COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
Technical Specifications
1 Introduction
The infrastructure guidelines will cover all the OSP & ISP standards that are applicable to
villas, buildings and Meet-Me- Room scenarios.
One of the operator shall be assigned as the Lead Operator to the Greenfield project and
accordingly shall take responsibility of coordination with the developer for Common
infrastructure requirements. The Lead Operator will assist the property developers through a
“No Objection Certificate” (NOC) process that includes OSP design drawing validation, ISP
design drawing validation, Validating ISP material to be from the Pre-Approved
Manufacturer list and Site inspections during implementation.
Developers are encouraged to engage with Lead Operator at an early stage so that any process
and / or design issues may be resolved. If property developers or tenants have special
requirements that may not be covered by these guidelines it is necessary to engage with Lead
Operator’s design teams at an early stage of development planning, to enable seamless delivery
of premium telecommunications services at launch.
We look forward for the feedback from developers as it helps us understand your issues and
incorporate valid suggestions in future designs.
For information on obtaining NOCs or for any design-related queries, please contact:
Etisalat: +971-4-2022442, email USERS-NOI-AUH@etisalat.ae or
mabdulal@etisalat.ae or visit www.gis4me.ae
du: +971-4-3915018, email noc.request@du.ae or visit
http://www.du.ae/personal/helpandsupport/no-objection-certificate
Warm regards,
du / Etisalat
2
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
Villa complexes
residential towers and groups of residential towers
commercial towers and groups of commercial towers
shopping malls
groups of shops and retail outlets
hospitals, hotels and other bulk service applications
warehouses and sheds
Note – However the above mentioned Buildings types are not limited.
The document is structured to cover all aspects of infrastructure for:
Meet-Me-Room spaces/Plot
Civil Infrastructure and Entry ducts
Telecom rooms
Mobile service and Roof-top rooms
Building pathways
OSP cables
ISP cables
Infrastructure Specification
3
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
4
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
(f) An entry/pull box must be installed for any right-angled or sharp bends in the
lead-in duct route;
(g) If required, at the entry to the main telecom room, a wide-angle long radius bend
(factory made) may be provided; alternatively an entry box may also be
provided; and
(h) All ducts must include a draw rope made of twisted mildew and resistant
polypropylene; minimum outside diameter of 6mm; minimum tensile strength of
2400lbs / 1000kg.
The quantity and location of the entry boxes will depend on the route from the main
telecom room to the Lead Operator networks. Entry boxes must be included wherever
the duct system has right-angle or sharp bends where there are other factors that might
restrict cable pulling.
The following specifications must be followed:
(a) Constructed of reinforced concrete;
(b) Fitted with a ductile iron frame and cover;
(c) Minimum load rating 400 kN;
(d) Cover to be marked ‘Telecoms’; and
(e) An earth rod must be provided with a resistance of less than 5 ohms.
5
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
In multi-story buildings the telecom rooms must be vertically aligned and linked by a
shared containment system. This containment system must not reduce the minimum
requested room space.
All telecom rooms must be dedicated for the use of the Lead Operator. The rooms must
be easily accessible to the Lead Operator personnel 24 hours a day and secured from
unauthorised entry.
Telecom rooms must not be in close proximity to any sources of the following:
(a) Heat;
(b) Moisture;
(c) Corrosive atmospheric or environmental conditions;
(d) High voltages;
(e) Radio frequency interference (RFI); and
(f) Electro-magnetic interference (EMI).
The rooms must not be directly beneath or next to wet areas such as:
6
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
(a) Showers;
(b) Washrooms;
(c) Swimming pools; and
(d) Garbage areas.
If for any reason it is proposed that any part of a telecom room will be located below
any kind of water source then this must be raised at the design stage. This situation will
require a floor (Attic slab) drain fitted with an automatic submersible pump to counter
any risk of water ingress. The rooms must be clean and free from any of the following
items unless otherwise specified in this document.
(a) Equipment
(b) Utility pipes
(c) Cables
(d) Sprinkler systems
(e) Windows
(f) Pests
In case of pests it should be noted that rodents often gnaw cables resulting in cable
damage and possibility of service disruption. Special attention must be given to prevent
pests entering telecom spaces and pathways. This should be through the use of best
practiced pest control methods. An additional measure could involve the installation of
covers to cable trays; if this is the case these covers must be removable to allow for the
installation of additional cables.
In order to move equipment into and out of telecom rooms no access from outside of
the building to these rooms must be less than 1000mmx 2100mm (W x H)
Floor Loading of Telecom room shall be 10kNm2 (distributed load)
7
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
Room should be provided with adequate lighting with minimum of 200 Lux at
table level
Room shall be comply with the fire and safety requirements like smoke detector,
fire alarm, emergency light etc. as per local authority standards. Any water
sprinklers to be avoided.
Also refer to Appendix-5- Summary Table- Electromechanical Specification, for
consolidated EM requirements
8
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
9
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
(d) All doors of telecom rooms to be of solid wood core or steel construction, fire
retardant with a minimum rating of 2 hours;
(e) All doors of telecom rooms must be outward opening with an automatic door
closer system fitted on the hinged edge;
(f) All doors of telecom rooms to be labelled with both du / Etisalat telecom room,
Refer to the Appendix-3 and;
(g) The room must be free from contaminants and pollutants
If the building developer has any concerns over safety, especially fire protection and
suppression systems, this should be raised with the Lead operator at the design stage.
The walls, floor, and ceiling must be finished so as to minimise dust and static electricity
and the walls and ceilings must be painted with a primer and light coloured finish coat.
4 x13A twin sockets fed from the essential power supply with dedicated
20A circuit breaker.
10
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
Add 2 x 63A TP isolator fed with dedicated feeder from essential power
supply (EDB)
Dedicated A/C system (ducted split FCU) with duty & standby units
with proper interlocking, to maintain the room temp. at 21°C ± 1°C
Room shall be comply with the fire and safety requirements like smoke
detector, fire alarm, emergency light etc. as per local authority standards.
Any water sprinklers to be avoided.
Roof-Top room design consideration
a) The floors of the Roof-Top rooms must have a minimum distributed load rating
of 10kN/m2.
b) Openings must be provided to the room to allow for cables to connect to external
antennas. These openings must be 600mm x 400mm (W x H), 500mm below the
room ceiling in walls facing the building’s roof-top area.
c) Space must be reserved on the roof-top of the building for the installation of
mobile-service antennas. This setup may vary from building to building
scenario, but this will be typically at the corners of the building or on any raised
structure on the roof-top. The exact details will be advised at the design NOC
stage with Lead Operator
11
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
a) The dedicated 3m x 3m x3m space shall be provided for every 10 floor, starting
from basement or Ground floor
b) The Location of the Mobile Service room must be close to the Floor Telecom
Room (FTC)
c) The Mobile service room shall be connected to building riser through 300mm
x 50mm Vertical cable tray
d) The doors to this room shall open outwards and have a minimum opening of
1000mm x 2100mm (W x H).
e) The following electromechanical must be provided while designing Mobile
service rooms
4 x13A twin sockets fed from the essential power supply with dedicated
20A circuit breaker.
Dedicated A/C system (ducted split FCU) with duty & standby units
with proper interlocking, to maintain the room temp. at 21°C ± 1°C
Room shall be comply with the fire and safety requirements like smoke
detector, fire alarm, emergency light etc. as per local authority
standards. Any water sprinklers to be avoided.
f) The floors of the Mobile-service rooms must have a minimum distributed load
rating of 10kN/m2.
12
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
(a) Concealed in the wall with the front of the cabinet flush with the wall;
(a) Located in an accessible area inside the home close to the entrance and not inside
the kitchen, laundry room or bedroom;
(b) Installed at a height of 1200mm (between finished floor level and the bottom
edge of the cabinet);
(c) An adequate safe working space around the location;
(d) Adequate lighting;
(e) Not close to the sources of water or heat;
(f) Not close to any electrical distribution or bus bars;
(g) Adequate ventilation must be provided; minimum of one air change per hour;
(h) Fitted with 24 port Copper patch panel;
(i) 24 number of CAT6 Cables or less per Tenant;
(j) Fiber terminal box fitted with 2 port of LC/APC adaptor & pigtails and with 2
port of SC/APC adaptor & pigtails for 4 core SM Fiber drop cable termination.
Refer to the Appendix-1-Figure-19
(k) Lockable front door;
(l) Horizontal cable management for unshielded twisted pair (UTP) patch cables;
(m) Sufficient cable entries to accommodate the incoming Fiber optic and UTP
cables;
(n) 13A dual socket must be provide inside consolidation cabinet with dedicated
circuit breaker on the domestic supply and not loop with other power sockets;
(o) Labelled with villa or floor/flat number.
Refer to the Appendix-1-Figure-20 for home consolidation elevation layout
13
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
2.2.2 Home Consolidation Cabinet- Serving more than 24 port of RJ-45 per Tenant
Minimum internal dimensions 600mm x 600mm x300 mm (H x W x D)
a) Concealed in the wall with the front of the cabinet flush with the wall;
b) Located in an accessible area inside the home close to the entrance and not inside the
kitchen, laundry room or bedroom;
c) Installed at a height of 1200mm (between finished floor level and the bottom edge of
the cabinet);
d) An adequate safe working space around the location;
e) Adequate lighting;
f) Not close to the sources of water or heat;
g) Not close to any electrical distribution or bus bars;
h) Adequate ventilation must be provided; minimum of one air change per hour;
i) Fitted with 24 port Copper patch panels;
j) More than 24 number of CAT6 Cables per Tenant;
k) Fiber terminal box fitted with 2 port of LC/APC adaptor & pigtails and with 2 port of
SC/APC adaptor & pigtails for 4 core SM Fiber drop cable termination. Refer to the
Appendix-1-Figure-19
l) Lockable front door;
m) Horizontal cable management for unshielded twisted pair (UTP) patch cables;
n) Sufficient cable entries to accommodate the incoming Fiber optic and UTP cables;
o) 13A dual socket must be provided inside consolidation cabinet with dedicated circuit
breaker on the domestic supply; and not loop with other power sockets;
p) Labelled with villa or floor/flat number.
Refer to the Appendix-1-Figure-21 for Home consolidation elevation layout
14
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
15
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
b) Pull 4 core SM drop Fiber cables from Tenant’s telecom cabinet to Mini-ODF inside
FTR
c) Multicore Fiber cables must be spliced on the dedicated splice trays, which are
reserved for Multicore SM Fiber cables splicing unit
d) Drop Fiber cables must be spliced on the dedicated splice trays, which are reserved
for drop fiber cables splicing
e) Sufficient cable entries to accommodate the multicore SM Fiber cables and drop
Fiber cables
f) Lockable panels all round lockable front door
g) Sufficient cable entries to accommodate the incoming Fiber optic cables;
h) Labelled with floor number
i) All Fiber cores must be clearly labelled per Lead operator specification and
standards
If Etisalat is the Lead Operator - The Mini ODF (Splice Cabinet) specifications are as
follows:
a) Fully Loaded with Pre- Terminated SC/APC pigtail and SC/APC adaptors
b) Pull 4 core drop Fiber cables from Tenant’s telecom cabinet to Mini-ODF cabinet
inside FTR
c) Multicore Fiber cables must be spliced on the dedicated splice trays, which are
reserved for multicore fiber cables splicing
16
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
d) Drop Fiber cables must be spliced on the dedicated splice trays, which are reserved
for drop fiber cables splicing
e) Sufficient cable entries to accommodate the multicore SM Fiber cables and drop
Fiber cables
f) Lockable panels all round lockable front door
g) Sufficient cable entries to accommodate the incoming Fiber optic cables;
h) Labelled with floor number
i) All Fiber cores must be clearly labelled per Lead operator specification and
standards
Refer to the Mini- ODF Cabinet detail in Appendix-1-Figure-23
Internal cable distribution to be coordinated directly between the building owner and
the tenant.
