1. A liquid level control system linearly converts
a displacement of 2 to 3 m into a 4 to 20 mA control signal. A relay serves as the two position controller to open or close an inlet valve. The relay closes at 12 mA and opens at 10 mA. Find (1) the relation between displacement level and current, and (b) the neutral zone or displacement gap in meters. Answers: H = 0.0625 I + 1.75 HH –HL = 2.5 – 2.375 = 0.125 m Problems on ON- OFF Controller 2. In a ON/OFF temperature control problem, temperature range is 30 to 400 0 C. Temperature is linearly converted in to 4 to 20 mA signal. A relay serves as the two position controller. The relay closes at 9 mA and opens at 7 mA. Find (1) the relation between Temperature and current, and (b) the neutral zone or displacement gap. Answers: T = 23.125 I – 62.5 TH –TL = 46.25 Problems Proportional Controller 1. For a proportional controller, the controlled variable is a process temperature with a range of 0 to 100 0C and a set-point of 50 0 C. Under nominal conditions, the set point is maintained with an output of 35%. If the output changes to 45% find the offset when PB = 40 %.Find the controller output when the temperature rises to 60 0C. Answers 4 %, ep= -10 %,10 %. Problems Proportional Controller 2. For a proportional controller, the controlled variable is a process temperature with a range of 50 to 130 0C and a set-point of 73.5 0 C. Under nominal conditions, the set point is maintained with an output of 50%. Find the offset for an output of 55% if the proportional gain is (a) 0.1, (b) 0.7, (c) 2.0 and (d) 5.0 3. For the same application, find the percentage controller output with the 73.5 0C set point and a proportional gain of 2.0 if the temperature is (a) 60 0C, (b) 122 0C and (c) a ramping temperature of (82+5t) 0C. Answers 2. 50, 7.14 , 2.5 , 1 3. 83.75, 0, 28.75-12.5t Problems on signal conditioning 1. circuits A sensor outputs a voltage ranging from -2.4 to -1.1 V. For interface to an analog to digital converter, this needs to be 0 to2.5 V. Develop the required signal conditioning. Answer:Vout = 3.846Vin – 5.5 2. A sensor resistance varies from 520 to 2500 ohm. This used for R1 in the divider with R2 = 500 ohm and Vs = 10.0 V. Develop signal conditioning circuit so that output voltage varies from 0 to 5 V as the resistance varies from 520 to 2500 ohms where 0 V corresponds to 520 ohms. Answer:Vout = 13Vin 3. A bridge circuit has R1=R2=R3 =120 ohms and V=10.0 V. Design a signal conditioning system that provides an output of 0.0 to 5.0 V as R4 varies from 120 to 140 ohms. Answer:Vout = 13Vin Problems on signal conditioning circuits 4. A sensor outputs a voltage ranging from 20 to 250 mV. Develop the required signal conditioning.to get output 0 to 5V. The circuit must have very high input impedance. Answer:Vout = 21.7(Vin – 0.02) Problems Integral Controller 1. An integral controller has reset action of 2.2 minutes. Express the integral controller constant in s -1. Find the output of this controller to a constant error of 2.2 2. An integral controller is used for speed control with a set- point of 12 rpm within a range of 10 to 15 rpm. The controller output is 22% initially. The constant K I = -0.15% controller output per second per percentage error. If the speed jumps to 13.5 rpm, calculate the controller output after 2 s for a constant ep. Ans: ep= -30 %, P = 31 %(after 2s) 3. A PI controller is reverse acting PB = 20, 12 repeats per minute. Find (a) the proportional gain, (b) the integral gain, and (c) the time that the controller output will reach 0% after a constant error of – 1.5 % starts. The controller o/p when the error occurred was 72%. Proportional Integral (PI) Controller For the given error plot graph of PI controller output as a function of time Kp = 5 , K I = 1.0 s -1, Po(I) = 20 %