Professional Documents
Culture Documents
Introduction
Atmospheric air makes up the environment in almost every type of air conditioning system.
Hence a thorough understanding of the properties of atmospheric air and the ability to analyze
various processes involving air is fundamental to air conditioning design.
Psychrometry is the study of the properties of mixtures of air and water vapor.
Atmospheric air is a mixture of many gases plus water vapor and a number of pollutants. The
amount of water vapor and pollutants vary from place to place. The concentration of water vapor
and pollutants decrease with altitude, and above an altitude of about 10 km, atmospheric air
consists of only dry air. The pollutants have to be filtered out before processing the air. Hence,
what we process is essentially a mixture of various gases that constitute air and water vapor. This
mixture is known as moist air.
At a given temperature and pressure the dry air can only hold a certain maximum amount of
moisture. When the moisture content is m aximum, then the air is known as saturated air, which
is established by a neutral equilibrium between the moist air and the liquid or solid phases of
water.
Methods for estimating properties of moist air
Substituting the values of the gas constants of water vapor and air Rv and Ra in the above
equation
Dew-point temperature: If unsaturated moist air is cooled at constant pressure, then the
temperature at which the moisture in the air begins to condense is known as dew-point
temperature (DPT) of air. An approximate equation for dew-point temperature is given by
Wet-bulb temperature (WBT): It is the temperature registered by a thermometer when the bulb
is covered by a wetted wick and is exposed to a current of rapidly moving air (twb).
Degree of saturation : The degree of saturation is the ratio of the humidity ratio W to the
humidity ratio of a saturated mixture Ws at the same temperature and pressure,
Enthalpy: The enthalpy of moist air is the sum of the enthalpy of the dry air and the enthalpy of
the water vapor. The enthalpy of moist air is given by:
Humid specific heat: From the equation for enthalpy of moist air, the humid specific heat of
moist air can be written as:
Since the second term in the above equation is very small compared to the first term, for all
practical purpose, the humid specific heat of moist air,cpm , can be taken as 1.0216kJ/kg dry air K
Psychrometric chart
In relation to the psychrometric chart, these terms can quickly indicate many things about the
condition of air, for example :
1. If dry bulb and wet bulb temperatures are known, the relative humidity can be read from the
chart.
2. If the dry bulb and relative humidity are known, the wet bulb temperature can be determined.
3. If wet bulb temperature and relative humidity are known, the dry bulb temperature can be
found.
4. If wet bulb and dry bulb temperatures are known, the dew point can be found.
5. If wet bulb and relative humidity are known, dew point can be read from the chart.
6. If dry-bulb and relative humidity are known, dew point can be found.
Calculation of psychrometric properties from p, DBT and WBT:
As mentioned before, to fix the thermodynamic state of moist air, we need to know three
independent properties. The properties that are relatively easier to measure, are: the barometric
pressure, dry-bulb temperature and wet-bulb temperature. For a given barometric pressure,
knowing the dry bulb and wet bulb temperatures, all other properties can be easily calculated
from the psychrometric equations. The following are the empirical relations for the vapor
pressure of water in moist air:
Psychrometric Processes
Introduction
In the design and analysis of air conditioning plants, the fundamental requirement is to identify
the various processes being performed on air. Once identified, the processes can be analyzed by
applying the laws of conservation of mass and energy. All these processes can be plotted easily
on a psychrometric chart. This is very useful for quick visualization and also for identifying the
changes taking place in important properties such as temperature, humidity ratio, enthalpy etc.
The important processes that air undergoes in a typical air conditioning plant are discussed
below.
Important psychrometric processes:
a) Sensible cooling:
During this process, the moisture content of air remains constant but its temperature decreases as
it flows over a cooling coil. For moisture content to remain constant, the surface of the cooling
coil should be dry and its surface temperature should be greater than the dew point temperature
of air. If the cooling coil is 100% effective, then the exit temperature of air will be equal to the
coil temperature. However, in practice, the exit air temperature will be higher than the cooling
coil temperature. The figure below shows the sensible cooling process O-A on a psychrometric
chart. The heat transfer rate during this process is given by
Where cpm is the humid specific heat (1.0216 kJ/kg dry air) and m is the mass flow rate of dry air
(kg/s). The figure below shows the sensible heating process on a psychrometric chart.
