WRT-10D: Winding Resistance Tester With Demagnetisation
WRT-10D: Winding Resistance Tester With Demagnetisation
111-1405, St-Jean-Baptiste
Québec (Qc)
Canada G2E 5K2
Tél : (418) 877-7701
Fax : (418) 877-7787
E-mail : mkt@ndbtech.com
Web : www.ndbtech.com
WRT-10D
Winding Resistance Tester with Demagnetisation
The WRT-10D is a high performance winding resistance tester de-
signed for Power Transformer and large motor applications.
Winding resistance testing is an • Rugged, highly regulated and The WRT-10D injects a DC current
important part of a power trans- filtered output current source for through the windings & measures
former maintenance or a manufac- fast stabilized measurements the voltage drop. The instrument
turing quality assurance program. • High Accuracy 0.1% of rdg calculates the resistance R= E / I.
Transformers & large motors are • High resolution with 4 ½ display, The challenge in winding resistance
subject to vibrations, overloading 0.1µΩ measurements is that the voltage
and environments with large tem- • Large, Color LCD display. across an inductor is defined by V
perature variations. Winding resis- • Full QWERTY keyboard for easy = L (di/dt), where L is the induc-
tance measurements can assure onsite data entry. tance of the winding & (di/dt) is rate
that the connections are made cor- of change of current. Therefore
• Large internal memory
rectly and that no opens or shorts small changes in the current, as
• Results for each transformer are
are present. Tap changers of may be caused by ripple or poor
stored in a file along with the
power transformers are a particu- regulation, can make it impossible
serial number and other details
larly critical element of a power to measure the DC resistance. The
system. The WRT is very effective • Reporting software automatically
generates a finished report from highly regulated and filtered current
in detecting Tap changer abnor- output of the WRT-10D allows for
malities. PC
winding resistance measurements
• Built-in thermal Printer
on very large power transformers.
Applications • Automatic or Manual Remote
• Power Transformers Tap Changer circuit Specifications
• Instrument Transformers • Stabilized reading indicator
• Protection against overvoltage • Included PC Software for data
• Voltage Regulators
Transients transfer, data analysis.
• Rotating Machines
• Filtered Input channels eliminat- • PC interface: RS-232C, & USB.
ing substation noises influence • Housing/case with wheels and
• Timed mode for logging heat run retractable handle
testing • 50 feet test leads cables
• Multi-language interface • High speed sensors will react to
• H o u s i n g i nt er n a l s to r a g e interruptions if the Load Tap
compartment for accessories or Changer is not operating correctly
leads • Timed mode with user defined
logging intervals from 5 sec to
100 sec
High voltage Power Transformer
Compartment for accessories or leads
Technical specifications
Power Input 90 to 132VAC 50/60 Hz
198 to 256VAC 50/60 Hz, 550VA max
Standard Accessories:
- Test Leads (50 Ft / 15m)
- Jumper Lead (30Ft / 9m)
- Tap Changer Cables
- Ground Cable
- RS-232C Cable
- USB Cable
- PC Software
- User Manual
- WRT Shipping Case
Optional Equipment :
WRT Printer Paper Roll
Specific custom-made test clips
Specific Custom length test leads
ndb Technologies inc. 111- 1405, St-Jean-Baptiste, Quebec, (Qc) Canada G2E 5K2, Tel: (418) 877-7701 Fax: (418) 877-7787