MN HW 1065 EC Installation Manual Ver2 (1) .0
MN HW 1065 EC Installation Manual Ver2 (1) .0
com
1065 EC Installation
Manual
This guide covers the basic physical installation of the 1065 EC PCB and required wiring. Once
installed the 1065 EC requires configuration using GMS software. For information and instructions on
how to complete the configuration refer to the Field Controller Configuration Guide.
Supporting Material
The following documents may provide further support when installing and configuring Pacom field
controllers:
• 1057 Installation Manual
• 1058 Installation Manual
• Field Controller Configuration Guide
Assumptions
It is assumed the technician has successfully completed an electrical trade or equivalent technical
training to satisfy local requirements and authorities. The technician may also be required to meet the
requirements of the Local Telecommunications Authority during the installation of the equipment
detailed in this guide. Some knowledge of networks and network types is also required.
PACOM SUPPORT
For Pacom product support E-mail: support@pacom.com
Note: This symbol indicates information that emphasizes or supplements points made in the main text or to help
users apply the procedures in the text to their specific needs.
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
ii About This Guide
Warning: This symbol indicates a caution or warning, where failure to take or avoid a specific action may result in
loss of data or physical damage to hardware or personnel.
COPYRIGHT © 2005
PACOM SYSTEMS PTY LTD
ALL RIGHTS RESERVED
No part of this document may be reproduced, transmitted, transcribed, stored in a retrieval system, or
translated into any language in any form by any means without the prior written consent of Pacom
Systems Pty Ltd.
Trademarks
All trademarks, brand and product names are property of their respective owners.
Pacom Systems Pty Ltd makes no warranty of any kind with regard to this product, including, but not
limited to, the implied warranties of merchantability and fitness for a particular purpose. Pacom
Systems Pty Ltd shall not be liable for errors contained herein or for incidental consequential damages
in connection with the furnishing, performance, or use of this product.
This document contains proprietary information and is protected by copyright. The information
contained within this document is subject to change without notice.
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
1065 EC Installation Manual i
TABLE OF CONTENTS
1. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.2 1065 I/O PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.3 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.1 1065 EC Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . .3
2.2 Installation Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.3 Setting the DIP Switches and Links . . . . . . . . . . . . . . . . . . . . . . . . .7
2.4 Installing Mezzanine Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2.5 Elevator Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2.6 RS485 wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.7 RS232 wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2.8 Power wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2.9 Earth Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
2.10 Recommended Wire Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
ii Table Of Contents
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
1065 EC Installation Manual 1
1. OVERVIEW
1.1. Introduction
The Pacom 1065 is a microprocessor controlled multi-purpose I/O card. There are currently three
variations of the 1065 these are.
1065 16 I/O 16 Input, 4 output, I/O module 1065 I/O Installation Manual
Each of the above variants uses what is essentially the same hardware for a different application.
The 1065EC is connected to a 1057 or 1058 or Witness field controller via an RS485 loop and is used to
control access to the floors serviced by an elevator. A card reader is positioned in the elevator car and
upon receipt of a valid card read the floors authorized for that card holder are enabled.
When connected to a 1057 or 1058 RTU each 1065EC can control access to up to 16 consecutively
numbered floors. If the Elevator services floor 1 and floors 20-30 although it is less than 16 floors it
may require two 1065ECs. A 1057 RTU can control access in up to 16 elevators with a maximum of
128 floors per elevator. A 1058 RTU can control access in up to 2 elevators with a maximum of 128
floors per elevator.
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
2 Overview
1.3. Specifications
Parameter Specification
Parameter Specification
LD1 RS485 - Rx
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
1065 EC Installation Manual 3
2. INSTALLATION
1. Option 1: The buttons for the floors that the card holder has access to will be enabled for the
duration of the strike time (see Section 2.2.1. Option 1).
2. Option 2: The 1065 EC will enable all the outputs for the floors that person has access to.
When the person pushes a floor button it will activate an input on the 1065EC. The 1065EC
on receipt of the input will disable all other floors until another valid card is read (see Section
2.2.2. Option 2).
3. Option 3: The buttons for the floors that the card holder has access to will be enabled for the
duration of the strike time (as in option 1) with the addition of a remote egress button and
programmable Extended Shunt/Strike time. This provides hold-on time for the remote egress
button. This Facility may be used in buildings where an intercom is used to identify non card
holders (visitors) and a remote button is activated to allow the visitor entry (e.g. to the front
door of the premises) (see Section 2.2.3. Option 3).
Note: Rev 5 and above 1065 PCBs have SIP resistor packs (See Figure 2-5). These resistor packs are used to
match the resistance of the End of Line resistors installed on each of the inputs points. The factory installed resistor
packs are 10kΩ and end of line resistors must be of the same value if these packs are used. This manual assumes
that the default packs are being used and all end of line resistors will be 10 kΩ. If the default packs have been
changed simply substitute the 10kΩ in the manual for the value of the new packs.
Warning: The operation of the 1065EC is designed to be fail safe, the relay links on the 1050-003 must be set to
NC (Normally Closed) so that if power is lost to the 1065EC all floors will be enabled.
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
4 Installation
2.2.1. Option 1
The wiring connections for option 1 are fairly simple, the normally open contacts of an auxiliary relay
(1 for each floor) are wired into the push button circuit for each floor. The floor button will only be
enabled when the auxiliary relay is energized. The output of the 1050-003 is used to activate the
auxiliary relay (See Figure 2-1).
2.2.2. Option 2
For option 2 wiring is a slightly more complex than option 1 because each floor button must also be
monitored.
Option 2 requires 2 relays per floor, one to monitor the floor button and one DPDT to enable the floor
button and the floor button relay.
