November 93.7 93.7 174.0 435.8 636.8 767.2 779.0 707.4 638.0
December 88.1 88.1 129.7 382.1 625.2 765.2 789.5 743.1 684.4
Month SSW SW WSW W WNW NW NNW HOR Mult
January 717.2 788.3 781.0 652.3 434.1 176.2 92.6 757.5 1.00
February 614.7 743.9 783.7 702.4 551.4 306.1 101.2 849.9 1.00
March 454.9 640.9 741.0 728.5 633.1 439.8 163.2 905.1 1.00
April 262.1 492.0 647.8 705.9 659.0 529.2 312.7 903.2 1.00
May 154.1 376.6 568.5 669.9 672.4 578.5 403.9 886.7 1.00
June 131.6 325.3 527.4 643.0 667.1 596.3 436.6 870.1 1.00
July 150.8 362.4 548.7 647.7 662.6 577.5 406.1 871.5 1.00
August 251.9 471.8 622.6 680.4 637.6 515.7 311.4 880.1 1.00
September 444.2 610.8 716.2 712.8 601.4 401.5 161.9 877.6 1.00
October 591.4 713.2 757.0 700.6 536.4 275.8 103.7 834.6 1.00
November 702.5 779.2 756.3 650.7 442.4 157.7 93.7 754.0 1.00
December 740.4 794.4 761.8 627.6 391.0 127.0 88.1 711.4 1.00
Mult. = User-defined solar multiplier factor.

2 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Schedule Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:47PM

EQUPMENT (Fractional)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

LIGHT (Fractional)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

3 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
Schedule Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:47PM

PEOPLE (Fractional)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

THERMO (Fan / Thermostat)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

O = Occupied; U = Unoccupied

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

4 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Wall Constructions
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:47PM

EXTERNAL WALL

Wall Details
Outside Surface Color Dark
Absorptivity 0.900
Overall U-Value 0.473 W/(m²-°K)

Wall Layers Details (Inside to Outside)


Thickness Density Specific Ht. R-Value Weight
Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m²
Inside surface resistance 0.000 0.0 0.00 0.12064 0.0
20mm cement plaster 20.000 1860.0 0.84 0.02600 0.0
100 mm thick CMU 100.000 1120.0 0.88 0.16500 112.0
Rigide insulation 50.000 32.0 1.21 1.51000 1.6
150 mm thick CMU 150.000 1120.0 0.88 0.24750 168.0
Outside surface resistance 0.000 0.0 0.00 0.04400 0.0
Totals 320.000 - 2.11314 281.6

Partition

Wall Details
Outside Surface Color Dark
Absorptivity 0.900
Overall U-Value 1.829 W/(m²-°K)

Wall Layers Details (Inside to Outside)


Thickness Density Specific Ht. R-Value Weight
Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m²
Inside surface resistance 0.000 0.0 0.00 0.12064 0.0
20mm cement plaster 20.000 1860.0 0.84 0.02600 37.2
150 mm thick CMU 200.000 1120.0 0.88 0.33000 224.0
20mm cement plaster 20.000 1860.0 0.84 0.02600 37.2
Outside surface resistance 0.000 0.0 0.00 0.04400 0.0
Totals 240.000 - 0.54664 298.4

5 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Roof Constructions
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:47PM

ROOF

Roof Details
Outside Surface Color Dark
Absorptivity 0.900
Overall U-Value 0.510 W/(m²-°K)

Roof Layers Details (Inside to Outside)


Thickness Density Specific Ht. R-Value Weight
Layers mm kg/m³ kJ / (kg - °K) (m²-°K)/W kg/m²
Inside surface resistance 0.000 0.0 0.00 0.16000 0.0
Concrete Slab 300.000 2240.0 0.80 0.23200 672.0
Concrete Screed 75.000 800.0 0.84 0.18000 60.0
Water proofing membran 2.000 1100.0 1.51 0.04000 2.2
50mm rigid insulation 50.000 32.0 1.21 1.34125 1.6
New Layer 30.000 32.0 0.92 0.00900 1.0
Outside surface resistance 0.000 0.0 0.00 0.00010 0.0
Totals 457.000 - 1.96235 736.8

6 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Window Constructions
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:47PM

CW

Window Details:
Detailed Input No
Height 1.00 m
Width 1.00 m
Overall U-Value 2.500 W/(m²-°K)
Overall Shade Coefficient 0.400

SKYLIGHT

Window Details:
Detailed Input No
Height 0.90 m
Width 0.90 m
Overall U-Value 0.910 W/(m²-°K)
Overall Shade Coefficient 0.320

WIND (1)

Window Details:
Detailed Input No
Height 2.50 m
Width 0.50 m
Overall U-Value 2.500 W/(m²-°K)
Overall Shade Coefficient 0.400

WIND (2)

Window Details:
Detailed Input No
Height 2.00 m
Width 0.50 m
Overall U-Value 2.500 W/(m²-°K)
Overall Shade Coefficient 0.400

WIND (3)

Window Details:
Detailed Input No
Height 0.50 m
Width 0.50 m
Overall U-Value 6.000 W/(m²-°K)
Overall Shade Coefficient 0.400

WIND (4)

Window Details:
Detailed Input No
Height 1.70 m
Width 0.50 m
Overall U-Value 6.000 W/(m²-°K)
Overall Shade Coefficient 0.400

WIND (5)

Window Details:
Detailed Input No
Height 2.00 m
Width 0.50 m
Overall U-Value 6.000 W/(m²-°K)
Overall Shade Coefficient 0.400

7 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
PAC-01
-Air System Output Data
-Air System Input Data
-Space Description

8 of 207
Air System Sizing Summary for PAC-01
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:50PM

Air System Information


Air System Name PAC-01 Number of zones 1
Equipment Class PKG ROOF Floor Area 322.0 m²
Air System Type SZCAV Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 53.5 kW Load occurs at Aug 1500
Sensible coil load 45.3 kW OA DB / WB 39.8 / 21.3 °C
Coil L/s at Aug 1500 3505 L/s Entering DB / WB 26.1 / 17.8 °C
Max block L/s 3505 L/s Leaving DB / WB 13.7 / 12.9 °C
Sum of peak zone L/s 3540 L/s Coil ADP 12.3 °C
Sensible heat ratio 0.846 Bypass Factor 0.100
m²/kW 6.0 Resulting RH 55 %
W/m² 166.1 Design supply temp. 13.1 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Central Heating Coil Sizing Data


Max coil load 6.5 kW Load occurs at Des Htg
Coil L/s at Des Htg 3505 L/s W/m² 20.0
Max coil L/s 3505 L/s Ent. DB / Lvg DB 19.1 / 20.8 °C
Water flow @ 11.1 °K drop N/A

Supply Fan Sizing Data


Actual max L/s 3505 L/s Fan motor BHP 5.87 BHP
Standard L/s 3029 L/s Fan motor kW 4.38 kW
Actual max L/(s-m²) 10.88 L/(s-m²) Fan static 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s 469 L/s L/s/person 3.15 L/s/person
L/(s-m²) 1.46 L/(s-m²)

9 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for PAC-01
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:50PM

Air System Information


Air System Name PAC-01 Number of zones 1
Equipment Class PKG ROOF Floor Area 322.0 m²
Air System Type SZCAV Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 32.4 3505 3505 Aug 2200 4.5 322.0 10.88

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
00- (G-03) MALE REVIEW H 1 15.5 Aug 2200 1670 1.8 153.0 10.92
00- (G-05) MONEY CHANGER 1 0.3 Oct 0200 37 0.1 7.5 4.99
00- (G-06) COM.MONEY CHA 1 0.7 Jan 2300 79 0.0 6.5 12.14
00- (G-07) OFFICE 1 2.3 Oct 1600 246 0.6 21.0 11.73
00- (G-08) OFFICE 1 1.2 Aug 1500 127 0.2 8.5 14.93
00- (G-10) OFFICE 1 1.4 Aug 1500 156 0.2 12.0 13.01
00- (G-11) OFFICE 1 1.5 Aug 1500 157 0.2 12.5 12.57
00-(G-02)1/2 INFORMATION 1 4.7 Aug 2200 508 0.6 50.5 10.06
00- (G-9,12) SOCIAL RESE 1 4.2 Jul 1500 449 0.4 37.0 12.14
00- (G-13) OFFICE 1 1.8 Aug 1500 189 0.4 13.5 14.03

10 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for PAC-01
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 58 m² 3065 - 58 m² - -
Wall Transmission 176 m² 758 - 176 m² 1159 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 58 m² 2244 - 58 m² 2007 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 84 m² 1070 - 84 m² 922 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 7285 W 5099 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 4600 W 4600 - 0 0 -
People 149 11175 8195 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2801 820 10% 409 0
>> Total Zone Loads - 30812 9015 - 4497 0
Zone Conditioning - 30576 9015 - 4074 0
Plenum Wall Load 25% 344 - 0 0 -
Plenum Roof Load 70% 0 - 0 0 -
Plenum Lighting Load 30% 2185 - 0 0 -
Return Fan Load 3505 L/s 0 - 3505 L/s 0 -
Ventilation Load 469 L/s 7770 -778 469 L/s 6754 0
Supply Fan Load 3505 L/s 4381 - 3505 L/s -4381 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 308 - 1% 45 -
>> Total System Loads - 45564 8236 - 6492 0
Central Cooling Coil - 45258 8239 - 0 0
Central Heating Coil - 0 - - 6451 -
>> Total Conditioning - 45258 8239 - 6451 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

11 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
PAC-01 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:48PM

1. General Details:
Air System Name PAC-01
Equipment Type Packaged Rooftop Units
Air System Type Single Zone CAV
Number of zones 1