2.4 PATHWAYS
2.4.1 CONTAINMENT – General
The following requirements must be applied to all containment systems:
(a) The containment system must be designed such that installed cables do not
exceed the minimum specified bend radius;
(b) All metal containment parts must be free from sharp edges and should be earth
bonded;
(c) Telecom riser openings must be sealed with a suitable fire retardant material;
(d) Cable trays must be easily accessible in common areas to facilitate any future
provision of additional cables;
(e) Any cable trays that are in publically accessible areas less than 4.8 m above the
floor must be covered;
(f) Containment systems must not run through areas exposed to excessive heat,
moisture, corrosive atmospheric or environmental conditions, high voltages,
radio frequency interference (“RFI”) or electro-magnetic interference (“EMI”);
(g) For all containment systems a minimum separation must be maintained from
sources of electromagnetic interference.
(h) The building developer may want to consider redundant containment systems,
particularly in commercial or prestigious developments. The Lead Operator must
be contacted at the design stage to discuss any such requirements.
17
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
The vertical cable tray size must be 450mm x 50mm (HDRF) inside the building
riser to accommodate building fiber optic cables
The vertical cable tray size must be 300mm x 50mm (HDRF) inside the building
riser to accommodate IBS cables to provision IBS-solution (GSM).
18
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
The Horizontal cable tray size must be 150mm x 50mm (HDRF) inside the
building corridor to accommodate mobile-service antenna cables to provision
IBS solution (GSM)
19
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
4 Port Fiber terminal box (with LC/APC and SC/APC pigtails & adaptors) inside
12U Cabinet of tenant premises (Home/Office/Retail/Villa/Warehouse)
Fully Loaded high density or Low density Fiber patch panels with SC/APC
adaptors and pigtails inside MTR– if Etisalat is the lead operator
Fully Loaded high density or Low density Fiber patch panels with LC/APC
adaptors and pigtails – if du is the lead operator
Wall Mount Mini ODF (direct splice cabinet) inside FTR are to be Used to splice
the multicore SM fiber cables with respective 4 core SM drop cables**
**The Capacity of the Mini ODF (direct splice Cabinet) depends on the
number of splice tray required per Mini ODF to accommodate minimum of 12
core fiber per splice tray
All metal plating’s and plastic materials of Optical splitter shall be RoHS
compliant
Optical Splitters shall have the operating wavelength (nm) range from 1260 nm
~1635 nm
Optical Splitters shall have the operating temperature range from -24°C to
+85°C
2 (in) x 32 (out)- Optical Splitters shall have the maximum insertion loss +
Connector loss (@ Operating wavelength from 1260 ~1635 nm) to ≤ 18 dB
Optical splitter shall have dust covers on the uplink and downlink connectors.
20
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
Each Modular Splitter shall have visible label holder for unique
identification
21
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
Note – * The Building Owner is responsible for supplying splitters, fiber patch cords,
and its related racks
* The Building Owner is responsible to installed the splitters and its related
Fiber patch cords to make neat pre-patching between Uplink ports and Outside
plant fiber patch panel & between the downlink ports and Inside plant fiber patch
panels
* The Building Owner shall supply the splitters only from the Pre-approved
manufacturer of du and Etisalat
Bend insensitive
22
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
Jacket to be halogen free and flame retardant material (which is LSZH type)
(b) Multicore Fiber Cable:
Single mode
Indoor type
Flexi Tube (Gel free) Micro Module cable/Micro bundle cable from 24 Fiber
core and above
Jacket to be halogen free and flame retardant material (which is LSZH type)
2.6.4 FIBER OPTIC CABLES – from main telecom room to Mini ODF (Splice
Cabinet) Floor Telecom room
The number of Fiber cores required will be dependent on the number of tenant in each
serving floors. The multicore Fiber cable must be provided from the main telecom room
to Mini ODF (Splice Cabinet) inside the floor telecom room
These Multicore Fiber cables must be continuous lengths free from joints, branches or
patching from main telecom room to each Mini ODF (Splice Cabinet) unit.
Location of multicore Mini ODF (Splice Cabinet) must always start from 1st floor to
cover maximum of three floor, for example- Mini ODF (Splice Cabinet) installed at 1st
floor will cover the 1st, 2nd and 3rd floor, next Mini ODF (Splice Cabinet) location must
23
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
be at 4th floor, this Mini ODF (Splice Cabinet) will cover, 4th, 5th and 6th floor, next Mini
ODF (Splice Cabinet) location must be at 7th floor, so on and so forth,
Refer to Appendix-1-Figure-15, 24, 25 and 26 and Appendix-2- Table-3 for more detail
Multicore Fiber cables must be directly spliced with 4 core SM Fiber cables using Mini
ODF (Splice Cabinet) cabinet inside FTR. Minimum 25% spare Fiber must be
considered while calculating multicore Fiber capacity for maintenance and additional
service demands. All Fiber optic cables should be supplied, spliced, labelled and tested
inside the Main Telecom Room and floor telecom room.
2.6.5 FIBER OPTIC CABLES – from Mini ODF (Splice Cabinet) Floor telecom
room to consolidation point (CP)
The 4 core SM Fiber cables must be provided from each CP Unit to its respective Mini
ODF (Splice Cabinet) inside the floor telecom room
These 4 core SM Fiber cables must be continuous lengths free from joints, branches or
patching from each CP Unit to its respective Mini ODF (Splice Cabinet) inside the floor
telecom room
All these 4 core SM Fiber cables must be directly splice with Multicore Fiber cables
using Mini ODF (Splice Cabinet) inside FTR. Refer to the Mini ODF (Splice Cabinet)
detail Appendix-1-Figure 15 and 24
4 - Brown 4-LC/APC du
24
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
2.6.6 FIBER OPTIC CABLES – from Main telecom room to each Mobile service
rooms and Roof Top room
2.6.6.1 Fiber Optic cables – If du is the Lead Operator then the following
Specifications shall be provided by building Owner to have IBS-connectivity (GSM)
within premises/buildings/high rise towers
24 core SM Indoor tight buffer fiber cables must be installed from main telecom
to each Mobile service rooms and Roof-Top
Install Pre- Terminated Cross connect Cabinet at each Mobile service room and
Roof-Top room.
Terminate the 24 core SM Indoor tight buffer fiber cables inside the rack at MTR
side by using 19th inch, 24 port LC/APC fiber patch panel
Terminate the 24 core SM Indoor tight buffer fiber cables inside the Pre-
Terminated Cross connect cabinet at Mobile service room side and Roof-Top
side
Pre- Terminated Cross connect Cabinet shall be minimum size of 600mm (W)
X 150mm (D)
2.6.6.2 Fiber Optic cables –If Etisalat is the Lead Operator then the following
Specifications shall be provided by building Owner to have IBS-connectivity (GSM)
within premises/buildings/high rise towers
24 core SM Indoor tight buffer fiber cables must be installed from main telecom
to each Mobile service rooms and Roof-Top
Install Pre-Terminated Cross connect Cabinet at each Mobile service room and
Roof-Top room.
Terminate the 24 core SM Indoor tight buffer fiber cables inside the rack at MTR
side by using 19th inch, 24 port SC/APC fiber patch panel
25
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
Terminate the 24 core SM Indoor tight buffer fiber cables inside the Pre-
Terminated Cross connect cabinet at Mobile service room side and Roof-Top
side
Pre- Terminated Cross connect Cabinet shall be minimum size of 600mm (W)
X 150mm (D)
26
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
(j) The components of the CAT6 system must compatible and it is preferred that
they are from a single manufacturer to insure optimum performance;
(k) Design must incorporate built-in flexibility to meet the growing needs of the
occupants; and
(l) Test result for CAT6 to be saved and recorded for reference purpose in future,
The Lead Operator to maintain the records for future reference
3. Bulk service
This kind of service solution usually applied to projects/buildings that are having their
own IT network (single tenant) and system operator such as Hotels, Hospitals, Schools,
Universities, Banks, Airports and other similar establishments. In this type of buildings,
the client will have his/her own IT server room and dedicated Main telecom room with
the size of 3m x 3m x 3m (L x B x H) to be allocated for the Parties for telecom/network
equipment installation. Letter from the client should be provided during the design stage
confirming the bulk service and explaining the service required to be provided up to the
client IT room.
The exact requirements related to telecom cabling and EM requirements will be
determined during the design stage based on the client’s service requirements.
However client shall provide the following minimum requirements for bulk services
setup
Installed and test 12 core SM Indoor tight buffer fiber cable between MTR &
Client Server room, terminate the 12 core SM fiber cables at both end by using
12 port Pre-Terminated fiber patch panel.
Installed and test 24 number of Cat6 UTP Copper cables between MTR and
Client Server room.
Installed 12 port Pre-Terminated fiber patch panel for Lead Operator’s uplink
fiber.
27
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
Client shall provide LC/APC adaptors and pigtail for fiber interfaces, if the Lead
Operator is du.
Client shall provide SC/APC adaptors and pigtail for fiber interfaces, if the Lead
Operator is Etisalat
Distance between MTR and Client server room must be maintain within 70
meter (to avoid 90 meter distance limitation, while provisioning fixed services
over Cat6 copper cables)
Extend 300mm x 50mm HDRF cable tray from MTR to Client server room
4 x13A twin sockets fed from the essential power supply with dedicated 20A
circuit breaker.
2 number of AC & DC earth bars connected to the dedicated earth pits with
resistance less than 1ohm.
Provide 2 x 40A TP isolator fed with dedicated feeder from essential power
supply (EDB)
Dedicated A/C system (ducted split FCU) with duty & standby units with proper
interlocking, to maintain the room temp. at 21°C ± 1°C.
Heat dissipation can be considered at 300 Watts/sq. meter. + 3kW per rack.
Room should be provided with adequate lighting with minimum of 200 Lux at
table level.
Room shall be comply with the fire and safety requirements like smoke detector,
fire alarm, emergency light etc. as per local authority standards. Any water
sprinklers to be avoided.
Raised Flooring system requirement shall be advice during design NOC stage
by Lead Operator.
Refer to Appendix-1-Figure-27 for Bulk service set-up layout
In case of any building transformation that would result in changing the type of service
required, the building owner should obtain the Lead Operator’s approval by submitting
amendment design.