The normal state of the Alarm inputs MUST BE reset (10kΩ) and go into alarm when the Button is
Pushed.
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
1065 EC Installation Manual 5
Note: The Zone has to be Shorted or read 5kΩ (50% of SIP pack resistance) for an alarm. It can not go open when
the button is pushed.
The jumper once installed, will short together all the output 1 and AC fail inputs for all 1065ECs
controlling a single elevator. This will enable the output number 1 of any 1065EC to trigger the AC Fail
inputs of all 1065ECs for that elevator (See Figure 2-3). When any floor button is pushed the 1065EC
that is monitoring that floor will activate its output number 1. This will signal the other cards that a
floor has been selected and all other floors should now be disabled.
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
6 Installation
2.2.3. Option 3
The wiring connections for option 3 similar to option 1, the normally open contacts of an auxiliary relay
(1 for each floor) are wired into the push button circuit for each floor. The floor button will only be
enabled when the auxiliary relay is energized. The output of the 1050-003 is used to activate the
auxiliary relay. The floors can also be enabled by a remote egress button (or any system trigger). This
remote egress button can be connected to the 1065EC as in Figure 2-4 or any other input in the system
(requires macro if not connected to 1065EC).
Note: Each elevator controller configured for the readers must have a unique address (option 3 only).
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
1065 EC Installation Manual 7
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
8 Installation
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
1065 EC Installation Manual 9
On Off On On On 10111 23 24
On On Off On On 11011 27 28
On On On Off On 11101 29 30
On On On On Off 11110 30 31
On On On On On 11111 31 32
The use and settings of DIP switches 6-8 for 1065EC are as follows:
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
10 Installation
3 RS485 Open 1065 EC is not the last device on the RS485 line
Termination (default)
7 RS485 relay Open 1065 will disconnect from device loop if line
bypass unstable, self-test and attempt to reconnect
every 30 seconds.
Closed 1065 will not disconnect from device loop
8-15 Open Used to connect a camera to the corresponding
input. 1065 EC does not support cameras.
21 Output 1 Power Open Link Recommended position when using external Power
Source Removed supply. Normal dry contact relay operation O/P 1.
Common will be shorted to NO when relay
energized and NC when relay is de-energized.
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
1065 EC Installation Manual 11
22 Output 2 Power Open Link Recommended position when using external Power
Source Removed supply. Normal dry contact relay operation O/P 2.
Common will be shorted to NO when relay
energized and NC when relay is de-energized.
23 Power for RS485 Open 1065 I/O does not provide power through RS485
port to power external devices (default).
Warning: hardware may be damaged if power is applied to mezzanine cards that are inserted incorrectly. Do not
attempt to install a mezzanine card with power applied.
Mezzanine cards are installed by inserting them into their slots on the 1065 and then securing them with
screws to the mezzanine card standoffs (2 each). The mezzanine card connectors on the 1065 are 24
pin, most mezzanine cards use only 20 or 22 pins, great care must be taken when inserting mezzanine
cards that they are correctly aligned with their standoffs this will ensure that the mezzanine card pins
are correctly aligned with the mezzanine card slot.
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
12 Installation
Pacom Data
10 57
N E TW O RK RX
N E TW O RK T X
D IAL UP RX
D IAL UP T X
PA N E L R X
Pacom Data
BA T T E R Y
PA N E L T X
10 5 7
LI NE FA I L
8
MA I NS
R E S ET
Cable 1
1064
Cable 4 Cable 2
Aux Relays
Cable 3
N E TW O R K R TS
N E T WO R K R X
N E T WO R K TX
DIA L UP RX
DIA L UP T X
1057
P A NE L RX
Pacom Data
B A T TE R Y
P A N E L TX
L I N E F A IL
8
RE S E T
M AI N S
Cable 1
1064
Cable 2
Floor Button
Monitoring
1065E Relays
Cable 6
Power Supply
12 VDC Aux Relays
Cable 4
Cable 3
Elevator Control
Interface
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
1065 EC Installation Manual 13
NE T WO RK CT S
NE T WO RK RT S
Pacom Data
10 57
N E TW O RK RX
N E TW O RK T X
D IAL UP RX
D IAL UP T X
PA N E L R X
BA T T E R Y
Pacom Data
PA N E L T X
10 5 7
LI NE FA I L
8
MA I NS
R E S ET
Cable 1
1064
Cable 2
Cable 4
Aux Relays
Cable 3
Remote Push Button
1 RS485 Communication 2
2 12 V DC Power 2
4 Cable between 1065EC and the external auxiliary relays 1 per floor + 1
common
5 Cable between the floor monitoring relays and the 1065EC 2 per floor
6 Cable between auxiliary relays and the floor monitoring relays 2 per floor
7 Cable between 1065EC and the remote push button. This button 2 per floor
may be wired in parallel with multiple buttons on the same floor
Table 2-4. Cable Requirements for Figures 2-7, 2-8 and 2-9.
Power Can also be supplied from an external source through the RS485 Loop (See Figure 2-12).
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
14 Installation
At 12 VDC:
• A Pacom 1058 RTU can supply up to 740mA.
• A Pacom 1057 RTU can supply up to 2A.
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
1065 EC Installation Manual 15
The same external supply could be used to power all devices on a device loop. In this case the Power
connections would usually be made via the RS485 terminals (see Section 2.6. RS485 wiring). The +12
and GND connectors would be left disconnected from the RS485 connections on the RTU which would
have its own supply and possibly backup batteries.
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
16 Installation
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
1065 EC Installation Manual 17
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved
18 Installation
Version 2.0, Modified 05/2005, Copyright © 2005 Pacom Systems Pty Ltd, All Rights Reserved