2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Airflow Rate 3540.0 L/s
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *
Capacity Control Cycled or Staged Compressor - Fan On

Central Heating Data:


Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Capacity Control Cycled or Staged Compressor - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 750 Pa
Overall Efficiency 60 %

Duct System Data:


Supply Duct Data:
Duct Heat Gain 1 %
Duct Leakage 1 %

Return Duct or Plenum Data:


Return Air Via Return Air Plenum
Wall Heat Gain to Plenum 25 %
Roof Heat Gain to Plenum 70 %
Lighting Heat Gain to Plenum 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
00- (G-03) MALE REVIEW H x1
00- (G-05) MONEY CHANGER x1
00- (G-06) COM.MONEY CHA x1
00- (G-07) OFFICE x1
00- (G-08) OFFICE x1
00- (G-10) OFFICE x1
00- (G-11) OFFICE x1
00-(G-02)1/2 INFORMATION x1
00- (G-9,12) SOCIAL RESE x1
00- (G-13) OFFICE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Supply Terminals Data:


Zone All
12 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
PAC-01 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:48PM

Terminal Type Diffuser


Minimum Airflow 0.00 L/s/person

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Electric Resistance


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.1 °C
Supply Fan Airflow 3504.6 L/s
Ventilation Airflow 469.1 L/s
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 3504.6 - -

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load 53.5 kW
Design OAT 35.0 °C
Equipment Sizing Auto-Sized
Capacity Oversizing Factor 0.0 %
ARI Performance Rating 2.96 EER
Conventional Cutoff OAT 12.8 °C
Low Temperature Operation Not used

13 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-03) MALE REVIEW H

1. General Details:
Floor Area 153.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 105.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 10.0 0 0 0
W 67.0 23 0 0
NW 20.0 0 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERNAL WALL

3.2. Construction Types for Exposure W


Wall Type EXTERNAL WALL
1st Window Type CW

3.3. Construction Types for Exposure NW


Wall Type EXTERNAL WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 34.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

14 of 207
Hourly Analysis Program v.4.4 Page 1 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-05) MONEY CHANGER

1. General Details:
Floor Area 7.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 15.0 0 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERNAL WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

15 of 207
Hourly Analysis Program v.4.4 Page 2 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-06) COM.MONEY CHA

1. General Details:
Floor Area 6.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

16 of 207
Hourly Analysis Program v.4.4 Page 3 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-07) OFFICE

1. General Details:
Floor Area 21.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 25.0 3 0 0
S 21.0 3 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (1)

3.2. Construction Types for Exposure S


Wall Type EXTERNAL WALL
1st Window Type WIND (1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

17 of 207
Hourly Analysis Program v.4.4 Page 4 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-08) OFFICE

1. General Details:
Floor Area 8.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 3 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

18 of 207
Hourly Analysis Program v.4.4 Page 5 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-10) OFFICE

1. General Details:
Floor Area 12.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 2 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

19 of 207
Hourly Analysis Program v.4.4 Page 6 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-11) OFFICE

1. General Details:
Floor Area 12.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 2 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

20 of 207
Hourly Analysis Program v.4.4 Page 7 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-13) OFFICE

1. General Details:
Floor Area 13.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 2 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 20.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

21 of 207
Hourly Analysis Program v.4.4 Page 8 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-9,12) SOCIAL RESE

1. General Details:
Floor Area 37.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2000.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 30.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

22 of 207
Hourly Analysis Program v.4.4 Page 9 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00-(G-02)1/2 INFORMATION

1. General Details:
Floor Area 50.5 m²
Avg. Ceiling Height 4.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 13.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 16.0 16 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERNAL WALL
1st Window Type CW

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

23 of 207
Hourly Analysis Program v.4.4 Page 10 of 10
PAC-02
-Air System Output Data
-Air System Input Data
-Space Description

24 of 207
Air System Sizing Summary for PAC-02
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:50PM

Air System Information


Air System Name PAC-02 Number of zones 1
Equipment Class PKG ROOF Floor Area 323.0 m²
Air System Type SZCAV Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 53.2 kW Load occurs at Jul 1500
Sensible coil load 45.0 kW OA DB / WB 39.8 / 21.3 °C
Coil L/s at Jul 1500 3505 L/s Entering DB / WB 26.1 / 17.9 °C
Max block L/s 3505 L/s Leaving DB / WB 13.8 / 13.0 °C
Sum of peak zone L/s 3540 L/s Coil ADP 12.4 °C
Sensible heat ratio 0.847 Bypass Factor 0.100
m²/kW 6.1 Resulting RH 55 %
W/m² 164.6 Design supply temp. 13.2 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Central Heating Coil Sizing Data


Max coil load 6.5 kW Load occurs at Des Htg
Coil L/s at Des Htg 3505 L/s W/m² 20.0
Max coil L/s 3505 L/s Ent. DB / Lvg DB 19.0 / 20.8 °C
Water flow @ 11.1 °K drop N/A

Supply Fan Sizing Data


Actual max L/s 3505 L/s Fan motor BHP 5.87 BHP
Standard L/s 3029 L/s Fan motor kW 4.38 kW
Actual max L/(s-m²) 10.85 L/(s-m²) Fan static 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s 469 L/s L/s/person 3.15 L/s/person
L/(s-m²) 1.45 L/(s-m²)

25 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for PAC-02
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:50PM

Air System Information


Air System Name PAC-02 Number of zones 1
Equipment Class PKG ROOF Floor Area 323.0 m²
Air System Type SZCAV Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 32.2 3505 3505 Aug 2200 4.5 323.0 10.85

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
00-(G-02)1/2 INFORMATION 1 4.7 Aug 2200 511 0.6 50.5 10.12
00- (G-22) OFFICE 1 1.7 Aug 1500 190 0.4 13.0 14.58
00- (G-32) FEM. REVIEW H 1 15.2 Aug 2200 1657 1.8 153.0 10.83
00- (G-24) OFFICE 1 1.5 Aug 1500 159 0.2 13.0 12.24
00- (G-23,26) SOCIAL RES 1 4.2 Jul 1500 452 0.4 37.0 12.22
00- (G-27) OFFICE 1 1.2 Aug 1500 128 0.2 8.5 15.02
00- (G-29) COM.MONEY CHA 1 0.7 Jan 2300 79 0.0 6.5 12.21
00- (G-28) OFFICE 1 2.2 Jun 1500 242 0.6 21.0 11.52
00- (G-30) MONEY CHANGER 1 0.3 Oct 0200 38 0.1 7.5 5.02
00- (G-25) OFFICE 1 1.5 Aug 1500 159 0.2 13.0 12.24

26 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for PAC-02
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 58 m² 3089 - 58 m² - -
Wall Transmission 176 m² 764 - 176 m² 1159 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 58 m² 2244 - 58 m² 2007 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 84 m² 1070 - 84 m² 922 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 7310 W 5117 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 4400 W 4400 - 0 0 -
People 149 11175 8195 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2786 820 10% 409 0
>> Total Zone Loads - 30644 9015 - 4497 0
Zone Conditioning - 30398 9015 - 4073 0
Plenum Wall Load 25% 347 - 0 0 -
Plenum Roof Load 70% 0 - 0 0 -
Plenum Lighting Load 30% 2193 - 0 0 -
Return Fan Load 3505 L/s 0 - 3505 L/s 0 -
Ventilation Load 469 L/s 7728 -899 469 L/s 6758 0
Supply Fan Load 3505 L/s 4381 - 3505 L/s -4381 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 306 - 1% 45 -
>> Total System Loads - 45353 8115 - 6496 0
Central Cooling Coil - 45049 8118 - 0 0
Central Heating Coil - 0 - - 6455 -
>> Total Conditioning - 45049 8118 - 6455 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

27 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
PAC-02 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:48PM

1. General Details:
Air System Name PAC-02
Equipment Type Packaged Rooftop Units
Air System Type Single Zone CAV
Number of zones 1

2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Airflow Rate 3540.0 L/s
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *
Capacity Control Cycled or Staged Compressor - Fan On

Central Heating Data:


Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND
Capacity Control Cycled or Staged Compressor - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 750 Pa
Overall Efficiency 60 %

Duct System Data:


Supply Duct Data:
Duct Heat Gain 1 %
Duct Leakage 1 %

Return Duct or Plenum Data:


Return Air Via Return Air Plenum
Wall Heat Gain to Plenum 25 %
Roof Heat Gain to Plenum 70 %
Lighting Heat Gain to Plenum 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
00-(G-02)1/2 INFORMATION x1
00- (G-22) OFFICE x1
00- (G-32) FEM. REVIEW H x1
00- (G-24) OFFICE x1
00- (G-23,26) SOCIAL RES x1
00- (G-27) OFFICE x1
00- (G-29) COM.MONEY CHA x1
00- (G-28) OFFICE x1
00- (G-30) MONEY CHANGER x1
00- (G-25) OFFICE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 L/s
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Supply Terminals Data:


Zone All
28 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
PAC-02 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 04:48PM

Terminal Type Diffuser


Minimum Airflow 0.00 L/s/person

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Electric Resistance


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.2 °C
Supply Fan Airflow 3504.6 L/s
Ventilation Airflow 469.4 L/s
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 3504.6 - -

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load 53.2 kW
Design OAT 35.0 °C
Equipment Sizing Auto-Sized
Capacity Oversizing Factor 0.0 %
ARI Performance Rating 2.96 EER
Conventional Cutoff OAT 12.8 °C
Low Temperature Operation Not used

29 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-22) OFFICE

1. General Details:
Floor Area 13.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 2 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 20.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

30 of 207
Hourly Analysis Program v.4.4 Page 1 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-23,26) SOCIAL RES