28
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
4 Labelling Scheme
4.1 GAID and EID Identification plate for each Unit/Tenant
The Identification plate must be installed at the door entrance of the residential /
commercial units. The Identification plate material could be made of plastic plate or
light metal plate. The Sample on Identification plate must be submitted during NOC
stage to Lead Operator for final approval.
The GAID and EID reference number detail will be made available by Lead Operator
during inspection stage.
0.50cm.
0.30cm. 0.30cm.
GAID – DXB_E3177U_12622_001001001
0.60cm.
7.00cm.
EID – AU007540000
0.30cm. 0.30cm.
10.00cm.
29
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
30
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
√
17 Construction of Meet-Me-Room
18 Commissioning of Meet-Me-Room √
Fiber optic cables supply, pulling, termination and testing from
the Main Telecom Room to each Mobile service room and Roof-
19 Top room √
Fiber Optic components for IBS-Connectivity (GSM) : Supply
and Installation of Fiber optic pre-terminated patch panels, Cross
20 connect Cabinets and Fiber patch cords √
Master
Villa’s
Item description Plan Lead Operator?
Developer
Developer
Lead-in ducts including
connection to manhole outside
1 villa boundaries √
31
COMMON DU & ETC - ISP AND OSP DESIGN GUIDELINES
32
Etisalat
Schematic Representation of Villas Scenario – Green Field
nearest POP
Appendix-1-Figure-1
Etisalat
nearest POP
Meet‐Me‐
du/Etisalat
Room
(MMR)
POP
Feeder Cables
by du
du nearest POP
Distribution Cables inside the development for Villas by Lead Operator
Appendix-1-Figure-2 Schematic Representation of Buildings Scenario –
Green Field
Feeder Cables by Etisalat
Etisalat
du nearest POP nearest POP
Feeder Cables by du
Meet‐Me‐Room
(MMR)
Connected to building
Connected to building splitters inside MTR
splitters inside MTR
SM Fiber Cables from Each
Building MTR to MMR
Schematic Representation of Buildings and Villas
Scenarios – Green Field
Feeder Cables by Etisalat
Appendix-1-Figure-3 Etisalat
du nearest POP nearest POP
Feeder Cables by du
Meet‐Me‐Room
(MMR)
Connected to building
splitters inside MTR
Distribution Cables
Villas
Plot
Distribution Cables Cables Connected to building
splitters inside MTR
for Villas by Lead Operator
Legends
MTR -3m x 3m
800x800
RACK
42U Rack – 800mm (W) X 800mm(D) X 42 U (H)
mm
3m.
AC Clean earth bar
Design Consideration
1) Targeting maximum of 150 Tenants per
Building
2) Terminate the Building Fiber cables into 42U
Rack‐1
OSP Fiber cable Entry by 3) Rack‐2 to be used for installing splitters
Lead Operator
4) Installed Overhead raceways over the Rack‐1
600mm. 13A twin socket fed from utility power with and Rack‐2 for proper routing of fiber patch
dedicated circuit breaker cords
800x800
RACK 2
mm
3m.
Smoke Detector
connected to BMS
5) Use SC/APC type Optical patch panel, if
Etisalat is the Lead Operator
800x800
RACK 1
mm
6) Use LC/APC type Optical patch panel, if du is
the Lead Operator
7) Cable tray must be installed at high level for
proper cables routing
8) Supply and Pre‐ Patching of Splitters
uplink and downlink ports will be under
Building Riser the Building Owner scope
9) Adequate lighting fixtures must be provided
450mm X 50mm Cable tray at high level
10) Refer to the Electromechanical (EM) notes
for detail EM requirements
Appendix-1-Figure-4
Legends
MTR -3m x 3m
3m.
Building
ODF
Building ODF Size – 900mm (W) X 450mm(D) X 47 U (H)
AC Clean earth bar
Open Rack
Open Rack – 900mm (W) X 450mm(D) X 47 U (H)
13A twin socket fed from utility
power with dedicated circuit
OSP Fiber cable Entry by
Lead Operator Design Consideration
1) Targeting maximum of 300 Tenants per
Open Rack
breaker
Building
2) Terminate the Building Fiber cables into 47U
3m.
Optical distribution Frame (ODF)
Building
3) Open rack to be used for installing splitters
ODF
4) Installed Overhead raceways over the ODF
and Open rack for proper routing of fiber patch
cords
5) Use SC/APC type Optical patch panel, if
Etisalat is the Lead Operator
450mm X 50mm Cable tray at high level 7) Cable tray must be installed at high level for
proper cables routing
8) Supply and Pre‐ Patching of Splitters
uplink and downlink ports will be under
the Building Owner scope
9) Adequate lighting fixtures must be provided
Appendix-1-Figure-5
10) Refer to the Electromechanical (EM) notes
for detail EM requirements
Legends
MTR -4m x 3m
3000mm.
Building
ODF
Building ODF Size – 900mm (W) X 450mm(D) X 47 U (H)
AC Clean earth bar
Open Rack
Open Rack – 900mm (W) X 450mm(D) X 47 U (H)
13A twin socket fed from utility power with
dedicated circuit breaker
OSP Fiber cable Entry by
4000mm.
Lead Operator Design Consideration
1) Targeting maximum of 600 Tenants per
Open Rack
Building
2) Terminate the Building Fiber cables into 47U
Optical distribution Frame (ODF)
Building
ODF
3) Open rack to be used for installing splitters
4) Installed Overhead raceways over the ODF
and Open rack for proper routing of fiber patch
cords
5) Use SC/APC type Optical patch panel, if
Etisalat is the Lead Operator
Building Riser
6) Use LC/APC type Optical patch panel, if du is
the Lead Operator
450mm X 50mm Cable tray at high level
7) Cable tray must be installed at high level for
proper cables routing
8) Supply and Pre‐ Patching of Splitters
uplink and downlink ports will be under
the Building Owner scope
9) Adequate lighting fixtures must be provided
Appendix-1-Figure-6
10) Refer to the Electromechanical (EM) notes
for detail EM requirements
Legends
MTR -4.5m x 3m
Building
ODF
Building ODF Size – 900mm (W) X 450mm(D) X 47 U (H)
Open Rack
Open Rack – 900mm (W) X 450mm(D) X 47 U (H)
Open Rack
1.1m.
Building
ODF-3
1
Open Rack
Building -
ODF-1
3
Design Consideration
4.5m.
13A twin socket fed from utility
Open Rack
Building
power with dedicated circuit 1) Targeting minimum of 1200 Tenants per
ODF-4
breaker Building
2
Earth bar
500mm. 2) Terminate the Building Fiber cables into
Open Rack
Optical distribution Frame Cabinet
Building
ODF-2
500mm.
4
3) Use SC/APC type High density Optical patch
panel, if Etisalat is the Lead Operator
OSP Fiber cable by Lead
Operator 4) Use LC/APC type High density Optical patch
panel, if du is the Lead Operator
5) Cable tray must be installed at high level for
proper cables routing
6) Adequate lighting fixtures must be provided
Appendix-1-Figure-7 7) Refer to the Electromechanical (EM) notes
for detail EM requirements
Building Fiber Termination by Using LC/APC Optical Patch Panel
( if du is the Lead Operator )
Appendix-1-Figure-9 High Level Overhead Fiber raceways
Rack No -2 Rack No -1
1 1
Uplink Fiber Patch Panel 1
2 2
LC/APC by Client 3 3 48 port LC/APC optical patch panel-
4 2
4
1U by Client
5 3
5
6 6
Termination
9 9
10 6 10
2 x32 LC/APC Splitters for du 11 7 11
by Client 12 12
13 8 13
14 9 14
15 15
16 10 16
17 11
17
18 18
19 19
Design Consideration
12
20 20
13
21 21
22 22 1) Targeting maximum of 150 Tenants
2 x32 SC/APC Splitters for 23 23 per Building
24 24
Etisalat by Client 25 25
26 26
2) 13 number of LC/APC Optical Patch Panel
27 27 required to terminate 600 core of building
28 28 Fiber Cables
29 29
30 30 3) 5 number of 2 x 32 LC/APC Low density
31 31 splitters required
32 32
33 33
4) 5 number of 2 x32 SC/APC Low density
34 34
35 35 splitter required
36 36
Note- Supply and Pre-Patching of 37 37 5) The Capacity of the Uplink Fiber patch panel LC/
Splitters 38 38 APC = [Total number of Splitters installed for du and
uplink and downlink ports with 39 39 Etisalat] X 2
respective fiber patch cords shall be 40 40
under the Building Owner scope 41 41
42 42 6) For 150 Tenants-
The Capacity of the Uplink Fiber patch panel LC/APC
= [10 splitters] X 2
= 20 core ~ 24 core LC/APC Fiber
patch panel
Building Fiber Termination by Using SC/APC Optical Patch Panel
( if Etisalat is the Lead Operator )
Appendix-1-Figure-10 High Level Overhead Fiber raceways
Rack No -2 Rack No -1
33 33
splitter required
21
34 34
Cable Manager-1U
35 22
35
5) The Capacity of the Uplink Fiber patch panel 36 23
36
SC/APC = [Total number of Splitters installed 37 37
for du and Etisalat] X 2 38 24
38
39 25
39
40 40
6) For 150 Tenants- 41 41
The Capacity of the Uplink Fiber patch panel 42 42 Note- Supply and Pre- Patching of Splitters
SC/APC = [10 splitters] X 2 uplink and downlink ports with respective
= 20 core ~ 24 core SC/APC fiber patch cords shall be under the
Fiber patch panel Building Owner scope
Appendix-1-Figure-11 Open Rack Elevation using SC/APC ODF ( if Etisalat is the Lead Operator )
High Level Overhead Fiber raceways
ODF Open Rack
Cables Guide
Design Consideration
FIBER SHELF
Uplink Fiber Patch Panel LC/APC by
Client
Cables Guide
Design Consideration
2m.
Building Riser
2m.