the 2nd term on the RHS of the above equation is normally small compared to the other terms,
so it can be neglected. Hence,
It can be observed that the cooling and de-humidification process involves both latent and
sensible heat transfer processes, hence, the total, latent and sensible heat transfer rates (Qt , Ql
and Qs) can be written as:
By separating the total heat transfer rate from the cooling coil into sensible and latent heat
transfer rates, a useful parameter called Sensible Heat Factor (SHF) is defined. SHF is defined as
the ratio of sensible to total heat transfer rate, i.e.,
From the above equation, one can deduce that a SHF of 1.0 corresponds to no latent heat transfer
and a SHF of 0 corresponds to no sensible heat transfer. A SHF of 0.75 to 0.80 is quite common
in air conditioning systems in a normal dry-climate. A lower value of SHF, say 0.6, implies a
high latent heat load such as that occurs in a humid climate.
In fig. 5 the temperature t s is the effective surface temperature of the cooling coil, and is known
as apparatus dew-point (ADP) temperature. In an ideal situation, when all the air comes in
perfect contact with the cooling coil surface, then the exit temperature of air will be same as
ADP of the coil. However, in actual case the exit temperature of air will always be greater than
the apparatus dew-point temperature due to boundary layer development as air flows over the
cooling coil surface and also due to temperature variation along the fins etc. Hence, we can
define a by-pass factor (BPF) as:
It can be easily seen that, higher the by-pass factor larger will be the difference between air outlet
temperature and the cooling coil temperature. When BPF is 1.0, all the air by-passes the coil and
there will not be any cooling or de-humidification. In practice, the by-pass factor can be
increased by increasing the number of rows in a cooling coil or by decreasing the air velocity or
by reducing the fin pitch.
d) Heating and Humidification (Process O-D):
During winter it is essential to heat and humidify the room air for comfort. As shown in Fig. 6,
this is normally done by first sensibly heating the air and then adding water vapor to the air
stream through steam nozzles as shown in the figure.
Where Q is the heat supplied through the heating coil and hw is the enthalpy of the steam. Since
this process also involves simultaneous heat and mass transfer, we can define a sensible heat
factor for the process in a way similar to that of a cooling and dehumidification process.
e) Cooling & humidification (Process O-E):
As the name implies, during this process, the air temperature drops and its humidity increases.
This process is shown in Fig.7. As shown in the figure, this can be achieved by spraying cool
water in the air stream. The temperature of water should be lower than the dry-bulb temperature
of air but higher than its dew-point temperature to avoid condensation (TDPT < Tw < TO).
Where Qt is the total heat transfer rate (sensible + latent) to the building, hi and
hs are the specific enthalpies of return air and supply air, respectively.
Compared to the conventional refrigeration based air conditioning systems, the amount of
airflow rate required for a given amount of cooling is much larger in case of evaporative cooling
systems. As shown by the above equation and also from Fig. 10, it is clear that for a given
outdoor dry bulb temperature, as the moisture content of outdoor air increases, the required
amount of supply air flow rate increases rapidly. And at a threshold moisture content value, the
evaporative coolers cannot provide comfort as the cooling and humidification line lies above the
conditioned space condition ‘i’. Thus evaporative coolers are very useful essentially in dry
climates, whereas the conventional refrigeration based air conditioning systems can be used in
any type of climate.
2. Indirect evaporative cooling system:
The figure below shows the schematic of a basic, indirect evaporative cooling system and the
process on a psychrometric chart. As shown in the figure, in an indirect evaporative cooling
process, two streams of air – primary and secondary are used. The primary air stream becomes
cooled and humidified by coming in direct contact with the wetted surface (o-o’), while the
secondary stream which is used as supply air to the conditioned space, decreases its temperature
by exchanging only sensible heat with the cooled and humidified air stream (o-s). Thus the
moisture content of the supply air remains constant in an indirect evaporative cooling system,
while its temperature drops. Obviously, everything else remaining constant, the temperature drop
obtained in a direct evaporative cooling system is larger compared to that obtained in an indirect
system, in addition the direct evaporative cooling system is also simpler and hence, relatively
inexpensive. However, since the moisture content of supply air remains constant in an indirect
evaporation process, this may provide greater degree of comfort in regions with higher humidity
ratio. The commercially available indirect evaporative coolers have saturation efficiency as high
as 80%.