1. General Details:
Floor Area 37.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2000.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 30.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

31 of 207
Hourly Analysis Program v.4.4 Page 2 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-24) OFFICE

1. General Details:
Floor Area 13.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 2 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

32 of 207
Hourly Analysis Program v.4.4 Page 3 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-25) OFFICE

1. General Details:
Floor Area 13.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 2 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

33 of 207
Hourly Analysis Program v.4.4 Page 4 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-27) OFFICE

1. General Details:
Floor Area 8.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 15.0 3 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

34 of 207
Hourly Analysis Program v.4.4 Page 5 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-28) OFFICE

1. General Details:
Floor Area 21.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 25.0 3 0 0
N 21.0 3 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (1)

3.2. Construction Types for Exposure N


Wall Type EXTERNAL WALL
1st Window Type WIND (1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

35 of 207
Hourly Analysis Program v.4.4 Page 6 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-29) COM.MONEY CHA

1. General Details:
Floor Area 6.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

36 of 207
Hourly Analysis Program v.4.4 Page 7 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-30) MONEY CHANGER

1. General Details:
Floor Area 7.5 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 1.0 Person
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 15.0 0 0 0

3.1. Construction Types for Exposure S


Wall Type EXTERNAL WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

37 of 207
Hourly Analysis Program v.4.4 Page 8 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00- (G-32) FEM. REVIEW H

1. General Details:
Floor Area 153.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 105.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 10.0 0 0 0
W 67.0 23 0 0
SW 20.0 0 0 0

3.1. Construction Types for Exposure N


Wall Type EXTERNAL WALL

3.2. Construction Types for Exposure W


Wall Type EXTERNAL WALL
1st Window Type CW

3.3. Construction Types for Exposure SW


Wall Type EXTERNAL WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 34.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

38 of 207
Hourly Analysis Program v.4.4 Page 9 of 10
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 04:49PM

00-(G-02)1/2 INFORMATION

1. General Details:
Floor Area 50.5 m²
Avg. Ceiling Height 4.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 13.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 16.0 16 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERNAL WALL
1st Window Type CW

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

39 of 207
Hourly Analysis Program v.4.4 Page 10 of 10
FCU-01
-Air System Output Data
-Air System Input Data
-Space Description

40 of 207
Air System Sizing Summary for FCU-01
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:03PM

Air System Information


Air System Name FCU-01 Number of zones 1
Equipment Class TERM Floor Area 29.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

41 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-01
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:03PM

Air System Information


Air System Name FCU-01 Number of zones 1
Equipment Class TERM Floor Area 29.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 2.0 216 216 Jul 2200 0.4 29.0 7.44

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 2.6 2.4 25.4 / 17.9 14.8 / 14.1 - Jul 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.6 20.0 / 22.7 - 216 0.121 0.090 21

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
01- (F-01) DEP. HEAD 1 2.0 Jul 2200 216 0.4 29.0 7.44

42 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-01
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:03PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.4 °C / 21.2 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 75 - 2 m² - -
Wall Transmission 25 m² 174 - 25 m² 163 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 2 m² 200 - 2 m² 183 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 725 W 725 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 5 375 275 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 175 28 10% 35 0
>> Total Zone Loads - 1923 303 - 381 0
Zone Conditioning - 1928 303 - 403 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 21 L/s 355 -61 21 L/s 306 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 90 - - -90 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2372 242 - 619 0
Terminal Unit Cooling - 2372 244 - 0 0
Terminal Unit Heating - 0 - - 619 -
>> Total Conditioning - 2372 244 - 619 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

43 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-01 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:02PM

1. General Details:
Air System Name FCU-01
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
01- (F-01) DEP. HEAD x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 215.8 - - 21.2

44 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-01 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:02PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 2.6 35.0 Auto-Sized - 0 - 2.96 12.8

45 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:03PM

01- (F-01) DEP. HEAD

1. General Details:
Floor Area 29.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 12.0 0 0 0
NW 15.0 2 2 0

3.1. Construction Types for Exposure W


Wall Type EXTERNAL WALL

3.2. Construction Types for Exposure NW


Wall Type EXTERNAL WALL
1st Window Type WIND (4)
2nd Window Type WIND (3)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

46 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-02
-Air System Output Data
-Air System Input Data
-Space Description

47 of 207
Air System Sizing Summary for FCU-02
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:05PM

Air System Information


Air System Name FCU-02 Number of zones 1
Equipment Class TERM Floor Area 83.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

48 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-02
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:05PM

Air System Information


Air System Name FCU-02 Number of zones 1
Equipment Class TERM Floor Area 83.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 7.4 793 793 Aug 2200 1.5 83.0 9.56

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 8.8 8.3 24.9 / 17.7 14.9 / 14.2 - Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 1.8 20.3 / 22.5 - 793 0.443 0.330 50

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
01- (F-02) OFFICE 1 7.4 Aug 2200 793 1.5 83.0 9.56

49 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-02
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:05PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 268 - 7 m² - -
Wall Transmission 62 m² 413 - 62 m² 408 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 7 m² 653 - 7 m² 584 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 31 m² 395 - 31 m² 340 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2075 W 2075 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 2000 - 0 0 -
People 10 750 550 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 655 55 10% 133 0
>> Total Zone Loads - 7209 605 - 1465 0
Zone Conditioning - 7085 605 - 1372 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 50 L/s 851 -119 50 L/s 713 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 330 - - -330 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8266 486 - 1754 0
Terminal Unit Cooling - 8266 492 - 0 0
Terminal Unit Heating - 0 - - 1754 -
>> Total Conditioning - 8266 492 - 1754 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

50 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-02 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:05PM

1. General Details:
Air System Name FCU-02
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
01- (F-02) OFFICE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 793.1 - - 49.9

51 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-02 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:05PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 8.8 35.0 Auto-Sized - 0 - 2.96 12.8

52 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:04PM

01- (F-02) OFFICE

1. General Details:
Floor Area 83.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2000.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 59.0 7 0 0
S 10.0 0 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

3.2. Construction Types for Exposure S


Wall Type EXTERNAL WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 31.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

53 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-03
-Air System Output Data
-Air System Input Data
-Space Description

54 of 207
Air System Sizing Summary for FCU-03
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:06PM

Air System Information


Air System Name FCU-03 Number of zones 1
Equipment Class TERM Floor Area 52.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

55 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-03
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:06PM

Air System Information


Air System Name FCU-03 Number of zones 1
Equipment Class TERM Floor Area 52.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 6.0 634 634 Aug 1500 1.5 52.0 12.19

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 6.9 6.6 24.6 / 17.4 14.7 / 14.0 - Aug 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 1.6 20.7 / 23.1 - 634 0.354 0.264 31

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
01- (F-04) OFFICE 1 6.0 Aug 1500 634 1.5 52.0 12.19

56 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-03
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:06PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 564 - 8 m² - -
Wall Transmission 62 m² 360 - 62 m² 408 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 8 m² 746 - 8 m² 667 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 23 m² 293 - 23 m² 252 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1300 W 1300 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1700 W 1700 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 541 33 10% 133 0
>> Total Zone Loads - 5954 363 - 1460 0
Zone Conditioning - 5780 363 - 1453 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 31 L/s 523 -55 31 L/s 442 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 264 - - -264 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6567 308 - 1631 0
Terminal Unit Cooling - 6567 316 - 0 0
Terminal Unit Heating - 0 - - 1631 -
>> Total Conditioning - 6567 316 - 1631 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

57 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-03 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:06PM

1. General Details:
Air System Name FCU-03
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
01- (F-04) OFFICE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 634.0 - - 30.6

58 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-03 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:06PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 6.9 35.0 Auto-Sized - 0 - 2.96 12.8

59 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:06PM

01- (F-04) OFFICE

1. General Details:
Floor Area 52.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1700.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 35.0 5 0 0
S 35.0 3 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

3.2. Construction Types for Exposure S


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 23.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

60 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-04
-Air System Output Data
-Air System Input Data
-Space Description

61 of 207
Air System Sizing Summary for FCU-04
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM

Air System Information


Air System Name FCU-04 Number of zones 1
Equipment Class TERM Floor Area 54.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

62 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-04
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM

Air System Information


Air System Name FCU-04 Number of zones 1
Equipment Class TERM Floor Area 54.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 5.1 545 545 Aug 1500 0.7 54.0 10.10

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 6.2 5.9 24.7 / 17.3 14.4 / 13.7 - Jul 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 1.0 20.6 / 22.3 - 545 0.305 0.227 31

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
01- (F-05) OFFICE 1 5.1 Aug 1500 545 0.7 54.0 10.10

63 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-04
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.4 °C / 21.2 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 475 - 5 m² - -
Wall Transmission 30 m² 189 - 30 m² 197 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 454 - 5 m² 417 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1350 W 1350 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1700 W 1700 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 462 33 10% 61 0
>> Total Zone Loads - 5079 363 - 676 0
Zone Conditioning - 5115 363 - 725 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 31 L/s 521 -42 31 L/s 453 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 227 - - -227 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5863 321 - 951 0
Terminal Unit Cooling - 5863 325 - 0 0
Terminal Unit Heating - 0 - - 951 -
>> Total Conditioning - 5863 325 - 951 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

64 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-04 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM

1. General Details:
Air System Name FCU-04
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
01- (F-05) OFFICE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 545.4 - - 31.2

65 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-04 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 6.2 35.0 Auto-Sized - 0 - 2.96 12.8

66 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:06PM

01- (F-05) OFFICE

1. General Details:
Floor Area 54.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1700.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 35.0 5 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

67 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-05
-Air System Output Data
-Air System Input Data
-Space Description