Mini ODF
(Splice Cabinet)
150 mm opening
Appendix-1-Figure-13
Appendix-1-Figure-14
Building Riser
1.5 meter from FFL
Mini ODF (Splice Cabinet )
Opening for Drop Fiber
Cables from Building Riser
Flip type splice tray with
storage capacity of 12 core
fibers
1 Cable/Tube Holder
2
3
Storage space for Drop Fiber Cables
4
Storage space for Fiber Tubes
5
6
600mmm
1
2
3
Mini ODF 4
5
6
(Wall Mount)
1
2
3 Notes –
4 Reserved
5
6 minimum of 1m X
1m space on the
side wall to mount
Mini ODF
Mount the Mini
Opening for Drop Fiber ODF at 1.5 m
Cables from Building Riser height from Finish
600mmm Floor Level (FFL)
Extend the Cable
tray at high level
from building riser
Cable Holder to Mini ODF
Appendix-1-Figure-15
Cable Entry for Multicore
Indoor Fiber cables
3m. Roof‐Top room/Mobile
Service room (Typical
AC Clean earth
DC Clean earth
Layout)
bar
bar
Cross Connect
cabinet
Cross connect
cabinet
Cable tray
Splice tray
Designated Splice tray
for Etisalat (1 to 12 core
of Indoor fiber cable)
600mmm
Splice tray
Designated Splice tray
Velcro
24 for du (13 to 24 core
23 of Indoor fiber cable)
22
21
20
Tube holder
19
18
Adaptors and Pigtails
17
16
Door 15
14
13
12
11
Ring to Manage Fiber
10 Patch cords and
9 Buffer Tubes
8
7
6
5
4
Design Consideration
3 1) Pre‐Terminated Cross connect cabinet capacity must be
2 suitable to splice
1 24 core SM Indoor tight buffer fiber cables
2) Splice tray capacity ‐12 slot per splice tray
3) Connector type must be LC/APC (if du is the Lead
Operator)
8 Cm
Fiber Terminal Box with 2 Port 4 core SM Indoor drop Fiber Cable
SC/APC and 2 Port LC/APC – Flat Cross section
Port-3 for du
Port-4 for du
SC/ SC/ LC/ LC/
APC APC
APC APC
SC/ SC/
APC APC
600mm
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
24 Port Cat 6 Patch Panel– 1U
Cable Manager – 1U
Fiber Terminal Box
with 4 port (with 2 port of SC/APC
FTB and 2 port of LC/APC)
12 U
13 A twin Socket
PERFORATED
3 U – Metallic Support to hold du
DOOR
and Etisalat ONTs
150mm
Design Consideration
1) Home Consolidation
cabinet – Serving up to 24
port of RJ-45 per Tenant
600mm
12 U
300 mm
Design Consideration
1) More Consolidation
13 A twin Socket cabinet – Serving more
than 24 port of RJ-45 per
Tenant
600mm
12 U
350 mm
Design Consideration
1) Business Consolidation
13 A twin Socket cabinet – Serving up to 24
port of RJ-45 per Tenant or
more
Splice tray
Splice tray
20 20
19 19
18 18
17 17
16 16
15 15
14 14
13 13
12 12
11 11
10 10
9
8
9
8 Splice Tray for splicing
7 7
Door 6
5
4
3
2
6
5
4
3
2
Multicore fiber cables
1 1
24 24
23 23
22 22
21 21
20 20
19 19
18 18
17 17 Adaptor holder
Splice tray
Splice tray
16 16
15 15
14 14
13 13
12 12
11 11
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
1 1
LC/APC or Opening for drop
SC/APC Fiber Cables from
Cable Entry for Multicore Pigtails tenants
Fiber cables from MTR
1 2 3 x
Schematic diagram for FTR‐7th floor
Mini ODF
Buildings (Splicing point)
4 core SM drop fiber cables from each unit to respective Mini ODF (Splicing Point) at FTR
1 2 3 x
Appendix-1-Figure-24
FTR‐6th floor
1 2 3 x
FTR‐5th floor
1 2 3 x
FTR‐4th floor
Mini ODF
Multicore Indoor fiber cables from MTR (Splicing point)
to respective splicing point at FTR
1 2 3 x
FTR‐3rd floor
ETC 1 2 3 x
Du POP
POP
FTR‐2nd floor
1 2 3 x
FTR‐1st floor
Mini ODF
(Splicing point)
1 2 3 x
MTR room with splitters
Meet‐Me‐Room (Supply of splitters will be
by Building Owner)
(MMR) Ground Floor
Core Assignment SLD – with SC/APC Fiber
Patch Panel 2 X 32 LC/APC GPON Splitter for du
SC/APC Up Link Down Link Ports
Port-1,2 Tenant-6
Ports
1 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
LC/APC
Port-3,4
SC/APC
Port-1,2 Tenant-5 Simplex Fiber patch cords -(LC/APC to
SC/APC)
LC/APC
Port-3,4
Mini ODF
SC/APC (Splice Cabinet) Tenant-1 Tenant-2 Tenant-3 Tenant-4 Tenant-5 Tenant-6
Port-1,2 2 4 6 8 10 12 14 16 18 20 22 24
Tenant-4
LC/APC 1 3 5 7 9 11 13 15 17 19 21 23
Port-3,4
24 port SC/APC
Fiberl patch Panel
SC/APC
Port-1,2 Tenant-3
LC/APC
Port-3,4 Simplex Fiber patch cords -(SC/APC to
SC/APC)
Up Link
SC/APC Ports
Port-1,2 Tenant-2 1 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
LC/APC
Down Link Ports
Port-3,4
24 port LC/APC
Port-3,4
SC/APC Tenant
Port-1,2 -3
LC/APC
Port-3,4
Simplex Fiber patch cords -(LC/APC to
SC/APC Tenant LC/APC)
Port-1,2 -4 Mini ODF
LC/APC
Port-3,4 (Splice Cabinet)
SC/APC
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48
Tenant
Port-1,2 -5
LC/APC
Port-3,4 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
Tenant- Tenant- Tenant- Tenant- Tenant- Tenant- Tenant- Tenant- Tenant- Tenant- Tenant- Tenant-
1 2 3 4 5 6 7 8 9 10 11 12
SC/APC Tenant
Port-1,2 -6
LC/APC
Port-3,4
SC/APC Tenant
Port-1,2
(LC/APC to SC/APC)
Port-3,4
1 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
SC/APC Tenant Up Link
Port-1,2 -8 Down Link Ports
LC/APC Ports
Port-3,4
SC/APC
Port-1,2
Tenant
-9
2 X 32 SC/APC GPON Splitter for Etisalat
LC/APC
Port-3,4
SC/APC Tenant
Port-1,2 -10
LC/APC
Port-3,4
Tight Buffer or Micro Modules LSZH Indoor Multi-Core
Fiber Cable
SC/APC Tenant
Port-1,2 -11
LC/APC
Port-3,4
4 core Flat type LSZH Indoor Drop Fibers Cables
SC/APC Tenant
Port-1,2 -12
LC/APC
Port-3,4
Appendix-1-Figure-26
MTR Room Client server Room
10U Space reserved for
OSP link (from MMR to
Building MTR) and ISP
link ( Building MTR to 01
02
01
02
Client Server room) 03 03 300mm x 50mm
04 04 Cable tray
05 05
Client’s Server Rack
06 06
07 07
08 08
09 09
10 10
11 11
12 12
16 U Space Reserved for 13
14
13
14
Lead Operator’s Active 15 15
16 16
Equipment 17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36 Raised Floor
37 37
16 U Space Reserved 38 38 Tiles
39 39
for Other Operator’s 40
41
40
41
Active Equipment 42 42
300mm.
Finished Floor Level
Appendix-1-Figure-27
Bulk Service design consideration
1) Client shall provide 3m x 3m x 3m telecom room to Lead Operator
2) Client Shall install and terminate 12 core SM Indoor Tight Buffer fiber cables between MTR and Client server room
3) Client Shall install and terminate 24 number of Cat6 UTP Copper cables between MTR and Client server room
4) Client shall provide 19 inch, 42 U Free standing rack and 12 port Pre-Terminated fiber patch panel for Lead Operator’s Uplink fiber
5) If the du is the Lead Operator, then Client shall provide LC/APC adapters and pigtails for Fiber Interfaces
6) If the Etisalat is the Lead Operator, then Client shall provide SC/APC adapters and pigtails for Fiber Interfaces.
7) Client shall provide 300mm X 50mm Cables tray between Lead Operator’s MTR and Client Server room
Appendix‐2 Table‐1
Single Villa Complex of Villas For Multi‐tenant Buildings shopping Mall Warehouse and Shed Bulk Service
2 xD56 (50mm) per Warehouse
2 XD54(100mm) Primary 2 XD54(100mm) Primary Route
2 xD56 (50mm) per Villa 2 XD54(100mm) Primary Route and 2xD54(100mm) Primary plot Entry
Ducts 2 xD56 (50mm) Route and 2 XD54(100mm) and 2XD54(100mm) Secondary
2xD54(100mm) for plot Entry 2 XD54(100mm) Secondary Route 2xD54(100mm) Secondary plot
Secondary Route Route
Entry
Appendix-2-Table-3-Core Assignment Mapping detail-LC Type
Fiber Core Assignment for Building Fiber Cable Termination By Using 19" 1U - 48 Port LC/APC Optical
Patch Panel
Apartment/Office/Retail Horizontal Distribution Vertical Distribution Building MTR
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 1 Blue - Core - 1 LC/APC-Port-1 ETC -Splitter Downlink Port-1
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 1 Orange - Core - 2 LC/APC-Port-2
Tenant - 1
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 1 Green - Core - 3 LC/APC-Port-3 du -Splitter Downlink Port-1
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 1 Slate - Core - 5 LC/APC-Port-5 ETC -Splitter Downlink Port-2
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 1 White - Core - 6 LC/APC-Port-6
Tenant - 2
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 1 Red - Core - 7 LC/APC-Port-7 du -Splitter Downlink Port-2
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 1 Yellow - Core - 9 LC/APC-Port-9 ETC -Splitter Downlink Port-3
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 1 Purple - Core - 10 LC/APC-Port-10
Tenant - 3
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 1 Pink - Core - 11 LC/APC-Port-11 du -Splitter Downlink Port-3
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 1 Blue/Black Stripe - Core - 13 LC/APC-Port-13 ETC -Splitter Downlink Port-4
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 1 Orange/Black Stripe - Core - 14 LC/APC-Port-14
Tenant - 4
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 1 Green/Black Stripe - Core - 15 LC/APC-Port-15 du -Splitter Downlink Port-4
Port-4 - LC/APC - du Brown - Core - 4 Splice Tray - 1 Brown/Black Stripe - Core - 16 LC/APC-Port-16
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 1 Slate/Black Stripe - Core - 17 LC/APC-Port-17 ETC -Splitter Downlink Port-5
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 1 White/Black Stripe - Core - 18 LC/APC-Port-18
Tenant - 5
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 1 Red/Black Stripe - Core - 19 LC/APC-Port-19 du -Splitter Downlink Port-5
Port-4 - LC/APC - du Brown - Core - 4 Splice Tray - 1 Black/Yellow Stripe - Core - 20 LC/APC-Port-20
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 1 Yellow/Black Stripe - Core - 21 LC/APC-Port-21 ETC -Splitter Downlink Port-6
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 1 Purple/Black Stripe - Core - 22 LC/APC-Port-22
Tenant - 6
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 1 Pink/Black Stripe - Core - 23 LC/APC-Port-23 du -Splitter Downlink Port-6
Port-4 - LC/APC - du Brown - Core - 4 Splice Tray - 1 Aqua/Black Stripe - Core - 24 LC/APC-Port-24
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 2 Blue - Core - 1 LC/APC-Port-25 ETC -Splitter Downlink Port-7
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 2 Orange - Core - 2 LC/APC-Port-26
Tenant - 7
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 2 Green - Core - 3 LC/APC-Port-27 du -Splitter Downlink Port-7
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 2 Slate - Core - 5 LC/APC-Port-29 ETC -Splitter Downlink Port-8