68 of 207
Air System Sizing Summary for FCU-05
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM

Air System Information


Air System Name FCU-05 Number of zones 1
Equipment Class TERM Floor Area 32.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

69 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-05
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM

Air System Information


Air System Name FCU-05 Number of zones 1
Equipment Class TERM Floor Area 32.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 2.2 236 236 Aug 1500 0.4 32.0 7.36

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 2.8 2.6 25.2 / 17.6 14.6 / 13.9 - Aug 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.6 20.2 / 22.7 - 236 0.132 0.098 20

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
01- (F-07) DEP. HEAD 1 2.2 Aug 1500 236 0.4 32.0 7.36

70 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-05
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:08PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.4 °C / 21.2 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 97 - 1 m² - -
Wall Transmission 12 m² 75 - 12 m² 79 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 91 - 1 m² 83 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 19 m² 236 - 19 m² 209 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 800 W 800 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 400 - 0 0 -
People 4 300 220 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 200 22 10% 37 0
>> Total Zone Loads - 2199 242 - 408 0
Zone Conditioning - 2159 242 - 428 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 20 L/s 327 -41 20 L/s 283 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 98 - - -98 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2585 201 - 613 0
Terminal Unit Cooling - 2585 204 - 0 0
Terminal Unit Heating - 0 - - 613 -
>> Total Conditioning - 2585 204 - 613 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

71 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-05 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM

1. General Details:
Air System Name FCU-05
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
01- (F-07) DEP. HEAD x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 235.6 - - 19.6

72 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-05 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:07PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 2.8 35.0 Auto-Sized - 0 - 2.96 12.8

73 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:08PM

01- (F-07) DEP. HEAD

1. General Details:
Floor Area 32.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 13.0 1 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 19.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

74 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-06
-Air System Output Data
-Air System Input Data
-Space Description

75 of 207
Air System Sizing Summary for FCU-06
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM

Air System Information


Air System Name FCU-06 Number of zones 1
Equipment Class TERM Floor Area 215.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

76 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-06
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM

Air System Information


Air System Name FCU-06 Number of zones 1
Equipment Class TERM Floor Area 215.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 12.3 1315 1315 Aug 2200 2.4 215.0 6.11

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 13.5 12.9 24.3 / 17.5 15.0 / 14.3 - Jun 2200

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 3.1 20.2 / 22.4 - 1315 0.735 0.548 97

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
01- (F-06) CORR 1 0.8 Jan 2300 88 0.0 30.0 2.93
01- (F-08) MAIN LOBBY 1 10.7 Aug 2200 1139 2.4 155.0 7.35
01- (F-14) CORR 1 0.8 Jan 2300 88 0.0 30.0 2.93

77 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-06
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 2200 HEATING DATA AT DES HTG
COOLING OA DB / WB 30.7 °C / 18.9 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 38 m² 4162 - 38 m² - -
Wall Transmission 12 m² 91 - 12 m² 79 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 38 m² 911 - 38 m² 1321 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 73 m² 565 - 73 m² 801 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 4300 W 4300 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 13 975 715 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1100 72 10% 220 0
>> Total Zone Loads - 12104 786 - 2421 0
Zone Conditioning - 11573 786 - 2287 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 97 L/s 737 -183 97 L/s 1385 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 548 - - -548 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 12858 604 - 3123 0
Terminal Unit Cooling - 12858 611 - 0 0
Terminal Unit Heating - 0 - - 3123 -
>> Total Conditioning - 12858 611 - 3123 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

78 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-06 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM

1. General Details:
Air System Name FCU-06
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
01- (F-06) CORR x1
01- (F-08) MAIN LOBBY x1
01- (F-14) CORR x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 1314.7 - - 97.0

79 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-06 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 13.5 35.0 Auto-Sized - 0 - 2.96 12.8

80 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:09PM

01- (F-06) CORR

1. General Details:
Floor Area 30.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

81 of 207
Hourly Analysis Program v.4.4 Page 1 of 3
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:09PM

01- (F-08) MAIN LOBBY

1. General Details:
Floor Area 155.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 50.0 38 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERNAL WALL
1st Window Type CW

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 73.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

82 of 207
Hourly Analysis Program v.4.4 Page 2 of 3
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:09PM

01- (F-14) CORR

1. General Details:
Floor Area 30.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

83 of 207
Hourly Analysis Program v.4.4 Page 3 of 3
FCU-07
-Air System Output Data
-Air System Input Data
-Space Description

84 of 207
Air System Sizing Summary for FCU-07
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM

Air System Information


Air System Name FCU-07 Number of zones 1
Equipment Class TERM Floor Area 29.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

85 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-07
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM

Air System Information


Air System Name FCU-07 Number of zones 1
Equipment Class TERM Floor Area 29.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 2.1 229 229 Oct 2100 0.4 29.0 7.89

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 2.9 2.6 25.7 / 18.0 14.8 / 14.0 - Aug 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.6 19.8 / 22.5 - 229 0.128 0.095 26

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
01- (F-19) DEP. HEAD 1 2.1 Oct 2100 229 0.4 29.0 7.89

86 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-07
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 63 - 2 m² - -
Wall Transmission 25 m² 167 - 25 m² 164 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 2 m² 187 - 2 m² 167 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 725 W 725 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 7 525 385 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 187 39 10% 33 0
>> Total Zone Loads - 2053 424 - 364 0
Zone Conditioning - 2060 424 - 363 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 26 L/s 449 -81 26 L/s 378 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 95 - - -95 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2605 342 - 646 0
Terminal Unit Cooling - 2605 343 - 0 0
Terminal Unit Heating - 0 - - 646 -
>> Total Conditioning - 2605 343 - 646 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

87 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-07 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM

1. General Details:
Air System Name FCU-07
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
01- (F-19) DEP. HEAD x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 228.7 - - 26.2

88 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-07 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:13PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 2.9 35.0 Auto-Sized - 0 - 2.96 12.8

89 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:14PM

01- (F-19) DEP. HEAD

1. General Details:
Floor Area 29.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 12.0 0 0 0
SW 15.0 2 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERNAL WALL

3.2. Construction Types for Exposure SW


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

90 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-08
-Air System Output Data
-Air System Input Data
-Space Description

91 of 207
Air System Sizing Summary for FCU-08
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:14PM

Air System Information


Air System Name FCU-08 Number of zones 1
Equipment Class TERM Floor Area 83.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

92 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-08
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:14PM

Air System Information


Air System Name FCU-08 Number of zones 1
Equipment Class TERM Floor Area 83.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 7.9 844 844 Aug 2200 1.4 83.0 10.17

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 9.2 8.7 24.7 / 17.5 14.8 / 14.1 - Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 1.7 20.6 / 22.5 - 844 0.472 0.352 50

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
01- (F-18) OFFICE 1 7.9 Aug 2200 844 1.4 83.0 10.17

93 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-08
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:14PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 268 - 7 m² - -
Wall Transmission 62 m² 421 - 62 m² 408 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 7 m² 653 - 7 m² 584 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 23 m² 293 - 23 m² 252 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2075 W 2075 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2500 W 2500 - 0 0 -
People 10 750 550 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 696 55 10% 124 0
>> Total Zone Loads - 7656 605 - 1368 0
Zone Conditioning - 7533 605 - 1365 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 50 L/s 857 -108 50 L/s 722 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 352 - - -352 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8741 497 - 1736 0
Terminal Unit Cooling - 8741 501 - 0 0
Terminal Unit Heating - 0 - - 1736 -
>> Total Conditioning - 8741 501 - 1736 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

94 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-08 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:14PM

1. General Details:
Air System Name FCU-08
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
01- (F-18) OFFICE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 843.8 - - 49.9

95 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-08 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:14PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 9.2 35.0 Auto-Sized - 0 - 2.96 12.8

96 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:14PM

01- (F-18) OFFICE

1. General Details:
Floor Area 83.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2500.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 59.0 7 0 0
N 10.0 0 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

3.2. Construction Types for Exposure N


Wall Type EXTERNAL WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 23.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

97 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-09
-Air System Output Data
-Air System Input Data
-Space Description

98 of 207
Air System Sizing Summary for FCU-09
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:15PM

Air System Information


Air System Name FCU-09 Number of zones 1
Equipment Class TERM Floor Area 32.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

99 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-09
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:15PM

Air System Information


Air System Name FCU-09 Number of zones 1
Equipment Class TERM Floor Area 32.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 2.2 235 235 Aug 1500 0.4 32.0 7.34

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 2.8 2.6 25.2 / 17.7 14.7 / 14.0 - Aug 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.5 20.1 / 22.3 - 235 0.131 0.098 20

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
01- (F-13) DEP. HEAD 1 2.2 Aug 1500 235 0.4 32.0 7.34

100 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-09
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:15PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.4 °C / 21.2 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1 m² 97 - 1 m² - -
Wall Transmission 11 m² 69 - 11 m² 72 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 1 m² 91 - 1 m² 83 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 19 m² 236 - 19 m² 209 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 800 W 800 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 400 - 0 0 -
People 4 300 220 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 199 22 10% 36 0
>> Total Zone Loads - 2192 242 - 401 0
Zone Conditioning - 2146 242 - 367 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 20 L/s 327 -42 20 L/s 280 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 98 - - -98 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2571 200 - 549 0
Terminal Unit Cooling - 2571 202 - 0 0
Terminal Unit Heating - 0 - - 549 -
>> Total Conditioning - 2571 202 - 549 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

101 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-09 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:15PM

1. General Details:
Air System Name FCU-09
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
01- (F-13) DEP. HEAD x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 234.8 - - 19.6

102 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-09 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:15PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 2.8 35.0 Auto-Sized - 0 - 2.96 12.8

103 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:16PM

01- (F-13) DEP. HEAD

1. General Details:
Floor Area 32.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 12.0 1 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 19.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

104 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-10
-Air System Output Data
-Air System Input Data
-Space Description

105 of 207
Air System Sizing Summary for FCU-10
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM

Air System Information


Air System Name FCU-10 Number of zones 1
Equipment Class TERM Floor Area 57.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

106 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-10
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM

Air System Information


Air System Name FCU-10 Number of zones 1
Equipment Class TERM Floor Area 57.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 5.9 627 627 Aug 1500 1.2 57.0 11.00

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 6.8 6.5 24.7 / 17.5 14.8 / 14.1 - Aug 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 1.4 20.6 / 22.8 - 627 0.350 0.261 32

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
01- (F-15) OFFICE 1 5.9 Aug 1500 627 1.2 57.0 11.00

107 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-10
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m² 601 - 6 m² - -
Wall Transmission 31 m² 196 - 31 m² 204 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 6 m² 560 - 6 m² 500 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 33 m² 420 - 33 m² 362 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1425 W 1425 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1700 W 1700 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 535 33 10% 107 0
>> Total Zone Loads - 5887 363 - 1173 0
Zone Conditioning - 5675 363 - 1203 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 32 L/s 547 -65 32 L/s 463 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 261 - - -261 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6483 298 - 1405 0
Terminal Unit Cooling - 6483 313 - 0 0
Terminal Unit Heating - 0 - - 1405 -
>> Total Conditioning - 6483 313 - 1405 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

108 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-10 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:18PM

1. General Details:
Air System Name FCU-10
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
01- (F-15) OFFICE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 626.9 - - 32.1

109 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-10 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:18PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 6.8 35.0 Auto-Sized - 0 - 2.96 12.8

110 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:16PM

01- (F-15) OFFICE

1. General Details:
Floor Area 57.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1700.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 37.0 6 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 33.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

111 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-11
-Air System Output Data
-Air System Input Data
-Space Description

112 of 207
Air System Sizing Summary for FCU-11
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM

Air System Information


Air System Name FCU-11 Number of zones 1
Equipment Class TERM Floor Area 52.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

113 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-11
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM

Air System Information


Air System Name FCU-11 Number of zones 1
Equipment Class TERM Floor Area 52.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 6.4 677 677 Jul 1500 1.7 52.0 13.03

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 7.3 7.0 24.5 / 17.4 14.7 / 14.0 - Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 1.8 20.7 / 23.3 - 677 0.378 0.282 31

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
01- (F-16) OFFICE 1 6.4 Jul 1500 677 1.7 52.0 13.03

114 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-11
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 687 - 9 m² - -
Wall Transmission 63 m² 386 - 63 m² 414 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 839 - 9 m² 751 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 33 m² 420 - 33 m² 362 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1300 W 1300 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1700 W 1700 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 578 33 10% 153 0
>> Total Zone Loads - 6362 363 - 1680 0
Zone Conditioning - 6159 363 - 1673 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 31 L/s 524 -53 31 L/s 442 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 282 - - -282 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6965 310 - 1833 0
Terminal Unit Cooling - 6965 317 - 0 0
Terminal Unit Heating - 0 - - 1833 -
>> Total Conditioning - 6965 317 - 1833 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

115 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-11 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM

1. General Details:
Air System Name FCU-11
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
01- (F-16) OFFICE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 677.4 - - 30.6

116 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-11 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:17PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 7.3 35.0 Auto-Sized - 0 - 2.96 12.8

117 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:17PM

01- (F-16) OFFICE

1. General Details:
Floor Area 52.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1700.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 37.0 6 0 0
N 35.0 3 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

3.2. Construction Types for Exposure N


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 33.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

118 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-12
-Air System Output Data
-Air System Input Data
-Space Description

119 of 207
Air System Sizing Summary for FCU-12
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:19PM

Air System Information


Air System Name FCU-12 Number of zones 1
Equipment Class TERM Floor Area 29.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

120 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-12
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:19PM

Air System Information


Air System Name FCU-12 Number of zones 1
Equipment Class TERM Floor Area 29.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 1.9 205 205 Aug 2200 0.3 29.0 7.06

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 2.5 2.3 25.5 / 18.0 14.8 / 14.1 - Aug 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.5 20.0 / 22.3 - 205 0.114 0.085 21

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
02- (S-02) SECRETARY 1 1.9 Aug 2200 205 0.3 29.0 7.06

121 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-12
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:19PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 76 - 2 m² - -
Wall Transmission 13 m² 91 - 13 m² 86 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 2 m² 187 - 2 m² 167 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 725 W 725 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 5 375 275 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 165 28 10% 25 0
>> Total Zone Loads - 1818 303 - 278 0
Zone Conditioning - 1827 303 - 278 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 21 L/s 363 -62 21 L/s 308 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 85 - - -85 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2275 240 - 500 0
Terminal Unit Cooling - 2275 241 - 0 0
Terminal Unit Heating - 0 - - 500 -
>> Total Conditioning - 2275 241 - 500 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

122 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-12 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:19PM

1. General Details:
Air System Name FCU-12
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
02- (S-02) SECRETARY x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 204.9 - - 21.2

123 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-12 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:19PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 2.5 35.0 Auto-Sized - 0 - 2.96 12.8

124 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:19PM

02- (S-02) SECRETARY

1. General Details:
Floor Area 29.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 15.0 2 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

125 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-13
-Air System Output Data
-Air System Input Data
-Space Description

126 of 207
Air System Sizing Summary for FCU-13
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:20PM

Air System Information


Air System Name FCU-13 Number of zones 1
Equipment Class TERM Floor Area 83.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

127 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-13
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:20PM

Air System Information


Air System Name FCU-13 Number of zones 1
Equipment Class TERM Floor Area 83.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 7.4 793 793 Aug 2200 1.5 83.0 9.56

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 8.8 8.3 24.9 / 17.7 14.9 / 14.2 - Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 1.8 20.3 / 22.5 - 793 0.443 0.330 50

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
01- (F-02) OFFICE 1 7.4 Aug 2200 793 1.5 83.0 9.56

128 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-13
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:20PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 268 - 7 m² - -
Wall Transmission 62 m² 413 - 62 m² 408 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 7 m² 653 - 7 m² 584 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 31 m² 395 - 31 m² 340 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2075 W 2075 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2000 W 2000 - 0 0 -
People 10 750 550 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 655 55 10% 133 0
>> Total Zone Loads - 7209 605 - 1465 0
Zone Conditioning - 7085 605 - 1372 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 50 L/s 851 -119 50 L/s 713 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 330 - - -330 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8266 486 - 1754 0
Terminal Unit Cooling - 8266 492 - 0 0
Terminal Unit Heating - 0 - - 1754 -
>> Total Conditioning - 8266 492 - 1754 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

129 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-13 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:20PM

1. General Details:
Air System Name FCU-13
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
01- (F-02) OFFICE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 793.1 - - 49.9

130 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-13 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:20PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 8.8 35.0 Auto-Sized - 0 - 2.96 12.8

131 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:20PM

02- (S-03) OFFICE MAN

1. General Details:
Floor Area 71.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 15.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 400.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 46.0 7 0 0
S 10.0 0 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERNAL WALL
1st Window Type WIND (4)

3.2. Construction Types for Exposure S


Wall Type EXTERNAL WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 71.0 0 0

4.1. Construction Types for Exposure H


Roof Type ROOF

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 22.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

132 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-14
-Air System Output Data
-Air System Input Data
-Space Description

133 of 207
Air System Sizing Summary for FCU-14
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:23PM

Air System Information


Air System Name FCU-14 Number of zones 1
Equipment Class TERM Floor Area 51.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

134 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-14
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:23PM

Air System Information


Air System Name FCU-14 Number of zones 1
Equipment Class TERM Floor Area 51.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 6.4 677 677 Aug 1500 1.9 51.0 13.28

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 7.2 6.9 24.5 / 17.4 14.7 / 14.0 - Aug 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 2.1 20.7 / 23.6 - 677 0.379 0.282 30

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
02- (S-08) OFFICE 1 6.4 Aug 1500 677 1.9 51.0 13.28

135 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-14
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:23PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.4 °C / 21.2 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 593 - 9 m² - -
Wall Transmission 61 m² 355 - 61 m² 403 -
Roof Transmission 51 m² 271 - 51 m² 361 -
Window Transmission 9 m² 799 - 9 m² 734 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 23 m² 285 - 23 m² 252 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1275 W 1275 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1700 W 1700 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 573 33 10% 175 0
>> Total Zone Loads - 6301 363 - 1925 0
Zone Conditioning - 6140 363 - 1942 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 30 L/s 508 -53 30 L/s 436 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 282 - - -282 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6930 310 - 2096 0
Terminal Unit Cooling - 6930 312 - 0 0
Terminal Unit Heating - 0 - - 2096 -
>> Total Conditioning - 6930 312 - 2096 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

136 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-14 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:21PM

1. General Details:
Air System Name FCU-14
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
02- (S-08) OFFICE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 677.4 - - 30.3

137 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-14 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:21PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 7.2 35.0 Auto-Sized - 0 - 2.96 12.8

138 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:22PM

02- (S-08) OFFICE

1. General Details:
Floor Area 51.0 m²
Avg. Ceiling Height 3.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1700.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 35.0 5 5 0
S 35.0 3 3 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (4)
2nd Window Type WIND (3)

3.2. Construction Types for Exposure S


Wall Type EXTERNAL WALL
1st Window Type WIND (4)
2nd Window Type WIND (3)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 51.0 0 0