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 2 White - Core - 6 LC/APC-Port-30
Tenant - 8
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 2 Red - Core - 7 LC/APC-Port-31 du -Splitter Downlink Port-8
Port-4 - LC/APC - du Brown - Core - 4 Splice Tray - 2 Black - Core - 8 LC/APC-Port-32
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 2 Yellow - Core - 9 LC/APC-Port-33 ETC -Splitter Downlink Port-9
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 2 Purple - Core - 10 LC/APC-Port-34
Tenant - 9
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 2 Pink - Core - 11 LC/APC-Port-35 du -Splitter Downlink Port-9
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 2 Blue/Black Stripe - Core - 13 LC/APC-Port-37 ETC -Splitter Downlink Port-10
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 2 Orange/Black Stripe - Core - 14 LC/APC-Port-38
Tenant - 10
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 2 Green/Black Stripe - Core - 15 LC/APC-Port-39 du -Splitter Downlink Port-10
Port-4 - LC/APC - du Brown - Core - 4 Splice Tray - 2 Brown/Black Stripe - Core - 16 LC/APC-Port-40
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 2 Slate/Black Stripe - Core - 17 LC/APC-Port-41 ETC -Splitter Downlink Port-11
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 2 White/Black Stripe - Core - 18 LC/APC-Port-42
Tenant - 11
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 2 Red/Black Stripe - Core - 19 LC/APC-Port-43 du -Splitter Downlink Port-11
Port-4 - LC/APC - du Brown - Core - 4 Splice Tray - 2 Black/Yellow Stripe - Core - 20 LC/APC-Port-44
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 2 Yellow/Black Stripe - Core - 21 LC/APC-Port-45 ETC -Splitter Downlink Port-12
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 2 Purple/Black Stripe - Core - 22 LC/APC-Port-46
Tenant - 12
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 2 Pink/Black Stripe - Core - 23 LC/APC-Port-47 du -Splitter Downlink Port-12
Port-4 - LC/APC - du Brown - Core - 4 Splice Tray - 2 Aqua/Black Stripe - Core - 24 LC/APC-Port-48
Appendix-2-Table-3-Core Assignment Mapping detail-SC Type
Fiber Core Assignment for Building Fiber Cable Termination By Using 19" 1U - 24 Port SC/APC Optical
Patch Panel
Apartment/Office/Retail Horizontal Distribution Vertical Distribution Building MTR
4 Port Fiber Terminal Box with 2 4 core Indoor SM Drop Wall Mount Splice Cabinet with 24 24 Core Indoor SM Multicore Fiber Cable - 24 Port SC/APC Etisalat - 2 x 32 SC/APC du - 2 x 32 LC/APC GPON
Tenant Number
LC/APC and 2 SC/APC Fiber Cables Fiber Splice Tray Capacity Micro Module/ Flexi Tube Optical Patch Panel GPON Splitter Splitter
Port-4 - LC/APC - du Brown - Core - 4 Splice Tray - 1 Brown/Black Stripe - Core - 16 SC/APC-Port-16
ETC -Splitter Downlink
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 1 Slate/Black Stripe - Core - 17 SC/APC-Port-17
Port-5
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 1 White/Black Stripe - Core - 18 SC/APC-Port-18
Tenant - 5
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 1 Red/Black Stripe - Core - 19 SC/APC-Port-19 du -Splitter Downlink Port-5
Port-4 - LC/APC - du Brown - Core - 4 Splice Tray - 1 Black/Yellow Stripe - Core - 20 SC/APC-Port-20
ETC -Splitter Downlink
Port-1 - SC/APC - Etisalat Blue - Core - 1 Splice Tray - 1 Yellow/Black Stripe - Core - 21 SC/APC-Port-21
Port-6
Port-2 - SC/APC - Etisalat Orange - Core - 2 Splice Tray - 1 Purple/Black Stripe - Core - 22 SC/APC-Port-22
Tenant - 6
Port-3 - LC/APC - du Green - Core - 3 Splice Tray - 1 Pink/Black Stripe - Core - 23 SC/APC-Port-23 du -Splitter Downlink Port-6
Port-4 - LC/APC - du Brown - Core - 4 Splice Tray - 1 Aqua/Black Stripe - Core - 24 SC/APC-Port-24
Appendix‐2‐Table‐4‐ Telecom Room Sizes‐For Mobile Services (IBS)
Number of Floors Mobile service room Sizes in Meter Roof‐Top room Sizes in Meter
(L X B X H) (L X B X H)
Up to G+10 Not Applicable 3m x 3m x 3m
G+11 to G+100 3m x 3m x 3m 3m x 3m x 3m
(Every 10 floors starting from the
basement level /Ground floor)
Shopping malls and Bulk services Will be Advised at NOC Stage Will be Advised at NOC Stage
buildings
Cluster of buildings with each having
more than G+5 floors Will be Advised at NOC Stage Will be Advised at NOC Stage
Appendix-3- du and ETC Telecom room Label
&
Telecom Room
Appendix‐4‐ Connectivity Wiring detail
Project Name:
Meet-Me- Room Main Telecom Room (MTR) Floor Telecom Room Tenant/Unit Notes
Fiber Termination Splitter Uplink Splitter Splitter downlink Splicing Point Fiber Terminal Box (FTB)
4 x 13A twin
socket with 4 x 13A twin socket
4 x 13A twin socket with 4 x 13A twin socket with
dedicated with dedicated
dedicated circuit dedicated circuit
circuit circuit
4 x 13A twin socket
Two number of AC and DC Two number of AC and DC
with dedicated circuit Two number Two number of
Earth Bar Earth Bar
Electrical To be determined during of AC and DC AC and DC Earth
1
Supply One number of AC and NOC design stage Earth Bar Bar
2 x 63A TP isolator fed from 2 x 40A TP isolator fed from
DC Earth Bar
EDB EDB
2 x 63A TP 2 x 63A TP isolator
isolator fed fed from EDB
from EDB
To be determined
To be determined during To be determined during
3 Floor Loading 10kNm2 (distributed load) 10kNm2 (distributed load)- 10kNm2 (distributed load)- during NOC design
NOC design stage NOC design stage
stage
2 x handheld CO2 2 x handheld CO2 cylinder 2 x handheld CO2 cylinder 2 x handheld 2 x handheld CO2
cylinder extinguishers extinguishers extinguishers CO2 cylinder cylinder
To be determined during
5 Fire protection 1 x smoke detectors per Room shall be comply with Room shall be comply with the extinguishers extinguishers
NOC design stage
room connected to the fire and safety fire and safety requirements like Room shall be Room shall be
BMS/FACP requirements like smoke smoke detector, fire alarm, comply with comply with the
Appendix-5 Summary Table- Electromechanical (EM) Specification
detector, fire alarm, emergency light etc. as per local the fire and fire and safety
emergency light etc. as per authority standards. Any water safety requirements like
local authority standards. sprinklers to be avoided. requirements smoke detector, fire
Any water sprinklers to be like smoke alarm, emergency
avoided. detector, fire light etc. as per
alarm, local authority
emergency standards. Any
light etc. as per water sprinklers to
local authority be avoided.
standards. Any
water
sprinklers to
be avoided.
Appendix-5- Summary Table- ISP Specification
Bulk Service
Building with Buildings – Group of Warehouses and
S. Infrastructure Building with Building with up
Building with up to 1200 Shopping Hotels, Factories
N Components Single Villa Complex of Villa up to 300 to 600 Tenant
up to 150 Tenant Mall Palaces and
o Name Tenant
Tenant Hospitals
200mm X
200mm X 50mm 200mm X 50mm 200mm X 50mm 50mm Cable
Cable Tray for Cable Tray for Cable Tray for Fixed 200mm X 50mm Tray for To be
Horizontal Cable Not applicable Not applicable Cable Tray for
Fixed Services Fixed Services Services Fixed determined
8 tray (Floor Fixed Services Not applicable
and 150 mm X and 150 mm X and 150 mm X Services during design
corridor) and 150 mm X
50mm for IBS 50mm for IBS 50mm for IBS and 150 mm NOC stage
(GSM) (GSM) (GSM) 50mm for IBS X 50mm for
(GSM) IBS (GSM)
For residential For residential
For residential
12U (H) X For residential 12U 12U (H) X
12U (H) X
600mm (W) X (H) X 600mm (W) X
600mm (W) X
150mm(D) for up 600mm (W) X 150mm(D) for up
150mm(D) for up
to 24 Cat6 Cables 150mm(D) for up to to 24 Cat6 Cables
to 24 Cat6 Cables
24 Cat6 Cables
For residential For residential
For residential
12U (H) X For residential 12U 12U (H) X For Retail
12U (H) X
12U (H) X 600mm (W) X (H) X 600mm (W) X 12U (H) X 12U (H) X
Consolidation 12U (H) X 600mm (W) X
9 600mm (W) X 300mm(D) for 600mm (W) X 300mm(D) for 600mm (W) Not applicable 600mm (W) X 150mm(D)
Point (Cabinet) 600mm (W) X 150mm(D) 300mm(D) for
150mm(D) above 24 Cat6 300mm(D) for above above 24 Cat6 X 300mm(D)
above 24 Cat6
Cables 24 Cat6 Cables Cables
Cables
For Commercial For Commercial For Commercial
For Commercial
12U (H) X 12U (H) X 12U (H) X
12U (H) X
600mm (W) X 600mm (W) X 600mm (W) X
600mm (W) X
350mm(D) 350mm(D) 350mm(D)
350mm(D)
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
key plan
02 70031-SCL-B00-A-100 SITE PLAN 1 : 100 03 A1 -- -- 02 70037-SCL-EP-100 SITE PLAN - POWER LAYOUT 1:50 01 A1 -- -- 02 70037-SCL-DR-101 GROUND AND ROOF FLOOR DRAINAGE LAYOUT 1:50 02 A1 -- --
03 70037-SCL-CC-100 SITE PLAN - CCTV & ACCESS CONTROL SYSTEM LAYOUT 1:50 01 A1 -- -- 03 70037-SCL-FF-101 GROUND FLOOR FIRE FIGHTING LAYOUT 1:50 02 A1 -- --
03 70031-SCL-B01-A-101 GROUND FLOOR PLAN & ROOF PLAN 1 : 50 03 A1 -- -- 05 70037-SCL-EL-101 LIGHTING LAYOUT 1:50 01 A1 -- --
05 70031-SCL-B01-A-801 DOOR AND WINDOW SCHEDULE 1 : 50 03 A1 -- -- 07 70037-SCL-EP-102 POWER SCHEMATIC DIAGRAM & LOAD SCHEDULE N.T.S 00 A1 -- --
BOUNDARY WALL 09 70037-SCL-CC-101 CCTV & ACCESS CONTROL SYSTEM LAYOUT 1:50 01 A1 -- --
06 70031-SCL-B01-A-101 BOUNDARY WALL PLAN 1 : 100 03 A1 -- -- 10 70037-SCL-DA-101 DATA CONTAINMENT LAYOUT AS SHOWN 01 A1 -- --
07 70031-SCL-B01-A-702 BOUNDARY WALL ELEVATIONS AND SECTIONS 1 : 100 03 A1 -- -- 11 70037-SCL-LP-101 EARTHING & LIGHTNING PROTECTION LAYOUT 1:50 01 A1 -- --
TYPICAL DETAILS
04 25.10.2016 TITLE CHANGE AS PER CLIENT'S COMMENT MA UB
08 70031-SCL-TY-A-901 MISCELLANEOUS DETAILS 03 A1 -- --
03 24.07.2016 TITLE CHANGE AS PER CLIENT'S COMMENT MA UB
02 07.06.2016 CORRECTED AS PER CLIENT'S COMMENT MA UB
01 28.04.2016 DETAILED DESIGN MA UB
00 14.04.2016 PRELIMINARY DESIGN MA UB
Rev Date Description Rev by Ckd by
Client
LIST OF STRUCTURAL DRAWINGS
01 70037-SCL-S-001 GENERAL NOTES 01 A1 -- --
Project
DISICIPLINE STATUS
ARCHITECTURAL DETAILED DESIGN
Drawing Title
LIST OF DRAWING
A1 70037-SCL-GN-A-003 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
10000 ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
PLOT LIMIT 2000 5500 2500 PLOT LIMIT
PLOT BOUNDARY
GRAVEL
2000
INTERLOCK
RWO
0
:10
:1
GRAVEL
E
PLOT BOUNDARY
P
O
L
S
PROPOSED
5000
MMR
GRAVEL
10000
INTERLOCK +4950 INTERLOCK
SSL.
CANOPY
+0.300 INTERLOCK
3000
1 SITE LAYOUT
A-100 SCALE: 1:50
MEP CONSULTANT
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
ARCHITECTURAL DETAILED DESIGN
Drawing Title
MMR ROOM
SITE PLAN
A1 70037-SCL-A-100 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
A B C A B C
-- -- -- -- -- --
5500
5300 5300
1 1
200
-- -- SCHEDULE OF FINISHES
RWO WALLS
W1 JOTUN - DURATHENE EPOXY PAINT SNOW WHITE COLOR GLOSSY
3350
3200
+6050 O SKIRTING
TOP LVL. L
S S1 FOSROC - SL 4000 LIGHT GREY
CEILINGS
MMR
5000
4800
5000
4800
A-201 A-201 A-201 ROOF A-201
C1 EPOXY PAINT - DURATHENE 50% LITE- GLOSS FINISH GREY (0115)
+0.750 +4950
SSL.
2 2
100
-- --
D02 +0.750
1300
1450
1450
200 3700 100 1300 200
3 3
200
-- D01 --
4200 +0.750 300
1000
CANOPY CANOPY
A A
A-201 +0.300 A-201
A-201 A-201
RAMP
5 x 75 x 75mm GALV.
TENSION CABLE / ROD
BRUSHED STAINLESS
STL. THREADED SHOE
SHANKLAND COX
ANGLE STIFFENER
75 x 75mm GALV. STL. STL. TUBULAR FRAME AS PER MFTR. PO Box 44936
PO Box 80670 PO Box 37133
ANGLE STIFFENER AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
SILICONE SEALANT BRUSHED STAINLESS STL. T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
75 x 75mm GALV. STEEL CHANNEL F +971 2 671 5362
W/ BACK ROD BRACKET FASTEN TO F +971 3 766 0032 F +971 4 338 0133
FIX TO WALL WITH EXPANSION BOLT alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
75 x 75mm GALV. STEEL 5 x 75 x 75mm GALV. ALUMINUM FRAME
AND FASTEN CANOPY FRAME WITH
EQ EQ EQ EQ STL. TUBULAR FRAME
THREADED BOLT (APPLIES TO OPPOSITE SIDE) CLADDING LINE CHANNEL FIX TO WALL SILICONE SEALANT AT GAP Project
WITH EXPANSION BOLT 75 x 75mm GALV. STL.
5 x 75 x 75mm GALV. AS PER MFTR. ANGLE STIFFENER RIGID FIXING SCREW
STL. TUBULAR FRAME RIGID FIXING SCREW 4mm THK. ALUM.
75 x 75mm GALV. STL. EL. +5.550 SHEET CLADDING
ANGLE STIFFENER ROOF T.O.SS
150
1900
1600
4mm THK. ALUM. MMR ROOM
1600 SHEET CLADDING
SL - 4000 FLOOR (INTERNAL) EXTERNAL PAINT LIKE STONE GROUND FLOOR PLAN &
ROOF PLAN
DETAILED PLAN DEATILED SECTION
Drawn MA Date 14.04.2016
Checked RM Scale 1:100
Approved BHATT Job no. 70037
3 CANOPY DETAIL Sheet Size Drawing No. Rev. No.
A-101 SCALE: 1:20
A1 70037-SCL-A-101 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
D01 D02
1200
200 800 200 1200
400 300
2500
2500
1800
200
200
1.5mm THK., 200mm (H) 1.5mm THK., 200mm (H)
STAINLESS STEEL KICK PLATE STAINLESS STEEL KICK PLATE
LOCATION: LOCATION:
MMP ROOM MMP ROOM
DESCRIPTION:
DESCRIPTION: PROVIDE 2 HOUR FIRE RATED SINGLE LEAF
SINGLE LEAF POWDER COATED GALVANIZED POWDER COATED GALVANIZED STEEL DOOR ON
STEEL DOOR (SANDWICH PANEL) POWDER COATED GALVANIZED STEEL FRAME
POWDER COATED GALVANIZED STEEL FRAME
SADDLE TYPE 2
SADDLE TYPES
04 25.10.2016 TITLE CHANGE AS PER CLIENT'S COMMENT MA UB
03 24.07.2016 TITLE CHANGE AS PER CLIENT'S COMMENT MA UB
02 07.06.2016 CORRECTED AS PER CLIENT'S COMMENT MA UB
01 28.04.2016 DETAILED DESIGN MA UB
TYPE 1 TYPE 2 TYPE 3 00 14.04.2016 PRELIMINARY DESIGN MA UB
Rev Date Description Rev by Ckd by
FIRE & SMOKE SEAL DOORS EXTERNAL DOOR WET AREA DOORS Client
FLOOR FIN
10
OUTDOOR FIN
15 12
FLOOR FIN
T.O.SS WITH OVER HEAD DOOR CLOSERS.
METAL SADDLE 175 GROUT GROUT
30 100 WATERPROOFING DOOR CONC SCREED
MEP CONSULTANT
MEMBRANE 30mm THK.
METAL THRESHOLD
WITH DRIP EDGE
WIDTH MARBLE
THRESHOLD
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
ARCHITECTURAL DETAILED DESIGN
Drawing Title
DOORS SCHEDULE
A1 70037-SCL-A-801 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
3 2 1 ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
- - -
A B C C B A
- - - - - -
100 1450 3350 100 key plan
100 3850 1450 100 CAT LADDER REMOVED 100 1450 3850 100
200
EXTERNAL FINISHES SCHEDULE
LEGEND:
1100
1100
1100
A A
+4950 +4950 +4950 A JOTUN - DURATHENE PAINT ON CEMENT PLASTER (COLOUR-1)
ROOF SSL. ROOF SSL. ROOF SSL. 15 mm WIDE GROOVE WITH ALUMINUM CHANNEL FIXED BY
B
B B SS SCREW
2600
D01 B
5750
5750
5750
4200
4200
4200
B
2500
+0.750 +0.750 +0.750
GF LEVEL GF LEVEL GF LEVEL
450
450
450
PAV. LEVEL PAV. LEVEL PAV. LEVEL
A A A
+6050
100 1450 3350 100 DET "R"
TOP LVL. +6050
TOP LVL. PAINTED CONCRETE
400 COPING
T.O.PARAPET
1100
A
1100
1300
+4950
+4950
100
ROOF SSL.
B ROOF SSL.
100
100
WALL FINISH
100 DRIP MOULD
MEP CONSULTANT
5750
STOPPER CONCRETE PARAPET T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
4000
Project
200
+0.750
+0.750
MMP ROOM
GF LEVEL
GF LEVEL
+0.300
450
+0.300
450
PAV. LEVEL
PAV. LEVEL
A
DISICIPLINE STATUS
ARCHITECTURAL DETAILED DESIGN
Drawing Title
A1 70037-SCL-A-201 04
NOTES
WALL FINISH 2. ALL DIMENSION ARE TO BE CHECKED AND CO-RELATED WITH OTHER
VARIES DRAWINGS PRIOR TO WORK COMMENCING ON SITE.
LIQUID APPLIED
MEMBRANE 50 150 50 T.O.S.S
100
80
130
250
90 30
TOP OF ROOF
MIN
STRUCTURE SLAB
50
DRIP MOULD
DOWN SPOUT
100 150 STEEL DOWEL CONCRETE SCREED
(SLOPE TO SCUPPER)
ELEVATION 1:10 SECTION 1:5
2 ROOF DRAIN DETAIL
1 ROOF DETAIL G-A91 1:5 3 SCUPPER DETAIL
G-A91 1:5 G-A91 AS SHOWN
PAINTED CONCRETE
400
COPING
T.O.PARAPET
100
100
100
WALL FINISH
100 DRIP MOULD
CMU/CONC.
WALL FINISH WALL
PLASTER
STOPPER CONCRETE PARAPET 20
IN OUT
20
04 25.10.2016 TITLE CHANGE AS PER CLIENT'S COMMENT MA UB
03 24.07.2016 TITLE CHANGE AS PER CLIENT'S COMMENT MA UB
200 30
02 07.06.2016 CORRECTED AS PER CLIENT'S COMMENT MA UB
PAINTED CEMENT PAINTED FAIR FACE 01 28.04.2016 DETAILED DESIGN MA UB
PLASTER GROOVE
PALSTER CONCRETE 00 14.04.2016 PRELIMINARY DESIGN MA UB
PAINTED BEAD WITH ALUMINUM Rev Date Description Rev by Ckd by
U SHAPE EXTERNAL GROOVE CHANEL Client
4 PARAPET DETAIL 5 PLASTER GROOVE DETAIL 6 FAIR FACE CONC. GROOVE DETAIL
G-A91 1:10 G-A91 1:2 G-A91 1:2
MEP CONSULTANT
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
ARCHITECTURAL DETAILED DESIGN
Drawing Title
TYPICAL DETAILS
A1 70037-SCL-TY-A-901 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
A-702
10000
200 3267 3067 3267 200
BOUNDARY WALL
100
100
3300
3300
RWO
0
:10
:1
BOUNDARY WALL
E
P
O
L
S
A-702
10000
10000
3200
3200
A-702
3300
Rev Date Description Rev by Ckd by
Client
RAMP
100
100
200 2125 1825 3700 100 1950 200
MEP CONSULTANT
Project
DISICIPLINE STATUS
ARCHITECTURAL DETAILED DESIGN
Drawing Title
A1 70037-SCL-BW-A-701 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
+6050
TOP LVL.
+6050
TOP LVL.
+4950
ROOF SSL.
+4950
ROOF SSL.