4.1. Construction Types for Exposure H


Roof Type ROOF

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 23.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

139 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-15
-Air System Output Data
-Air System Input Data
-Space Description

140 of 207
Air System Sizing Summary for FCU-15
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM

Air System Information


Air System Name FCU-15 Number of zones 1
Equipment Class TERM Floor Area 28.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

141 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-15
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM

Air System Information


Air System Name FCU-15 Number of zones 1
Equipment Class TERM Floor Area 28.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 5.9 627 627 Aug 1500 0.9 28.0 22.40

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 6.5 6.3 24.5 / 17.4 14.8 / 14.2 - Aug 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.9 21.0 / 22.4 - 627 0.350 0.261 18

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
02- (S-09) CONTROL ROOM 1 5.9 Aug 1500 627 0.9 28.0 22.40

142 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-15
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m² 551 - 6 m² - -
Wall Transmission 23 m² 142 - 23 m² 148 -
Roof Transmission 28 m² 148 - 28 m² 198 -
Window Transmission 6 m² 513 - 6 m² 459 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 700 W 700 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3000 W 3000 - 0 0 -
People 4 300 220 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 535 22 10% 81 0
>> Total Zone Loads - 5890 242 - 886 0
Zone Conditioning - 5755 242 - 887 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 18 L/s 310 -36 18 L/s 267 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 261 - - -261 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6327 206 - 893 0
Terminal Unit Cooling - 6327 204 - 0 0
Terminal Unit Heating - 0 - - 893 -
>> Total Conditioning - 6327 204 - 893 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

143 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-15 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM

1. General Details:
Air System Name FCU-15
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
02- (S-09) CONTROL ROOM x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 627.1 - - 18.4

144 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-15 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 6.5 35.0 Auto-Sized - 0 - 2.96 12.8

145 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:22PM

02- (S-09) CONTROL ROOM

1. General Details:
Floor Area 28.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 3000.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 28.0 5 5 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (4)
2nd Window Type WIND (3)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 28.0 0 0

4.1. Construction Types for Exposure H


Roof Type ROOF

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

146 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-16
-Air System Output Data
-Air System Input Data
-Space Description

147 of 207
Air System Sizing Summary for FCU-16
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:25PM

Air System Information


Air System Name FCU-16 Number of zones 1
Equipment Class TERM Floor Area 51.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

148 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-16
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:25PM

Air System Information


Air System Name FCU-16 Number of zones 1
Equipment Class TERM Floor Area 51.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 4.2 450 450 Aug 1500 0.8 51.0 8.82

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 5.2 4.9 25.0 / 17.6 14.7 / 14.0 - Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 1.0 20.3 / 22.4 - 450 0.251 0.187 30

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
02- (S-12) ARCHIVE 1 4.2 Aug 1500 450 0.8 51.0 8.82

149 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-16
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:25PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 324 - 3 m² - -
Wall Transmission 17 m² 106 - 17 m² 110 -
Roof Transmission 51 m² 270 - 51 m² 361 -
Window Transmission 3 m² 308 - 3 m² 275 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1275 W 1275 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1100 W 1100 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 383 33 10% 75 0
>> Total Zone Loads - 4215 363 - 821 0
Zone Conditioning - 4148 363 - 768 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 30 L/s 514 -60 30 L/s 433 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 187 - - -187 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4850 303 - 1014 0
Terminal Unit Cooling - 4850 307 - 0 0
Terminal Unit Heating - 0 - - 1014 -
>> Total Conditioning - 4850 307 - 1014 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

150 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-16 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM

1. General Details:
Air System Name FCU-16
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
02- (S-12) ARCHIVE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 449.6 - - 30.3

151 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-16 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:24PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 5.2 35.0 Auto-Sized - 0 - 2.96 12.8

152 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:26PM

02- (S-12) ARCHIVE

1. General Details:
Floor Area 51.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1100.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 20.0 3 3 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (4)
2nd Window Type WIND (3)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 51.0 0 0

4.1. Construction Types for Exposure H


Roof Type ROOF

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

153 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-17
-Air System Output Data
-Air System Input Data
-Space Description

154 of 207
Air System Sizing Summary for FCU-17
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:26PM

Air System Information


Air System Name FCU-17 Number of zones 1
Equipment Class TERM Floor Area 402.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

155 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-17
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:26PM

Air System Information


Air System Name FCU-17 Number of zones 1
Equipment Class TERM Floor Area 402.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 21.7 2307 2307 Aug 2200 5.7 402.0 5.74

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 24.1 23.1 24.4 / 17.4 14.8 / 14.2 - Aug 2200

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 6.7 20.1 / 22.8 - 2307 1.289 0.961 178

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
02- (S-20) CORR 1 1.0 Jul 0400 108 0.2 30.0 3.59
02- (S-11,10) WAT.&CORR 1 1.6 Jul 0400 173 0.3 37.0 4.66
02- (S-15) MAIN LOBB 1 6.5 Jul 1500 691 1.1 217.0 3.19
02- (S-15) MULTI PURPOSE 1 13.0 Aug 2200 1387 4.0 118.0 11.75

156 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-17
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:26PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 2200 HEATING DATA AT DES HTG
COOLING OA DB / WB 31.2 °C / 18.9 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 53 m² 5988 - 53 m² - -
Wall Transmission 29 m² 226 - 29 m² 191 -
Roof Transmission 185 m² 1013 - 185 m² 1310 -
Window Transmission 53 m² 1344 - 53 m² 1842 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 65 m² 166 - 65 m² 222 -
Partitions 146 m² 1198 - 146 m² 1602 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 8040 W 8040 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 23 1725 1265 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1970 127 10% 517 0
>> Total Zone Loads - 21671 1392 - 5683 0
Zone Conditioning - 20675 1392 - 5133 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 178 L/s 1454 -384 178 L/s 2530 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 961 - - -961 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 23090 1008 - 6702 0
Terminal Unit Cooling - 23090 1019 - 0 0
Terminal Unit Heating - 0 - - 6702 -
>> Total Conditioning - 23090 1019 - 6702 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

157 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-17 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:26PM

1. General Details:
Air System Name FCU-17
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
02- (S-20) CORR x1
02- (S-11,10) WAT.&CORR x1
02- (S-15) MAIN LOBB x1
02- (S-15) MULTI PURPOSE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

158 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-17 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:26PM

1 2307.4 - - 178.1

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 24.1 35.0 Auto-Sized - 0 - 2.96 12.8

159 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:26PM

02- (S-11,10) WAT.&CORR

1. General Details:
Floor Area 37.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 37.0 0 0

4.1. Construction Types for Exposure H


Roof Type ROOF

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

160 of 207
Hourly Analysis Program v.4.4 Page 1 of 4
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:26PM

02- (S-15) MAIN LOBB

1. General Details:
Floor Area 217.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 65.0 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 30.0 °C
Ambient at Space Max Temp. 39.8 °C
Unconditioned Space Min Temp. 15.0 °C
Ambient at Space Min Temp. 7.1 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 73.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

161 of 207
Hourly Analysis Program v.4.4 Page 2 of 4
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:26PM

02- (S-15) MULTI PURPOSE

1. General Details:
Floor Area 118.0 m²
Avg. Ceiling Height 3.2 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 82.0 53 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERNAL WALL
1st Window Type CW

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 118.0 0 0

4.1. Construction Types for Exposure H


Roof Type ROOF

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 0.0 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 30.0 °C
Ambient at Space Max Temp. 39.8 °C
Unconditioned Space Min Temp. 15.0 °C
Ambient at Space Min Temp. 7.1 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 73.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

162 of 207
Hourly Analysis Program v.4.4 Page 3 of 4
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:26PM

02- (S-20) CORR

1. General Details:
Floor Area 30.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2.0 People
Wattage 20.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 30.0 0 0

4.1. Construction Types for Exposure H


Roof Type ROOF

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

163 of 207
Hourly Analysis Program v.4.4 Page 4 of 4
FCU-18
-Air System Output Data
-Air System Input Data
-Space Description

164 of 207
Air System Sizing Summary for FCU-18
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:32PM

Air System Information


Air System Name FCU-18 Number of zones 1
Equipment Class TERM Floor Area 29.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

165 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-18
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:32PM

Air System Information


Air System Name FCU-18 Number of zones 1
Equipment Class TERM Floor Area 29.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 2.3 242 242 Aug 2200 0.5 29.0 8.35

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 3.0 2.7 25.6 / 18.1 15.0 / 14.2 - Aug 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.8 19.8 / 22.8 - 242 0.135 0.101 26

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
02- (S-24) DEP. HEAD 1 2.3 Aug 2200 242 0.5 29.0 8.35

166 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-18
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:32PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 84 - 2 m² - -
Wall Transmission 10 m² 68 - 10 m² 64 -
Roof Transmission 29 m² 154 - 29 m² 205 -
Window Transmission 2 m² 205 - 2 m² 183 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 725 W 725 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 7 525 385 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 196 39 10% 45 0
>> Total Zone Loads - 2157 424 - 499 0
Zone Conditioning - 2134 424 - 496 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 26 L/s 448 -90 26 L/s 376 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 101 - - -101 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2683 333 - 771 0
Terminal Unit Cooling - 2683 332 - 0 0
Terminal Unit Heating - 0 - - 771 -
>> Total Conditioning - 2683 332 - 771 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

167 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-18 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:32PM

1. General Details:
Air System Name FCU-18
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
02- (S-24) DEP. HEAD x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 242.2 - - 26.2

168 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-18 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:32PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 3.0 35.0 Auto-Sized - 0 - 2.96 12.8

169 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:28PM

02- (S-24) DEP. HEAD

1. General Details:
Floor Area 29.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 7.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 12.0 2 2 0