EL. +2.800
T.O.WALL EL. +2.800
T.O.WALL
2500
2800
2500
2800
EL. +0.300
PAV. LEVEL EL. +0.300
300
PAV. LEVEL
300
ROAD LEVEL
HINGED EMBEDDED IN ROAD LEVEL
PLASTER GROOVES
BARBED WIRE IN CONCRETE COLUMN
PLASTER GROOVES BARBED WIRE IN
ROLL FORM DOUBLE SHUTTER MOTORIZED ROLL FORM
EPOXY PAINT ON GATE 25MM SQ. ALUMINUM EPOXY PAINT ON
CEMENT PLASTER TUBE POWDER COATED CEMENT PLASTER
1 ELEVATION - 1 2 ELEVATION - 2
A-701 SCALE: 1:50 A-701 SCALE: 1:50
CEMENT PLASTER
300
BEAM REF TO STRUC
150
DWG EL. +2.800
+4950 +4950 T.O.WALL
200
ROOF SSL. ROOF SSL.
400
GROOVES IN PLASTER
EPOXY PAINT ON
CEMENT PLASTER
MEP CONSULTANT
2600
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
200mm THK HOLLOW F +971 2 671 5362
F +971 3 766 0032 F +971 4 338 0133
BLOCK alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
2500
2500
2800
2800
Project
400
REF TO CIVIL DWGS.
ROAD LEVEL ROAD LEVEL
ROAD LEVEL
PLASTER GROOVES BARBED WIRE IN PLASTER GROOVES BARBED WIRE IN
ROLL FORM ROLL FORM DISICIPLINE STATUS
WATER PROOFING
EPOXY PAINT ON EPOXY PAINT ON
ARCHITECTURAL DETAILED DESIGN
CEMENT PLASTER CEMENT PLASTER
Drawing Title
BOUNDARY WALL
3 ELEVATION - 3 4 ELEVATION - 4 5 TYPICAL SECTION ELEVATIONS & SECTION
A-701 SCALE: 1:50 A-701 SCALE: 1:50 A-702 SCALE: AS SHOWN
A1 70037-SCL-BW-A-702 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
MAIN CONSULTANT
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
STRUCTURAL DETAILED DESIGN
Drawing Title
GENERAL NOTES
A1 70037-SCL-S-001 03
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
MAIN CONSULTANT
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
STRUCTURAL DETAILED DESIGN
A1 70037-SCL-S-002 03
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
OPENING MORE THAN 150mm 07 TYPICAL DETAIL OF ISOLATION JOINT - IJ 03 25.10.2016 TITLE CHANGE AS PER CLIENT'S COMMENT LV UB
02b AND LESS THAN 450mm 02 24.07.2016 TITLE CHANGE AS PER CLIENT'S COMMENT LV UB
01 28.04.2016 DETAILED DESIGN LV UB
00 14.04.2016 FOR APPROVAL LV UB
Rev Date Description Rev by Ckd by
Client
B
MAIN CONSULTANT
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
08a DETAIL-B
TYPICAL DETAILS OF PLINTH TYPICAL COVERED ROOF PENETRATION
06 FOR MEP SERVICES
05 ON SOLID SLAB
(UNLESS OTHERWISE INDICATED ON DRGS.)
STANDARD DETAILS-2
A1 70037-SCL-S-003 03
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
2 SECTION - A 3 SECTION - B
S-101 SCALE: 1:25 S-101 SCALE: 1:25
1 BOUNDARY WALL LAYOUT
S-101 SCALE: 1:50
MAIN CONSULTANT
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
4 COLUMN - C1 5 COLUMN - C2
S-101 SCALE: 1:25 S-101 SCALE: 1:25
DISICIPLINE STATUS
STRUCTURAL DETAILED DESIGN
Drawing Title
A1 70037-SCL-S-101 03
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
A B C A B C OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
-- -- -- -- -- -- CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
5300 5300 COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
3850 1450 3850 1450
3 COLUMN - C1 key plan
S-102 SCALE: 1:25
1 1
-- --
+0.750
3350
3350
SSL.
4800
4800
2 2
-- --
1450
1450
3 3
-- --
5 SECTION - B
S-102 SCALE: 1:25
MAIN CONSULTANT
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
STRUCTURAL DETAILED DESIGN
6 SECTION - D 5 SECTION - C Drawing Title
S-102 SCALE: 1:25 S-102 SCALE: 1:25
FOUNDATION LAYOUT AND
TIE BEAM LAYOUT
A1 70037-SCL-S-102 03
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
A B C
-- -- --
5300
3850 1450
1
--
+6.050
TOP OF PARAPET
3350
+4.950
SSL.
4800
2
--
1450
3
--
1 ROOF PLAN 03
02
25.10.2016
24.07.2016
TITLE CHANGE AS PER CLIENT'S COMMENT
TITLE CHANGE AS PER CLIENT'S COMMENT
LV
LV
UB
UB
S-103 SCALE: 1:50 2 SECTION - A 01
00
28.04.2016
14.04.2016
DETAILED DESIGN
FOR APPROVAL
LV
LV
UB
UB
S-103 SCALE: 1:25 Rev Date Description Rev by Ckd by
Client
MAIN CONSULTANT
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
STRUCTURAL DETAILED DESIGN
Drawing Title
ROOF PLAN
A1 70037-SCL-S-103 03
NOTES
LEGEND 1. NO DIMENSIONS ARE TO BE SCALED.
10000
PLOT BOUNDARY
GRAVEL
2000
INTERLOCK
RWO
0
:10
:1
GRAVEL
PLOT BOUNDARY E
P
O
L
S
PROPOSED
5000
MMR
GRAVEL
10000
INTERLOCK INTERLOCK
CANOPY 04
03
25.10.2016
24.07.2016
CORRECTED AS PER CLIENTS COMMENTS
CORRECTED AS PER CLIENTS COMMENTS
LM
LM
UB
UB
INTERLOCK 02 06.07.2016 CORRECTED AS PER CLIENTS COMMENTS LM UB
01 28.04.2016 DETAILED DESIGN LM UB
00 14.04.2016 PRELIMINARY DESIGN LM UB
3000
3400
PLOT LIMIT PLOT LIMIT
MAIN
ENTRANCE
Project
DISICIPLINE STATUS
ELECTRICAL DETAILED DESIGN
Drawing Title
SITE PLAN
CCTV & ACCESS CONTROL SYSTEM LAYOUT
A1 70037-SCL-CC-100 04
NOTES
LEGEND 1. NO DIMENSIONS ARE TO BE SCALED.
SYMBOL DESCRIPTION 2. ALL DIMENSION ARE TO BE CHECKED AND CO-RELATED WITH OTHER
DRAWINGS PRIOR TO WORK COMMENCING ON SITE.
13A SINGLE SWITCHED SOCKET OUTLET
3. DRAWINGS TO BE READ IN CONJUNCTION WITH WRITTEN SPECIFICATION, IT
15A SINGLE SWITCHED SOCKET IS THE CONTRACTOR'S RESPONSIBILITY TO BRING THIS TO THE ATTENTION OF
OUTLET FOR FCU THE ENGINEER.
THREE PHASE ISOLATOR 4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
SINGLE PHASE ISOLATOR OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
FLEX OUTLET FOR ACCESS CONTROL PANEL NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
FLEX OUTLET FOR FACP
10000
PLOT BOUNDARY
GRAVEL
2000
INTERLOCK
RWO
0
:10
:1
GRAVEL
PLOT BOUNDARY E
P
O
L
S
PROPOSED
5000
MMR
GRAVEL
10000
INTERLOCK INTERLOCK
Y7/DB-GF
CANOPY 04
03
25.10.2016
24.07.2016
CORRECTED AS PER CLIENTS COMMENTS
CORRECTED AS PER CLIENTS COMMENTS
LM
LM
UB
UB
INTERLOCK 02 06.07.2016 CORRECTED AS PER CLIENTS COMMENTS LM UB
01 28.04.2016 DETAILED DESIGN LM UB
00 14.04.2016 PRELIMINARY DESIGN LM UB
3000
3400
PLOT LIMIT PLOT LIMIT
MAIN
ENTRANCE
Project
DISICIPLINE STATUS
ELECTRICAL DETAILED DESIGN
Drawing Title
SITE PLAN
POWER LAYOUT
A1 70037-SCL-EP-100 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
10000
PLOT BOUNDARY
C GRAVEL C
2000
INTERLOCK
RWO
100
: 1:
GRAVEL
E
PLOT BOUNDARY
P
O
L
S
PROPOSED
5000
GRAVEL
10000
CANOPY
INTERLOCK
3000
DISICIPLINE STATUS
ELECTRICAL DETAILED DESIGN
Drawing Title
SITE PLAN
LIGHTING LAYOUT
A1 70037-SCL-EL-100 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
10000
PLOT BOUNDARY
GRAVEL
2000
INTERLOCK
RWO
100
: 1:
GRAVEL
E
PLOT BOUNDARY
P
O
L
S
PROPOSED
5000
MMR
GRAVEL
10000
INTERLOCK INTERLOCK
GRAVEL
PAVEMENT RAMP
60mm THK.
PLOT LIMIT
MAIN
PLOT LIMIT SHANKLAND COX
ENTRANCE
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
1 SITE LAYOUT -DATA CONTAINMENT LAYOUT T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
- SCALE: 1:50 F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
ELECTRICAL DETAILED DESIGN
Drawing Title
SITE PLAN
DATA CONTAINMENT LAYOUT
A1 70037-SCL-DA-101 04
NOTES
LEGEND 1. NO DIMENSIONS ARE TO BE SCALED.
A B C A B C
-- -- -- -- -- --
5300 5300
1 1
-- -- ACP
CCTV RACK /
ACCESS CONTROL
SERVER
PANEL
3350
3350
MMR MMR
5000
4800
5000
4800
BG
CR
2 2 M DC
-- --
CR
04 25.10.2016 CORRECTED AS PER CLIENTS COMMENTS LM UB
1450
1450
03 24.07.2016 CORRECTED AS PER CLIENTS COMMENTS LM UB
02 06.07.2016 CORRECTED AS PER CLIENTS COMMENTS LM UB
BG 01 28.04.2016 DETAILED DESIGN LM UB
CR 00 14.04.2016 PRELIMINARY DESIGN LM UB
3 3 M DC Rev Date Description Rev by Ckd by
-- --
CR Client
CANOPY CANOPY
RAMP RAMP
1 GROUND FLOOR PLAN CCTV LAYOUT 2 GROUND FLOOR PLAN ACCESS CONTROL LAYOUT
- SCALE: 1:50 - SCALE: 1:50
MEP CONSULTANT
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
ELECTRICAL DETAILED DESIGN
Drawing Title
MMR ROOM
CCTV & ACCESS CONTROL SYSTEM LAYOUT
A1 70037-SCL-CC-101 04
NOTES
S PHOTO ELECTRIC SMOKE DETECTOR 4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
SOUNDER STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
FIRE RATED DOOR NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
EXIT EMERGENCY EXIT LIGHT - SELF CONTAINED - MAINTAINED ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
A B C A B C
-- -- -- -- -- --
5300 5300
1 1
-- --
3350
3350
IFU
MMR MMR
5000
4800
5000
4800
2 2
-- --
1450
1450
IFU
3 3
-- --
CANOPY CANOPY
NOTE:
S S S IFU IFU 01. THE RISER REPRESENTS A TYPICAL SYSTEM AND IS NOT INTENDED FOR MEP CONSULTANT
INSTALLATION SYSTEM SUPPLIER SHALL PROVIDE INSTALLATION DRAWINGS AND
2Lx2.5sq.mm
FIRE ALARM CABLE
WIRING DIAGRAMS BASED UPON CONTRACT DRAWING.