3.1. Construction Types for Exposure W


Wall Type EXTERNAL WALL
1st Window Type WIND (4)
2nd Window Type WIND (3)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 29.0 0 0

4.1. Construction Types for Exposure H


Roof Type ROOF

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

170 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-19
-Air System Output Data
-Air System Input Data
-Space Description

171 of 207
Air System Sizing Summary for FCU-19
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM

Air System Information


Air System Name FCU-19 Number of zones 1
Equipment Class TERM Floor Area 84.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

172 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-19
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM

Air System Information


Air System Name FCU-19 Number of zones 1
Equipment Class TERM Floor Area 84.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 8.4 892 892 Aug 2200 1.8 84.0 10.62

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 9.5 9.0 24.7 / 17.6 15.0 / 14.3 - Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 2.1 20.5 / 22.8 - 892 0.499 0.372 50

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
02- (S-23) OFFICE 1 8.4 Aug 2200 892 1.8 84.0 10.62

173 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-19
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 295 - 8 m² - -
Wall Transmission 61 m² 416 - 61 m² 403 -
Roof Transmission 84 m² 445 - 84 m² 595 -
Window Transmission 8 m² 718 - 8 m² 642 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2100 W 2100 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2500 W 2500 - 0 0 -
People 10 750 550 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 722 55 10% 164 0
>> Total Zone Loads - 7946 605 - 1804 0
Zone Conditioning - 7802 605 - 1795 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 50 L/s 862 -126 50 L/s 724 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 372 - - -372 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 9035 479 - 2147 0
Terminal Unit Cooling - 9035 502 - 0 0
Terminal Unit Heating - 0 - - 2147 -
>> Total Conditioning - 9035 502 - 2147 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

174 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-19 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM

1. General Details:
Air System Name FCU-19
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
02- (S-23) OFFICE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 892.2 - - 50.2

175 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-19 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 9.5 35.0 Auto-Sized - 0 - 2.96 12.8

176 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:28PM

02- (S-23) OFFICE

1. General Details:
Floor Area 84.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 10.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 2500.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 59.0 7 7 0
N 10.0 0 0 0

3.1. Construction Types for Exposure W


Wall Type EXTERNAL WALL
1st Window Type WIND (4)
2nd Window Type WIND (3)

3.2. Construction Types for Exposure N


Wall Type EXTERNAL WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 84.0 0 0

4.1. Construction Types for Exposure H


Roof Type ROOF

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

177 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-20
-Air System Output Data
-Air System Input Data
-Space Description

178 of 207
Air System Sizing Summary for FCU-20
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM

Air System Information


Air System Name FCU-20 Number of zones 1
Equipment Class TERM Floor Area 24.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

179 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-20
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM

Air System Information


Air System Name FCU-20 Number of zones 1
Equipment Class TERM Floor Area 24.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 1.6 166 166 Jul 1600 0.5 24.0 6.93

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 2.0 1.8 25.3 / 17.8 14.8 / 14.0 - Aug 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.6 20.1 / 23.7 - 166 0.093 0.069 15

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
02- (S-18) DEP. HEAD 1 1.6 Jul 1600 166 0.5 24.0 6.93

180 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-20
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.4 °C / 21.2 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 12 m² 79 - 12 m² 79 -
Roof Transmission 24 m² 127 - 24 m² 170 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 15 m² 190 - 15 m² 165 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 600 W 600 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 3 225 165 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 142 17 10% 41 0
>> Total Zone Loads - 1563 182 - 455 0
Zone Conditioning - 1512 182 - 481 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 15 L/s 245 -35 15 L/s 212 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 69 - - -69 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1826 147 - 624 0
Terminal Unit Cooling - 1826 148 - 0 0
Terminal Unit Heating - 0 - - 624 -
>> Total Conditioning - 1826 148 - 624 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

181 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-20 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM

1. General Details:
Air System Name FCU-20
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
02- (S-18) DEP. HEAD x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 166.4 - - 14.7

182 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-20 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:31PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 2.0 35.0 Auto-Sized - 0 - 2.96 12.8

183 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:28PM

02- (S-18) DEP. HEAD

1. General Details:
Floor Area 24.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 200.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 12.0 0 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 24.0 0 0

4.1. Construction Types for Exposure H


Roof Type ROOF

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 15.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

184 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-21
-Air System Output Data
-Air System Input Data
-Space Description

185 of 207
Air System Sizing Summary for FCU-21
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:30PM

Air System Information


Air System Name FCU-21 Number of zones 1
Equipment Class TERM Floor Area 57.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

186 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-21
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:30PM

Air System Information


Air System Name FCU-21 Number of zones 1
Equipment Class TERM Floor Area 57.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 5.9 627 627 Aug 1500 1.2 57.0 11.00

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 6.8 6.5 24.7 / 17.5 14.8 / 14.1 - Aug 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 1.4 20.6 / 22.8 - 627 0.350 0.261 32

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
02- (S-19) OFFICE 1 5.9 Aug 1500 627 1.2 57.0 11.00

187 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-21
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:30PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m² 601 - 6 m² - -
Wall Transmission 31 m² 196 - 31 m² 204 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 6 m² 560 - 6 m² 500 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 33 m² 420 - 33 m² 362 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1425 W 1425 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1700 W 1700 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 535 33 10% 107 0
>> Total Zone Loads - 5887 363 - 1173 0
Zone Conditioning - 5675 363 - 1203 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 32 L/s 547 -65 32 L/s 463 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 261 - - -261 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6483 298 - 1405 0
Terminal Unit Cooling - 6483 313 - 0 0
Terminal Unit Heating - 0 - - 1405 -
>> Total Conditioning - 6483 313 - 1405 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

188 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-21 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:30PM

1. General Details:
Air System Name FCU-21
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
02- (S-19) OFFICE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 626.9 - - 32.1

189 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-21 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:30PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 6.8 35.0 Auto-Sized - 0 - 2.96 12.8

190 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:28PM

02- (S-19) OFFICE

1. General Details:
Floor Area 57.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1700.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 37.0 6 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 33.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

191 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-22
-Air System Output Data
-Air System Input Data
-Space Description

192 of 207
Air System Sizing Summary for FCU-22
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:29PM

Air System Information


Air System Name FCU-22 Number of zones 1
Equipment Class TERM Floor Area 52.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

193 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Zone Sizing Summary for FCU-22
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:29PM

Air System Information


Air System Name FCU-22 Number of zones 1
Equipment Class TERM Floor Area 52.0 m²
Air System Type SPLT-FC Location NAGRAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s Peak zone sensible load Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m²) L/(s-m²)
Zone 1 6.4 677 677 Jul 1500 1.7 52.0 13.03

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 7.3 7.0 24.5 / 17.4 14.7 / 14.0 - Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 1.8 20.7 / 23.3 - 677 0.378 0.282 31

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
02- (S-21) OFFICE 1 6.4 Jul 1500 677 1.7 52.0 13.03

194 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Air System Design Load Summary for FCU-22
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:29PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.8 °C / 21.3 °C HEATING OA DB / WB 7.1 °C / 0.3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 687 - 9 m² - -
Wall Transmission 63 m² 386 - 63 m² 414 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 839 - 9 m² 751 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 33 m² 420 - 33 m² 362 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1300 W 1300 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1700 W 1700 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 578 33 10% 153 0
>> Total Zone Loads - 6362 363 - 1680 0
Zone Conditioning - 6159 363 - 1673 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 31 L/s 524 -53 31 L/s 442 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 282 - - -282 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6965 310 - 1833 0
Terminal Unit Cooling - 6965 317 - 0 0
Terminal Unit Heating - 0 - - 1833 -
>> Total Conditioning - 6965 317 - 1833 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

195 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
FCU-22 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:29PM

1. General Details:
Air System Name FCU-22
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Ventilation System Components:


(Common Ventilation System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
02- (S-21) OFFICE x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 22.0 °C
Cooling T-stat: Unocc. 26.0 °C
Heating T-stat: Occ. 21.0 °C
Heating T-stat: Unocc. 18.0 °C
T-stat Throttling Range 2.00 °K

Thermostat Schedule THERMO


Unoccupied Cooling is Not Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule * * MAMJJASO* *

Heating Coil:
Design Supply Temperature 43.3 °C
Heating Source Electric Resistance
Schedule JF* * * * * * * * ND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:


Zone All
Terminal Type Fan Coil
Minimum Airflow 0.00 L/s/person
Fan Performance 250 Pa
Fan Overall Efficiency 60 %

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 43.3 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 °K
Hot Water Delta-T 11.1 °K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 677.4 - - 30.6

196 of 207
Hourly Analysis Program v.4.4 Page 1 of 2
FCU-22 Input Data
Project Name: MOSA (13503) 08/21/2011
Prepared by: Zuhair Fayez Partnership 05:29PM

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity ARI


Maximum Cooling Oversizing Compressor + Performance Conventional
Load Design OAT Equipment Capacity Factor OD Fan Power Rating Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) (EER) (°C)
All 7.3 35.0 Auto-Sized - 0 - 2.96 12.8

197 of 207
Hourly Analysis Program v.4.4 Page 2 of 2
Space Input Data
MOSA (13503) 08/21/2011
Zuhair Fayez Partnership 05:28PM

02- (S-21) OFFICE

1. General Details:
Floor Area 52.0 m²
Avg. Ceiling Height 3.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 2.5 L/s/person
OA Requirement 2 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Std 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6.0 People
Wattage 25.00 W/m² Activity Level User defined
Ballast Multiplier 1.00 Sensible 75.0 W/person
Schedule LIGHT Latent 55.0 W/person
Schedule PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 0 W
Schedule None Schedule None
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 1700.0 Watts
Schedule EQUPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 37.0 6 0 0
N 35.0 3 0 0

3.1. Construction Types for Exposure E


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

3.2. Construction Types for Exposure N


Wall Type EXTERNAL WALL
1st Window Type WIND (5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 33.0 m²
U-Value 1.829 W/(m²-°K)
Uncondit. Space Max Temp 30.0 °C
Ambient at Space Max Temp 39.8 °C
Uncondit. Space Min Temp 15.0 °C
Ambient at Space Min Temp 7.1 °C

198 of 207
Hourly Analysis Program v.4.4 Page 1 of 1
Ventilation Calculations

199 of 207
Zuhair Fayez Partnership
Made by :ASIS Date 20/08/2011 Project Ministry Of Social Affairs
Bldg. J10-13503
Checked by : SMM Date 20/08/2011 Contract : Sheet No. 1 of 2
Revised by : SMM Date : Section : HVAC Calc. No.
Checked by HAHA Date : Job No. J10-13503 File
Subject : VENTILATION VOLUME FLOW RATE CALCULATIONS
Room Dimensions Fan Selection Data
Space Name & No. Length Width Height Volume No. of Air Air flow rate
m m m m3 change/Hour LPS

TOILET & WASHES (B1-G-15) 4.40 3.80 3.00 50.2 12 167


TOILET & WASHES (B1-G-20) 4.40 3.80 3.00 50.2 12 167
TOILET & WASHES (B1-1-10) 10.00 3.00 3.00 90.0 12 300
TOILET & WASHES (BI-2-13) 10.00 3.00 3.00 90.0 12 300
JANTOR (B1-1-12) 2.00 1.50 3.00 9.0 12 30
JANTOR (B1-2-17) 2.00 1.50 3.00 9.0 12 30
994
EF-B1-01 SAY 995 LPS

TOILET (B1-2-04) 2.50 2.50 3.00 18.8 10 52


52
EF-B1-02
EF B1 02 SAY 55 LPS

SERVICE (B1-2-06) 2.50 2.50 3.00 18.8 10 52


52
EF-B1-03 SAY 55 LPS

ENTRANCE (G&F&S) 535.00 1.00 3.25 1738.8 6 2898

SMEF-B1-01 SAY 2900 LPS

TOILET (B2-01) 7.00 3.20 3.00 67.2 12 224


224
EF-B2-01 SAY 225 LPS

TOILET (B3-01) 7.00 3.20 3.00 67.2 12 224


224
EF-B3-01 SAY 225 LPS

TOILET (B4-02) 2.50 1.70 3.00 12.8 10 35


35
EF-B4-01 SAY 35 LPS

TRANSFORMAR (B5-01) 6.00 4.00 3.25 78.0 60 1300


1300
EF-B5-01 SAY 2 FANS 650 LPS EACH

TRANSFORMAR (B5-01) 6.00 4.00 3.25 78.0 6 130


130
EF-B5-02 SAY 130 LPS

200 of 207
Zuhair Fayez Partnership
Made by :ASIS Date 20/08/2011 Project Ministry Of Social Affairs
Bldg. J10-13503
Checked by : SMM Date 20/08/2011 Contract : Sheet No. 2 of 2
Revised by : SMM Date : Section : HVAC Calc. No.
Checked by HAHA Date : Job No. J10-13503 File
Subject : VENTILATION VOLUME FLOW RATE CALCULATIONS
Room Dimensions Fan Selection Data
Space Name & No. Length Width Height Volume No. of Air Air flow rate
m m m m3 change/Hour LPS

ELEC (B5-02)
ELEC. (B5 02) 4 00
4.00 3 00
3.00 3 25
3.25 39 0
39.0 6 65
65
EF-B5-03 SAY 65 LPS

GENERATOR (B5-03) 4.00 4.50 3.25 58.5 6 98


98
EF-B5-04 SAY 100 LPS

TOILET (B6-04 ) 2.50 1.70 3.00 12.8 10 35


35
EF-B6-01 SAY 35 LPS

SERVICE (B6-07) 2.50 1.70 3.00 12.8 10 35


35
EF-B6-02 SAY 35 LPS

SITE PUMPS ROOM 10.00 4.50 3.50 157.5 15 656


656
EF-01 SAY 660 LPS

201 of 207
External Static Pressure
Calculations

202 of 207
Zuhair Fayez Partnership
Made by :ASIS Date : 21.08.11 Project Ministry Of Social Affairs
Bldg. 503
Checked by : SMM Date : 21.08.11 Contract : Sheet No. 1 of 2
Revised by : SMM Date : Section : HVAC Calc. No.
Checked by : Date : Job No. J10-13503 File
Subject : EXTERNAL STATIC LOSSES SUMMARY

PAC-01 EXTERNAL STATIC PRESSURE CALCULATION :

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 40 + 12
= 52 M
Supply duct static losses = Total equ. length x Δ Pa/M
= 52 x 0.8
= 41.6 Pa

Additional Static Losses On Supply Air Duct :


1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
5- Fire Damper 25 Pa
6- Flexible Duct 25 Pa

Total Supply Duct Static Losses = 191.6 Pa

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 35 + 14
= 49 M
Return duct static losses = Total equ. length x Δ Pa/M
49 x 0.7
34.3 Pa
Additional Static Losses On Return Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- Fire Damper 25 Pa
5- Return Plenum & B.M.O. 25 Pa

Total Return Duct Static Losses = 184.3 Pa

Total external static losses = Total supply duct losses + Total return duct losses
Total external static losses = 375.9 Pa
Adding 10% factor of safety = 37.59 Pa
Total external static losses = 413.49 Pa

Say 415 Pa

203 of 207
Zuhair Fayez Partnership
Made by :ASIS Date : 21.08.11 Project Ministry Of Social Affairs
Bldg. 503
Checked by : SMM Date : 21.08.11 Contract : Sheet No. 1 of 2
Revised by : SMM Date : Section : HVAC Calc. No.
Checked by : Date : Job No. J10-13503 File
Subject : EXTERNAL STATIC LOSSES SUMMARY

PAC-02 EXTERNAL STATIC PRESSURE CALCULATION :

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 40 + 12
= 52 M
Supply duct static losses = Total equ. length x Δ Pa/M
= 52 x 0.8
= 41.6 Pa

Additional Static Losses On Supply Air Duct :


1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
5- Fire Damper 25 Pa
6- Flexible Duct 25 Pa

Total Supply Duct Static Losses = 191.6 Pa

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 35 + 14
= 49 M
Return duct static losses = Total equ. length x Δ Pa/M
49 x 0.7
34.3 Pa
Additional Static Losses On Return Air Duct :
1- Sound Attenuator 50 Pa
2- Volume Damper 25 Pa
3- Ceiling Diffuser 25 Pa
4- Fire Damper 25 Pa
5- Return Plenum & B.M.O. 25 Pa

Total Return Duct Static Losses = 184.3 Pa

Total external static losses = Total supply duct losses + Total return duct losses
Total external static losses = 375.9 Pa
Adding 10% factor of safety = 37.59 Pa
Total external static losses = 413.49 Pa

Say 415 Pa

204 of 207
Air Balance

205 of 207
Zuhair Fayez Partnership
Made by :ASIS Date : 21.08.11 Project Ministry Of Social Affairs
Bldg. 503
Checked by : SMM Date : 21.08.11 Contract : Sheet No. 1 of 2
Revised by : SMM Date : Section : HVAC Calc. No.
Checked by : Date : Job No. J10-13503 File
Subject : Zone [Load/M3 , Air Balance & No. of Air Change/Hr.]

INPUT DATA :

ZONE NO. : 01

ZONE DESCRIPTION : GROUND FLOOR

A/C UNIT : PAC-01

ZONE AREA = 322 M²

ZONE HEIGHT= 3 M

ZONE TOTAL COOLING LOAD = 53.50 KW

SUPPLY AIR FLOW RATE = 3540 LPS

FRESH AIR FLOW RATE = 470 LPS

ZONE EXHAUST AIR FLOW RATE = 310 LPS EF-01 = 310 LPS(part)

OUTPUT DATA :

ZONE VOLUME = 966.00 M3

TOTAL LOAD/UNIT VOLUME = 55.38 W/M3

PRESSURIZATION PERCENT = 4.52 %

AIR CHANGE / HOUR = 13.19 NO.

FRESH AIR CHANGE / HOUR = 1.75 NO.

206 of 207
Zuhair Fayez Partnership
Made by :ASIS Date : 21.08.11 Project Ministry Of Social Affairs
Bldg. 503
Checked by : SMM Date : 21.08.11 Contract : Sheet No. 1 of 2
Revised by : SMM Date : Section : HVAC Calc. No.
Checked by : Date : Job No. J10-13503 File
Subject : Zone [Load/M3 , Air Balance & No. of Air Change/Hr.]

INPUT DATA :

ZONE NO. : 02

ZONE DESCRIPTION : GROUND FLOOR

A/C UNIT : PAC-02

ZONE AREA = 323 M²

ZONE HEIGHT= 3 M

ZONE TOTAL COOLING LOAD = 53.20 KW

SUPPLY AIR FLOW RATE = 3540 LPS

FRESH AIR FLOW RATE = 470 LPS

ZONE EXHAUST AIR FLOW RATE = 310 LPS EF-02 = 310 LPS(part)

OUTPUT DATA :

ZONE VOLUME = 969.00 M3

TOTAL LOAD/UNIT VOLUME = 54.90 W/M3

PRESSURIZATION PERCENT = 4.52 %

AIR CHANGE / HOUR = 13.15 NO.

FRESH AIR CHANGE / HOUR = 1.75 NO.

207 of 207