02. THIS DIAGRAM IS NOT INTENDED TO SHOW EXACT QUANTITIES OF DEVICES. REFER
SHANKLAND COX
TO DRAWINGS FOR DEVICES QUANTITIES AND LOCATIONS.
2Lx1.5sq.mm PO Box 80670 PO Box 44936 PO Box 37133
03. FIRE ALARM CABLE SHALL BE FP200 (2c 1.5 OR 2c 2.5) OR APPROVED EQUIVALENT. AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
FIRE ALARM CABLE
04. ELECTRICAL & MECHANICAL OPENING SHALL BE FILLED WITH FIRE RETARDANT T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
MATERIAL. abudhabi@shanklandcox.com
CIRCUIT-1 CIRCUIT-2 LOOP-2 LOOP-1 alain@shanklandcox.com dubai@shanklandcox.com
05. DURING FIRE CONDITION CCU SHALL BE SWITCHED OFF.
06. EXIT LIGHT SHALL BE MAINTAINED TYPE. Project
AUTO DIALER
07. ISOLATOR MODULES SHALL BE PROVIDED AS PER MANUFACTURER'S INSTRUCTION.
08. LOCATION OF INTERFACING MODULES SHALL BE COORDINATED AT SITE.
09. FIRE ALARM CONTROL PANEL SHALL BE EQUIPPED WITH STANDARD BATTERIE WHICH
WILL POWER THEM FOR 24 HOURS IN QUIESCENT CONDITION AND 15 MIN. IN ALARM
CONDITION.
10. FIRE ALARM SYSTEM SHALL BE INTERFACED WITH THE FOLLOWING EQUIPMENT :
230V 50Hz SUPPLY
HVAC SYSTEM, (CCU,DX UNITS, DAMPERS) ACCESS CONTROL SYSTEM
11. SEE MECHANICAL & ELECTRICAL DRAWINGS FOR LOCATION OF EQUIPMENTS TO BE
FIRE & FAULT SIGNAL TO SNMP
INTERFACED WITH THE FIRE ALARM SYSTEM.
12. ALL CONTROL CABINETS SHALL BE GROUNDED AS PER NEC REQUIREMNTS AND
SPECIFICATIONS.
13. EMERGENCY LIGHT MONITORING PANEL TO BE PROVIDED IF REQUIRED BY DISICIPLINE STATUS
AUTHORITY HAVING JURISDICTION.
ELECTRICAL DETAILED DESIGN
Drawing Title
MMR ROOM
FIRE ALARM & EMERGENCY LIGHTING LAYOUT
A1 70037-SCL-FA-101 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
40A TP
ISO
+1c-16mm2 PVC Y/G AS ECC
1x4c-10mm2 XLPE/SWA/PVC
TCL=22.30kW TCL=10.0kW
FUTURE FIRST FUTURE FIRST
FLOOR DB FLOOR CCU SPACE SPACE
R Y B
A A A V S/S
MEP CONSULTANT
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
ELECTRICAL DETAILED DESIGN
Drawing Title
MMR ROOM
POWER SCHEMATIC DIAGRAM &
LOAD SCHEDULE
A1 70037-SCL-EP-102 04
NOTES
LEGEND 1. NO DIMENSIONS ARE TO BE SCALED.
SYMBOL DESCRIPTION 2. ALL DIMENSION ARE TO BE CHECKED AND CO-RELATED WITH OTHER
DRAWINGS PRIOR TO WORK COMMENCING ON SITE.
13A SINGLE SWITCHED SOCKET OUTLET
3. DRAWINGS TO BE READ IN CONJUNCTION WITH WRITTEN SPECIFICATION, IT
15A SINGLE SWITCHED SOCKET IS THE CONTRACTOR'S RESPONSIBILITY TO BRING THIS TO THE ATTENTION OF
OUTLET FOR FCU THE ENGINEER.
THREE PHASE ISOLATOR 4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
SINGLE PHASE ISOLATOR OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
SPLIT UNIT A/C CONTROL PANEL NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
FLEX OUTLET FOR ACCESS CONTROL PANEL
5500
A B C A B C
-- 5500 -- -- -- -- --
5300 5300
C6/DB-U-GF
1 1
-- ACP
--
CCTV RACK /
SERVER
C5/DB-U-GF RWO
C1/DB-U-GF
0
10
RYB5/DB-GF RYB6/DB-GF : 1:
RYB2/MDB-MMR E
P
3350
3350
R7/DB-GF O Y8/DB-GF
L
S
MMR
5000
4800
5000
4800
ROOF
C11/DB-U-GF
2 2 04 25.10.2016 CORRECTED AS PER CLIENTS COMMENTS LM UB
-- --
C8/DB-U-GF 03 24.07.2016 CORRECTED AS PER CLIENTS COMMENTS LM UB
02 06.07.2016 CORRECTED AS PER CLIENTS COMMENTS LM UB
C2/DB-U-GF C3/DB-U-GF 01 28.04.2016 DETAILED DESIGN LM UB
1450
1450
00 14.04.2016 PRELIMINARY DESIGN LM UB
Rev Date Description Rev by Ckd by
Client
3 C4/DB-U-GF 3
-- --
CANOPY
C9/DB-U-GF CANOPY
RAMP RAMP
MEP CONSULTANT
1 GROUND FLOOR PLAN POWER LAYOUT 2 ROOF PLAN POWER LAYOUT
- SCALE: 1:50 - SCALE: 1:50
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
ELECTRICAL DETAILED DESIGN
Drawing Title
MMR ROOM
POWER LAYOUT
A1 70037-SCL-EP-101 04
NOTES
key plan
5500
A B C A B C
-- 5500 -- -- -- -- --
5300 5300
1 1
-- --
RWO
100
: 1:
E
P
3350
3350
O
L
S
MMR
5000
4800
5000
4800
ROOF
2 2
-- --
04 25.10.2016 CORRECTED AS PER CLIENTS COMMENTS LM UB
Y1/DB-GF
1450
1450
03 24.07.2016 CORRECTED AS PER CLIENTS COMMENTS LM UB
R1/DB-GF
02 06.07.2016 CORRECTED AS PER CLIENTS COMMENTS LM UB
01 28.04.2016 DETAILED DESIGN LM UB
00 14.04.2016 PRELIMINARY DESIGN LM UB
3 3 Rev Date Description Rev by Ckd by
-- --
Client
CANOPY CANOPY
RAMP RAMP
1 GROUND FLOOR PLAN LIGHTING LAYOUT 2 ROOF PLAN LIGHTING LAYOUT
- SCALE: 1:50 - SCALE: 1:50
MEP CONSULTANT
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
ELECTRICAL DETAILED DESIGN
Drawing Title
MMR ROOM
LIGHTING LAYOUT
A1 70037-SCL-EL-101 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
A B C
-- -- --
5300
600
--
800
300
1200
600
600
B B
-
-
3350
1200
1000
4800
MMR
5000
4800
3400
1200
2
--
2200
938
1450
MMP ROOM
900
300
--
-
A
CANOPY
1000
2 SECTION A-A
1 RAMP LAYOUT
GROUND FLOOR PLAN DATA CONTAINMENT - SCALE: 1:50
- SCALE: 1:50
SCREWED
EXPANSION INSERT
600
alain@shanklandcox.com dubai@shanklandcox.com
SLOTTED 'U' CHANNEL
Project
2200
DISICIPLINE STATUS
ELECTRICAL DETAILED DESIGN
2 SECTION B-B Drawing Title
- SCALE: 1:50
MMR ROOM
DATA CONTAINMENT LAYOUT
A1 70037-SCL-DA-101 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
A B C A B C
-- -- -- -- -- --
5500
5300 5300
1 1
-- --
RWO
100
: 1:
E
P
3350
3350
O
L
S
MMR
5000
4800
5000
4800
ROOF
2 2
-- --
1450
1450
04 25.10.2016 CORRECTED AS PER CLIENT'S COMMENT SR UB
03 24.07.2016 CORRECTED AS PER CLIENT'S COMMENT SR UB
02 07.06.2016 CORRECTED AS PER CLIENT'S COMMENT SR UB
3 3 01 28.04.2016 DETAILED DESIGN SR UB
-- -- 00 12.04.2016 PRELIMINARY DESIGN SR UB
Rev Date Description Rev by Ckd by
CANOPY CANOPY Client
RAMP
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
MECHANICAL DETAILED DESIGN
Drawing Title
A1 70037-SCL-AC-101 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
A B C
-- -- --
5300
1
--
3350
MMR
5000
4800
2
-- 1450
CANOP Rev
Client
Date Description Rev by Ckd by
RAMP
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
MECHANICAL DETAILED DESIGN
Drawing Title
A1 70037-SCL-FF-101 04
NOTES
4. THIS DRAWING AND ALL ITS DESIGNS AND DETAILS WERE CREATED BY THE
ARCHITECTS SHANKLANDCOX ON THE DATE SHOWN BELOW AND (UNLESS
STATED OTHERWISE BY CONSULTANCY AGREEMENT) MAY NOT BE COPIED
OR REPRODUCED IN WHOLE OR PART SAVED WITHOUT PRIOR WRITTEN
CONSENT. FOR THE PURPOSE OF UNITED ARAB EMIRATES FEDERAL LAW
NUMBER 40 FOR 1992 CONCERNING INTELLECTUAL PROPERTY RIGHTS AND
COPY RIGHTS SUCH DRAWINGS, DESIGN AND DETAILS WERE PUBLISHED,
ON THAT DATE, IN THE UNITED ARAB EMIRATES FOR THE FIRST TIME.
key plan
A B C A B C
-- -- -- -- -- --
5500
5300 5300
1 1
-- --
RWO
100
: 1:
E
P
3350
3350
O
L
S
MMR
5000
4800
5000
4800
ROOF
2 2
-- --
1450
1450
04 25.10.2016 CORRECTED AS PER CLIENT'S COMMENT SR UB
03 24.07.2016 CORRECTED AS PER CLIENT'S COMMENT SR UB
02 07.06.2016 CORRECTED AS PER CLIENT'S COMMENT SR UB
3 3 01 28.04.2016 DETAILED DESIGN SR UB
-- -- 00 12.04.2016 PRELIMINARY DESIGN SR UB
Rev Date Description Rev by Ckd by
CANOPY CANOPY Client
RAMP
SHANKLAND COX
PO Box 80670 PO Box 44936 PO Box 37133
AL AIN, UAE ABU DHABI, UAE DUBAI, UAE
T +971 3 766 9334 T +971 2 671 5411 T +971 4 338 0144
F +971 3 766 0032 F +971 2 671 5362 F +971 4 338 0133
alain@shanklandcox.com abudhabi@shanklandcox.com dubai@shanklandcox.com
Project
DISICIPLINE STATUS
MECHANICAL DETAILED DESIGN
Drawing Title
A1 70037-SCL-DR-101 04